14-428R-005Scope O CD 1. The fire alarm should be UL certificated. I I. All Alarm notification devices shall be audible and visual and shall be done via Strobe and /or Hornl5trobe combination devices. Strobes shall be with minimum intensity of 15 candelas as per 2. The Fire Alarm 5y5tem is designed for the "ChM of south Miami Interior renovation" located at 6350 5W 9 Article 18.5.4 of the NFPA 72 2010 Edition. 72nd street Miami, Florida 33143. Scope will be the installation of a new Fire Alarm System in a renovated ry office. 12. Horn/5trobe and Strobe devices shall be placed 80" (G' -8 ") to the bottom of lens above the The existing building is a 3 stones not spnnkled building. highest floor level within the space or G" below the ceiling whichever is lower as per article 18.5.4 of the NFPA 72 2010 Edition , 3. All equipment shall be new, U.L. Listed and Compatible. SECUR11Y SYSTEMS COPYRIGHT 02014 13. The distance from any place to a notification device shall not exceed 50'a5 per article 4.28 5. The installation of the Fire Alarm System shall also comply with the NFPA -70 National Electrical Code (NEC) (7) and (8) of the Flonda Acce5511216ty Code for Budding Construction. 201 1 edition and the Florida Accessibility Code For Building Construction. The installation shall also comply 14. Pull Stations and zone number shall be installed at 48" AFF to lever as per article 4.2.5 of the with NFPA -101, 2012 and NFPA -72, 2010. Florida Accessibility Code for Building Construction. G. The Fire Alarm System shall consist of an Automatic, Manual Fire Alarm Detection and Notification devices. 15. The location of the audible devices has been designed as to be effectively heard 15 dB above The Fire Alarm Control Panel shall be a new E5T 105OOGD ambient noise level obtained under normal condition of occupancy as per article 18.4.3.1 of the NFPA 72 2010 Edition, the NFPA 101 2012 Edition article 9.G.3 and the Florida Accessibility 7. All Fire Alarm equipment for this project shall be rated " POWER LIMITED " Code for Budding Construction and the Florida Budding Code. 8. The Fire Alarm Control Panel shall have a standby battery backup as per NFPA 72, 2010, Article I G. This design was based on calculations over a set of plans provided to the design engineer. If 10.5.G.3.1 providing battery power capacity for the entire system to operate for 24 hours the post installation on site tests conducted by the authority having junsdiction determine that, in normal mode and then, at the end of the period, for 5 minutes in the emergency mode. because unforeseen conditions or changes in field parameters, the audible alarm level falls below the required level in specific areas, the number of audible horn/strobes shall be mcreased to General Notes comply with the requirements and to the satisfaction of the authority having,lunsdiction I. Cable size shall comply \&nth article 7GO -179 and the cable installation shall comply with the separation and 17• Visible Signals shall not be required in Exit Stair Enclosures as per Article 9.6.3.5,5 of NFPA use of conductors and cables as specified in articles and 7GO -154 of the National Electrical Code. 101 2012 Edition. 18. This system will be Certificated or Placarded as a Central Station 5emce Fire Alarm System 2. Building wirng shall specifically confirm with the National Electrical Code article 7GO part III for and as stated as such on the Plans (24 hours of secondary power supply). Power- Limited Fire Protection Signal Circuits with emphasis on article 7GO- 130(8) relating to Power Limited Wiring Method and Materials. 3. MINIMUM CABLE 51ZE: A. # 18 AWG Copper (2 # 18 FPLP) for: Smoke Detectors, Duct Detectors, Pull Stations, Water 4l-J and Tamper Switches. o ° B. # 14 AWG Copper (2 # 14 FPLP) for: Horns, Strobes and Horn/5trobe5 notification devices. 