11-481-0220,,,ass i f;
&U,
SJ's t eo
`
CAJ5068
0
0
Project:
Location:
Installer.
Signature:
POWER
24
VDC
OR
120
VAC
U.L.LISTED
�offoam
3735 Green Rd.
Beachwood, OH, 44122
Drawing not to scale
The products used in the above astantly have
The above described assembly and
been test N accordance wits tie fuaoairg.
products have been tested and are
ASTM E814 (111.1479) Standard Tee[ Mahod
based on both pest and anticipated
for Through Penetration Flred*ptg.
performance allwU . Tremoo stall
less than 48" deep
not be liable fa any damages, died
Width between 28" & 48"
OUTSIDE INSULATION
or consequential, resulli g from use
Date: 2/1!95
DraY(rin TR -5068
g'
of this material a design. Tremco
16" depth or less
AIR FLOW
shall only be responsible for replacing
Approved by, C. Tuzzeo
material found to be defedNa
FROM OTHER DETECTOR
(IF APPLICABLE ) IONIZATION SMOKE DETECTOR
(SEE HVAC PLANS)
M 10
:617.
1 1/2" X 26 GA. GALV.
STEEL HANGER STRAP
(5' O.C.)
AIR DUCT (SEE PLAN VIEW)
SEAL JOINT W/
LOW FRICTION LOSS
DUCT SEALER AND
BRANCH TAKE -OFF FITTING
48: Wide or grade
METAL ROUND FITTING
TAPE
QUADRANT OPERATOR TO BE
less than 48" deep
6 ft
Width between 28" & 48"
OUTSIDE INSULATION
and greater than 16" deep
6 ft
Less than 29" wide and
PROVIDE INSULATION GUARD
16" depth or less
AIR FLOW
WHERE NECESSARY
INSULATE TOP
OF DIFFUSER.
DETECTOR TEST PANEL
OR FIRE ALARM PANEL
IF APPLICABLE
LIGHT
INDICATOR
AUDIBLE ALARM
IN NORMALLY
OCCUPIED AREA
OR THROUGH
BUILDING FIRE
ALARM SYSTEM
IF APPLICABLE
EVAPORATOR FAN MOTOR
AUXILIARY CONTACT TO
SHUT DOWN UNIT IN CASE
OF SMOKE SENSING
AIR CONDITIONING DUCT SMOKE DETECTOR. VERIFY AT SITE.
(FOR UNITS OVER 2000 CFM.
NOTIFIED DHX -501 INTELLIGENT IONIZATION SENSOR
1/8" 0 STAINLESS STEEL WIRE CABLE ) ANCHORED TO CONCRETE
(MIN. OF WITH 3 /82TURNBUCKLE FOR AD USTMENTD
CONDENSING UNIT
FASTEN G.U. TO 2" GALV.
STEEL CHANNEL USING 1/4"
GALV. STEEL BOLTS, NUTS
& WASHERS WITH ISOMODE
PAD. AT EACH CORNER.
FASTEN CHANNEL TO LINE OF BLDG.
CONCRETE USING 3/8'
ROUND WEDGE ANCHORS, 90' SOLDERED
ONE 0 EACH END OF
ELBOW. (TYP.)
CHANNEL AND EMBEDDED
2' DEEP.
2° GALV. STEEL CHANNEL (TYP.)
:.' • : \—CAULK LINES WITH
•A�,i•. r .'... . z ;Ar ' ' �.. ELASTOMERIC
CONCRETE PAD. MATERIAL AT BOTH
\� �\�� ������ ENDS.
ANCHOR BOLT OF 500 POUNDS
MINIMUM PULL OUT CAPACITY. (TYP.)
NOTE: ALL CONDESATE UNIT SHALL BE ANCHORED TO THE CONCREYTE SLAB, ON THE
INSIDE OF THE UNIT, W/ AN ANCHOR BOLT OF 500 POUNDS MINIMUM PULL OUT CAPACITY.
CONDENSING UNIT MOUNTING DETAIL
N.T.S.
SUPPORT FROM
UNDERSIDE OF
STRUCTURE.
AIR FLOW
L
INSULATED FLEX. DUCT
SEAL JOINT WITH DUCT
SEALER AND TAPE
DIFFUSER W/ OPPOSED
BLADE DAMPER
ADAPTER ROUND TO SQUARE
IF REQUIRED
FLEXIBLE DUCT CONNECTION DETAIL
TURNING VANI
FOR SMACNA
STANDARDS.
DUCT HANGER DETAIL
N.T.S.
At Ir+T
TYPICAL 90- DEGREE VANED ELBOW DETAIL.
FIBER GL ''S DUCT CONNECTION
TO EQUI ` ENT NTS
NOTE:
Sheet metal connections must be using glass fabric
and mastic (GFM)
EXCEPTION:
When construction pressure class is 1"W.G. or less
and sheet metal surfaces are cleaned carefully UL listed
pressure - sensitive aluminum tape may be used.
All connections of fibrous glass duct to equipment and
metal duct must be mechanically attached 12" (max) on
centers.
