11-481R-001ELECTRICAL LEGEND
0 EXHAUST FAN
_(� LIGHT FIXTURE
ELECTRICAL DEMOLITION PLAN
SCALE: 1/ " =1' -011
LIGHT COLOR DENOTES EXISTING ELECTRICAL ITEMS TO REMAIN AS IS.
DARK COLOR DENOTES EXISTING ELECTRICAL ITEMS TO BE DEMOLISHED.
N TELEPHONE
O JUNCTION BOX
GFI GROUND -FAULT INTERRUPTER
QUADRUPLE RECEPTACLE
MOUNTED 18" AFF U.O.N.
O ELECTRICAL METER
GENERAL DEMOLITION NOTES:
1. WHERE ELECTRIC LIGHTING FIXTURES, SWITCHES, RECEPTACLES;" BOXES, _ -- - - -- -
CABINETS, DEVICES, ETC. ARE TO BE REMOVED, AND BOXES AND- CONDUITS ARE o N
TO REMAIN, ALL CONDUCTORS SHALL BE DE— ENERGIZED, DISCONNECTED AT BOTH J
ENDS, REVERSED INTO THE BOX,- AND THE BOX PLUGGED WITH CEMENT PLASTER pro=
OR OTHER APPROVED MATERIAL AND THE WALL, FLOOR, - CEILING -AND THE LIKE, z_ 'yi<
RESTORED TO MATCH THE SURROUNDING FINISH TO THE SATISFACTION OF THE
OWNER. WHERE ANY MECHANICAL ITEMS ARE TO BE REMOVED, ALL ABOVE w
FINISHES ARE TO BE RESTORED. o;
2. WHERE ELECTRICAL FIXTURES, SWITCHES, OUTLETS, RECEPTACLES, BOXES, w �••'•,••� ���v�
CABINETS, DEVICES, ETC. ARE TO BE REMOVED, AND THEIR REMOVAL AFFECTS J * •z�••' �?;
THE OPERATION OF ANY EQUIPMENT, FIXTURE, RECEPTACLES, ETC. THAT IS TO a ��';�,.
REMAIN (INCLUDING ITEMS THAT MAY NOT BE SHOWN IN THE DRAWINGS BUT ARE o Q a .4-0
t Do
PRESENTLY EXISTING IN PLACE) THE CONTRACTOR SHALL RECIRCUIT THEM Cn L� ri
(INCLUDING BOXES, CONDUIT, WIRES, ETC.) TO RESTORE THEM TO THE LL,_I ° a-
ORIGINAL OPERATING CONDITION, ALL AT NO ADDITIONAL COST TO THE OWNER. 0 LrJ
o � o
° Q
3. UNUSED OPENINGS IN BOXES, CABINETS, PANEL BOARDS, ROOFS, ETC., r2 < ¢ vi =
WHERE SOMETHING IS REMOVED OR PREVIOUSLY EXISTED —SHALL BE PLUGGED OR LL_ E ,n ••
BLANKED OUT BY APPROVED METHODS, IF THE -- OPENING IS TO REMAIN. w Q N Q w
4. ALL EXPOSED CONDUIT, WIRES, OUTLETS, ETC. NOT TO BE REUSED IN THE NEW 0 w :2
O U
REMODELED LAYOUT, SHALL BE REMOVED. J
............ ...............................
5. EXISTING PIPE OR CONDUIT RUNS, STUBBING UP THRU FLOORS, IN AREAS WHERE
WALLS ARE TO BE REMOVED, SHALL HAVE THEIR CONDUCTORS DE— ENERGIZED AND
REMOVED, CONDUIT CUT —OFF GROUND FLUSH WITH FLOOR AND PLUGGED WITH
CEMENT MORTAR OR ANY OTHER APPROVED MATERIAL THE SAME APPLIES WITH
EXISTING CONDUITS OR PIPES THAT ARE STUBBED OUT OF WALLS AND FLOORS.
6. WHERE PRACTICAL, EXISTING CONDUCTORS AND WIRES THAT ARE IN GOOD
CONDITION, MAY BE REUSED IN PLACE AND INCORPORATED IN THE NEW
REMODELED LAYOUT, PROVIDED IT IS OF PROPER SIZE, TYPE OF CONDUCTOR
AND WITH THE APPROVAL OF THE OWNER.
7. ABANDONED CIRCUIT CONDUCTORS IN PANELBOARDS, SHALL BE DISCONNECTED,
TAPED AND IDENTIFIED.
