Loading...
09-412-016Sys�2���� F T Ratings - 0, 314 and 3 Hr (See Item 2) L Rating At Ambient - 1 CFM /sq ft L Rating At 400 F - Less Than 1 CFMIsq ft W Rating - Class 1 (See Item 3A) §-A I I I- A Section A -A 1. Floor or Wall Assembly - Min 4 -1/2 in. (114 mm) thick reinforced lightweight or normal weight (100 -150 pcf or 1600 -2400 kglm3) concrete. Floor may also be constructed of any min 6 in. (152 mm) thick UL Classified hollow -core Precast Concrete Units* . Wall may also be constructed of any UL Classified Concrete Blocks* . Diam of opening to be min 3/8 in. (10 mm) to max 314 in. (19 mm) larger than outside diam of through penetrant. Max diam of opening Is in. (178 mm). See Concrete Blocks (CAZT) and Precast Concrete Units (CFTV) categories in the Fire Resistance Directory for names of manufacturers. 2. Through Penetrants - One nonmetallic pipe or conduit to be installed concentrically or eccentrically within the firestop system. The annular space between the pipe or conduit and the periphery of the opening shall be min 0 in. (0 mm, p oint contact ) to max 3/8 in. (10 mm) except as noted under Item 3D. Pipe or conduit to be rigidly supported on both sides of floor or wall. The following types and sizes of pipes or conduits may be used: A. Polyvinyl Chloride (PVC) Pipe - Nom 6 in. (152 mm) diam (or smaller) Schedule 40 solid core PVC pipe for use in closed (process or supply) or vented (drain, waste, or vent) piping systems. B. Acrylonitrile Butadiene Styrene (ABS) Pipe- Nom 6 in. (152 mm) diam (or smaller) Schedule 40 cellular or solid core ABS pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems. C. Chlorinated Polyvinyl Chloride (CPVC) Pipe - Nom 6 in. (152 mm) diam (or smaller) SDR 13.5 CPVC pipe for use in closed (process or supply) piping systems. D. Rigid Nonmetallic Conduit+ - Nom 6 in (152 mm) diam (or smaller) Schedule 40 PVC conduit installed in accordance with the National Electrical Code, (NFPA No. 701) E. Fiberglass Reinforced Pipe (FRP) - Nom 6 in. (152 mm) diam (or smaller) glass fiber reinforced thermosetting resin pipe for use in closed (process or control) or vented (drain, waste or vent) piping systems. The F and T Ratings of the firestop system are dependent upon the type of through penetrant used as tabulated belOW: T-T-FE of PENETRANT F RATING HR T RATING HR FVG PIPE 3 3 CFVC FIFE 3 3 FVC CONDUIT 3 3 AE35 PIPE 3 0 FRF FIFE 2 3/4 3. Firestop System - The firestop system shall consist of the following: A. Fill, Void or Cavity Material* -Sealant or Putty - Min 112 in. (13 mm) thickness of fill material applied within the annulus, flush with top surface of floor or with both surfaces of wall. At the point contact location between penetrating item and concrete, a min 114 in. (6 mm) diam bead of fill material shall be applied at the concrete /penetrating item interface on the top surface of floor and on both surfaces of wall. SPECIFIED TECHNOLOGIES INC - SpecSeal 100, 101, 102, 105, 120 or 129 Sealant, SpecSeal LCI Sealant, SpecSeal Putty, Pensil 300 Sealant, Pensil 300 S/L Sealant. W Rating applies only when Pensil 300 Sealant or Pensil 300 S/L Sealant is used in floors. B. Fill, Void or Cavity Material* -Wrap Strip - Nom 1 -112 in. {38 mm) wide by 114 in. (6 mm) thick or nom 2 in. (51 mm) wide by 118 in. (3.2 mm) or 3116 in. (4.8 mm) thick intumescent strips faced on both sides with a plastic film. In floor assemblies, two stacks of wrap strips, each consisting of three wrap strips, are individually wrapped around the through penetrant with the ends butted and held in place with masking tape. Butted ends in successive layers may be aligned or offset. The edge of the wrap strips shall abut the surface of the concrete floor or wall. In floor assemblies, the two stacks of wrap strips are installed on the bottom side of the concrete floor. In wall assemblies, the two stacks of wrap strips are installed on each side of the concrete wall. SPECIFIED TECHNOLOGIES INC - SpecSeal BLU Wrap Strip, SpecSeal BLU2 Wrap Strip or SpecSeal RED Wrap