Loading...
14-428-002NQTI !rl n ve by Hort"well FCPS -24s8 Power Supply Protected Premises: CHI SOUTH MIAMI Date: 3/1812014 Address: 6350 SW 72ND STREET City. South Miami State: FL Zip: 33143 Clear Project lnbrmation' AC Branch Current Requirements FT.2-0-1 AMPS @ 120 VAC .H cheek Current required by source to powerthe fire alarm system. Primary Standby Load 0.09 Amps Check Current load on the primary power supply during non -alarm conditions. Primary Alarm Load 3.71 Amps check Current load on the primary power supply during alarm conditions. Secondary Load Requirements 2.25 Amp Hours check Total Secondary Load from the calculation table below. Current tr 3/18/2014 + Secondary Standby Load Required Standby Time Use yellow cells to enter quantities and current values. 0.065 A x 24 hours 1.56 Secondary Alarm Load Required Alarm Time (hours) C2 3.711 A To clear selected devices. select "Clear Selections ". 3.711 A x 0.084 hours 0.31 _ Total Secondary Load 1.87 CIRCUrr OUTPUT VOLTAGE= 20.4 OR CALCULATIONS rc USA C Canada Derating factor x 1.2 SR75 0.158 Secondary Load Requirements 2.25 Battery Selection r� Amp Hours check Select batteries from the list below. 7 AH BAT 1270 Battery (12,voR) r, Two 0 Four (two 12VDC sets in parallel) tJ NOTI VIKW AH CHI SOUTH MIAMI 3/18/2014 Select devices using the "Qty" column. NAC #1 NAC SCHEDULE / VOLTAGE DROP CALCULATION Use yellow cells to enter quantities and current values. /CURRENT DRAW VOLTAGE DROP TOTALS C11 0.091 A To` show only selected devices, select "Show Selected Devices ". ESTIMATED 75M H/S C2 3.711 A To clear selected devices. select "Clear Selections ". TOTAL WIRE C3 0.065 A _ TOTAL t Clear Selections ? Show Selected DWces I Show All Deuces CIRCUrr OUTPUT VOLTAGE= 20.4 OR CALCULATIONS CIRCUIT LENGTH FCPS- 24SO Main Circuit Board 1 x 0.09100 0.09100 1 x I Q14500 0.14500 1 x' a06500 0.06 0 SR75 0.158 C KE LOAD AMPS - § P0175 ! 5 - x 0.00000 0.00000 5 x I all 7600 0.88000 5 x 0.00000 0.00000 VOLTAGE DROP % VOLTAGE DROP (VOLTS) SR75 17' x 0.00000 0.00000 17 x 015800 2.68600 17 x I 0.00000 0.00000 ALLOWABLE CKT. LENGTH NAC # & output #. Total Non- Total Alarm Total Standby 0.091 3.71 i 0.065 CKT# N3-1 HomlStrobes Alarm Lo a d: Load: Load: CHI SOUTH MIAMI 3/18/2014 FCPS 24S8 NAC #1 NAC SCHEDULE / VOLTAGE DROP CALCULATION APPLIANCE QUANTITIES /CURRENT DRAW VOLTAGE DROP TOTALS 17 % MAXb11IJM VOLTAGE DROP ESTIMATED 75M H/S 75CD STROBE TOTAL WIRE ACTUAL ACTUAL TOTAL MAXIMUM CIRCUrr OUTPUT VOLTAGE= 20.4 OR CALCULATIONS CIRCUIT LENGTH P2R75 0.176 SR75 0.158 C KE LOAD AMPS GAUGE 18, 16, 14, 12 VOLTAGE DROP % VOLTAGE DROP (VOLTS) CIRCUIT RESISTANCE ALLOWABLE CKT. LENGTH NAC # & output #. DESCRIPTION CKT# N3-1 HomlStrobes 175 IL 2 9 1.774 16 14.88% 3.036 1.7 Ohms 235 ft. CKT# N3-2 Horn/Strobes 175 