4. All new wiring installed in ducts, plenums and other spaces used for environmental air shall be type FPLP, as per NEC (National Electrical Code) article 7GO -154. 5. The Design installation complies with FBC 11-4 -28.3. n G. Smoke Detectors shall be installed as per article 17.7.3.2 of NFPA 72, 2010 edition. 00 7. Fire wall penetrations shall have steel sleeves 8. Conduit fill shall not exceed 40% as per NEC (National Electrical Code) edition 201 1. •� 9. Conduit shall be a minimum of 3!4" . 10. The room containing the FACP and/or Power Supply (NAC) shall be Mechanically ventilated. i System No, W -L -3060 F Rating - 2 Hr T Rating - 0 Hr 1 ' CD CD CHECK BY: A.E. DATE: 9 -29 -14 System No, W -L -3065 F Ratings - I'and 2 Hr ( See Item I) T Rating - 0 Hr SECTION A -A 1. Wall Assembly -- The 1 or 2 fire -rated gypsum wallboard /stud wail assembly shall be constructed of the materials and in the manner specified in the individual U300 or U400 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following construction features: A. Studs -- Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. lumber spaced 16 in. OC. Steel studs to be min 2 -1/2 in . wide and spaced max 24 in. OC. B. Gypsum Board* -- Nom 5/8 in. thick gypsum wallboard, with square or tapered edges. The gypsum wallboard type, thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual U300 or U400 Series Designs in the UL Fire Resistance Directory, Max diam of opening is 4 in. The F Rating of the firestop system is equal to the fire rating of the wall assembly. 2. Metallic Sleeve -- (Optional) - Nom 4 in. diam (or smaller) steel electrical metallic tubing (EMT) or Schedule 5 (or heavier) steel pipe or min 0.016 in. thick (28 MSG) golv steel sleeve cast into wall assembly with joint compound and installed flush with wall surfaces. When Schedule 5 steel pipe or EMT is used, sleeve may extend up to 18 in. beyond the wall surfaces. Reproduced by HILTI, inc, Courtesy of Underwriters Lavatories, Inc, FIRESTOP SYSTEMS January 28, 2003 III Fire Alarm System 5ecpence Of Operation Automatic response functions shall be initiated only by the first fire alarm received. Additional alarms shall be received, annunciated and shall initiate functions associated exclusively with subsequent alarm. Common alarm function shall not be initiated unless the first alarm as returned to normal. The actuation of the fire alarm initiating device shall automatically initiate the function detailed below: A. MANUAL FiRE ALARM PULL 5TATION Activation of the Manual Fire Alarm Pull Station shall initiate the following functions: I. Generate an audible alarm signal at the Fire Alarm Control 2. Generate an audible alarm signal simultaneously on all areas of the building by means of a Horn devices. Generate a visual alarm signal simultaneously on all areas of the budding by the use of strobe devices or combination Horn/5trobe notification devices. 3. Indicate the location of the Pull Station by displaying, in English, the alarmed device and its location on the FACP alphanumeric display and on the Remote Annunciator alphanumeric display. 4. Transmit a fire alarm signal to the designated third party Lasted Central Station by way of DACT. B. SMOKE DETECTORS Activation of Smoke Detectors shall initiate the following functions: 1. Generate an Audible alarm signal at the Fire Alarm Control Panel and at the Remote Annunciator Panel 2. Generate an audible alarm signal simultaneously on all areas of the budding by means of a Horn devices. Generate a visual alarm signal simultaneously on all areas of the building by the use of strobe dunces or combination Horn/5trobe notification devices. 3. Indicate the location of the Smoke Detector by displaying, in English, the alarmed device and its location on the FACP alphanumeric display and on the Remote Annunciator alphanumeric display. 