09-412-016Sys�2����
F
T Ratings - 0, 314 and 3 Hr (See Item 2)
L Rating At Ambient - 1 CFM /sq ft
L Rating At 400 F - Less Than 1 CFMIsq ft
W Rating - Class 1 (See Item 3A)
§-A
I
I
I- A
Section A -A
1. Floor or Wall Assembly - Min 4 -1/2 in. (114 mm) thick reinforced lightweight or normal weight (100 -150 pcf or
1600 -2400 kglm3) concrete. Floor may also be constructed of any min 6 in. (152 mm) thick UL Classified hollow -core
Precast Concrete Units* . Wall may also be constructed of any UL Classified Concrete Blocks* . Diam of opening to
be min 3/8 in. (10 mm) to max 314 in. (19 mm) larger than outside diam of through penetrant. Max diam of opening Is
in. (178 mm).
See Concrete Blocks (CAZT) and Precast Concrete Units (CFTV) categories in the Fire Resistance Directory for
names of manufacturers.
2. Through Penetrants - One nonmetallic pipe or conduit to be installed concentrically or eccentrically within the
firestop system. The annular space between the pipe or conduit and the periphery of the opening shall be min 0 in. (0
mm, p oint contact ) to max 3/8 in. (10 mm) except as noted under Item 3D. Pipe or conduit to be rigidly supported on
both sides of floor or wall. The following types and sizes of pipes or conduits may be used:
A. Polyvinyl Chloride (PVC) Pipe - Nom 6 in. (152 mm) diam (or smaller) Schedule 40 solid core PVC pipe for use in
closed (process or supply) or vented (drain, waste, or vent) piping systems.
B. Acrylonitrile Butadiene Styrene (ABS) Pipe- Nom 6 in. (152 mm) diam (or smaller) Schedule 40 cellular or solid
core ABS pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems.
C. Chlorinated Polyvinyl Chloride (CPVC) Pipe - Nom 6 in. (152 mm) diam (or smaller) SDR 13.5 CPVC pipe for use
in closed (process or supply) piping systems.
D. Rigid Nonmetallic Conduit+ - Nom 6 in (152 mm) diam (or smaller) Schedule 40 PVC conduit installed in
accordance with the National Electrical Code, (NFPA No. 701)
E. Fiberglass Reinforced Pipe (FRP) - Nom 6 in. (152 mm) diam (or smaller) glass fiber reinforced thermosetting resin
pipe for use in closed (process or control) or vented (drain, waste or vent) piping systems.
The F and T Ratings of the firestop system are dependent upon the type of through penetrant used as tabulated
belOW:
T-T-FE of PENETRANT
F RATING HR
T RATING HR
FVG PIPE
3
3
CFVC FIFE
3
3
FVC CONDUIT
3
3
AE35 PIPE
3
0
FRF FIFE
2
3/4
3. Firestop System - The firestop system shall consist of the following:
A. Fill, Void or Cavity Material* -Sealant or Putty - Min 112 in. (13 mm) thickness of fill material applied within the
annulus, flush with top surface of floor or with both surfaces of wall. At the point contact location between penetrating
item and concrete, a min 114 in. (6 mm) diam bead of fill material shall be applied at the concrete /penetrating item
interface on the top surface of floor and on both surfaces of wall.
SPECIFIED TECHNOLOGIES INC - SpecSeal 100, 101, 102, 105, 120 or 129 Sealant, SpecSeal LCI Sealant,
SpecSeal Putty, Pensil 300 Sealant, Pensil 300 S/L Sealant. W Rating applies only when Pensil 300 Sealant or
Pensil 300 S/L Sealant is used in floors.