ft. 3 8 1.792 16 15.03% 3.067 1.7 Ohms 233 tt. CKT# N3-3 SPARE ft. 1 0.000 14 0.00% 0.000 0.0 Ohms 0 ft. CKT# N34 SPARE ft. U 1 0.000 14 0.00% 0.000 0.0 Cams 0 ft. U Appliance Summa Total Load (AMPS) Max Load (AMPS) Max Load (AMPS) Per Circuit 5 r 17 1 3.566 1 6.000 1 3.000 Wire Resistance At W 75 Degrees Celsius METHOD USED TO CALCULATE PERCENT OF VOLTAGE DROP: Ohm11000 ft j(CIRCUR LENGTH IN FEET X2) (AMPS X OHMS/FOOT)] X 100 10GA = 121 20.4 VOLTS � 12GA = '11.93 14GA =13.07 Q Z Z 16GA = r4.89 4'. W Lt 1 8G = F7.77 WIRE RESISTANCE BASED ON TABLE 8 FROM NATIONAL ELECTRICAL CODE (UNCOATED SOLID COPPER WIRE) NOTE: LUMP SUM METHOD WAS USED TO CALCULATE ALLOWABLE VOLTAGE DROP. THIS METHOD ALLOWS FOR A SMALL MARGIN Z OF SAFETY, TAKING KrO CONSIDERATION THE ACTUAL INSTALLED CIRCUIT ROUTING MAY DIFFER FROM WHAT IS SHOWN Rg�Q ON THE SHOP DRAWINGS. IF THE ACTUAL CIRCUIT LENGTH IS GOING TO E)CEED THE M MMUM ALLOWABLE CIRCUIT S g1 (!) LENGTH, CONTACT THE FIRE ALARM CONTRACTOR 5 =15 LU FIRE ALARM GENERAL NOTES 1. EXISTING SIMPLEX 4001 FIRE ALARM PANEL IS POWER LIMITED AND HAVE BATTERY BACKUP. 2. BUILDING IS EXISTING 3. BUILDING IS NOT SPRINKLERED. 4. OCCUPANCY: EXISTING HEALTHCARE PROPOSED S.F.: APPROX. 4,451 S.F. BUILDING HAS 2 FLOORS FLOOR ELEV.: SEE PLAN SYSTEM AND INSTALLATION TO COMPLY WITH: FLORIDA FIRE PREVENTION CODE (FFPC) 2010 FLORIDA BUILDING CODE (FBC) 2010 NFPA 1, 2009 "FIRE CODE" NFPA 101, 2009 "LIFE SAFETY CODE" NFPA -72 2007 EDITION "NATIONAL FIRE ALARM CODE" NFPA -70 2008 EDITION "NATIONAL ELECTRICAL CODE" 5. WIRING MINIMUMS: INITIATING CIRCUITS 18/2 FPL INDICATING CIRCUITS 14/2 FPL (NAC) 6. CONDUIT IF REQUIRED WILL MINIMUM 1/2 MINIMUM 40% FILL MAX. 7. ALL DEVICES TO BE MOUNTED PER NFPA GUIDELINES OR ADA WHERE REQUIRED. 8. SYSTEM COMPONENTS SHALL BE U.L. LISTED AND COMPATIBLE. 9. CIRCUITS TO BE CLASS B. 10. WHERE AUDIBLE APPLIANCES ARE INSTALLED, THEY SHALL HAVE A SOUND LEVEL OF AT LEAST 15db ABOVE THE AVERAGE AMBIENT SOUND LEVEL OR 5db ABOVE THE MAXIMUM SOUND LEVEL, HAVING A DURATION OF AT LEAST 60 SECONDS MEASURED 5 FEET ABOVE THOUGHOUT ALL OCCUPIED AREAS. CONTRACTOR WILL CERTIFY THE DBA LEVEL WITH AN APPROVED DBA METER PRIOR TO THE ISSUANCE OF THE CERTIFICATE OF OCCUPANCY. 11. AUDIBLE RATINGS, AS MEASURED BY THE MANUFACTURER AND THE QUALIFIED TESTING LABS, ARE SPECIFIED AS A DECIBEL RATING AT A PREDETERMINED DISTANCE, USUALLY 10 FEET. THE RULE OF THUMB IS THAT THE OUTPUT OF AN AUDIBLE NOTIFICATION APPLIANCE IS REDUCED BY 6dB IF THE DISTANCE BETWEEN THE APPLICANCE AND LISTENER IS DOUBLED. 12. THE DESIGN INSTALLATION COMPLIES WITH FBC 2010. 