Strip recut 0.022 in. (0.6 mm) thick (No. 26 MSG) gale sheet steel available G. Steel Collar - Collar fabricated from coils of p from wrap strip manufacturer. Collar shall be nom 3 in. (76 mm) or 4 in. (102 mm) deep to accommodate wrap strip width with min six 1 in. (25 mm) wide by 2 in. (51 mm) long anchor tabs for securement to the concrete floor or wall. Retainer tabs, 3/4 in. (19 mm) wide tapering down to 3/8 in. (10 mm) wide and located opposite the anchor tabs, are folded 90 degree toward through - penetrant surface to maintain the annular space around the through- penetrant and to retain the wrap strips. Steel collar wrapped around wrap strips and through penetrant with a 1 in. (25 mm) wide overlap along its perimeter joint. Steel collar tightened around wrap strips and through penetrant using min 112 in. (13 mm) wide by 0.028 in. (0.7 mm) thick stainless steel hose clamp installed at midheight of the collar. Collar secured to concrete surface with 1/4 in. (6 mm) diam by min 1 -1/4 in. (32 mm) long steel concrete screws in conjunction with min 1 in. (25 mm) diam steel fender washers. D. Firestop Device* - (Not Shown) As an alternate to the wrap strip and the steel collar (Item Nos. 313 and 3C), a firestop device consisting of steel collar lined with an intumescent material sized to fit the specific diam of the nonmetallic through penetrant may be used. Device shall be installed in accordance with the accompanying installation instructions. Device incorporates anchor tabs for securement to bottom surface of floor or both surfaces of wall assembly by means of 1/4 in. (6 mm) diam by min 1 -1/4 in. (32 mm) long steel concrete screws in conjunction with min 1 in. (25 mm) diam steel fender washers. SPECIFIED TECHNOLOGIES INC - SpecSeal Firestop Collar, SpecSeal LCC Collar. When SpecSeal LCC Collar is used, the max annular space shall be 1/8 in. (3 mm) for max 2 -1/2 in. (64 mm) diam pipe or conduit and shall be max 114 in. (6 mm) for pipe or conduit larger than 2 -112 in. (64 mm) diam. +Bearing the UL Listing Mark *Bearing the UL Classification Mark Specified Technologies Inc. 200 Evans Way Somerville NJ 08876 -p g y � V - Reproduced courtesy of Underwriters Laboratories, Inc. L �T�T Created or Revised: MARCH -3 -2006 C -AJ -212 7 l 1 (8Dr0J992 -1180. (908)526 8000 •FAX (908)231 -8415 • E- Mail:techserv@stifirestop.com • Websitomww.stifirestop.corn PAGE 2 OF 1 _System No. C -AJ -5138 December 05, 2000 F Rating - 2 Hr T Ratings - 314 and 1 Hr (See Item 2) r-A IL --- A Section A -A 1. Floor or Wall Assembly - Min 2 -1/2 in. thick reinforced lightweight or normal weight (100 -150 pcf) concrete floor. Floor may also be constructed of any min 6 in. thick hollow -core Precast Concrete Units*. Wall may also be constructed of any UL Classified Concrete Blocks*. Max diam of opening is 12 in. Max diam of opening in floors constructed of hollow -core precast concrete units is 7 in. See Concrete Blocks (CAZT) or Precast Concrete Units (CFTV) categories in the Fire Resistance Directory for names of manufacturers. 2. Steel Sleeve (Optional) - Nom 12 in. diam (or smaller) Schedule 10 (or heavier) steel pipe cast or grouted into floor or wall assembly. Steel sleeve may be installed flush or may project a max 2 in. beyond the floor or wall surfaces. When steel sleeve is used, the T Rating is 314 hr. When steel sleeve is omitted in min 4 -112 in. thick concrete, the T Rating is 1 hr. 3. Through Penetrant - One metallic pipe or tube to be installed eccentrically or concentrically within the firestop system. Pipe or tube to be rigidly supported on both sides of the floor or wall assembly. The following types and sizes of metallic pipes and tubes may be used: A. Steel Pipe - Nom 6 in. diam (or smaller) Schedule 5 (or heavier) steel pipe. B. Iron Pipe - Nom 6 in. diam (or smaller) cast or ductile iron pipe. C. Copper Pipe - Nom 4 in. diam (or smaller) Regular (or heavier) copper pipe. D. Copper Tube - Nom 4 in. diarn (or smaller) Regular L (or heavier) copper tube. 4. Pipe