4. Transmit a fire alarm signal to the designated third party Lasted Central Station by way of DACT. C. DUCT DETECTOR5 Activation of Duct Detectors shall initiate the following functions: I . Generate a 5upem5ory signal at the Fire Alarm Control Panel and at the Remote Annunciator Panel. 2. Indicate the location of the Duct Detector by displaying, in English, the alarmed device and its location on the FACP alphanumeric display and on the Remote Annunciator alphanumeric display. 3. Transmit a 5upem5ory signal to the designated third party Listed Central Station by way of DACT. 4. Activation of a Duct Detector shall shut the WC unit associated with it down immediately, without delay. System No, W -L -3065 F Ratings - I and 2 Hr (See Item D T Rating - 0 Hr 3. Cables -- Aggregate cross - sectional area of cable in opening to be max 45 percent of the cross- sectionol area of the opening, The annular space between the cable bundle and the periphery of the opening to be min 1/4 in. to max 3/4 in. Cables to be rigidly supported on both sides of the wall assembly. Any combination of the following types and sizes of copper conductor cables may be used: A, Max 7/C No. 12 AWG with polyvinyl chloride (PVC) insulation and jacket, B. Max 25 pair No. 24 AWG telephone cable with PVC insulation and jacket. C. Type RG /U coaxial cable with polyethylene (PE) insulation and PVC jacket having a max outside diameter of % in. D. Multiple fiber optical communication cable jacketed with PVC and having a max OD of 5/8 in, I- Through Penetrating Products * -- Max three copper conductor No. 8 AWG . Metal -Clad Cable +, AFC CABLE SYSTEMS INC F. Max 3/C (with ground)(or smaller) No. 8 AWG copper conductor cable with PVC insulation and jacketing. 4. Fill, Void or Cavity Material* -- Sealant Fill material applied within the annulus, flush with each end of the steel sleeve or wall surface. Fill material installed symmetrically on both sides of the wall. A min 5/8 in. thickness of sealant is required for the 1 or 2 hr F Rating . An additional 1/2 in. diam bead of fill moterial shall be applied around the perimeter of sleeve on both sides of the wall when sleeve extends beyond surface of wall. HILTI CONSTRUCTION CHEMICALS, DIV OF HILT] INC -- CP601S, CP606 or FS -One Sealant *Bearing the UL Classification Mark �srFf�� a�@ Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc. FiRESTOP SYSTEMS January 28, 2W3 III E. TROUBLE Activation of the Trouble shall initiate the following functions: i . Generate an audible Trouble Signal at the fire Alarm control Panel and at the remote Annunciator Panel 2. Indicate the location of the Trouble by displaying, in English, the troubled device and its location on the FACP alphanumeric display and on the Remote Annunciator display. 3. Generate an audible Trouble Condition Signal at the fire Alarm control Panel and at the remote Annunciator Panel. 4. Indicate the location of the Trouble Condition by displaying, in English, the device and its location on the FACP alphanumeric display and on the Remote Annunciator display. 5. Transmit a Trouble signal to the designated third party Listed Central Station by way of DACT. The maximum time penod from actuation of the initiating device until initiation of all related functions as listed above shall be ten seconds. ALL INITIATING DEVICE CIRCUITS SHALL BE CLA55 B, STYLE B ALL NOTIFICATION APPLIANCE CIRCUITS SHALL BE CLA55 B, STYLE Y ALL 51GNALING LINE CIRCUIT5 SHALL BE CLA55 B, STYLE 4 • 6" BELOW CEILING 1 24" MIN HANDICAP BEDROOM STROBE SYNCHRONIZE MORE THAN TWO APPLIANCES ANY FIELD OF SYNCHRONIZED NFPA 72 2010 EDITION 80" MIN 96" MAX NFPA 72 2010 EDITION FINISHED FLOOR Fire Alarm System Sequence Of Operation Elevator Recall Automatic response functions shall be initiated only by the first fire alarm received. Additional alarms shall be received, annunciated and shall initiate functions associated exclusively with subsequent alarm. Common alarm function