13. INITIATING DEVICES ARE CLASS 'B', STYLE W. NOTIFICATION CIRCUITS ARE CLASS 'B', STYLE Y. FIRE ALARM SYSTEM SEQUENCE OF OPERATION, THE ACTUATION OF THE FIRE ALARM INITIATING DEVICES SHALL AUTOMATICALLY INITIATE THE FOLLOWING FUNCTIONS THROUGHOUT THE BUILDING: SYSTEM IS "GENERAL ALARM". FOR ANY INCIDENCE: IS GOING TO ANNUNCIATE THE "ALARM, TROUBLE OR SUPERVISORY" SIGNAL AT FACP AND REMOTE ANNUNCIATOR., FOR ANY INCIDENCE: TRANSMIT THE ALARM, TROUBLE OR SUPERVISORY" SIGNAL TO THE LISTED CENTRAL STATION. A. MANUAL FIRE ALARM PULL STATION: ACTIVATION OF THE MANUAL PULL STATION SHALL INITIATE THE FOLLOWING FUNCTIONS: 1. GENERATE AN AUDIBLE ALARM SIGNAL AT THE FIRE ALARM CONTROL PANEL AND REMOTE ANNUNCIATORS. 2. GENERATE AN AUDIOVISUAL SIGNAL SIMULTANEOUSLY THROUGHOUT THE BUILDING BY THE USE OF STROBES AND/OR COMBINATION OF HORN /STROBES APPLIANCES. 3. INDICATE THE LOCATION OF THE PULL STATION BY DISPLAYING THE ALARMED DEVICE ON THE FACP LCD DISPLAY AND ON THE REMOTE ANNUNCIATOR. B. SMOKE DETECTORS: ACTIVATION OF SMOKE DETECTORS SHALL INITIATE THE FOLLOWING FUNCTIONS: 1. GENERATE AN AUDIBLE ALARM SIGNAL AT THE FIRE ALARM CONTROL PANEL AND REMOTE ANNUNCIATORS. 2. GENERATE AN AUDIO VISUAL SIGNAL SIMULTANEOUSLY THROUGHOUT THE BUILDING BY THE USE OF STROBES AND/OR COMBINATION OF HORWSTROBES APPLIANCES. 3. INDICATE THE LOCATION OF THE SMOKE DETECTOR BY DISPLAYING THE ALARMED DEVICE ON THE FACP LCD DISPLAY AND ON THE REMOTE ANNUNCIATOR. C. ELEVATOR LOBBY SMOKE AND/OR HEAT DETECTORS. 1- ACTIVATION OF ANY SINGLE ELEVATOR LOBBY SMOKE DETECTOR SHALL INITIATE THE FOLLOWING FUNCTIONS: 2- GENERATE AN AUDIBLE ALARM SIGNAL AT THE FIRE ALARM CONTROL PANEL AND REMOTE ANNUNCIATORS. 3- GENERATE AN AUDIO VISUAL ALARM SIGNAL SIMULTANEOUSLY THROUGHOUT THE BUILDING BY THE USE OF STROBES AND/OR COMBINATION OF HORN /STROBES APPLIANCES. 4 INDICATE THE LOCATION OF THE SMOKE DETECTOR BY DISPLAYING THE ALARMED DEVICE AND ITS LOCATION ON THE FACP ALPHANUMERIC DISPLAYAND ON THE REMOTE ANNUNCIATORS. 5- INITIATE THE AUTOMATIC ELEVATOR RECALL FUNCTION AS FOLLOW a) IF THE FIRST FLOOR ELEVATOR LOBBY SMOKE DETECTOR GOES OFF IN ALARM, RECALL IS GOING TO SEND ELEVATOR CAB TO THE ALTERNATE OR SECOND FLOOR. b) IF ANY FLOOR ELEVATOR LOBBY SMOKE DETECTOR OTHER THAN THE FISRT FLOOR, GOES OFF IN ALARM, RECALL IS GOING TO SEND ELEVATOR CAB TO THE FIRST FLOOR. D. ELEVATOR HOIST WAY AND MACHINERY ROOM SMOKE AND/OR HEAT DETECTORS AND SHUNT -TRIP POWER MONITORING. ACTIVATION OF ANY HOISTWAY OR ELEVATOR MECHANICAL ROOM SMOKE DETECTORS ARE GOING TO PERFORM ALL STEPS DESCRIBED ON "C" ABOVE AND: 1- ACTIVATION OF ANY HOISTWAY OR ELEVATOR MECHANICAL ROOM SMOKE DETECTORS ARE GOING TO ACTIVATE THE ELEVATOR WARNING LIGHT RELAY AND THE ELEVATOR WARNING LIGHT IS GOING TO FLASH INDICATING NOT TO USE ELEVATORS. SHUNT -TRIP POWER MONITORING: - CONTROL CIRCUITS TO SHUTDOWN ELEVATOR POWER IS MONITORED FOR PRESENCE OF OPERATING VOLTAGE. LOSS OF VOLTAGE TO THE CONTROL CIRCUIT FOR THE