Coverings - One of the following types of pipe coverings shall be used: A. Pipe and Equipment Covering Materials* - Nom 2 in. thick hollow cylindrical heavy density (min 3.5 pcf) glass fiber units jacketed on the outside with an all service jacket. Longitudinal joints sealed with metal fasteners or factory - applied self - sealing lap tape. Transverse joints secured with metal fasteners or butt tape supplied with the product. See Pipe and Equipment Covering Materials (BRGU) category in the Building Materials Directory for names of manufacturers. Any pipe covering material meeting the above specifications and bearing the UL Classification Marking with a Flame Spread Index of 25 or less and a Smoke Developed Index of 50 or less may be used. B. Pipe Covering Materials* - Nom 2 in. thick unfaced mineral fiber pipe insulation having a nom density of 3.5 pcf (or heavier) and sized to the outside diam of pipe or tube. Pipe insulation secured with min No. 8 AWG steel wire spaced max 12 in. OC. OWENS CORNING HT INC, DIV OF OWENS CORNING - High Temperature Pipe Insulation 1200, High Temperature Pipe Insulation BWT and High Temperature Pipe Insulation Thermaloc C. Sheathing Material* -Used in conjunction with Item 4B. Foil- scrim -kraft or all service jacket material shall be wrapped around the outer circumference of the pipe insulation (Item 4B) with the kraft side exposed. Longitudinal joints and transverse joints sealed with metal fasteners or butt tape. See Sheathing Materials (BVDV) category in the Building Materials Directory for names of manufacturers. Any sheathing material meeting the above specifications and bearing the UL Classification Marking with a Flame Spread Index of 25 or less and a Smoke Developed Index of 50 or less may be used. 5. Firestop System - The firestop system shall consist of the following: A. Packing Material - Min 4 pcf mineral wool batt insulation compressed and tightly packed into opening as a permanent form . Packing material recessed from top surface of floor or both surfaces of wall as required to accommodate fill material (Item 5B). In floors constructed of hollow -core precast concrete units, packing material to be recessed from both top and bottom surfaces of floor, as required to accommodate fill material (Item 5B). When steel sleeve projects from top of floor or from both sides of wall, the thickness of mineral wool batt packing material should be increased by an amount equal to the distance that the sleeve extends past the floor or wall surface. Packing material depth is dependent upon several variables, as shown in the table under Item 5B. B. Fill, Void or Cavity Material* - Sealant - Fill material applied within annulus, flush with top surface of floor assembly or top edge of steel sleeve. In walls, fill material applied within annulus flush with both surfaces of wall assembly or both ends of steel sleeve. In floors constructed of hollow -care precast concrete units, fill material installed symmetrically on both surfaces of floor. Fill material depth is dependent upon several variables, as shown in the following table: MIN FLOOD: Ofi' ANNULAfiz 1�'l1N F'ACKINC� MIN WALL SPACE, MAT��IAI_ FILL 1"IATFzFI,4L THICKNESS, IN- IN. pEPTN, IN. I�EPTN, IN. 2 -1/2 114 TO 5/8 1 -1/2 1 4 -1/2 1/4 TO 1 5/8 3 1/2 SPECIFIED TECHNOLOGIES INC - SpecSeal LCI Sealant `Bearing the UL Classification Mark 7V- Specified Technologies Inc. 200 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. @C;_AJ-513� Created or Revised: DECEMBER - 5,2000 STI(aOO)992 -1180 • (908)526 -8000 • FAX(908)231 -8415 • E- Mail:techserv@stifirestop.com •website:vvwvv.stifire5top.com PAGE I OF I Svstem No. W -L -2188 F Rating - 1 or 2 Hr T Rating - 1 or 2 Hr L Rating At Ambient - Less Than 1 CFM /sq ft L Rating At 400 F - Less Than 1 CFM /sq ft LA seCtlorl A °A 1. Wall Assembly - The 1 or 2 hr fire -rated gypsum wallboard /stud wall assembly shall be constructed of the materials and in the manner specified in the individual U300 or U400 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following