Loading...
10-748-002rd f0 6 0 I 'a U) J �1 a= �I d L v a_ r�> ev t w w z w f� } 0 cvv w 0 CL Q e, - I FIRE LITE MS-9200ODLS FIRE ALARM PANEL BATTERY CALCULATION REGULATED LOAD IN STANDBY DEVICE TYPE NUMBER OF DEVICES REQUIRED STANDBY -TIME IN HOURS CURRENT (AMPS) X TOTAL CURRENT (AMPS) MAIN CIRCUIT BOARD 1 X 0.137 = 0.137 SMOKE /DUCT DETECTORS 33 X 0,0003 = 0,0099 PULL STATIONS 6 X 0.00023 - 0.00' RELAY 1 X 0.00023 - 0.00023 _ REMOTE ANNUNCIATOR 1 X 0.015 = 0.015 2 1.276 18.43 9.67 %% NOTES: STROBE 75CD 7 X 0158 s 1.106 NAC #2 CURRENT= 1.862A SUM COLUMN FOR STANDBY LOAD _ 0,164 AMPS REGULATED LOAD IN ALARM - DEVICE TYPE NUMBER OF DEVICES REQUIRED STANDBY -TIME IN HOURS CURRENT (AMPS) X TOTAL CURRENT (AMPS) MAIN CIRCUIT BOARD 1 X 0.360 - 0.360 90.040 REMOTE ANNUNCIATOR 1 X 0.040 = 0.083 = 0.037 MAXIMUM ALARM FOR DEVICES 1 X 0.04 = 0,040 SUM COLUMN FOR ALARMY LOAD: 0.440 AMPS BATTERY LOAD CALCULATION CALCULATION IN TOTAL SHEET STANDBY LOAD NUMBER OF DEVICES REQUIRED STANDBY -TIME IN HOURS CURRENT (AMPS) X (24 HRS.) 0.164 NUMBER OF 24 = 3.94 ALARM LOAD CIRCUIT NAME VOLTAGE CURRENT WIRE TYPE NUMBER 1 ��� FT REQUIRED ALARM -TIME IN HOURS CURRENT (AMPS) X (5 MINUTES = 0.083) 0.440 w 0.083 = 0.037 ADD STANDBY AND ALARM LOAD FOR REQUIRED AMPERE HOUR BATTERY 3.98 MULTIPLY BY 'THE DERATING FACTOR OF 1.2 TOTAL AMPERE HOURS REQUIRED 4.77 RECOMENDED BATTERY = 7 AH BATTERY CHECK THE MS- 920OUD CAN CHARGE THIS SIZE BATTERY THE BATTERIES CAN BE STORED IN -THE PANEL CABINET CURRENT DRAW CHECK STANDBY + ALARM CURRENT = 0.164A + 0.44 A = 0.604 A THE REQUIRED OUTPUT CURRENT IS WITHIN THE PANEL'S LIMITATIONS WITH THE BUILT -IN TRANSFORMER INSTALLED. USE 7 A/H BATTERIES FIRE LITE FCPS-24FS8 BOOSTER `,i W R SUPPLY BAT -FERY CALCULATION REGULATED LOAD IN STANDBY REGULATED LOAD IN ALARM DEVICE TYPE NUMBER OF DEVICES REQUIRED STANDBY TIME IN HOURS CURRENT (AMPS) X TOTAL DEVICE TYPE NUMBER OF X CURRENT CIRCUIT NAME VOLTAGE CURRENT WIRE TYPE NUMBER 1 ��� FT CURRENT NAC 1 DEVICES HORN /STROBE 75CD (AMPS) w (AMPS) MAIN CIRCUIT BOARD 1 X 0.065 = 0.065 SUM COLUMN FOR STANDBY LOAD 0.065 AMPS REGULATED LOAD IN ALARM DEVICE TYPE NUMBER OF DEVICES REQUIRED STANDBY TIME IN HOURS CURRENT (AMPS) X TOTAL CURRENT (AMPS) MAIN CIRCUIT BOARD 1 X 0.145 CIRCUIT NAME VOLTAGE CURRENT WIRE TYPE NUMBER 1 ��� FT 0.145 NAC 1 X HORN /STROBE 75CD 3 w 0.176 = 0.528 STROBE 75CD 7 X 0.15$ = 1.106 -✓.