8. SALVAGED ITEMS SHALL BE RETURNED TO THE OWNER, AND DELIVERED WHERE
DIRECTED BY HIM. ITEMS AND MATERIALS CONSIDERED UNSALVAGEABLE BY THE
OWNER, SHALL BE DISPOSED OF AS DIRECTED BY THE OWNER. REMOVED WALL
SWITCHES, DIFFUSERS, RECEPTACLES AND LIGHTING OR PLUMBING FIXTURES
SHALL NOT BE REUSED IN NEW CONSTRUCTION.
9. ALL ROOF OPENINGS OR WALL OPENINGS WHERE MECHANICAL OR ELECTRICAL
DEVICES OR OTHER ITEMS ARE TO BE REMOVED SHALL BE RESTORED AND
FINISHED TO A FINAL FINISH, AND WATER PROOFED.
GENERAL ELECTRICAL NOTES
1 . ALL WORK SHALL BE IN ACCORDANCE WITH NATIONAL ELECTRICAL CODE,
FLORIDA BUILDING CODE AND OTHER APPLICABLE CODES AND STANDARDS.
2 . a) THE DRAWINGS ARE DIAGRAMMATIC AND DO NOT SHOW ALL OFFSETS, BENDS AND
BOXES REQUIRED TO MAKE A COMPLETE NEAT INSTALLATION IN ACCORDANCE WITH
N.E.C.
b) WHEN CONFLICTS ARISE IN LOCATIONS WIRING DEVICES, ELECTRICAL EQUIPMENT,
DISCONNECTS, PANELBOARDS, ETC. DUE TO FIELD CONDITION OR IMPROPER FIELD
COORDINATION CONTRACTOR SHALL BRING IT TO THE A / E's ATTENTION AND AT NO
EXTRA COST RELOCATE, AND OR EXTEND WITHIN A REASONABLE DISTANCE SUCH ITEM
WHICH IS IN CONFLICT. THE CONTRACTOR IS RESPONSIBLE FOR COORDINATING
LOCATION OF ALL COMPONENT PRIOR TO ROUGH IN WITH ALL TRADES NO EXTRAS WILL
BE ALLOWED FOR FAILURE TO DO SO.
3 . THE CONTRACTOR IS RESPONSIBLE FOR EVALUATING FIELD CONDITIONS BY VISITING
THE SITE PRIOR TO COMMENCING / BIDDING WORK.
4 . THE CONTRACTOR SHALL SATISFACTORILY REPAIR /REPLACE EQUIPMENT OR PART OF
STRUCTURE DAMAGED AS A RESULT OF HIS WORK. SURFACES AND FINISHED AREAS
SHALL BE RESTORED TO MATCH ADJACENT AREAS.
5 . APPROVAL SHALL BE OBTAINED FROM AN STRUCTURAL ENGINEER PRIOR TO CUTTING
OR DRILLING ANY STRUCTURAL SUPPORT MEMBER.
6 . ALL DEVICE BOXES SHALL BE INSTALLED FLUSH AND CONDUITS RUN CONCEALED IN
FINISHED AREAS EXCEPT AS SPECIFICALLY SHOWN /NOTED OTHERWISE.
7 . ALL ELECTRICAL EQUIPMENT SHALL BE REMOVED FROM STRUCTURE TO BE REMOVED.
ACCESSIBLE RACEWAYS, WIRES, BOXES, SWITCHES AND OTHER ELECTRICAL ITEMS
ASSOCIATED WITH THIS WORK SHALL BE REMOVED IF NOT REQUIRED FOR NEW
EQUIPMENT TO CONTINUE IN SERVICE.
8 . WIRE SHALL BE REMOVED BACK TO SOURCE FROM INACCESSIBLE RACEWAYS NOT
REUSED. INSTALL BLANK PLATES ON FLUSH OUTLETS NOT REUSED. PLATE
COLOR SHALL MATCH ADJACENT SURFACE AS NEAR AS POSSIBLE IN FINISHED
AREAS.
9 . INSTALL POWER AND CONTROL WIRING AND REQUIRED CONTROL COMPONENTS FOR
AIR CONDITIONING SYSTEMS AS SHOWN /NOTED ON THESE DRAWINGS AND PER OTHER
APPLICABLE DRAWINGS / INSTRUCTIONS. SEE AIR CONDITIONING DRAWING.
