ELECTRICAL LEGEND
ANOL
Qj EXHAUST FAN
LIGHT FIXTURE
�41 TELEPHONE
Q
JUNCTION BOX
3"
Revision
GENERAL DEMOLITION NOTES:
By
SWITCH
SEAL
DUPLEX RECEPTACLE
WP
WEATHER-PROOF
ELECTRIC PANEL
Lo
DISCONNECT
ANOL
Qj EXHAUST FAN
LIGHT FIXTURE
�41 TELEPHONE
Q
JUNCTION BOX
3"
Revision
GENERAL DEMOLITION NOTES:
By
35 ALL LOAD IN EXISTING PANELBOARDS ARE ESTIMATED.
36 ALL RACEWAY ROUTED, INSULATED CONDUCTORS SYSTEM SHALL BE COLOR CODED
AS FOLLOWS,
SEAL
PHASE "A' BLACK
PROPOSED DAYCARE
PHASE "B" RED
AT EXIST. MMWRCIAL
26
ALL LUMINARIES SHALL BE PROPERLY SUPPORTED IN ACCORDANCE WITH THE CEILING
'Too,
SYSTEM MANUFACTURER RECOMMENDATIONS AND LOCAL CODE REQUIREMENTS,
37
ALL ROUGH IN DIMENSION ARE TO CENTER LINE O F D EVICE UNLESS OTHERWISE NOTED,
27
RISERS ARE DIAGRAMMATIC ONLY. THEY DO NOT SHOW EVERY BEND REQUIRED FOR
THE INSTALLATION.
SITE ADDRESS:
39
CONTRACTOR IS ALLOWED T O R EARRANGE THE DISTRIBUTION OF THE ELECTRICAL
28
THIS DRAWING IS A GUIDE FOR THE ELECTRICAL INSTALLATION . THE ELECTRICAL
Z'
/?
CONTRACTOR IS RESPONSIBLE TO PROVIDE A FUNCTIONING SYSTEM.
>
49
FLEXIBLE CONDUIT SHALL BE USED FOR CONNECTION TO ALL VIBRATING EQUIPMENT
29
ALL CABLES SHALL BE RUN WITHOUT SPLICES EXCEPT OTHERWISE INDICATED.
0
40
ELECTRICAL CONTRACTOR SHALL VERIFY THE CEILING FINISHES AND SUSPENSION
30
ALL PULL AND JUNCTION BOXES SHALL BE ACCESSIBLE AT ALL TIMES.
TENANT:
31
EXACT POINT AND METHODS OF CONNECTION SHALL B E D ETERMINED IN FIELD.
SIGNATURE
35 ALL LOAD IN EXISTING PANELBOARDS ARE ESTIMATED.
36 ALL RACEWAY ROUTED, INSULATED CONDUCTORS SYSTEM SHALL BE COLOR CODED
AS FOLLOWS,
PHASE "A' BLACK
PROPOSED DAYCARE
PHASE "B" RED
AT EXIST. MMWRCIAL
NEUTRAL WHITE
BUILDING
GROUND GREEN
37
ALL ROUGH IN DIMENSION ARE TO CENTER LINE O F D EVICE UNLESS OTHERWISE NOTED,
38
CONTRACTOR TO PROVIDE END UNE FUSES FOR FLUORESCENT LIGHT FIXTURES.
SITE ADDRESS:
39
CONTRACTOR IS ALLOWED T O R EARRANGE THE DISTRIBUTION OF THE ELECTRICAL
LOADS CONNECTED TO BRANCH CIRCUITS IN FIELD AS LONG AS LOAD BALANCE &
6333 S. W. 72 ST.
INDEPENDING CIRCUIT LOADING IS IN COMPLIANCE WITH NEC.
MIAW., FLORMA 33143
49
FLEXIBLE CONDUIT SHALL BE USED FOR CONNECTION TO ALL VIBRATING EQUIPMENT
SUCH AS MOTORS.
40
ELECTRICAL CONTRACTOR SHALL VERIFY THE CEILING FINISHES AND SUSPENSION
SYSTTURE. EM FOR SELECTION OF THE PROPER TRIM AND SUPPORT ARRANGEMENT OF THE
TENANT:
FIX
TINffiVMW
PP,F-SCHOOL
41.
WHEN INSTALLING J. BOXES 0 FIRE RATED WALLS:
Ph:(786) 274-3668
a) J. BOXES TO BE SPACED 6" MIN. WITHOUT EXCEEDING THE NEC SPACING
REQUIREMENTS.
b) PROVIDE 2 HOURS FIRE RATED PUTTY PAD AS MANUFACTURED BY 3M.
42
DISCONNECTING MEANS. EACH MULTIVARE BRANCH CIRCUIT SHALL HAVE A MEANS
TO SIMULTANEOUSLY DISCONNECT ALL UNGROUNDED CONDUCTORS AT THE POINT
WHERE THE BRANCH CIRCUIT ORIGINATES
43
GROUPING. THE UNGROUNDED AND NEUTRAL CONDUCTORS OF A MULTIWIRE BRANCH
CIRCUIT SHALL BE GROUPED TOGETHER IN AT LEAST ONE LOCATION BY WIRE TIES OR
SIMILAR MEANS AT THE POINT OF ORIGINATION
44
ALL 15A AND 20A, 125V RECEPTACLES INSTALLED WITHIN 6 FT OF THE OUTSIDE EDGE OF
THE SINK SHALL BE GFCI-PROTECTED
45
OVERCURRENT DEVICES SHALL NOT BE LOCATED OVER STEPS OF A STAIRWAY
46
AN EQUIPMENT BONDING JUMPER IS NOT REQUIRED FOR RECEPTACLES ATTACHED TO
Consultant
LISTED EXPOSED WORK COVERS WHEN THE RECEPTACLE IS ATTACHED TO THE COVER
WITH TWO PERMANENT FASTENERS (RIVETS), OR HAVE A THREADED OR SCREW
LOCKING MEANS; AND THE COVER MOUNTING HOLES ARE LOCATED ON A FLAT
Drawn: D.G.
NON-RAISED PORTION OF THE COVER
Checked: D.G.
47 .
ALL OVER CURRENT PROTECTION DEVICES SHALL BE SERIES COORDINATED FOR AN
INTEGRATED INTERRUPTIVE CAPACITY GREATER THAN THE EXISTING AT ELECTRICAL
Date 4/5/11
SERVICE POINT
47 .
ALL PANELBOARDS OR SWITCHBOARDS TO HAVE A SIGN SPECIFYING THAT THE
Scale AS—SHOWN
HIGH-LEG (PHASE B) VOLTAGE TO GROUND IS 208 V,
48
ALL SWITCHBOARDS, PANELBOARDS, METER SOCKETS, & ALL OTHER PANELS TO
Job No.
HAVE A SIGN TO READ AS FOLLOW: ARC FLASH HAZARD. APPROPRIATE PPE REQUIRED
49 .
CONTRACTOR TO INCREASE FEEDER SIZE AS NECCESARY TO PROVIDE A MAXIMUM
Sheet
VOLTAGE DROP OF 2%
rE
50 .
MINIMUM COVER MUST BE PROVIDED FOR UNDERGROUND RACEWAYS OR CABLES TO
COMPLY WITH NEC 300.5