� NAC #1 CURRENT= 1.634A NAC 2 1 HORN STROBE 75CD 1 X 0.176 m 0.176 HORN STROBE 177CD 2 1.276 18.43 9.67 %% NOTES: STROBE 75CD 7 X 0158 s 1.106 NAC #2 CURRENT= 1.862A NAC 3 ��� HORN STROBE 75CD 3 X 0.176 - 0.528 STROBE 75CD 5 X 0.158 = 0.790 NAC #3 CURRENT- - 1,318A NAC 4 3. INDICATE -THE LOCATION OF THE DUCT SMOKE DETECTOR BY DISPLAYING, IN ENGLISH, THE ALARMED DEVICE HORN /STROBE 75CD 1 X 0.176 = 0.176 HORN STROBE 177CD 2 X 0.290 - 0.580 STROBE 75CD 5 X 0.158 - 0.790 NAC #4 CURRENT= 1.546A SUM COLUMN FOR ALARM LOAD = 6.505 AMPS * CURRPF' LIMITATION PER NAC = 3.0 AMPS * 'TOTAL (:1)RRENT DRAW FROM ALL 'TERMINALS CANNOT EXCEED 6.0 AMPS BATTERY LOAD CALCULATION CALCULATION IN TOTAL SHEET STANDBY LOAD - PB #1 REQUIRED STANDBY TIME IN HOURS CURRENT (AMPS) X (24 HRS,) 0.065 TOTAL 24 = 1.56 ALARM LOAD CIRCUIT NAME VOLTAGE CURRENT WIRE TYPE NUMBER 1 ��� FT REQUIRED ALARM TIME IN HOURS CURRENT (AMPS) X (5 MINUTES = 0.083) 6.505 w 0.083 = 0.540 ADD STANDBY AND ALARM LOAD FOR REQUIRED AMPERE HOUR BATTERY 2.100 MULTIPLY BY THE DERATING FACTOR OF 1.2 TOTAL AMPERE HOURS REQUIRED 2.520 RECOMENDED BATTERY 7 AH BATTERY CHECK THE FCPS -24FS8 CAN CHARGE THIS SIZE BATTERY THE BATTERIES CAN BE STORED IN THE PANEL CABINET CURRENT DRAW CHECK 9 STANDBY + ALARM CURRENT = 0.065A + 6.505 A = 6.570 A THE REQUIRED OUTPUT CURRENT IS WITHIN THE PANEL'S LIMITATIONS USE 7 A/H BATTERIES V uV V Utit V V V VDU'. -� V V uuu 'J v v v� v V V U VOL -FACE DROP CALCULATIONS - PB #1 11� ACTIVATION OF SMOKE DETECTORS SHALL INITIATE THE FOLLOWING FUNCTIONS: w d SUPPLY ALARM CIRCUIT OHMS/ LENGTH TOTAL VOLTAGE VOLTAGE CIRCUIT NAME VOLTAGE CURRENT WIRE TYPE NUMBER 1 ��� FT RESISTANCE (FEET} w LAST DROP% (VDC) (A) w (OHMS) DEVICE 2. INDICATE LOCATION OF THE SMOKE DETECTOR BY DISPLAYING, I ENGLISH, DISPLAYING, THE ALARMED DEVICE 1 NAC 1 20.4 1.634 2# 14 FPLP 3,19 200 1.276 18.32 10.22% 2 NAC 2 20.4 1,862 2# 14 FPLP 3.19 200 1.276 18.02 11.65% 3 NAC 3 20.4 1.318 2# 14 FPLP 3.19 200 1.276 18.72 8.24 % 4 NAC 4 20.4 1.546 2# 14 FPLP 3.19 200 1.276 18.43 9.67 %% NOTES: 2� W° U 1.) WIRE RESISTANCE IS TAKEN FROM CHAPTER 9 TABLE 8 OF -THE NATIONAL ELECTRIC CODE (NFPA70). 