shall not be initiated unless the first alarrra is returned to normal. The actuation of the fire alarm initiating device shall automatically initiate the function detailed below: • An alarm condition on the budding fire alarm system and shall visible indicate, at the control unit and remote required annunciators as per NFPA 72 (edition 20 10) chapter 6.15.3.8. J. ELEVATOR RECALL a. Fire alarm initiating devices (smoke detectors) used to initiate Phase I Emergency Recall Operation shall be installed in conformance with the requirements of NFPA 72, and shall be located: a. at each floor served by the elevator. b. in the associated elevator machine room. Phase I Emergency Recall Operation (Garage Level): The activation of any fire alarm initiating device specified in (a,b) at any floor other than at the Garage Level, shall cause all elevators that serve that i floor to be returned nonstop to the Garage Level. Phase I Emergency Recall Operation (I st Fl. Level): The activation of any fire alarm initiating device at the Garage Level, shall cause all elevators serving that level to be recalled to an alternate level. Elevator Warning Lights: Actuation of any elevator machine room smoke detector shall also initiate the elevator warning lights to alert emergency personnel that the elevator are not safe for use as required in NFPA 72 (2010 edition) chapter G. 15.3.9. REV11�5ED ALL 5IGNALiNG LINE CIRCUIT5 5HALL BE CLA55 B, STYLE 4 ALL NOTIFICATION APPLIANCE CIRCUIT5 SHALL BE CLA55 B TAM-- ALL INITIATING DEVICE CIRCUIT5 SHALL BE CLA55 B AUDIO/VISUAL & VISUAL-ONLY #EVICES ACCEPTED HERE IMPORTANT O VERIFY EXACT REQUIREMENTS WITH MANUFACTURERS DATA SHEETS + o•• 0r- LESS 3" T 3JP i a 1XIMn. 21M, ii 0 /1 Illy"MMA s � MEASUREMENTS SHOWN R TO THE CLOSEST OF THE DETECTOR. a tlfliT�Titl{>A� CU5TOMER APPROVAL I have reviewed these plans and they conform to Accepted as is F-I our requirements, I understand that any modifications Accepted as noted ED to these plans will be an additional -service. Unaccepted ED �rt CD 1871 NW 7th S[reef 6Pari3 324.E � VP CP :' 3Q�x 13125 tf1 vcke rox 305324,0008 ry .'S INTEGRATED E mui = infoCrTeamiSS.cm M PROPRIETARY TO INFLGRATED SECUR11Y SYSTEMS COPYRIGHT 02014 System No, W -L -3065 F Ratings - I'and 2 Hr ( See Item I) T Rating - 0 Hr SECTION A -A 1. Wall Assembly -- The 1 or 2 fire -rated gypsum wallboard /stud wail assembly shall be constructed of the materials and in the manner specified in the individual U300 or U400 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following construction features: A. Studs -- Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. lumber spaced 16 in. OC. Steel studs to be min 2 -1/2 in . wide and spaced max 24 in. OC. B. Gypsum Board* -- Nom 5/8 in. thick gypsum wallboard, with square or tapered edges. The gypsum wallboard type, thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual U300 or U400 Series Designs in the UL Fire Resistance Directory, Max diam of opening is 4 in. The F Rating of the firestop system is equal to the fire rating of the wall assembly. 2. Metallic Sleeve -- (Optional) - Nom 4 in. diam (or smaller) steel electrical metallic tubing (EMT) or Schedule 5 (or heavier) steel pipe or min 0.016 in. thick (28 MSG) golv steel sleeve cast into wall assembly with joint compound and installed flush with wall surfaces. When Schedule 5 steel pipe or EMT is used, sleeve may extend up to 18 in. beyond the wall surfaces. Reproduced by HILTI, inc, Courtesy of Underwriters Lavatories, Inc, FIRESTOP SYSTEMS January 28, 2003 III Fire Alarm System 5ecpence Of Operation Automatic response functions shall be initiated only by the first fire alarm received. Additional alarms shall be received, annunciated and shall initiate functions associated exclusively with subsequent alarm. Common alarm function shall not be initiated unless the first alarm as returned to normal. The actuation of the fire alarm initiating device shall automatically initiate the function detailed below: A. MANUAL FiRE ALARM PULL 5TATION Activation of the Manual Fire Alarm Pull Station shall initiate the following functions: I. Generate an audible alarm signal at the Fire Alarm Control 2. Generate an audible alarm signal simultaneously on all areas of the building by means of a Horn devices. Generate a visual alarm signal simultaneously on all areas of the budding by the use of strobe devices or combination Horn/5trobe notification devices. 