10 . ALL MATERIAL REMOVED SHALL BE DISPOSED OF AS DIRECTED BY OWNER.
11 . WIRE SIZE SHALL BE 12 THHN / THWN UNLESS OTHERWISE NOTED ON PLANS.
14 ALL WIRES SHALL BE THWN. INSULATION.
15 . ALL CONDUCTOR SHALL BE COPPER.
16 . ALL CONDUCTORS SHALL BE RUN IN CONDUIT (METALLIC TYPE). IF PVC SCHEDULE 40
IS USED FOR UNDERGROUND FEEDERS ONLY, AN EQUIPMENT GROUND CONDUCTOR
SIZED IN ACCORDANCE WITH N.E.C. 250 -122 MUST BE INSTALLED AND CONDUIT SIZE
INCREASE AS REQUIRED.
17 . ALL MATERIALS SHALL BE U.L. APPROVED.
18 NEW TYPEWRITTEN PANEL TALLY SHALL BE FURNISHED AFTER JOB IN COMPLETED
REFLECTING ALL CHANGES AND ADDITIONS.
19 . ALL BRANCH CIRCUITS SHALL BE PROPERLY PHASE BALANCED.
20 SEE ARCHITECTURAL DRAWING FOR INFORMATION CONCERNING EXISTING CONDITIONS,
NEW WORK AND COUNTER DETAILS.
21 ALL WIRING DEVICES TO BE SPECIFICATION GRADE WITH HIGH ABUSE NYLON COVER
PLATES EQUAL TO LEVITON 53500 SERIES (SWITCHES); 5252 SERIES (RECEPTACLES).
22 ALL BRANCH CIRCUITS TO HAVE A GREEN EQUIPMENT GROUNDING CONDUCTOR SIZED
AS PER N.E.C. 250.122.
23 . FUSES SHALL BE DUAL ELEMENT, TIME DELAY TYPE UNLESS OTHERWISE NOTED.
24 . A/C EQUIPMENT WIRING, BREAKER AND FUSE SIZES ARE BASED ON A/C EQUIPMENT
SPECIFIED ON CONTRACT DRAWING. CONTRACTOR IS RESPONSIBLE FOR PROVIDING ALL
WIRING, BREAKER AND FUSES SIZES IN ACCORDANCE WITH A/C EQUIPMENT NAMEPLATE
REQUIREMENTS IF DIFFERENT FROM THAT SPECIFIED ON DRAWINGS, AS WELL AS ANY
FEEDER CHANGES BEING AFFECTED BY THIS CHANGE CONTRACTOR SHALL MAKE
ABOVE MENTIONED CHANGES AT NO EXTRA COST.
25 . CONTRACTOR SHALL COORDINATE ALL HIS WORK WITH OTHER TRADES IN OTHER TO
FURNISH AND INSTALL ALL CONTROL WIRING AND RACEWAYS, ALL POWER CONTROL
CIRCUIT WIRING AND RACEWAY AS SHOWN ON THE AIR CONDITIONING DRAWING OR
SPECIFICATIONS. IF AIR CONDITIONING IF DRAWING REFER TO MANUFACTURERS
WIRING DIAGRAMS, THE CONTRACTOR SHALL VERIFY WITH SAID MANUFACTURER ALL
REQUIREMENTS AND INCLUDE ALL RELATED WORK IN HIS CONTRACT.
26
SWITCH
®=
DUPLEX RECEPTACLE
NP
WEATHER -PROOF
B
ELECTRIC PANEL
L❑
DISCONNECT
0 EXHAUST FAN
_(� LIGHT FIXTURE
ELECTRICAL DEMOLITION PLAN
SCALE: 1/ " =1' -011
LIGHT COLOR DENOTES EXISTING ELECTRICAL ITEMS TO REMAIN AS IS.
DARK COLOR DENOTES EXISTING ELECTRICAL ITEMS TO BE DEMOLISHED.
N TELEPHONE
O JUNCTION BOX
GFI GROUND -FAULT INTERRUPTER
QUADRUPLE RECEPTACLE
MOUNTED 18" AFF U.O.N.