construction features: A. Studs - Wall framing may consist of either wood or steel channel studs. Wood studs to consist of nom 2 by 4 in. (51 by 102 mm) lumber spaced max 24 in. (610 mrn) OC. Steel studs to be min 3 -1/2 in. (89 mm) wide and spaced max 24 in. (610 mm) OC. B. Gypsum Board* - 5/8 in. (16 mm) thick, 4 ft (1219 mm) wide with square or tapered edges. The gypsum wallboard type, thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual U300 or U400 Series Design in the UL Fire Resistance Directory. Max diam of opening is 12 in. (305 mm)_ The hourly F and T Ratings of the firestop system are equal to the hourly fire rating of the wall assembly in which it is installed. 2. Metallic Sleeve - (Optional) -- Nom 12 in. (305 mrn) diam (or smaller) cylindrical sleeve fabricated ) ( from min 0.016 in. 0.4 mm thick (28 gauge) galvanized steel and having a min 2 in. (51 mm) lap at the longitudinal seam. Sleeve friction fitted into wall assembly, flush with wall surfaces. 3. Through Penetrants - One nonmetallic pipe to be installed within the opening. A nom annular space of 5/8 in. (16 mm) is required within the firestop system. Pipe to be rigidly supported on both sides of wall assembly. The following types and sizes of nonmetallic pipe may be used: A. Polyvinyl Chloride (PVC) Pipe - Nom 10 in. (254 mm) diam (or smaller) Schedule 40 PVC Pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems. B. Chlorinated Polyvinyl Chloride (CPVC) Pipe - Nom 10 in. (254 mm) diam (or smaller) SDR 13.5 CPVC pipe for use in closed (process or supply) piping systems. 4. Firestop System - The firestop system shall consist of the following: A. Packing Material Min 4 pcf (64 kg /m3) mineral wool insulation cut to size to fill the annulus within the opening and stud cavity. Mineral wool insulation wrapped around the outer circumferences of the through penetrant and secured together by means of No. 24 AWG steel tie wire when steel sleeve (Item 2) is not used. Mineral wool insulation slid into annulus of opening and recessed from both surfaces of wall to accommodate the required thickness of fill material. B. Fill Void or Cavity Materials* - Sealant - Min 112 in. (13 mrn) thickness of fill material applied within the annulus, flush with both surfaces of wall assembly. SPECIFIED TECHNOLOGIES INC - SpecSeal 100, 101, 102, 105,120 or 129 Sealant. C. Aluminum Foil Tape - (Not shown) - Nom 3 mil (0.08 mm) thick pressure sensitive aluminum foil tape wrapped around the outer circurnference of the through penetrant with a 1 in. (25 mm)wide overlap along its perimeter joint. Foil tape shall abut against both surfaces of the wall and extend a min 6 in. (152 mrn) from both surfaces of the wall. D. Fill Void or Cavity Materials -Wrap Strip - Nom 1/8 or 3/16 in. (3.2 or 4.8 mrn) thick intumescent material faced on both sides with a plastic film, supplied in 2 in. (51 mm) wide strips_ Two and one -half stacks (5 in. or 127 mm height) of wrap strips are individually or continuously wrapped around the through penetrant. Each stack shall consist of four layers. When wrap strips are individually wrapped, ends of wrap strips shall be butted and held in place with tape, Butted ends in successive layers may be aligned or offset. The edge of the wrap strips shall abut the surface of the wall assembly. In wall assemblies, the two and one -half stacks of wrap strips are installed on each side of the gypsum wallboard wall. SPECIFIED TECHNOLOGIES INC - SpecSeal BLU Wrap Strip or SpecSeal BLU2 Wrap Strip E. Steel Collar - Collar fabricated from coils of precut 0.029 in. (0.7 mm) thick (No. 22 MSG) galv sheet steel available from wrap strip manufacturer. Collar shall be nom 5 in. (127 mrn) deep with min six 1 in. (25 mm) wide by 2 in. (51 mm) long anchor tabs for securement to the wall. Retainer tabs, 314 in. (19 mm) wide tapering down to 1/4 in. (6 mm) wide and located opposite the anchor tabs, are folded 90 degrees toward through penetrant and to maintain the annular space around