3. Indicate the location of the Pull Station by displaying, in English, the alarmed device and its location on the FACP alphanumeric display and on the Remote Annunciator alphanumeric display. 4. Transmit a fire alarm signal to the designated third party Lasted Central Station by way of DACT. B. SMOKE DETECTORS Activation of Smoke Detectors shall initiate the following functions: 1. Generate an Audible alarm signal at the Fire Alarm Control Panel and at the Remote Annunciator Panel 2. Generate an audible alarm signal simultaneously on all areas of the budding by means of a Horn devices. Generate a visual alarm signal simultaneously on all areas of the building by the use of strobe dunces or combination Horn/5trobe notification devices. 3. Indicate the location of the Smoke Detector by displaying, in English, the alarmed device and its location on the FACP alphanumeric display and on the Remote Annunciator alphanumeric display. 4. Transmit a fire alarm signal to the designated third party Lasted Central Station by way of DACT. C. DUCT DETECTOR5 Activation of Duct Detectors shall initiate the following functions: I . Generate a 5upem5ory signal at the Fire Alarm Control Panel and at the Remote Annunciator Panel. 2. Indicate the location of the Duct Detector by displaying, in English, the alarmed device and its location on the FACP alphanumeric display and on the Remote Annunciator alphanumeric display. 3. Transmit a 5upem5ory signal to the designated third party Listed Central Station by way of DACT. 4. Activation of a Duct Detector shall shut the WC unit associated with it down immediately, without delay. System No, W -L -3065 F Ratings - I and 2 Hr (See Item D T Rating - 0 Hr 3. Cables -- Aggregate cross - sectional area of cable in opening to be max 45 percent of the cross- sectionol area of the opening, The annular space between the cable bundle and the periphery of the opening to be min 1/4 in. to max 3/4 in. Cables to be rigidly supported on both sides of the wall assembly. Any combination of the following types and sizes of copper conductor cables may be used: A, Max 7/C No. 12 AWG with polyvinyl chloride (PVC) insulation and jacket, B. Max 25 pair No. 24 AWG telephone cable with PVC insulation and jacket. C. Type RG /U coaxial cable with polyethylene (PE) insulation and PVC jacket having a max outside diameter of % in. D. Multiple fiber optical communication cable jacketed with PVC and having a max OD of 5/8 in, I- Through Penetrating Products * -- Max three copper conductor No. 8 AWG . Metal -Clad Cable +, AFC CABLE SYSTEMS INC F. Max 3/C (with ground)(or smaller) No. 8 AWG copper conductor cable with PVC insulation and jacketing. 4. Fill, Void or Cavity Material* -- Sealant Fill material applied within the annulus, flush with each end of the steel sleeve or wall surface. Fill material installed symmetrically on both sides of the wall. A min 5/8 in. thickness of sealant is required for the 1 or 2 hr F Rating . An additional 1/2 in. diam bead of fill moterial shall be applied around the perimeter of sleeve on both sides of the wall when sleeve extends beyond surface of wall. HILTI CONSTRUCTION CHEMICALS, DIV OF HILT] INC -- CP601S, CP606 or FS -One Sealant *Bearing the UL Classification Mark �srFf�� a�@ Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc. FiRESTOP SYSTEMS January 28, 2W3 III E. TROUBLE Activation of the Trouble shall initiate the following functions: i . Generate an audible Trouble Signal at the fire Alarm control Panel and at the remote Annunciator Panel 2. Indicate the location of the Trouble by displaying, in English, the troubled device and its location on the FACP alphanumeric display and on the Remote Annunciator display. 