B. Fill, Void or Cavity Material* -Wrap Strip - Nom 1 -112 in. {38 mm) wide by 114 in. (6 mm) thick or nom 2 in. (51
mm) wide by 118 in. (3.2 mm) or 3116 in. (4.8 mm) thick intumescent strips faced on both sides with a plastic film. In
floor assemblies, two stacks of wrap strips, each consisting of three wrap strips, are individually wrapped around the
through penetrant with the ends butted and held in place with masking tape. Butted ends in successive layers may be
aligned or offset. The edge of the wrap strips shall abut the surface of the concrete floor or wall. In floor assemblies,
the two stacks of wrap strips are installed on the bottom side of the concrete floor. In wall assemblies, the two stacks
of wrap strips are installed on each side of the concrete wall.
SPECIFIED TECHNOLOGIES INC - SpecSeal BLU Wrap Strip, SpecSeal BLU2 Wrap Strip or SpecSeal RED Wrap
Strip
recut 0.022 in. (0.6 mm) thick (No. 26 MSG) gale sheet steel available
G. Steel Collar - Collar fabricated from coils of p
from wrap strip manufacturer. Collar shall be nom 3 in. (76 mm) or 4 in. (102 mm) deep to accommodate wrap strip
width with min six 1 in. (25 mm) wide by 2 in. (51 mm) long anchor tabs for securement to the concrete floor or wall.
Retainer tabs, 3/4 in. (19 mm) wide tapering down to 3/8 in. (10 mm) wide and located opposite the anchor tabs, are
folded 90 degree toward through - penetrant surface to maintain the annular space around the through- penetrant and
to retain the wrap strips. Steel collar wrapped around wrap strips and through penetrant with a 1 in. (25 mm) wide
overlap along its perimeter joint. Steel collar tightened around wrap strips and through penetrant using min 112 in. (13
mm) wide by 0.028 in. (0.7 mm) thick stainless steel hose clamp installed at midheight of the collar. Collar secured to
concrete surface with 1/4 in. (6 mm) diam by min 1 -1/4 in. (32 mm) long steel concrete screws in conjunction with min
1 in. (25 mm) diam steel fender washers.
D. Firestop Device* - (Not Shown) As an alternate to the wrap strip and the steel collar (Item Nos. 313 and 3C), a
firestop device consisting of steel collar lined with an intumescent material sized to fit the specific diam of the
nonmetallic through penetrant may be used. Device shall be installed in accordance with the accompanying
installation instructions. Device incorporates anchor tabs for securement to bottom surface of floor or both surfaces of
wall assembly by means of 1/4 in. (6 mm) diam by min 1 -1/4 in. (32 mm) long steel concrete screws in conjunction
with min 1 in. (25 mm) diam steel fender washers.
SPECIFIED TECHNOLOGIES INC - SpecSeal Firestop Collar, SpecSeal LCC Collar. When SpecSeal LCC Collar is
used, the max annular space shall be 1/8 in. (3 mm) for max 2 -1/2 in. (64 mm) diam pipe or conduit and shall be max
114 in. (6 mm) for pipe or conduit larger than 2 -112 in. (64 mm) diam.
+Bearing the UL Listing Mark
*Bearing the UL Classification Mark
Specified Technologies Inc. 200 Evans Way Somerville NJ 08876
-p g y � V
- Reproduced courtesy of Underwriters Laboratories, Inc. L
�T�T Created or Revised: MARCH -3 -2006 C -AJ -212
7 l 1 (8Dr0J992 -1180. (908)526 8000 •FAX (908)231 -8415 • E- Mail:techserv@stifirestop.com • Websitomww.stifirestop.corn PAGE 2 OF 1
_System No. C -AJ -5138
December 05, 2000
F Rating - 2 Hr
T Ratings - 314 and 1 Hr (See Item 2)
r-A
IL --- A
Section A -A
1. Floor or Wall Assembly - Min 2 -1/2 in. thick reinforced lightweight or normal weight (100 -150 pcf) concrete floor.
Floor may also be constructed of any min 6 in. thick hollow -core Precast Concrete Units*. Wall may also be constructed
of any UL Classified Concrete Blocks*. Max diam of opening is 12 in. Max diam of opening in floors constructed of
hollow -core precast concrete units is 7 in.
See Concrete Blocks (CAZT) or Precast Concrete Units (CFTV) categories in the Fire Resistance Directory for names
of manufacturers.
