Miami, May 25, 2011
Ms. V iana V ivir
DORAL IMAGING INSTITUTE, LLC.
7775 NW 48t1i Street, Suite 150
Doral, FL 33166
Re: Property @
6361 Sunset Drive
Miami, FL 33143
Dear Ms. Vivir:
Pursuant to your request, DYNATECH ENGINEERING CORP. conducted an Asbestos Interior
Survey on May 25, 2011 at the above referenced project. The purpose of our inspection was to
secure bulk samples for analysis to determine the presence of Asbestos Containing Building
Materials (A.C.B.M.). The scope of our inspection covered the following areas:
Interior was tested only at the above referenced project (see attached plan)
Based on our laboratory analysis; it was evident that asbestos fibers were found in the following
secured bulk samples:
A- Category I Non - Friable Material:
1) Black A/C Duct Mastic: Black a/c mastic was found with 4 -5% Chrysotile fibers (see
sample numbers 13, 14, 15, and attached sketch).
Black a/c duct mastic is considered Category INon- Friable material this material is presently in
s
good condition and does not need to be removed; however; in the event of renovation; where the
black a/c duct mastic's will be disturbed and removed, all work should be conducted by a Florida
Licensed Asbestos Abatement Contractors under full supervision of a Florida Licensed Asbestos
Consultant and in compliance with Federal, State and Local regulations.