DISCONNECTING MEANS SHALL CAUSE A SUPERVISORY SIGNAL TO BE INDICATED AT THE MAIN "FACP" AND THE REMOTE ANNUNCIATOR. MECHANICAL HEAT DETECTORS: 1- MECHANICAL HEAT DETECTORS LOCATED IN THE ELEVATOR MECHANICAL ROOM AND AT TOP OF ELEVATOR SHAFT, IF ACTIVATED ARE GOING TO SEND AND ALARM SIGNAL TO THE FACP BY THE ADDRESSABLE MONITOR MODULE INTERCONNECTED TO IT. 2- INDICATE THE LOCATION OF THE HEAT DETECTOR BY DISPLAYING THE ALARMED DEVICE AND ITS LOCATION ON THE FACP ALPHANUMERIC DISPLAY AND ON THE REMOTE ANNUNCIATORS. 3- MECHANICAL HEAT DETECTORS LOCATED IN THE ELEVATOR MECHANICAL ROOM AND AT TOP OF ELEVATOR SHAFT, IF ACTIVATED ARE GOING TO ACTIVATE THE SHUNT -TRIP BREAKER, DISCONNECTING MAIN POWER TO ELEVATORS CONTROLLER. E. WATER FLOWSWITCHES: IN NO CASE "WATERFLOW ALARM' CAN BE SILENCE WHILE WATER IS FLOVMNG. NOTE: INITIATION OF THE ALARM SIGNAL SHALL OCCUR WITHIN 90 SECONDS OF WATERFLOWAT THE ALARM- INITIATING DEVICE WHEN FLOW OCCURS. ACTIVATION OF WATER FLOW SWITCHES SHALL INITIATE THE FOLLOWING FUNCTIONS 1. GENERATE AN AUDIBLE ALARM SIGNAL AT THE FIRE ALARM CONTROL PANEL AND REMOTE ANNUNCIATORS. 2. GENERATE A AUDIOVISUAL SIGNAL SIMULTANEOUSLY THROUGHOUT THE BUILDING BY THE USE OF STROBES AND/OR COMBINATION OF HOR WSTROBES APPLIANCES. 3. INDICATE THE LOCATION OF THE WATER FLOW SWITCH BY DISPLAYING THE ALARMED DEVICE ON THE FACP LCD DISPLAY AND ON THE REMOTE ANNUNCIATOR. F. TAMPER SWITCHES (VALVES): ACTIVATION OF TAMPER SWITCHES SHALL INITIATE THE FOLLOWING FUNCTIONS 1. GENERATE AN AUDIBLE SUPERVISORY SIGNALAT THE FIRE ALARM CONTROL PANEL AND REMOTE ANNUNCIATORS. 2. INDICATE THE LOCATION OF THE TAMPER SWITCH BY DISPLAYING ITS LOCATION ON THE FACP LCD DISPLAY AND ON THE REMOTE ANNUNCIATOR. G. 'TROUBLE" CONDITION. 1. GENERATE AN AUDIBLE TROUBLE SIGNAL AT THE FIRE ALARM CONTROL PANEL IF ANY OPEN, SHORT OR GROUND CIRCUIT OCCUR IN WIRING. DUCT DETECTORS ALSO REPORT A TROUBLE SIGNAL AT FACP IF ACTIVATED. QA M I A W -WADE CC'3 $N7 -Y FIrRE D PAPT1IiEl` BiDC4.i° t." i ALARM, F'.RESUPP _0^ 11� fx EEc DATIE: `7 ('� f }'1 era. FTRE ALARM SYSTEM TO BE (NSTA 1E33 H4 ACCC ANCE V`M'h NFPA 72-,70,- 101 FIRE ALAI fM SHALL 13E A CENTRAL STATiO N SERVICE. A CEIRTiFICATC- OR PLACARD SHALL BE POSTED AT FINAL INSPECTION, AS PER NFPA 72 REV[ IONS M t Q t) Ch _ Q _ O LL lO LO Q M � Co U o I"- W U W O W 12 W � Q Z Z Q J 4'. W Lt D Z Z Rg�Q N S g1 (!) G7 Cf) 5 =15 LU a 4 H N 88 ts .40 Q H M W � 15 = o W cM ° °4 Z u CO ;1 foij FL O W 0 0 l0 6 N I- Z Q N N o :5 5W WW Q LO w 8 _ �j W �$ G W ° 6 K W I- U .2 - a 0 6 CL Z " 06° e� C00 �44 0: e O @ m IS U I-- � tH Z O U 6 2 p s w e: ° Ld an m iZ aD to S s LuelCDR a F- Q: 1L U U O n m _ C, ca W z 0: z X z l Q y C& O U1 z U W O W Q a p z DATE: 03 -18 -2014 SCALE: SEE PLAN' DRAWN BY: M.S. CHECKED BY: R.G. SHEET FA- 2 OF 2