0Y [n r✓Jiti1 ��11r �-C° ��� RESISTANCE SHOWN IS CALCULATED AT 75 DEGREES CENTIGRADE (167 FARENHEIT). DUCT DETECTORS " w 2.) FORMULA USED FOR CALCULATION: TOTAL RESISTANCE = (LENGTH X 2/ 1000) X OHMS PER 1000 FT. W L>_. !a i VOLTAGE LAST DEVICE = SUPPLY VOLTAGE - (ALARM CURRENT X TOTAL RESISTANCE) 2 tt 3. INDICATE -THE LOCATION OF THE DUCT SMOKE DETECTOR BY DISPLAYING, IN ENGLISH, THE ALARMED DEVICE 3.) CALCULATIONS ARE BASED ON AVERAGE CURRENT DRAW OF DEVICES USING A REGULATED POWER SUPPLY ONLY, ITS LOCATION ON THE FACP ALPHANUMERIC DISPLAY AND ON THE REMOTE ANNUNCIATOR ALPHANUMERIC DISPLAY. FIRE ('I11AL 4.) FROM FARADAY NOTIFICATION DEVICES SPECS SHEETS: 4. SHUT DOWN THE AIR HANDLING UNIT AND A/C EQUIPMENT ASSOCIATED WITH THE DUCT DETECTOR. Sim fN FP_RA(.X :. A curnFICATE cr OPERATING VOLTAGE RANGE : ** 24V: 16 -32V OR PLACARD SF1f LL BE P m AF IL LL I1 5. CLOSE CONTACTS WITHIN THE FACP FOR CENTRAL STATION MONITORING TO REPORT SUPERVISORY (SEE SPECS SHEETS ATTACHED). J, A.4 P!-:R fgr-PA 72 i IN THE EVENT OF A TROUBLE CONDITION THE FOLLOWING FUNCTIONS WILL OCCUR ON THE PANEL : * *THESE PRODUCTS SHOULD BE OPERATED WITHIN THEIR RATED VOLTAGE RANGE. kIIZL; A1�- 1ItIv1 S ' STE:M TO I3IJ SPECIFICATIONS: * ALL EQUIPMENT SHALL BE UL APPROVED. * ALL FIRE ALARM EQUIPMENT FOR THIS PROJECT SHALL BE RATED FOR POWER- LIMITED. * CABLE SIZE SHALL COMPLY WITH ARTICLE 760 -71 AND THE CABLE INSTALATION SHALL COMPLY WITH THE SEPARATION AND USE OF CONDUCTORS AND CABLES AS SPECIFIED IN ARTICLES 760 -54 AND 760 -61F THE NEC. * BUILDING WIRING SHALL SPECIFICALLY CONFORM WITH THE NEC ARTICLE 760 PART C FOR POWER- LIMITED FIRE PROTECTION SIGNAL CIRCUITS WITH EMPHASIS ON ARTICLE 760 -52(B) ON POWER LIMITED WIRING METHODS AND MATERIALS. * MINIMUM CABLE SIZE: A.- # 18 FPL FOR: PULL STATIONS, SMOKE DETECTORS, DUCT DETECTORS, WATER AND TAMPER SWITCHES. B.- # 14 TFIHN FOR: STROBES AND HORN /STROBES NOTIFICATION DEVICES. * ALL NEW WIRING INSTALLED IN DUCTS, PLENUMS AND OTHER SPACES USED FOR ENVIRONMENTAL AIR SHALL BE FPLP AS PER NEC ARTICLE 760 -61. * ALL ALARM NOTIFICATION DEVICES SHALL BE AUDIBLE AND VISUAL (UNLESS SPECIFIED) AND SHALL BE VIA HORN /STROBE COMBINATION DEVICES. STROBES SHALL BE CLEAR XENON TYPE, WITH INTENSITY OF 75 CANDELAS AS PER