2. Steel Sleeve (Optional) - Nom 12 in. diam (or smaller) Schedule 10 (or heavier) steel pipe cast or grouted into floor
or wall assembly. Steel sleeve may be installed flush or may project a max 2 in. beyond the floor or wall surfaces. When
steel sleeve is used, the T Rating is 314 hr. When steel sleeve is omitted in min 4 -112 in. thick concrete, the T
Rating is 1 hr.
3. Through Penetrant - One metallic pipe or tube to be installed eccentrically or concentrically within the firestop
system. Pipe or tube to be rigidly supported on both sides of the floor or wall assembly. The following types and sizes of
metallic pipes and tubes may be used:
A. Steel Pipe - Nom 6 in. diam (or smaller) Schedule 5 (or heavier) steel pipe.
B. Iron Pipe - Nom 6 in. diam (or smaller) cast or ductile iron pipe.
C. Copper Pipe - Nom 4 in. diam (or smaller) Regular (or heavier) copper pipe.
D. Copper Tube - Nom 4 in. diarn (or smaller) Regular L (or heavier) copper tube.
4. Pipe Coverings - One of the following types of pipe coverings shall be used:
A. Pipe and Equipment Covering Materials* - Nom 2 in. thick hollow cylindrical heavy density (min 3.5 pcf) glass fiber
units jacketed on the outside with an all service jacket. Longitudinal joints sealed with metal fasteners or
factory - applied self - sealing lap tape. Transverse joints secured with metal fasteners or butt tape supplied with the
product.
See Pipe and Equipment Covering Materials (BRGU) category in the Building Materials Directory for names of
manufacturers. Any pipe covering material meeting the above specifications and bearing the UL Classification Marking
with a Flame Spread Index of 25 or less and a Smoke Developed Index of 50 or less may be used.
B. Pipe Covering Materials* - Nom 2 in. thick unfaced mineral fiber pipe insulation having a nom density of 3.5 pcf (or
heavier) and sized to the outside diam of pipe or tube. Pipe insulation secured with min No. 8 AWG steel wire spaced
max 12 in. OC.
OWENS CORNING HT INC, DIV OF
OWENS CORNING - High Temperature Pipe Insulation 1200, High Temperature Pipe Insulation BWT and High
Temperature Pipe Insulation Thermaloc
C. Sheathing Material* -Used in conjunction with Item 4B. Foil- scrim -kraft or all service jacket
material shall be
wrapped around the outer circumference of the pipe insulation (Item 4B) with the kraft side exposed. Longitudinal
joints and transverse joints sealed with metal fasteners or butt tape.
See Sheathing Materials (BVDV) category in the Building Materials Directory for names of manufacturers. Any
sheathing material meeting the above specifications and bearing the UL Classification Marking with a Flame Spread
Index of 25 or less and a Smoke Developed Index of 50 or less may be used.
5. Firestop System - The firestop system shall consist of the following:
A. Packing Material - Min 4 pcf mineral wool batt insulation compressed and tightly packed into opening as a
permanent form . Packing material recessed from top surface of floor or both surfaces of wall as required to
accommodate fill material (Item 5B). In floors constructed of hollow -core precast concrete units, packing material to
be recessed from both top and bottom surfaces of floor, as required to accommodate fill material (Item 5B). When
steel sleeve projects from top of floor or from both sides of wall, the thickness of mineral wool batt packing material
should be increased by an amount equal to the distance that the sleeve extends past the floor or wall surface.
Packing material depth is dependent upon several variables, as shown in the table under Item 5B.
B. Fill, Void or Cavity Material* - Sealant - Fill material applied within annulus, flush with top surface of floor assembly
or top edge of steel sleeve. In walls, fill material applied within annulus flush with both surfaces of wall assembly or
both ends of steel sleeve. In floors constructed of hollow -care precast concrete units, fill material installed
symmetrically on both surfaces of floor. Fill material depth is dependent upon several variables, as shown in the
following table:
MIN FLOOD: Ofi'
ANNULAfiz
1�'l1N F'ACKINC�
MIN
WALL
SPACE,
MAT��IAI_
FILL 1"IATFzFI,4L
THICKNESS, IN-
IN.
pEPTN, IN.