wrap strips and through penetrant and to retain the wrap strips. Steel collar wrapped around wrap strips and through penetrant with a 1 in. (25 mm) wide overlap along its perimeter joint. Steel collar tightened around wrap strips and through penetrant using min 112 in. (13 mm) wide by 0.028 in. (0.7 mm) thick stainless steel hose clamps located 1 in. (25 mm) from wall surface and spaced 2 in. (51 mrn) OC. Collar secured to wall with 1/4 in. diam by min 1 -3/4 in. (45 mm) long steel molly bolts in conjunction with min 114 in. (6 mm) by 1 -1/4 in. (32 mm) diam steel fender washers. *Bearing the UL Classification Mark ® Specified Technologies Inc 200 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. Created or Revised: OCTOBER -14 -2003 &W -L -2188 STI(000)992-1180 • (908)526 -8000 • FAX(908)231 -8415 • E- Mail:techsery @stifirestop.com • Website:wwwstifirestol` PAGE 2 O I System Na. W -J -1098 F Rating - 2 Hr T Ratings - 1/4, 3/4 and 1 Hr (See Item 2) A I I I v A Section A -A 1. Wall Assembly Min 6 in. (152 mm) thick reinforced lightweight or normal weight (100 -150 pof or 1600 -2400 kg /m3) concrete. Wall may also be constructed of any UL Classified Concrete Blocks *. Max diam of opening is 2 in. (51 mm) larger than OD of through penetrant. See Concrete Blocks (CAZT) category in the Fire Resistance Directory for names or manufacturers. 2. Through Penetrant One metallic pipe, conduit or tube to be installed eccentrically or concentrically within the firestop system. Pipe, conduit or tubing may be installed at an angle not greater than 45 degrees from perpendicular to the wall surface. The annular space between the pipe, conduit or tube and the periphery of the opening shall be min 0 in. (0 mm, point contact) to max 2 in. (51 mm). Pipe, conduit or tube to be rigidly supported on both sides of the wall assembly. The following types and sizes of metallic pipes, conduits and tubes may be used: A. Steel Pipe Nom 8 in. (203 mm) diam (or smaller) Schedule 5 (or heavier) steel pipe. B. Iron Pipe Nom 8 in. (203 mm) diam (or smaller) cast or ductile iron pipe. C. Conduit Nom 6 in. (152 mm) diam (or smaller) rigid steel conduit, nom 4 in. (102 mm) diam (or smaller) steel electrical metallic tubing (EMT) or nom 4 in. (102 mm) diam (or smaller) flexible steel conduit. D. Copper Pipe Nom 4 in. (102 mm) diam (or smaller) Regular (or heavier) copper pipe. E_ Copper Tube Norn 4 in. (102 mm) diam (or smaller) Type L (or heavier) copper tube. TYPE OF PENETRANT MAX DIAM T RATINCs STEEL OR IRON PIPF, STEI =1- CONDUIT OR EMT 21N. (51 MM) I HR STEEL OR IRON PIPE, STEEL CONDUIT OR EMT BIN. (203 MM) 3/4 HR COi=pER f IFF= OR TUBE 21N. (102 MM) 1/4 HR 2A. Through Penetrating Product* -Flexible Metal Piping As an alternate to Item 2, one nom 1 -114 in. (3 mm) ar aoe between steel flexible metal pipe to be installed either concentrically or eccentrically within the firestop system. Th e annular p the p ipe and the periphery of the opening shall be min 0 in. (0 mm, point contact) to max 2 in. (51 mm). Pipe to be rigidly supported on both sides of the wall assembly. When flexible metal piping is used, T Rating is 1 hr. OMEGA FLEX INC TITEFLEX CORP A BUNDY CO WARD MFG INC Cavity Material* - Sealant Min 518 in. (16 mm) thickness of fill material applied within annulus, flush with both 3. Fill, Void o r y in 114 in. (6 mm) diam bead of fill material applied at metallic pipe/concrete surfaces of wall assembly. At point contact location, m interface on both surfaces of wall. SPECIFIED TECHNOLOGIES INC - SpecSeal LCI Sealant *Bearing the UL Classification Mark _ - Specified Technologies Inc 200 Evans Way Somerville, NJ 08876 Reproduced co y urtes of Underwriters Laboratories, Inc. e Created or Revised: September 24, 2004 W -J -198 STI(800)992 -1180 • (908)526 -8000 • FAX(908)231 -8415 • E- Mail:techsery @stifirestop.com • Website:www.stifirestop.com PAGE I OF I System No. W -L -1222 F Ratings - 1 and 2 Hr (See Item 1) T Ratings - 114, 314 and 1 Hr (See Item 2) F--A i 1 I 1B A Section A -A Wall