13-1085-020GENERAL NOTES 1. LOCATION AND INSTALLATION OF DUCT WORK, DIFFUSES, EQUIPMENT AND ALL RELATED WORK SHALL BE FIELD COORDINATED WITH ARCHITECTURAL, STRUCTURAL, ELECTRICAL AND PLUMBING SYSTEM. THIS INCLUDES WALL AND ROOF PENETRATIONS AND REQUIRED ELECTRICAL SERVICE AND CONTROL WIRING. PLUMBER IS TO PROVIDE A MINIMUM 1 1 INCH CONDENSATE TRAP SEAL, AT EACH FAN COIL UNIT, PIPE TO OUTSIDE OF BUILDING. 2. EQUIPMENT SHALL HAVE CAPACITIES REQUIRED TO OBTAIN A SUITABLE OPERATING BALANCE BETWEEN ASSOCIATED ITEMS OF EQUIPMENT, ALL DAMPERS AND CONTROLS SHALL BE ADJUSTED TO OBTAIN THE REQUIRED CAPACITIES UNDER ACTUAL OPERATING CONDITIONS OF EACH ITEM OF EQUIPMENT SHALL NOT EXCEED THE RATED MOTOR HORESEPOWER. BALANCED CAPACITIES SHALL BE EQUAL TO THOSE SCHEDULED AT DESIGN CONDITIONS. 3. COOLING SYSTEMS ARE DESIGNED FOR 78F DB AND 50% RELATIVE HUMIDITY INSIDE CONDITIONS WITH OUTSIDE AIR TEMPERATURE OF 91F D.B., 79F W.B./ HEATING SYSTEMS ARE DESIGNED TO MAINTAIN MINIMUM INSIDE TEMPERATURE OF 72F D.B. WITH AN OUTSIDE TEMPERATURE OF 45F D.B. 4. AIR DISTRIBUTION DEVICES SHALL BE CONSTRUCTED OF ALUMINUM. EXPOSED GRILLAGE SHALL BE PAINTED OF SAME COLOR OF THE CEILING OR WALL IN WHICH IT IS LOCATED IN AND ALL SCREWS SHALL BE OF THE COUNTERSUNK TYPE ALSO PAINTED AS GRILLAGE. 5. CONSTRUCT AIR CONDITIONING DUCTWORK FROM 1 1/2" THICK FOR DUCTWORK THAT RUNS WITHIN ATTIC SPACE, STANDARD WEIGHT, FIBROUS GLASS DUCTBOARD, FABRICATED, SEAL AND INSTALLED PER LATEST SMACNA FIBROUS GLASS DUCT MANUAL RECOMMENDATIONS. DUCT SIZES NOTED ARE CLEAR INSIDE DIMENSIONS. PROVIDE ALL ELBOWS WITH DOUBLE THICKNESS TURNING VANES AT ALL BRANCH DUCT TAKE- OFFS AS REQUIRED FOR PROPER AIR BALANCING. 6. AIR COOLED CONDENSING UNITS • BE AS SCHEDULE, OR APPROVED EQUAL. PROVIDE EACH UNIT WITH ANTI-CYCLING DEVICE OR TIMER, HIGH AND LOW PRESSURE CONTROLLERS, AND FILTER DRIER. 7. FAN COIL UNITS TO BE AS SCHEDULE, OR APPROVED EQUAL COORDINATE WITH ELECTRICIAN TO CONNECT MULTI-SPEED FAN MOTOR TO PROPER SPEED TAPS TO DELIVER SCHEDULED AIR QUANTITIES, AGAINST SYSTEM RESISTANCE AS INSTALLED, DURING THE COOLING MODE AND TO DELIVER MINIMUM SUPPLY AIR CFM, AS RECOMMENDED BY UNIT MANUFACTURER, DURING THE HEATING MODE. 8. INSULATE REFRIGERANT SUCTION PIPE WITH [ INCH THICK FOAM PLASTIC INSULATION, (ARMAFLEX). FINISH INSULATION EXPOSED TO WEATHER NTH TWO COATS OF GLASSFAB. AND MASTIC PROVIDE 3" PVC JACKET FOR ALL REFRIGERANT LINES UNDER GROUND FLOOR. 9. THERMOSTAT SHALL HAVE A MAXIMUM HEATING MODE TEMPERATURE SETTING OF 78F AND A MINIMUM COOLING MODE TEMPERATURE SETTING OF 70F. IT SHALL BE ADJUSTABLE TO PROVIDE A TEMPERATURE OF UP TO 1OF BETWEEN FULL HEATING AND FULL COOLING. HEATING AND COOLING TO BE N • -CONCURRENT. THERMOSTAT TO HAVE REQUIRED STAGES OF COOLING AND HEATING FOR COMPATIBILITY WITH AIR CONDITIONING EQUIPMENT PROVIDED. 10. THE AIR FLOW AT EACH SUPPLY OUTLET SHOWN ARE PRELIMINARY AND FINAL FLOW AT EACH OUTLET SHALL BE DETERMINED BY DEGREE • COMFORT TEMPERATURE. 11. CONTRACTOR SHALL VERIFY SELECTED AIR HANDLING UNIT AND CONDENSINt UNIT IS ADEQUATE FOR REPLACEMENT OF EXISTING UNITS IF APPLICABLE. C= 0 SUPP. DUCT LIQUID LINE SUCTION LINE Gm -SECOND FINISHED FLOOR.