O ELECTRICAL METER
GENERAL DEMOLITION NOTES:
1. WHERE ELECTRIC LIGHTING FIXTURES, SWITCHES, RECEPTACLES;" BOXES, _ -- - - -- -
CABINETS, DEVICES, ETC. ARE TO BE REMOVED, AND BOXES AND- CONDUITS ARE o N
TO REMAIN, ALL CONDUCTORS SHALL BE DE— ENERGIZED, DISCONNECTED AT BOTH J
ENDS, REVERSED INTO THE BOX,- AND THE BOX PLUGGED WITH CEMENT PLASTER pro=
OR OTHER APPROVED MATERIAL AND THE WALL, FLOOR, - CEILING -AND THE LIKE, z_ 'yi<
RESTORED TO MATCH THE SURROUNDING FINISH TO THE SATISFACTION OF THE
OWNER. WHERE ANY MECHANICAL ITEMS ARE TO BE REMOVED, ALL ABOVE w
FINISHES ARE TO BE RESTORED. o;
2. WHERE ELECTRICAL FIXTURES, SWITCHES, OUTLETS, RECEPTACLES, BOXES, w �••'•,••� ���v�
CABINETS, DEVICES, ETC. ARE TO BE REMOVED, AND THEIR REMOVAL AFFECTS J * •z�••' �?;
THE OPERATION OF ANY EQUIPMENT, FIXTURE, RECEPTACLES, ETC. THAT IS TO a ��';�,.
REMAIN (INCLUDING ITEMS THAT MAY NOT BE SHOWN IN THE DRAWINGS BUT ARE o Q a .4-0
t Do
PRESENTLY EXISTING IN PLACE) THE CONTRACTOR SHALL RECIRCUIT THEM Cn L� ri
(INCLUDING BOXES, CONDUIT, WIRES, ETC.) TO RESTORE THEM TO THE LL,_I ° a-
ORIGINAL OPERATING CONDITION, ALL AT NO ADDITIONAL COST TO THE OWNER. 0 LrJ
o � o
° Q
3. UNUSED OPENINGS IN BOXES, CABINETS, PANEL BOARDS, ROOFS, ETC., r2 < ¢ vi =
WHERE SOMETHING IS REMOVED OR PREVIOUSLY EXISTED —SHALL BE PLUGGED OR LL_ E ,n ••
BLANKED OUT BY APPROVED METHODS, IF THE -- OPENING IS TO REMAIN. w Q N Q w
4. ALL EXPOSED CONDUIT, WIRES, OUTLETS, ETC. NOT TO BE REUSED IN THE NEW 0 w :2
O U
REMODELED LAYOUT, SHALL BE REMOVED. J
............ ...............................
5. EXISTING PIPE OR CONDUIT RUNS, STUBBING UP THRU FLOORS, IN AREAS WHERE
WALLS ARE TO BE REMOVED, SHALL HAVE THEIR CONDUCTORS DE— ENERGIZED AND
REMOVED, CONDUIT CUT —OFF GROUND FLUSH WITH FLOOR AND PLUGGED WITH
CEMENT MORTAR OR ANY OTHER APPROVED MATERIAL THE SAME APPLIES WITH
EXISTING CONDUITS OR PIPES THAT ARE STUBBED OUT OF WALLS AND FLOORS.
6. WHERE PRACTICAL, EXISTING CONDUCTORS AND WIRES THAT ARE IN GOOD
CONDITION, MAY BE REUSED IN PLACE AND INCORPORATED IN THE NEW
REMODELED LAYOUT, PROVIDED IT IS OF PROPER SIZE, TYPE OF CONDUCTOR
AND WITH THE APPROVAL OF THE OWNER.
7. ABANDONED CIRCUIT CONDUCTORS IN PANELBOARDS, SHALL BE DISCONNECTED,
TAPED AND IDENTIFIED.
8. SALVAGED ITEMS SHALL BE RETURNED TO THE OWNER, AND DELIVERED WHERE
DIRECTED BY HIM. ITEMS AND MATERIALS CONSIDERED UNSALVAGEABLE BY THE
OWNER, SHALL BE DISPOSED OF AS DIRECTED BY THE OWNER. REMOVED WALL
SWITCHES, DIFFUSERS, RECEPTACLES AND LIGHTING OR PLUMBING FIXTURES
SHALL NOT BE REUSED IN NEW CONSTRUCTION.
9. ALL ROOF OPENINGS OR WALL OPENINGS WHERE MECHANICAL OR ELECTRICAL
DEVICES OR OTHER ITEMS ARE TO BE REMOVED SHALL BE RESTORED AND
FINISHED TO A FINAL FINISH, AND WATER PROOFED.
