Loading...
11-626-011Air-System Sizing Summary for 4 "roject Name: DORAL IMAGING INSTITUTE PrpQared by: JMM CONSULTING Air System Information System Name---­­---- AHU-1 Equipment Class_SPLTAHIJ Number of Zones System Type ­.- --SZCAV Floor Area Sizing Calculation Information Zone and Space Sizing Method: 1230 CFM Zone CFM —­ r. - -----Peak zone sensible load Space CFM -------.Coincident space loads Central Cooling Coil Sizing Data Total coil load 2.8 Tons Sensible coil load 2.1 Tons Coil CFM at Oct 1400 ­­1230 CFM Max possible CFM .1230 CFM Design supply temp., 55.0 *F ft'/Ton BTU/hr/ft2 Water flow @ 10.0 *F rise — - — ------- gpm Central Heating Coil Sizing Data Max Coil load 8683 BTU/hr Coil CFM at Des Htg­.-­­­-----1230 CFM Max possible CFM ­ ­ ­­­ --1230 CFM Water flow @ 20.0 'F drop gpm Supply Fan Sizing Data Actual max CFM at Nov 1400 1230 CFM Standard CFM CFM Actual max CFM/ft2 CFM1ft2 Outdoor Ventilation Air Data Design airflow CFM CFM CFM/ft2 CIP M/ft2 Garner Hourly An2l'Y'SiS- Program v4,04 Calculation Months Sizing Data Load occurs at OA D8 / WB. Entering DIS W5 Leaving DB WB Coil ADP Bypass factor Resulting RH Zone T-stat Check 9$5.0 ft2 to Dec -Calculated Oct 1400 36.7 / 74.9 * F --.....77.9166.5 *F - 58.7157.6 'F 56.5 'F 0.100 55 % 1 of I OK Load occurs at Htq BTU/hr/ft2 Ent. DIS / Lvg 67.9 / 74.5 'F Fan motor BHP BHP Fan motor kW . ..... . kW Fan static in. wg. CFM/person ­, 06/16/11 07:27 AM 8.50 CFM/person Page 1