3. Generate an audible Trouble Condition Signal at the fire Alarm control Panel and at the remote Annunciator Panel. 4. Indicate the location of the Trouble Condition by displaying, in English, the device and its location on the FACP alphanumeric display and on the Remote Annunciator display. 5. Transmit a Trouble signal to the designated third party Listed Central Station by way of DACT. The maximum time penod from actuation of the initiating device until initiation of all related functions as listed above shall be ten seconds. ALL INITIATING DEVICE CIRCUITS SHALL BE CLA55 B, STYLE B ALL NOTIFICATION APPLIANCE CIRCUITS SHALL BE CLA55 B, STYLE Y ALL 51GNALING LINE CIRCUIT5 SHALL BE CLA55 B, STYLE 4 • 6" BELOW CEILING 1 24" MIN HANDICAP BEDROOM STROBE SYNCHRONIZE MORE THAN TWO APPLIANCES ANY FIELD OF SYNCHRONIZED NFPA 72 2010 EDITION 80" MIN 96" MAX NFPA 72 2010 EDITION FINISHED FLOOR Fire Alarm System Sequence Of Operation Elevator Recall Automatic response functions shall be initiated only by the first fire alarm received. Additional alarms shall be received, annunciated and shall initiate functions associated exclusively with subsequent alarm. Common alarm function shall not be initiated unless the first alarrra is returned to normal. The actuation of the fire alarm initiating device shall automatically initiate the function detailed below: • An alarm condition on the budding fire alarm system and shall visible indicate, at the control unit and remote required annunciators as per NFPA 72 (edition 20 10) chapter 6.15.3.8. J. ELEVATOR RECALL a. Fire alarm initiating devices (smoke detectors) used to initiate Phase I Emergency Recall Operation shall be installed in conformance with the requirements of NFPA 72, and shall be located: a. at each floor served by the elevator. b. in the associated elevator machine room. Phase I Emergency Recall Operation (Garage Level): The activation of any fire alarm initiating device specified in (a,b) at any floor other than at the Garage Level, shall cause all elevators that serve that i floor to be returned nonstop to the Garage Level. Phase I Emergency Recall Operation (I st Fl. Level): The activation of any fire alarm initiating device at the Garage Level, shall cause all elevators serving that level to be recalled to an alternate level. Elevator Warning Lights: Actuation of any elevator machine room smoke detector shall also initiate the elevator warning lights to alert emergency personnel that the elevator are not safe for use as required in NFPA 72 (2010 edition) chapter G. 15.3.9. REV11�5ED ALL 5IGNALiNG LINE CIRCUIT5 5HALL BE CLA55 B, STYLE 4 ALL NOTIFICATION APPLIANCE CIRCUIT5 SHALL BE CLA55 B TAM-- ALL INITIATING DEVICE CIRCUIT5 SHALL BE CLA55 B AUDIO/VISUAL & VISUAL-ONLY #EVICES ACCEPTED HERE IMPORTANT O VERIFY EXACT REQUIREMENTS WITH MANUFACTURERS DATA SHEETS + o•• 0r- LESS 3" T 3JP i a 1XIMn. 21M, ii 0 /1 Illy"MMA s � MEASUREMENTS SHOWN R TO THE CLOSEST OF THE DETECTOR. a tlfliT�Titl{>A� CU5TOMER APPROVAL I have reviewed these plans and they conform to Accepted as is F-I our requirements, I understand that any modifications Accepted as noted ED to these plans will be an additional -service. Unaccepted ED �rt CD afi -A ry a M E ; cry U v � W E L 4­0 O M a °- Sheet Number FA03 of 04 C- 4­0 3 4l-J M M o ° V } 00 n 0 00 •� i Ln CD Cn o LL. Z •= rn CD � MCo Z> Q UJ Wm F-~ ED<M )- Ix M 0k W� Ln,-. �R m <C O 0 } u_ 10 LL_ z d LU p � � n U U m U CD afi a a a M ; cry v � � O a °- Sheet Number FA03 of 04