I�EPTN, IN.
2 -1/2
114 TO 5/8
1 -1/2
1
4 -1/2
1/4 TO 1 5/8
3
1/2
SPECIFIED TECHNOLOGIES INC - SpecSeal LCI Sealant
`Bearing the UL Classification Mark
7V- Specified Technologies Inc. 200 Evans Way Somerville, NJ 08876
Reproduced courtesy of Underwriters Laboratories, Inc. @C;_AJ-513�
Created or Revised: DECEMBER - 5,2000
STI(aOO)992 -1180 • (908)526 -8000 • FAX(908)231 -8415 • E- Mail:techserv@stifirestop.com •website:vvwvv.stifire5top.com PAGE I OF I
Svstem No. W -L -2188
F Rating - 1 or 2 Hr
T Rating - 1 or 2 Hr
L Rating At Ambient - Less Than 1 CFM /sq ft
L Rating At 400 F - Less Than 1 CFM /sq ft
LA
seCtlorl A °A
1. Wall Assembly - The 1 or 2 hr fire -rated gypsum wallboard /stud wall assembly shall be
constructed of the materials and in the manner specified in the individual U300 or U400 Series Wall
and Partition Designs in the UL Fire Resistance Directory and shall include the following construction
features:
A. Studs - Wall framing may consist of either wood or steel channel studs. Wood studs to consist of
nom 2 by 4 in. (51 by 102 mm) lumber spaced max 24 in. (610 mrn) OC. Steel studs to be min 3 -1/2
in. (89 mm) wide and spaced max 24 in. (610 mm) OC.
B. Gypsum Board* - 5/8 in. (16 mm) thick, 4 ft (1219 mm) wide with square or tapered edges. The
gypsum wallboard type, thickness, number of layers, fastener type and sheet orientation shall be
as specified in the individual U300 or U400 Series Design in the UL Fire Resistance Directory. Max
diam of opening is 12 in. (305 mm)_
The hourly F and T Ratings of the firestop system are equal to the hourly fire rating of the
wall assembly in which it is installed.
2. Metallic Sleeve - (Optional) -- Nom 12 in. (305 mrn) diam (or smaller) cylindrical sleeve fabricated
)
(
from min 0.016 in. 0.4 mm thick (28 gauge) galvanized steel and having a min 2 in. (51 mm) lap at
the longitudinal seam. Sleeve friction fitted into wall assembly, flush with wall surfaces.
3. Through Penetrants - One nonmetallic pipe to be installed within the opening. A nom annular
space of 5/8 in. (16 mm) is required within the firestop system. Pipe to be rigidly supported on both
sides of wall assembly. The following types and sizes of nonmetallic pipe may be used:
A. Polyvinyl Chloride (PVC) Pipe - Nom 10 in. (254 mm) diam (or smaller) Schedule 40 PVC Pipe
for use in closed (process or supply) or vented (drain, waste or vent) piping systems.
B. Chlorinated Polyvinyl Chloride (CPVC) Pipe - Nom 10 in. (254 mm) diam (or smaller) SDR 13.5
CPVC pipe for use in closed (process or supply) piping systems.
4. Firestop System - The firestop system shall consist of the following:
A. Packing Material Min 4 pcf (64 kg /m3) mineral wool insulation cut to size to fill the annulus within
the opening and stud cavity. Mineral wool insulation wrapped around the outer circumferences of
the through penetrant and secured together by means of No. 24 AWG steel tie wire when steel
sleeve (Item 2) is not used. Mineral wool insulation slid into annulus of opening and recessed from
both surfaces of wall to accommodate the required thickness of fill material.
B. Fill Void or Cavity Materials* - Sealant - Min 112 in. (13 mrn) thickness of fill material applied
within the annulus, flush with both surfaces of wall assembly.