ARTICLE 4.28 (I) - THROUGH (5) OF THE ADA GUIDELINES OF JULY 26,1992 AND AS PER ARTICLE 4.28.2 & 4.28.3 OF THE FLORIDA ACCESIBILITY CODE 1997 EDITION. * HORN /STROBES AND STROBES DEVICES SHALL BE PLACED 80" (6' 8 ") ABOVE THE FLOOR LEVEL WITHIN THE SPACE OR 6" BELOW THE CEILING WHICHEVER IS LONER AS PER ADA GUIDELINES AND ARTICLE 4.28(6) OF THE FACBC 1997 EDITION. * MANUAL INITIATING DEVICES SHALL BE PLACED 48" (4') ABOVE FINISH FLOOR. * MAXIMUM OVER CURRENT PROTECTION FOR FIRE ALARM PANEL AND BOOSTER SHALL BE 20A. * THE DISTANCE FROM ANY PLACE TO A NOTIFICATION DEVICE SHALL NOT EXCEED 50' AS PER ARTICLE 4.28(7) AND (8) OF THE FACBC 1997 EDITION. * CONDUITS TO BE FILLED ONLY UP TO 40% OF ITS CAPACITY. * MAXIMUM VOLTAGE DROP OF 20% PER CIRCUIT. 1. ALL SYSTEM DEVICES SHALL BE U.L. LISTED r-OR THEIR INTENDED USE AND AS A COMPATIBLE SYSTEM. 2. COMPLETE SYSTEM TO BE FULLY, ELECTRICALLY SUPERVISED. ANY DISARRANGEMENT OF THE SYSTEM WIRING, REMOVING OF DEVICES OR LOSS OF NORMAL A.C. POWER SHALL CAUSE THE SYSTEM TROUBLE SIGNAL TO SOUND. 3. LOSS OF NORMAL A.C. POWER SHALL, IN ADDITION TO SOUNDING THE TROUBLE SIGNAL, CAUSE THE SYSTEM TO SHIFT TO THE STANDBY BATTERIES. 4. SYSTEM TO BE INSTALLED IN ACCQRDANCE WITH N.F.P.A. 72 EDITION 2002 AND N.F.P.A. 101. SYSTEM WIRING SHALL COMPLY WITH N.E.C. ARTICLES 250, 300 AND 760. 5. SYSTEM SHALL BE POWER LIMITED. AUTOMATIC RESPONSE FUNCTIONS SHALL BE INITIATED ONLY BY THE FIRST ALARM RECEIVED. ADDITIONAL ALARMS SHALL BE RECEIVED, ANNUNCIATED AND SHALL INITIATE FUNCTIONS ASSOCIATED EXCLUSIVELY WITH SUBSEQUENT ALARM. COMMON ALARM SHALL NOT BE INITIATED UNLESS THE FIRST ALARM IS RETURNED TO NORMAL. THE ACTUATION OF THE FIRE ALARM INITIATING DEVICES SHALL AUTOMATICALLY INITIATE THE FUNCTION DETAILED BELOW: MANUAL_ FIRE ALARM PULL STATION ACTIVATION OF THE MANUAL FIRE ALARM PULL STATION SHALL INITIATE THE FOLLOWING FUNCTIONS: 1. GENERATE AN AUDIBLE ALARM SIGNAL AT THE FACP AND AT THE REMOTE ANNUNCIATOR. 2. GENERATE AN AUDIBLE ALARM SIGNAL SIMULTANEOUSLY ON ALL AREAS OF THE BUILDING BY MEANS OF HORN DEVICES. GENERATE A VISUAL SIGNAL SIMULTANEOUSLY ON ALL AREAS OF THE BUILDING BY THE USE OF STROBE DEVICES OR COMBINATION HORN /STROBE NOTIFICATION DEVICES. 