� Fol KIM SO al & -03 A WIL -4 "M a I Val I 24" 0 CONCRETE -0 OR CLAY PIPE W/0 COVER FILLED XWITH 0 2" CONDENSATE 3/4" COARSE GRAVEL C> Q DRAIN LINE FROM BUILDING, SEE PLAN FOR SIZE —2 CONDENSATE DRAIN DETAIL N.T.S. MANUFACTURER NuTONE -------------- ----------------------------- ----------- ------------------------------ ----------- ---------------------------------- ---------------------------------------------- IMSTENG --------------- ---------------------------------- - --------------------------- ---------- cu (-D ----- EXisnxa -------------- ----------KITCHEN - -- - ------------ --- --------- ---- - NEW ----------------------- ------------------------------------ 24 X 24 RETURN EXLST --- ---- ---------------------------- ---------- -------------------------------- -- 6 X 12 1130 CFM. 211 SUPPLY 16 x 15 - ----------------------------- _-- _--- - - -LIB __--- ___ -___ V ---------- ---------- Allu-1-L ------ -------------- ---------- - ----- ---------------------------------- tl:d -34 --------- -- ----------- ------- Exm ------ -------------------------- -------- - 4 dFLi--- ----------- I ------------ is I IN CLOSET Z 6X9 ---------- ------------------ SUPPLY -- ----- ---------------- 6 --------------- !� W_ -- ----------- ---------- rrw V TAKE 1260!al�L 0 x 16 0 OFF AT 1600 CPJ 01 CF N) ----- ----------------------- ------------- ---------- ------ ------------- BOTTOMTO ---------- - FEED DUCT ........................... --------- ---------------------- ---------------------------- ----- EXISTING 150 CFM . ..... NEW MST. 49 i T7vTzl OFFICE 6X9 6 X 12 ------------- _�_t ------------------------- ------- ------------------- 7, EXISTING Q190 11 150 CRI -cm-, 50 DINING ROOM -4� --------------- ---------------- — ------------------ ----------- -------- --- ---------------- • EXISTING ------------------------------------------- - --------- mo-- -0- ------ t' BATMOOTNf i 440 t--FM 6XIO *NOTE: NEW DUCT IAIOFJ"- TO CONNECT R/A --------- -- TO EXISTING DIFFUSERS AT FIRST FLOOR- --6; -T6U-CF7vr --------------------------------- ------------ ------------- -------- MST. Z_11300 CFM 5X12 _4 ---- — ------------- SL4213LY ------------------------------------ r ------------------- -------- NOTE: EXISTING A/C UNIT IS TO BE S17 3 00 CFM- RETAINED WITH DUCT WORK REVISION ­ 4 J'Mcr� . ............ ----------- r ------------------------------- cy ---------------- ---------------------- i Li_ -7 TO CONFORM TO THE NEW LAYOUT. OFF AT 140 CFM 6X9 /2\ BOTTOM TO SUPPLY -------------------------------------------------------- 67X6m ---------------------------- 14O`Mm --------- 'I --- -------------- ------------------ --------------------------------------------------------- --------- YS ------------------------------- EXISTING --------------------------- ------------------------------------------------ FAMILY ROOM EXISTING -------------------------------------------------- B ------------ ------------------- ------ ----------------------------------------------------- ---------------- ----------------------- ------------------------ ---------------------------------------------------------- ---------- -------------------------------------------- - -------------------------------------------- ----------- -------- 44 ------------------------------------------------ . . ........... ...... ------- ----------------------------- — -- --------------------- CONDENSING UNIT MOUNTING - N.T.S. AIR TERM I N AL RCN E H LE . . ......... . . . ... . . ... EXISTING GARAGE EXHAUST FAN SCHEDULE UNIT DESIGNATION X-1 AREA SERVED BATHROOM 1 LOCATION CEILING FAN TYPE EXHAUST DRIVE TYPE DIRECT TOTAL AIR, CFM 70 FLA 018 ELECTRICAL SERVICE I 120 SINGLE PHASE DISCHARGE ROOF JACK GRAVITY DAMPERS BACK DRAFT DAM ER MODEL 671R ELECTRIC HEAT MANUFACTURER NuTONE -------------- ----------------------------- ----------- ------------------------------ ----------- ---------------------------------- ---------------------------------------------- IMSTENG --------------- ---------------------------------- - --------------------------- ---------- cu (-D ----- EXisnxa -------------- ----------KITCHEN - -- - ------------ --- --------- ---- - NEW ----------------------- ------------------------------------ 24 X 24 RETURN EXLST --- ---- ---------------------------- ---------- -------------------------------- -- 6 X 12 1130 CFM. 211 SUPPLY 16 x 15 - ----------------------------- _-- _--- - - -LIB __--- ___ -___ V ---------- ---------- Allu-1-L ------ -------------- ---------- - ----- ---------------------------------- tl:d -34 --------- -- ----------- ------- Exm ------ -------------------------- -------- - 4 dFLi--- ----------- I ------------ is I IN CLOSET Z 6X9 ---------- ------------------ SUPPLY -- ----- ---------------- 6 --------------- !� W_ -- ----------- ---------- rrw V TAKE 1260!al�L 0 x 16 0 OFF AT 1600 CPJ 01 CF N) ----- ----------------------- ------------- ---------- ------ ------------- BOTTOMTO ---------- - FEED DUCT ........................... --------- ---------------------- ---------------------------- ----- EXISTING 150 CFM . ..... NEW MST. 49 i T7vTzl OFFICE 6X9 6 X 12 ------------- _�_t ------------------------- ------- ------------------- 7, EXISTING Q190 11 150 CRI -cm-, 50 DINING ROOM -4� --------------- ---------------- — ------------------ ----------- -------- --- ---------------- • EXISTING ------------------------------------------- - --------- mo-- -0- ------ t' BATMOOTNf i 440 t--FM 6XIO *NOTE: NEW DUCT IAIOFJ"- TO CONNECT R/A --------- -- TO EXISTING DIFFUSERS AT FIRST FLOOR- --6; -T6U-CF7vr --------------------------------- ------------ ------------- -------- MST. Z_11300 CFM 5X12 _4 ---- — ------------- SL4213LY ------------------------------------ r ------------------- -------- NOTE: EXISTING A/C UNIT IS TO BE S17 3 00 CFM- RETAINED WITH DUCT WORK REVISION ­ 4 J'Mcr� . ............ ----------- r ------------------------------- cy ---------------- ---------------------- i Li_ -7 TO CONFORM TO THE NEW LAYOUT. OFF AT 140 CFM 6X9 /2\ BOTTOM TO SUPPLY -------------------------------------------------------- 67X6m ---------------------------- 14O`Mm --------- 'I --- -------------- ------------------ --------------------------------------------------------- --------- YS ------------------------------- EXISTING --------------------------- ------------------------------------------------ FAMILY ROOM EXISTING -------------------------------------------------- B ------------ ------------------- ------ ----------------------------------------------------- ---------------- ----------------------- ------------------------ ---------------------------------------------------------- ---------- -------------------------------------------- - -------------------------------------------- ----------- -------- 44 ------------------------------------------------ . . ........... ...... ------- ----------------------------- — -- --------------------- CONDENSING UNIT MOUNTING - N.T.S. AIR TERM I N AL RCN E H LE SERVICE MP.RK 7— CFM I LOCATION JACCESSORIES I SIZE I REMARKS SUPPLY EXT. STATIC PRESSURE (IN H20) 200 CEILING — EXISTING EXISTING SUPPLY ELECTRIC HEAT 160 CEILING — 6"X9" NEW 3 WAY SUPPLY �/Hz/V 190 CEILING — EXISTING EXISTING SUPPLY D 300 CEILING INTERLOCKED WITH EXISTING EXISTING SUPPLY Q 140 CEILING — EXISTING EXISTING SUPPLY (D 150 CEILING — EXISTING EXISTING SUPPLY 9) 50 CEILING — EXISTING EXISTING SUPPLY 0 70 FLOOR — 6f'X6' 3 WAY SUPPLY 50 FLOOR 6"X6" 3 WAY SUPPLY 70 FLOOR 6"X6" 3 WAY SEE EXAUST FAN SHEDULE ______ ---- ---- — — ------------------------------------- 4 --------------------- _44.5 — — — — — — — — — A&z - — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — 70 Eli cF.