SPECIFIED TECHNOLOGIES INC - SpecSeal 100, 101, 102, 105,120 or 129 Sealant.
C. Aluminum Foil Tape - (Not shown) - Nom 3 mil (0.08 mm) thick pressure sensitive aluminum foil
tape wrapped around the outer circurnference of the through penetrant with a 1 in. (25 mm)wide
overlap along its perimeter joint. Foil tape shall abut against both surfaces of the wall and extend a
min 6 in. (152 mrn) from both surfaces of the wall.
D. Fill Void or Cavity Materials -Wrap Strip - Nom 1/8 or 3/16 in. (3.2 or 4.8 mrn) thick
intumescent material faced on both sides with a plastic film, supplied in 2 in. (51 mm) wide strips_
Two and one -half stacks (5 in. or 127 mm height) of wrap strips are individually or continuously
wrapped around the through penetrant. Each stack shall consist of four layers. When wrap strips
are individually wrapped, ends of wrap strips shall be butted and held in place with tape, Butted
ends in successive layers may be aligned or offset. The edge of the wrap strips shall abut the
surface of the wall assembly. In wall assemblies, the two and one -half stacks of wrap strips are
installed on each side of the gypsum wallboard wall.
SPECIFIED TECHNOLOGIES INC - SpecSeal BLU Wrap Strip or SpecSeal BLU2 Wrap Strip
E. Steel Collar - Collar fabricated from coils of precut 0.029 in. (0.7 mm) thick (No. 22 MSG) galv
sheet steel available from wrap strip manufacturer. Collar shall be nom 5 in. (127 mrn) deep with
min six 1 in. (25 mm) wide by 2 in. (51 mm) long anchor tabs for securement to the wall. Retainer
tabs, 314 in. (19 mm) wide tapering down to 1/4 in. (6 mm) wide and located opposite the anchor
tabs, are folded 90 degrees toward through penetrant and to maintain the annular space around
wrap strips and through penetrant and to retain the wrap strips. Steel collar wrapped around wrap
strips and through penetrant with a 1 in. (25 mm) wide overlap along its perimeter joint. Steel collar
tightened around wrap strips and through penetrant using min 112 in. (13 mm) wide by 0.028 in.
(0.7 mm) thick stainless steel hose clamps located 1 in. (25 mm) from wall surface and spaced 2 in.
(51 mrn) OC. Collar secured to wall with 1/4 in. diam by min 1 -3/4 in. (45 mm) long steel molly bolts
in conjunction with min 114 in. (6 mm) by 1 -1/4 in. (32 mm) diam steel fender washers.
*Bearing the UL Classification Mark
®
Specified Technologies Inc 200 Evans Way Somerville, NJ 08876
Reproduced courtesy of Underwriters Laboratories, Inc.
Created or Revised: OCTOBER -14 -2003 &W -L -2188
STI(000)992-1180 • (908)526 -8000 • FAX(908)231 -8415 • E- Mail:techsery @stifirestop.com • Website:wwwstifirestol` PAGE 2 O I
System Na. W -J -1098
F Rating - 2 Hr
T Ratings - 1/4, 3/4 and 1 Hr (See Item 2)
A
I
I
I
v
A
Section A -A
1. Wall Assembly Min 6 in. (152 mm) thick reinforced lightweight or normal weight (100 -150 pof or 1600 -2400 kg /m3) concrete.
Wall may also be constructed of any UL Classified Concrete Blocks *. Max diam of opening is 2 in. (51 mm) larger than OD of
through penetrant.
See Concrete Blocks (CAZT) category in the Fire Resistance Directory for names or manufacturers.
2. Through Penetrant One metallic pipe, conduit or tube to be installed eccentrically or concentrically within the firestop system.
