11-626-014_ 2.3 Tons Airstem Sizing Summary for AHU -2 Project Name: DORAL IMAGING INSTITUTE Sensible coil load 'Prevared by: JMM CONSULTING OA DB / WB 50,7 / 76,5 'F Air System Information _ -_1026 CFM Entering DB / WB._ System Name AHU -2 _ 1026 CFM Equipment Class, . -, -_ SPLT AHU Number of Zones _ System Type ,,, __ - ,._.- _SZCAV Floor Area Sizing Calculation Information _265.0 Bypass factor Zone and Space Sizing Method: BTU /hr /ft2 41.5 Zone CFM ,__ .. —peak zone sensible load Calculation Months Space CFM , _ _ _ _Coincident space loads Sizing Data _ Central Cooling Coil Sizing Data CFM /ftz . -_ _ ,0.06 CFM /ft2 06/15/11 07:27 AM 1 667.0 ft2 .__-... Jan to Dec _Calculated Total coil load 2.3 Tons Load occurs at Jul 1600 Sensible coil load 1.8 Tons OA DB / WB 50,7 / 76,5 'F Coil CFM at Jul 1600 _ -_1026 CFM Entering DB / WB._ 76.3 1 66.1 'F Max possible CFM _. _ 1026 CFM Leaving D6 / WB_ -. 56.4 157.3 'F Design supply temp. 55.0 'F Coil ADP_ 'F ft2/Ton _265.0 Bypass factor _56.2 0.100 BTU /hr /ft2 41.5 Resulting RH— . _ _ 53 Water flow @ 10.0 'F rise _._._ _ gpm Zone T -stet Check _ -._. 1 of 1 OK Central Heating Coil Sizing Data Max coil load - _ 7036 BTU /hr Load occurs at Coil CFM at Des Htg _ 1026 CFM _ BTU /hr /ft2 Max possible CFM ,. 1026 CFM Ent. DB / Lvg DS Water flow @ 20.0 'F drop _ _- gpm Supply Fan Sizing Data Actual max CFM at Jul 1600 1026 CFM Fan motor BHP BHP- Standard Standard CFM —1025 CFM Fan motor kW Max CFM /ftz _- -. 1.54 CFM /ft2 Fan static _ Outdoor Ventilation Air Data Design airflow CFM 55 CFM CFM /person CFM /ftz . -_ _ ,0.06 CFM /ft2 Carrier Hourly Analysis Program v4.04 -__ Des Htg 10.5 _68.3 / 74.6 'F .00 BHP .00 kW .00 in. wg. _ 11.17 CFM /person P2ge 4