3. INDICATE THE LOCATION OF THE PULL STATION BY DISPLAYING, IN ENGLISH, THE ALARMED DEVICE AND ITS LOCATION ON THE FRCP ALPHANUMERIC DISPLAY AND ON THE REMOTE ANNUNCIATOR ALPHANUMERIC DISPLAY, 4. CLOSE CONTACTS WITHIN THE FACP FOR CENTRAL STATION MONITORING. 5, PROVIDE COILING FIRE DOORS AND DAMPERS ACTIVATION. .V I u u v vuv d� vvu ��� /�, •ss+ J �.- V z wC z J 6 P °�a vuuou uvuvV uutiuu LuVU.� k y .d < } W z4 V U U U u u u U u S (u u, ra j (a�i !%1• `a r..,s y W vvuu a uuuuu u u u u u Lvcrd 6 • w .a Lu . c) b c CI U %J 0 0 CJ (0 fl. SMOKE DETECTORS 11� ACTIVATION OF SMOKE DETECTORS SHALL INITIATE THE FOLLOWING FUNCTIONS: w d u w W z z 6- 0 1. GENERATE A SUPERVISORY SIGNAL AT THE FACP AND AT THE REMOTE ANNUNCIATOR., w 3 `TFi w (� F it d 2. INDICATE LOCATION OF THE SMOKE DETECTOR BY DISPLAYING, I ENGLISH, DISPLAYING, THE ALARMED DEVICE AND ITS oEtYc( U) f-90 LOCATION ON THE FACP ALPHANUMERIC DISPLAY AND ON THE REMOTE ANNUNCIATOR ALPHANUMERIC DISPLAY, I01`0-m� 2z 4. CLOSE CONTACTS WITHIN THE FACP FOR CENTRAL STATION MONITORING. IMM C�I1,A"C yl .1'2'1 r 0� wq c *JtDr"-[ (= 0 ,A-r �r'J'v� o i c d V J tLi w J J u- to u J 2� W° U 0Y [n r✓Jiti1 ��11r �-C° ��� ui DUCT DETECTORS " w C 1. GENERATE AN AUDIBLE ALARM SIGNAL AT THE FACP. W L>_. !a i 2. GENERATE AN AUDIBLE ALARM SIGNAL AT THE FACP FOR TROUBLESHOOTING. 2 tt 3. INDICATE -THE LOCATION OF THE DUCT SMOKE DETECTOR BY DISPLAYING, IN ENGLISH, THE ALARMED DEVICE AND N C ITS LOCATION ON THE FACP ALPHANUMERIC DISPLAY AND ON THE REMOTE ANNUNCIATOR ALPHANUMERIC DISPLAY. FIRE ('I11AL W 4. SHUT DOWN THE AIR HANDLING UNIT AND A/C EQUIPMENT ASSOCIATED WITH THE DUCT DETECTOR. Sim fN FP_RA(.X :. A curnFICATE cr OR PLACARD SF1f LL BE P m AF IL LL I1 5. CLOSE CONTACTS WITHIN THE FACP FOR CENTRAL STATION MONITORING TO REPORT SUPERVISORY .FINAL 11 PEC`J'101 J, A.4 P!-:R fgr-PA 72 i IN THE EVENT OF A TROUBLE CONDITION THE FOLLOWING FUNCTIONS WILL OCCUR ON THE PANEL : kIIZL; A1�- 1ItIv1 S ' STE:M TO I3IJ THE TROUBLE LED WILL FLASH �LNSTALIED IN AO( :ORDt' NCEWffli THE INTERNAL BUZZER WILL SOUND , t 17PA'72; 7 101- A 5 THE ALPHANUMERIC DISPLAY WILL SHOW 'THE ADDRESS AND MESSAGE FOR THE DEVICE IN TROUBLE L LS) @) 1 � -S n®feel =, THE FIRE ALARM PANEL WILL TRANSMIT A TROUBLE SIGNAL TO THE CENTRAL STATION VIA PDACT. fir, ) P 0!; IN -THE EVENT OF A SUPEERVISORY CONDITION THE FOLLOWING FUNCTIONS WILL OCCUR ON THE PANEL : f IA]MI -DAIDe 0,0UW Y F RED PAR TNI �. J m THE SUPERVISORY LED WILL FLASH BLDG. PE-RO61JT FIAEGUPPR.3410ra FIRE ALARM MAIWE T. ".