Pipe, conduit or tubing may be installed at an angle not greater than 45 degrees from perpendicular to the wall surface. The annular
space between the pipe, conduit or tube and the periphery of the opening shall be min 0 in. (0 mm, point contact) to max 2 in. (51
mm). Pipe, conduit or tube to be rigidly supported on both sides of the wall assembly. The following types and sizes of metallic
pipes, conduits and tubes may be used:
A. Steel Pipe Nom 8 in. (203 mm) diam (or smaller) Schedule 5 (or heavier) steel pipe.
B. Iron Pipe Nom 8 in. (203 mm) diam (or smaller) cast or ductile iron pipe.
C. Conduit Nom 6 in. (152 mm) diam (or smaller) rigid steel conduit, nom 4 in. (102 mm) diam (or smaller) steel electrical
metallic tubing (EMT) or nom 4 in. (102 mm) diam (or smaller) flexible steel conduit.
D. Copper Pipe Nom 4 in. (102 mm) diam (or smaller) Regular (or heavier) copper pipe.
E_ Copper Tube Norn 4 in. (102 mm) diam (or smaller) Type L (or heavier) copper tube.
TYPE OF PENETRANT
MAX DIAM
T RATINCs
STEEL OR IRON PIPF, STEI =1- CONDUIT OR EMT
21N. (51 MM)
I HR
STEEL OR IRON PIPE, STEEL CONDUIT OR EMT
BIN. (203 MM)
3/4 HR
COi=pER f IFF= OR TUBE
21N. (102 MM)
1/4 HR
2A. Through Penetrating Product* -Flexible Metal Piping As an alternate to Item 2, one nom 1 -114 in. (3 mm) ar aoe between
steel flexible metal pipe to be installed either concentrically or eccentrically within the firestop system. Th e annular p
the p ipe and the periphery of the opening shall be min 0 in. (0 mm, point contact) to max 2 in. (51 mm). Pipe to be rigidly
supported on both sides of the wall assembly. When flexible metal piping is used, T Rating is 1 hr.
OMEGA FLEX INC
TITEFLEX CORP
A BUNDY CO
WARD MFG INC
Cavity Material* - Sealant Min 518 in. (16 mm) thickness of fill material applied within annulus, flush with both
3. Fill, Void o r y
in 114 in. (6 mm) diam bead of fill material applied at metallic pipe/concrete
surfaces of wall assembly. At point contact location, m
interface on both surfaces of wall.
SPECIFIED TECHNOLOGIES INC - SpecSeal LCI Sealant
*Bearing the UL Classification Mark
_ - Specified Technologies Inc 200 Evans Way Somerville, NJ 08876
Reproduced co y
urtes of Underwriters Laboratories, Inc.
e
Created or Revised: September 24, 2004 W -J -198
STI(800)992 -1180 • (908)526 -8000 • FAX(908)231 -8415 • E- Mail:techsery @stifirestop.com • Website:www.stifirestop.com PAGE I OF I
System No. W -L -1222
F Ratings - 1 and 2 Hr (See Item 1)
T Ratings - 114, 314 and 1 Hr (See Item 2)
F--A
i
1 I 1B
A Section A -A
Wall Assembly - The 1 or 2 hr fire -rated gypsum board /stud wall assembly shall be constructed of the materials and in the manner
specified in the individual U300 or U400 Series Wall or Partition Design in the UL Fire Resistance Directory and shall include the following
construction features:
A. Studs - Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. (51 by 102 mm
lumber spaced 16 in. (406 mm) OC. Steel studs to be min 3 -112 in. (89 mm) wide and spaced max 24 in. (610 mm) OC.
B. Gypsum Board* - Thickness, type, number of layers and fasteners as specified in the individual Wall and Partition Design. Max diam of
opening is 10 -518 in. (270 mm).
The hourly F Rating of the firestop system is equal to the hourly fire rating of the wall assembly in which it is installed.