Assembly - The 1 or 2 hr fire -rated gypsum board /stud wall assembly shall be constructed of the materials and in the manner specified in the individual U300 or U400 Series Wall or Partition Design in the UL Fire Resistance Directory and shall include the following construction features: A. Studs - Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. (51 by 102 mm lumber spaced 16 in. (406 mm) OC. Steel studs to be min 3 -112 in. (89 mm) wide and spaced max 24 in. (610 mm) OC. B. Gypsum Board* - Thickness, type, number of layers and fasteners as specified in the individual Wall and Partition Design. Max diam of opening is 10 -518 in. (270 mm). The hourly F Rating of the firestop system is equal to the hourly fire rating of the wall assembly in which it is installed. 2. Through Penetrant - One metallic pipe, conduit or tube to be installed eccentrically or concentrically within the firestop system. Pipe, conduit or tubing may be installed at an angle not greater than 45 degrees from perpendicular. The annular space between the pipe, conduit or tube and the periphery of the opening shall be min 0 in. (0 mm, point contact) to max 2 in. (51 mm). Pipe, conduit ortube to be rigidly supported on both sides of the wall assembly. The following types and sizes of metallic pipes, conduits and tubes may be used: A. Steel Pipe - Nom 8 in. (203 mm) diam (or smaller) Schedule 5 (or heavier) steel pipe. B. Iron Pipe - Nom 8 in. (203 mm) diam (or smaller) cast or ductile iron pipe. C. Conduit - Nom 6 in. (152 mm) diam (or smaller) rigid steel conduit, nom 4 in. (102 mm) diam (or smaller) steel electrical metallic tubing (EMT) or nom 4 in. (102 mm) diam (or smaller) flexible steel conduit. D. Copper Pipe - Nom 4 in. (102 mm) diam (or smaller) Regular (or heavier) copper pipe. E. Copper Tube - Nom 4 in. (102 mm) diam (or smaller) Type L (or heavier) copper tube. TYPE OF PENETRANT MAX DIAM T RATING STEEL OR IRON PIPE, STEEL 21N. (51 MM) I HR CONDUIT OR EMT AA 0003014 STEEL OR IRON PIPE, STIFEL alN. (203 MM) 3/4 HR CONDUIT OR EMT 1526 N.W. 89th CT COPPER PIPE OR TUBE 21N. (102 MM) 1 1/4 HR 2A. Through Penetrating Product* - Flexible Metal Piping - As an alternate to Item 2, one nom 1 -1 /4 in. (32 mm) diam (or smaller) steel flexible metal pipe to be installed either concentrically or eccentrically within the firestop system. The annular space between the pipe and the periphery of the opening shall be min 0 in. (0 mm, point contact) to max 2 in. (51 mm). Pipe to be rigidly supported on both sides of the wall assembly. OMEGA FLEX INC TITEFLEX CORP A BUNDY CO WARD MFG INC of 3. Fill, Void or Cavity Material"` - Sealant - Min 5/8 in. (16 mm) thickness m fill material applied within pe/guyus, flush with both surfaces h wall assembly. At point contact location, min 1/4 in. (6 mm) diam bead of fill material applied at metallic i e/ psum board interface on both surface s of wall. SPECIFIED TECHNOLOGIES INC - SpecSeal LCI Sealant *Bearing the UL Classification Mark Specified Technologies Inc 200 Evans Way Somerville, NJ 08876 -- Reproduced courtesy of Underwriters Laboratories, Inc. �� Created or Revised: July 26, 2006 � W -L -1222 STI(500)992 -1180 • (908)526 -8000 • FAX (908)231 -8415 • E- Mail:techsery @stifirestop.corn • Website:www.stifirestop.com PAGE I OF 1 C DrETAILS 4 NOTES SCALE AS NOTED PROJECT NO. 091016 DATE 03.18.09 REVISIONS: SHEET A9.2 OF 20 ARLOS DIAZ & ASSOC. ARCHITECTS, PA AA 0003014 ARCHITECTURE INTERIOR DESIGN 1526 N.W. 89th CT MIAMI, FLORIDA 33172 TEL: 305 599 2888 FAX: 305 599 3885 1997 cARI -o5 pIAX a ASSOC. ARCHITFGT5, PA. ne Design and Drawings for this Project are the roperty or the Architect and are protected under e Capyrlght Protection Act. ARCHITECTURE c.ARL05 DIAZ 0%31 1526 N.W. 89th CT. MIAMI, FL 33112 PH: (305) 599 -2888 U Z J 62 uJ O Z M w O J a Q > W O t/1 z W oG Q O ry) x Vw Ln Z O TERAHEN, INC. A Florida Corporation 6333 8UN5ET PR SOUTH MIAMI, FLORIDA 33143 DrETAILS 4 NOTES SCALE AS NOTED PROJECT NO. 091016 DATE 03.18.09 REVISIONS: SHEET A9.2 OF 20