GENERAL ELECTRICAL NOTES
1 . ALL WORK SHALL BE IN ACCORDANCE WITH NATIONAL ELECTRICAL CODE,
FLORIDA BUILDING CODE AND OTHER APPLICABLE CODES AND STANDARDS.
2 . a) THE DRAWINGS ARE DIAGRAMMATIC AND DO NOT SHOW ALL OFFSETS, BENDS AND
BOXES REQUIRED TO MAKE A COMPLETE NEAT INSTALLATION IN ACCORDANCE WITH
N.E.C.
b) WHEN CONFLICTS ARISE IN LOCATIONS WIRING DEVICES, ELECTRICAL EQUIPMENT,
DISCONNECTS, PANELBOARDS, ETC. DUE TO FIELD CONDITION OR IMPROPER FIELD
COORDINATION CONTRACTOR SHALL BRING IT TO THE A / E's ATTENTION AND AT NO
EXTRA COST RELOCATE, AND OR EXTEND WITHIN A REASONABLE DISTANCE SUCH ITEM
WHICH IS IN CONFLICT. THE CONTRACTOR IS RESPONSIBLE FOR COORDINATING
LOCATION OF ALL COMPONENT PRIOR TO ROUGH IN WITH ALL TRADES NO EXTRAS WILL
BE ALLOWED FOR FAILURE TO DO SO.
3 . THE CONTRACTOR IS RESPONSIBLE FOR EVALUATING FIELD CONDITIONS BY VISITING
THE SITE PRIOR TO COMMENCING / BIDDING WORK.
4 . THE CONTRACTOR SHALL SATISFACTORILY REPAIR /REPLACE EQUIPMENT OR PART OF
STRUCTURE DAMAGED AS A RESULT OF HIS WORK. SURFACES AND FINISHED AREAS
SHALL BE RESTORED TO MATCH ADJACENT AREAS.
5 . APPROVAL SHALL BE OBTAINED FROM AN STRUCTURAL ENGINEER PRIOR TO CUTTING
OR DRILLING ANY STRUCTURAL SUPPORT MEMBER.
6 . ALL DEVICE BOXES SHALL BE INSTALLED FLUSH AND CONDUITS RUN CONCEALED IN
FINISHED AREAS EXCEPT AS SPECIFICALLY SHOWN /NOTED OTHERWISE.
7 . ALL ELECTRICAL EQUIPMENT SHALL BE REMOVED FROM STRUCTURE TO BE REMOVED.
ACCESSIBLE RACEWAYS, WIRES, BOXES, SWITCHES AND OTHER ELECTRICAL ITEMS
ASSOCIATED WITH THIS WORK SHALL BE REMOVED IF NOT REQUIRED FOR NEW
EQUIPMENT TO CONTINUE IN SERVICE.
8 . WIRE SHALL BE REMOVED BACK TO SOURCE FROM INACCESSIBLE RACEWAYS NOT
REUSED. INSTALL BLANK PLATES ON FLUSH OUTLETS NOT REUSED. PLATE
COLOR SHALL MATCH ADJACENT SURFACE AS NEAR AS POSSIBLE IN FINISHED
AREAS.
9 . INSTALL POWER AND CONTROL WIRING AND REQUIRED CONTROL COMPONENTS FOR
AIR CONDITIONING SYSTEMS AS SHOWN /NOTED ON THESE DRAWINGS AND PER OTHER
APPLICABLE DRAWINGS / INSTRUCTIONS. SEE AIR CONDITIONING DRAWING.
10 . ALL MATERIAL REMOVED SHALL BE DISPOSED OF AS DIRECTED BY OWNER.
11 . WIRE SIZE SHALL BE 12 THHN / THWN UNLESS OTHERWISE NOTED ON PLANS.
14 ALL WIRES SHALL BE THWN. INSULATION.
15 . ALL CONDUCTOR SHALL BE COPPER.
16 . ALL CONDUCTORS SHALL BE RUN IN CONDUIT (METALLIC TYPE). IF PVC SCHEDULE 40
IS USED FOR UNDERGROUND FEEDERS ONLY, AN EQUIPMENT GROUND CONDUCTOR
SIZED IN ACCORDANCE WITH N.E.C. 250 -122 MUST BE INSTALLED AND CONDUIT SIZE
INCREASE AS REQUIRED.
17 . ALL MATERIALS SHALL BE U.L. APPROVED.
18 NEW TYPEWRITTEN PANEL TALLY SHALL BE FURNISHED AFTER JOB IN COMPLETED
REFLECTING ALL CHANGES AND ADDITIONS.