� . THE INTERNAL BUZZER WILL SOUND •.-.. .r THE ALPHANUMERIC DISPLAY WILL SHOW THE ADDRESS AND MESSAGE FOR THE DEVICE IN SUPERVISORY �° t ° 4 (5 C) THE FIRE ALARM PANEL WILL TRANSMIT A SUPERVISORY SIGNAL TO THE CENTRAL STATION VIA DACT. bnr • NOTES: 1. SYSTEM IS A CERTli FICATED CENTRAL STATION SERVICE 2. ROOM CONTAINING 'THE FACP IS PROVIDED WITH AIR CONDITIONING. 3. BUILDING IS NOT SPRINKLERED. * SINGLE STANDARD SCL LOOP, NFPA STYLE 4. * SYSTEM IS A CENTRAL STATION FIRE ALARM SYSTEM. * POWER LIMITED SYSTEM. * NOTIFICATION APPLIANCE CIRCUITS STYLE Y. * 2 CONDUCTORS # 14, THHN OR EQUIVALENT FOR THE NOTIFICATION CIRCUIT. * NOTIFICATION APPLIANCES - MAXIMUN CURRENT PER CIRCUIT AS NOTED. * FOR SLC LOOP, 2 CONDUCTORS # 18 FPL OR APPROVED EQUAL. * NOTIFICATION CIRCUIT TO BE 15 DB ABOVE AMBIENT NOISE IN ALL AREAS. * DETECTORS MUST BE PLACED 3 FT MIN AWAY FROM ANY AIR DIFFUSER. O 11� U) w d u w W z z 6- 0 LL w F" m 0 w (� F it d Lu C U 2 U) f-90 J � S3 u 2z Ui z Uw /Y LY r 0� wq � 2f ° r C) Fe c d V J tLi w J J u- to u J 2� W° U 0Y [n ui s- " w C W W L>_. !a i 2 tt Lu `0 w N C F- W a) b {��0 cr ff o IL LL I1 rw LL cu L`_ 0' Z-E 0 OD .�. (Z) m (D cw 08002 ra ------------------ Date -- - - - - - - - - . -. I kale L LS) @) 1 � -S n®feel =, S3 U - - -- -- -...- -` v� (DI J m jrxa_� I I'I U) 0 C) cn _zb . C i N Lh Cu 0 4 U L � O 11� U) w d u w W 6- 0 LL w F" m 0 w (� F it d Lu C U 2 U) f-90 J � S3 u 2z Ui z Uw /Y LY r 0� wq � 2f ° r C) Fe c d V J tLi w J J u- to u J 2� W° U 0Y [n U s- " w C W L>_. !a i cf.) tt Lu `0 w V] W a) a {��0 t� ff o IL LL I1 rw LL cu L`_ 0' Z-E 0 OD .�. (Z) m (D cw 08002 ra ------------------ Date -- - - - - - - - - . -. I kale L LS) @) 1 � -S n®feel =, F- - - -- - - - -- -- -...- -` v� (DI jrxa_� I I'I U) 0 cn _zb . uJ O 11� 4JI 0 Ld 6- 0 LL F" m 0 v Z z w �- L 2z Ui z r 0� wq c �y CL Q 2� W° U 0Y [n I- W z 0 " Z LL I W L>_. !a i Z z tt GICJ V] W a t� w G a) IL LL I1 rw LL 0' 00 2 Project No. 08002 ------------------ Date -- - - - - - - - - . -. I kale L 01 -29 -2010 � -S n®feel =, F- - - -- - - - -- -- -...- -` IFA- F