GFM
CLOSURE -,
#10 X 1Ya" SHEET METAL
SCREWS 12-(MAX)
MIN. PER SIDE ��(\
FIBROUS GLASS DUCT
22 GAUGE SHEET METAL, FLANGE
1"X 1"X 1" CHANNEL
FASTENED TO
METAL FLANGE
CONNECTING DUCTWORK
t EXHAUST FAN CABINET
CEILING INTAKE GRILLE
EXHAUST FAN DETAIL (EF-_11
N.T.S.
EXTERIOR WALL
1" EMBEDMENT 1/4 "- EXPANSION BOLTS
(TYP) (4) REQUIRED
M ETAL WALL CAP
4 "- METAL DUCT
24 GAUGE DRYE
BACKI
DAMP
— 1/4" BIRD SCREEN
RUST RESISTANT
WALL CAP DETAIL
N.T.S.
PERFORATED CAP
CLEAN OUT
DRAIN PAN
PITCH DOWN 18" MIN
TOWARD DRAIN
4" MIN
DRAIN LINE SHALL BE AT LEAST THE
SAME SIZE AS THE NIPPLE ON THE
DRAIN PAN
TYPICAL CONDENSATE DRAIN TRAP
NO SCALE
STANDARD 3" WIDE HANGERS
Hanger extension to be the sum
of the distances between the hanging
wires and the duct size, ID(Smacna)
Duct size, Inches
Maximun Hanger
Spacing
48: Wide or grade
4 ft
Less than 48" wide and
less than 48" deep
6 ft
Width between 28" & 48"
and greater than 16" deep
6 ft
Less than 29" wide and
8 ft
16" depth or less
VARE .
�ptJ
001 (MI ( _r
CHANNEL SELECTION
If Total Minimun Minimun
Extension is Channel Channel
not greater than: Gauge Gauge
6" 24 3" X 1.5"
18" 22 3" X 2"
30" 18 3" X 2"
USE OF 2" WIDE
22 gauge 2' x 1.5' hangers may substituted
for 3" hangers for ducts with widths not over 48"
and depths not over 24" provided that not more
than one joint occurs between hangers and the
maximum hanger spacing 4ft. Exception: When duct
perimeter is 80" or less and does not require
reinforcement two joints are permitted between
hangers
1 p ONG SAP
,rd6_.. tr PER
DUCT HANGER AND SUPPORTS
NTS
galv. cap
�k_bird screen
2' —O,t
flashing
roof
2 "x4" blh "g
06 sheet metal duct
g. 26 to return plenum.
PROVIDE 10' MIN. FROM ANY VENT. COORDINATE W/ PLUMBING
CONTRACTOR BEFORE JOB COMMENCEMENT.
AIR INTAKE VENT LOCATED ON ROOF SHALL BE PROPERLY
MARKED WITH A UNIVERSAL MARKING "INTAKE" AS PER FBC 2810.
ROOF CAP TYPICAL DETAILS.
N.T.S.
AUX. FLOAT SWITi
EZ TRAP. INC, MO
NU I L5:
AHU MOUNTING DETAIL
N.T.S.
GRADE
°�o0 00 f
I!IIIII111 0 0 0o IIl1�l —ll
_
C>
24" IIII �° Q o IrI
24" DIAMETER CONCRETE o�
°
OR CLAY PIPE WITHOUT o ° °
COVER FILLED WITH P ° o ° o
3/4" CRUSHED ROCK °
°
° o
o C
° o
0 0
CONDENSATE DRAIN
co o ° o LINE FROM BUILDING
<=>
° SEE PLAN FOR SIZE.
0
o
° ° O
O O O
N.T.S.
DUCT HANGER DETAIL
MAK
o CO Z Z rn
Z
z1�towo- W o
LU M 2 0 W W 3 � W o W
aazz>.FF WFA0tyt0.��
X- 8 4~ 621010
o-
tYOZaoO °NO�!µr�'I¢
VOZW -jW W°oZWDu.
oitoou> >a� wt=
rna °u41W _ owya
��p =�� �wwt= -•�Z
0 W Ri Cvu�J (n,��Z0� W
QZQp =O Qv=imtnW�
Z< >W T% S 9 m g g M W
�mwz_J }m000g =0
Z W a U N w V> N m
�.DOZoo O°zZj
<W > (La00tnULL��
4 W >W O
z�0>Omf-'ZZZO °a
,WLLo gg000Waa
ay w
o¢ o.W�zf��pl —LL
¢K°XwWXFnzpO°wma
o=wooW¢a°�° ca
¢m�3¢tiWL Wu-2 <
•
1
r
PROPOSED DAYCARE
AT EXIST. COMMERCIAL
BUILDING
SITE ADDRESS:
IY11/1111, 1 "WA %I ✓!
TENANT:
TIMEVIEW
PRESCHOOL
Ph:(786) 274 -3668
AGUDELIO
ARCHITECT P.A.
A.A.26002013
Address:
9885 N.W. 51 Terrace
Doral, Florida 33178
Phone #:
(786) 738 -8236
e -mail address:
german @agudeloarchitecL net
SEAL:
STATE OF FLORIDA
6E�MARt<
ARCH ITECT.F®R°THE FIRM
LICENSE # AR -0091594„
DAM GONZALEZ, P.E.
LICENSE No. 67574
11537 S.W. 64 ST. UNIT A. MIAMI, FL. 33173
FAX:(305) 630 -2643, TEL:(305) 794 -5813 OF
e -mail: dani.gonzalez @atLnet -3