2. Through Penetrant - One metallic pipe, conduit or tube to be installed eccentrically or concentrically within the firestop system. Pipe,
conduit or tubing may be installed at an angle not greater than 45 degrees from perpendicular. The annular space between the pipe, conduit or
tube and the periphery of the opening shall be min 0 in. (0 mm, point contact) to max 2 in. (51 mm). Pipe, conduit ortube to be rigidly
supported on both sides of the wall assembly. The following types and sizes of metallic pipes, conduits and tubes may be used:
A. Steel Pipe - Nom 8 in. (203 mm) diam (or smaller) Schedule 5 (or heavier) steel pipe.
B. Iron Pipe - Nom 8 in. (203 mm) diam (or smaller) cast or ductile iron pipe.
C. Conduit - Nom 6 in. (152 mm) diam (or smaller) rigid steel conduit, nom 4 in. (102 mm) diam (or smaller) steel electrical metallic tubing
(EMT) or nom 4 in. (102 mm) diam (or smaller) flexible steel conduit.
D. Copper Pipe - Nom 4 in. (102 mm) diam (or smaller) Regular (or heavier) copper pipe.
E. Copper Tube - Nom 4 in. (102 mm) diam (or smaller) Type L (or heavier) copper tube.
TYPE OF PENETRANT
MAX DIAM
T RATING
STEEL OR IRON PIPE, STEEL
21N. (51 MM)
I HR
CONDUIT OR EMT
AA 0003014
STEEL OR IRON PIPE, STIFEL
alN. (203 MM)
3/4 HR
CONDUIT OR EMT
1526 N.W. 89th CT
COPPER PIPE OR TUBE
21N. (102 MM)
1 1/4 HR
2A. Through Penetrating Product* - Flexible Metal Piping - As an alternate to Item 2, one nom 1 -1 /4 in. (32 mm) diam (or smaller) steel
flexible metal pipe to be installed either concentrically or eccentrically within the firestop system. The annular space between the pipe and
the periphery of the opening shall be min 0 in. (0 mm, point contact) to max 2 in. (51 mm). Pipe to be rigidly supported on both sides of the
wall assembly.
OMEGA FLEX INC
TITEFLEX CORP
A BUNDY CO
WARD MFG INC of
3. Fill, Void or Cavity Material"` - Sealant - Min 5/8 in. (16 mm) thickness m fill material applied within pe/guyus, flush with both surfaces h
wall assembly. At point contact location, min 1/4 in. (6 mm) diam bead of fill material applied at metallic i e/ psum board interface on both
surface s of wall.
SPECIFIED TECHNOLOGIES INC - SpecSeal LCI Sealant
*Bearing the UL Classification Mark
Specified Technologies Inc 200 Evans Way Somerville, NJ 08876
-- Reproduced courtesy of Underwriters Laboratories, Inc. ��
Created or Revised: July 26, 2006 � W -L -1222
STI(500)992 -1180 • (908)526 -8000 • FAX (908)231 -8415 • E- Mail:techsery @stifirestop.corn • Website:www.stifirestop.com PAGE I OF 1
C
DrETAILS 4 NOTES
SCALE AS NOTED
PROJECT NO. 091016
DATE 03.18.09
REVISIONS:
SHEET
A9.2
OF 20
ARLOS DIAZ & ASSOC.
ARCHITECTS, PA
AA 0003014
ARCHITECTURE
INTERIOR DESIGN
1526 N.W. 89th CT
MIAMI, FLORIDA 33172
TEL: 305 599 2888
FAX: 305 599 3885
1997 cARI -o5 pIAX a ASSOC. ARCHITFGT5, PA.
ne Design and Drawings for this Project are the
roperty or the Architect and are protected under
e Capyrlght Protection Act.
ARCHITECTURE
c.ARL05 DIAZ
0%31
1526 N.W. 89th CT.
MIAMI, FL 33112
PH: (305) 599 -2888
U
Z
J
62 uJ
O Z
M
w
O J a
Q
> W
O t/1 z
W
oG Q
O ry)
x
Vw
Ln
Z
O
TERAHEN, INC.
A Florida Corporation
6333 8UN5ET PR
SOUTH MIAMI, FLORIDA
33143
DrETAILS 4 NOTES
SCALE AS NOTED
PROJECT NO. 091016
DATE 03.18.09
REVISIONS:
SHEET
A9.2
OF 20