\f __ 4�' � x rA --------------------------------- ----------- NEW ----------------- ----------- 6X6 7x 1_111� FLOOR FLOOR -r -------------- DIFTUSM, ------------ =,V-§_ER --------- ; --------------------------------- 70 CFM 70 CFM��,�,-j ----------------------------- 44 ------------------------------------ L ------- ------ -------- po� --- R/A ------- --------------------------- 420 CFM ---- 44-20-X16 ------------ ---------- -------- ---- -- ------- ---------------------------------- NEW ------- -- -- ---------------------------------- - -- GRILL A9 t 7 ------------------------------------- 340 CFM 4 A16-fl --------------- ----------------- ------------------------- ---------- ---------------------------------- 18"0 t ----------------- 126QAmi-- ------------------------- -------------------------------- --------------------------- ------------------------------- 18"0 -7 0 ------------------ 1260-C-M --------- " --- --------------- - ----------- p. ------------- -------------------------------------------------------------- cm lq NEXY ---------- 6X6 - --------------- ------- 910 CFM I Er, 70a --- ------- ------------------------------------ ---------- - 4.5'0 P 90 CFNf zi ra --------------------------------- ---------------------- j4.5"0 3! CFM - -- ------------------------------ - --------------------------- ------ ------- FLOGR ------------------- 4 Tf 910 1--TNI T DWFUSER 70 CFNI ----------------------------- ----------------------------- ---- - --------------------- --- --- 80 270 CFM �DHTUSER a ----------- ------------ ----------- 50= -------------- ---------- ------- i __ 'r ------------------ 430 CFT\4 --------------------------------- -------------------------------- ----------------------------------- - ------ --------- ------------------------------- ------------------------------- - ---------- ---------------- ---------------------- 4.5'21 ------------------------------- 'A 4�5` ------------------ -mcFw ---------------------- - ------ -7D -CFNr ----------- -------------- i ---------------------------------- ------ ��EW_ 4- - ---------------- ------------------------- 6-,N 6 6,X6 „FLOOR "DR ------------------------------------ ------- 4�-DIFFUSER; ------------------ t ---- --------------------- 70 CFM 70 CF.%vl ------------------------------- --------- --------------------------------- ------------------------------ ------------------ ------- ------------ ------- ------- - ---------------------- -------- N --------------------- -------- 47i SECOND FLOOR MECFLA-NICAL PLAN 17-7 SCALE. Y4" = l'-O" EXISTING AIR HANDLING UNIT SCHEDULE MARK No. SUPPLY AIR (CFM) • OUTSIDE AIR (CFM) COOLING CAPACITY SC TIC) (M•H) EXT. STATIC PRESSURE (IN H20) AMBIENT AIR EMP. FAN MOTOR (HP) I L REFRIGERANT TYPE ELECTRIC HEAT CAPACITY (kW) LINE No. OF STAGES COMPRESSOR ELECTRICAL SERVICE �/Hz/V FILTER TYPE 2 GRILLES MANUFACTURER hrr MODEL No. t /Hz/V INTERLOCKED WITH ACCESSORIES DIMENSIONS (HxWxD) TRANSFER 2 GRILLES MANUFACTURER MODEL No. C,_ -I;- C 1-3- #•: -1 A ENS SEE EXAUST FAN SHEDULE ______ ---- ---- — — ------------------------------------- 4 --------------------- _44.5 — — — — — — — — — A&z - — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — 70 Eli cF.