Loading...
11-626-001h' GECyTECHNICAL TESTING LABORATORIES r:~ ENVIRONMENTAI DRILLING SERVICES HYDROGEOLOGY INSPECTION SERVICES ASBESTOS ROOFING DY'NATECH IENGINEERING CORP. Miami, May 25, 2011 Ms. V iana V ivir DORAL IMAGING INSTITUTE, LLC. 7775 NW 48t1i Street, Suite 150 Doral, FL 33166 Re: Property @ 6361 Sunset Drive Miami, FL 33143 Dear Ms. Vivir: Pursuant to your request, DYNATECH ENGINEERING CORP. conducted an Asbestos Interior Survey on May 25, 2011 at the above referenced project. The purpose of our inspection was to secure bulk samples for analysis to determine the presence of Asbestos Containing Building Materials (A.C.B.M.). The scope of our inspection covered the following areas: Interior was tested only at the above referenced project (see attached plan) Based on our laboratory analysis; it was evident that asbestos fibers were found in the following secured bulk samples: A- Category I Non - Friable Material: 1) Black A/C Duct Mastic: Black a/c mastic was found with 4 -5% Chrysotile fibers (see sample numbers 13, 14, 15, and attached sketch). Black a/c duct mastic is considered Category INon- Friable material this material is presently in s good condition and does not need to be removed; however; in the event of renovation; where the black a/c duct mastic's will be disturbed and removed, all work should be conducted by a Florida Licensed Asbestos Abatement Contractors under full supervision of a Florida Licensed Asbestos Consultant and in compliance with Federal, State and Local regulations. 750 West 84 Street, Hialeah, FL 33014 -3618 - Phone: (305) 828 -7499 - Fax: (305) 828 -9598 E -Mail: Dynatech @Bellsouth.net CO P,6,».. mow. P,,.,