19 . ALL BRANCH CIRCUITS SHALL BE PROPERLY PHASE BALANCED.
20 SEE ARCHITECTURAL DRAWING FOR INFORMATION CONCERNING EXISTING CONDITIONS,
NEW WORK AND COUNTER DETAILS.
21 ALL WIRING DEVICES TO BE SPECIFICATION GRADE WITH HIGH ABUSE NYLON COVER
PLATES EQUAL TO LEVITON 53500 SERIES (SWITCHES); 5252 SERIES (RECEPTACLES).
22 ALL BRANCH CIRCUITS TO HAVE A GREEN EQUIPMENT GROUNDING CONDUCTOR SIZED
AS PER N.E.C. 250.122.
23 . FUSES SHALL BE DUAL ELEMENT, TIME DELAY TYPE UNLESS OTHERWISE NOTED.
24 . A/C EQUIPMENT WIRING, BREAKER AND FUSE SIZES ARE BASED ON A/C EQUIPMENT
SPECIFIED ON CONTRACT DRAWING. CONTRACTOR IS RESPONSIBLE FOR PROVIDING ALL
WIRING, BREAKER AND FUSES SIZES IN ACCORDANCE WITH A/C EQUIPMENT NAMEPLATE
REQUIREMENTS IF DIFFERENT FROM THAT SPECIFIED ON DRAWINGS, AS WELL AS ANY
FEEDER CHANGES BEING AFFECTED BY THIS CHANGE CONTRACTOR SHALL MAKE
ABOVE MENTIONED CHANGES AT NO EXTRA COST.
25 . CONTRACTOR SHALL COORDINATE ALL HIS WORK WITH OTHER TRADES IN OTHER TO
FURNISH AND INSTALL ALL CONTROL WIRING AND RACEWAYS, ALL POWER CONTROL
CIRCUIT WIRING AND RACEWAY AS SHOWN ON THE AIR CONDITIONING DRAWING OR
SPECIFICATIONS. IF AIR CONDITIONING IF DRAWING REFER TO MANUFACTURERS
WIRING DIAGRAMS, THE CONTRACTOR SHALL VERIFY WITH SAID MANUFACTURER ALL
REQUIREMENTS AND INCLUDE ALL RELATED WORK IN HIS CONTRACT.
26
ALL LUMINARIES SHALL BE PROPERLY SUPPORTED IN ACCORDANCE WITH THE CEILING
SYSTEM MANUFACTURER RECOMMENDATIONS AND LOCAL CODE REQUIREMENTS.
�•
27 .
RISERS ARE DIAGRAMMATIC ONLY. THEY DO NOT SHOW EVERY BEND REQUIRED FOR
�'
THE INSTALLATION.
t
28 .
THIS DRAWING IS A GUIDE FOR THE ELECTRICAL INSTALLATION . THE ELECTRICAL
CONTRACTOR IS RESPONSIBLE TO PROVIDE A FUNCTIONING SYSTEM.
W
29 .
ALL CABLES SHALL BE RUN WITHOUT SPLICES EXCEPT OTHERWISE INDICATED.
Q
30 .
ALL PULL AND JUNCTION BOXES SHALL BE ACCESSIBLE AT ALL TIMES.
u
f
31 .
EXACT POINT AND METHODS OF CONNECTION SHALL BE DETERMINED IN FIELD.
/��
VJ
Q
32 .
ALL WORK SHALL BE DONE IN A NEAT AND WORKMANLIKE MANNER.
Q
Q
^'
33 .
BRANCH CIRCUIT BREAKERS SHALL BE OF THE BOLT —ON TYPE. PLUG IN CIRCUIT
r/
BREAKERS WILL NOT BE ACCEPTED.
O
34 .
ALL NEW BRANCH CIRCUIT BREAKERS SHALL MATCH EXISTING CONDUCTOR SIZE
IF CONDUCTOR SIZE IS LESS THAN CIRCUIT BREAKER SIZE, CHANGE CONDUCTOR
J
TO MATCH CIRCUIT BREAKER. FOR EXISTING MOTOR, NOTIFY ENGINEER BEFORE
LL
ROUGHING —IN.
/ �
C n
—
35 .
ALL LOAD IN EXISTING PANELBOARDS ARE ESTIMATED.
nO
't.r1J
36 .