\f __ 4�' � x rA --------------------------------- ----------- NEW ----------------- ----------- 6X6 7x 1_111� FLOOR FLOOR -r -------------- DIFTUSM, ------------ =,V-§_ER --------- ; --------------------------------- 70 CFM 70 CFM��,�,-j ----------------------------- 44 ------------------------------------ L ------- ------ -------- po� --- R/A ------- --------------------------- 420 CFM ---- 44-20-X16 ------------ ---------- -------- ---- -- ------- ---------------------------------- NEW ------- -- -- ---------------------------------- - -- GRILL A9 t 7 ------------------------------------- 340 CFM 4 A16-fl --------------- ----------------- ------------------------- ---------- ---------------------------------- 18"0 t ----------------- 126QAmi-- ------------------------- -------------------------------- --------------------------- ------------------------------- 18"0 -7 0 ------------------ 1260-C-M --------- " --- --------------- - ----------- p. ------------- -------------------------------------------------------------- cm lq NEXY ---------- 6X6 - --------------- ------- 910 CFM I Er, 70a --- ------- ------------------------------------ ---------- - 4.5'0 P 90 CFNf zi ra --------------------------------- ---------------------- j4.5"0 3! CFM - -- ------------------------------ - --------------------------- ------ ------- FLOGR ------------------- 4 Tf 910 1--TNI T DWFUSER 70 CFNI ----------------------------- ----------------------------- ---- - --------------------- --- --- 80 270 CFM �DHTUSER a ----------- ------------ ----------- 50= -------------- ---------- ------- i __ 'r ------------------ 430 CFT\4 --------------------------------- -------------------------------- ----------------------------------- - ------ --------- ------------------------------- ------------------------------- - ---------- ---------------- ---------------------- 4.5'21 ------------------------------- 'A 4�5` ------------------ -mcFw ---------------------- - ------ -7D -CFNr ----------- -------------- i ---------------------------------- ------ ��EW_ 4- - ---------------- ------------------------- 6-,N 6 6,X6 „FLOOR "DR ------------------------------------ ------- 4�-DIFFUSER; ------------------ t ---- --------------------- 70 CFM 70 CF.%vl ------------------------------- --------- --------------------------------- ------------------------------ ------------------ ------- ------------ ------- ------- - ---------------------- -------- N --------------------- -------- 47i SECOND FLOOR MECFLA-NICAL PLAN 17-7 SCALE. Y4" = l'-O" EXISTING AIR HANDLING UNIT SCHEDULE MARK No. SUPPLY AIR (CFM) • OUTSIDE AIR (CFM) COOLING CAPACITY SC TIC) (M•H) EXT. STATIC PRESSURE (IN H20) AMBIENT AIR EMP. FAN MOTOR (HP) I L REFRIGERANT TYPE ELECTRIC HEAT CAPACITY (kW) LINE No. OF STAGES COMPRESSOR ELECTRICAL SERVICE �/Hz/V FILTER TYPE DISP • LE MANUFACTURER hrr MODEL No. t /Hz/V INTERLOCKED WITH ACCESSORIES DIMENSIONS (HxWxD) 53.25 x 24 x 22 -XISTING AIR COOLED CONDENSIN UNIT SCHEDULE IL GERALD FI.I.DE,MARCO A R _c- ji Pl°',T E z' 4A -P '4u GERALD ' F. DE MARCO 0 0 0 8 8 1 8 A 7241 S.W. 168TH STREET - SUITE E MIAMI, FLORIDA 33157 305155.2999 - 305.255.4499(1`A:o PROJECT NO.: 1212 DATE: 11-21-12 DRAINN BY: ARB RE\ASION BY DATE /1\ A B 10-21-1 A -Ry 01-2 AREA SERVED NOMINAL CAPACITY (M•H) AMBIENT AIR EMP. • F I L REFRIGERANT TYPE 'LIQUID LINE/SUCTION LINE COMPRESSOR CONDENSER FAN FLA ELECTRICAL SERVICE t /Hz/V ACCESSORIES THERMOSTAT MANUFACTURER MODEL No. C,_ -I;- C 1-3- #•: -1 A ENS DIMENSIONS (HxWxD) 9-9 x • x 36.25 IL GERALD FI.I.DE,MARCO A R _c- ji Pl°',T E z' 4A -P '4u GERALD ' F. DE MARCO 0 0 0 8 8 1 8 A 7241 S.W. 168TH STREET - SUITE E MIAMI, FLORIDA 33157 305155.2999 - 305.255.4499(1`A:o PROJECT NO.: 1212 DATE: 11-21-12 DRAINN BY: ARB RE\ASION BY DATE /1\ A B 10-21-1 A -Ry 01-2