ALL RACEWAY ROUTED, INSULATED CONDUCTORS SYSTEM SHALL BE COLOR CODED
L�
J
AS FOLLOWS.
O
120/240 V SYSTEM
PHASE "A" BLACK
PHASE "B" RED
NEUTRAL WHITE
(1
GROUND GREEN
l_L_
37 .
ALL ROUGH IN DIMENSION ARE TO CENTER LINE OF DEVICE UNLESS OTHERWISE NOTED.
38 .
CONTRACTOR TO PROVIDE END LINE FUSES FOR FLUORESCENT LIGHT FIXTURES.
39 .
CONTRACTOR IS ALLOWED TO REARRANGE THE DISTRIBUTION OF THE ELECTRICAL
LOADS CONNECTED TO BRANCH CIRCUITS IN FIELD AS LONG AS LOAD BALANCE &
INDEPENDING CIRCUIT LOADING IS IN COMPLIANCE WITH NEC.
49 .
FLEXIBLE CONDUIT SHALL BE USED FOR CONNECTION TO ALL VIBRATING EQUIPMENT
SUCH AS MOTORS.
40 .
ELECTRICAL CONTRACTOR SHALL VERIFY THE CEILING FINISHES AND SUSPENSION
SYSTEM FOR SELECTION OF THE PROPER TRIM AND SUPPORT ARRANGEMENT OF THE
FIXTURE.
41 .
WHEN INSTALLING J. BOXES ® FIRE RATED WALLS:
a) J. BOXES TO BE SPACED 6" MIN. WITHOUT EXCEEDING THE NEC SPACING
1Q 8/25/11
REQUIREMENTS.
b) PROVIDE 2 HOURS FIRE RATED PUTTY PAD AS MANUFACTURED BY 3M.
42 .
DISCONNECTING MEANS. EACH MULTIWIRE BRANCH CIRCUIT SHALL HAVE A MEANS
TO SIMULTANEOUSLY DISCONNECT ALL UNGROUNDED CONDUCTORS AT THE POINT
WHERE THE BRANCH CIRCUIT ORIGINATES
43 .
GROUPING. THE UNGROUNDED AND NEUTRAL CONDUCTORS OF A MULTIWIRE BRANCH
CIRCUIT SHALL BE GROUPED TOGETHER IN AT LEAST ONE LOCATION BY WIRE TIES OR
SIMILAR MEANS AT THE POINT OF ORIGINATION
44 .
ALL 15A AND 20A, 125V RECEPTACLES INSTALLED WITHIN 6 FT OF THE OUTSIDE EDGE OF
THE SINK SHALL BE GFCI — PROTECTED
45 .
OVERCURRENT DEVICES SHALL NOT BE LOCATED OVER STEPS OF A STAIRWAY
46 .
AN EQUIPMENT BONDING JUMPER IS NOT REQUIRED FOR RECEPTACLES ATTACHED TO
Drawn By.
LISTED EXPOSED WORK COVERS WHEN THE RECEPTACLE IS ATTACHED TO THE COVER
WITH TWO PERMANENT FASTENERS (RIVETS), OR HAVE A THREADED OR SCREW
R. B.
LOCKING MEANS; AND THE COVER MOUNTING HOLES ARE LOCATED ON A FLAT
NON— RAISED PORTION OF THE COVER
Checked:
47 .
ALL OVER CURRENT PROTECTION DEVICES SHALL BE SERIES COORDINATED FOR AN
INTEGRATED INTERRUPTIVE CAPACITY GREATER THAN THE EXISTING AT ELECTRICAL
SERVICE POINT
Date:
47 .
ALL PANELBOARDS OR SWITCHBOARDS TO HAVE A SIGN SPECIFYING THAT THE
08/25/11
HIGH —LEG (PHASE B) VOLTAGE TO GROUND IS 208 V.
Scale:
48 . ALL SWITCHBOARDS, PANELBOARDS, METER SOCKETS, & ALL OTHER PANELS TO
HAVE A SIGN TO READ AS FOLLOW: ARC FLASH HAZARD. APPROPRIATE PPE REQUIRED
AS
Shown
49 .
CONTRACTOR TO INCREASE FEEDER SIZE AS NECCESARY TO PROVIDE A MAXIMUM
Sheet:
VOLTAGE DROP OF 2%
50 .
MINIMUM COVER MUST BE PROVIDED FOR UNDERGROUND RACEWAYS OR CABLES TO
COMPLY WITH NEC 300.5
E-1