Conduit
U.L. SYSTEM NO. WL1054
METAL PIPE THROUGH GYPSUM WALL ASSEMBLY
F RATING =1 -HR. OR 2 -HR.
T RATING = 0 -HR.
L RATING AT AMBIENT = LESS THAN 1 CFM /SQ. FT.
L RATING AT 400 °F = LESS THAN 4 CFM /SQ. FT.
FRONT VIEW SECTION A -A
re stop sealant
Fire Stop S
Rated Gypsum Wall
it
1. GYPSUM WALL ASSEMBLY (UL/ULC CLASSIFIED 0300 OR 0400 SERIES) Stud Wall
(1 -HR. OR 2 -HR. FIRE - RATING) (2 -HR. SHOWN).
2. [Not Shown] WOOD STUDS TO CONSIST OF NOMINAL 2" X 4" LUMBER STEEL
STUDS TO BE MINIMUM 2 -1/2" WIDE.
3. PENETRATING ITEM TO BE ONE OF THE FOLLOWING:
A. MAXIMUM 30" DIAMETER STEEL PIPE (SCHEDULE 10 OR HEAVIER)
B. MAXIMUM 30" DIAMETER CAST IRON PIPE.
C. MAXIMUM 6" NOMINAL DIAMETER COPPER PIPE.
D. MAXIMUM 6" NOMINAL DIAMETER STEEL CONDUIT.
E. MAXIMUM 4" NOMINAL DIAMETER EMT.
4. a. MINIMUM 5/8" DEPTH HILTI FS -ONE INTUMESCENT FIRESTOP SEALANT OR EQUIVALENT = 1 -HR. FIRE - RATING
b. MINIMUM 1 -1/4" DEPTH HILTI FS -ONE FIRESTOP SEALANT OR EQUIVALENT = 2 -HR. FIRE - RATING
5. MINIMUM 1/2" BEAD HILTI FS -ONE FIRESTOP SEALANT OR EQUIVALENT FOR POINT OF CONTACT.
NOTES:
1. MAXIMUM DIAMETER OF OPENING:
A. 32 -1/4" FOR STEEL STUD WALLS.
B. 14 -1/2" FOR WOOD STUD WALLS.
2. ANNULAR SPACE = MINIMUM 0 ", MAXIMUM 2 -1/4"
3. PIPE MAY BE INSTALLED WITH CONTINUOUS POINT OF CONTACT.
4. PIPE MAY BE INSTALLED AT AN ANGLE NOT GREATER THAN 45 DEG. FROM PERPENDICULAR
INSTALLATION INSTRUCTIONS FOR UL NO. WL1054
STEP 1 - PREPARATION: ALL SURFACES MUST BE CLEAN,SOUND, DRY AND FROST
FREE PRIOR TO APPLICATION OF FIRESTOPPING MATERIALS.
STEP 2 - FIRESTOPPING SEALANT: APPLY A MINIMUM 5/8" OR 1 -1/4" DEPTH OF FS -ONE
TOOL EXCESS SEALANT BEYOND PERIMETER OF THE SEAL UNDISTURBED FOR 48 HOURS.
CONDUIT FIRESTOPPING DETAIL
NOT TO SCALE
0
N
I
0
N
ME
11
;a
0
N
I
N
1
0
0
0
co
LL
a
t
0
O
,2
0
T'
CEILING MOUNTED
SMOKE /HEAT
DETECTOR
6"6EL jCEIL"r- 24" MIN HANDICAP
BEDROOM STROBE
_1�07 1 r=,M=
SYNCHRONIZE MORE THAN
TWO APPLIANCES IN ANY
FIELD OF VIEW, SPACED A
MINIMUM OF 50' FROM EACH
OTHER IN ROOMS 80' x 80'
OR GREATER.
NFPA 72 2007 EDITION
(SECTION 7.5.4.3.2)
80" MIN
96" MAX
NFPA 72 2007
EDITION
(SECTION 7.4.7.1)
FINISHED
FLOOR
3` (MIN
AUDIO /VISUAL
& VISUAL —ONLY
DEVICES
A/C SUPPLY
DIFFUSER
) I
ACCEPTED HERE
IMPORTANT NOTE
VERIFY EXACT MOUNTING
REQUIREMENTS WITH MANUFACTURERS DATA SHEETS
MANUAL
PULL
STATION
FIRE
PHONE
JACK o I
48" MAX (ADA)
42" MIN /54" MAX (NFPA)
NFPA 72 2007
EDITION (SECTION 5.13.4)
MAGNETIC
DOOR
HOLDER
LESS 3"
6"
DEVICE MOUNTING HEIGHTS
SCALE: N.T.S.
•
PENETRATION DETAIL # t�7
SYSTEM No. C -AJ -1505
February 18, 2004
F Rating - 3 Hr
T Rating - 3/4 Hr
�A
i
0
3
f • • -d }
2
SECTION A -A
E
1. Floor or Wall Assembly - Min 4 -1/2 in. 114 mm) thick reinforced lightweight or normal weight
(100 -150 pcf (1600 -2400 kg /cu meter structural concrete. Floor may also be constructed of any min 6
in. 152 mm) thick UL Classified hollow -core Precast Concrete Wall may also be constructed of any
UL Classified Concrete Blocks *. Max diam of opening is 3 in. (76 mm).
See Precast Concrete Units (CFTV) and Concrete Block (CAZT) categories in the Fire
Resistance Directory for names of manufacturers.
2. Through Penetrants One metallic pipe, conduit or tubing to be installed within the firestop system.
The annular space shall be min 3/8 10 mmto max 3/4 in.19 mm). Pipe, conduit or tubing to be rigidly
supported on both sides of floor or wall assembly. The following types and sizes of metallic pipes,
conduits or tubing may be used:
A. Steel Pipe Nom 1 -1/2 in. (38 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe.
B. Conduit Nom 1 -1/2 in. (38 mm) diam (or smaller) steel electrical metallic tubing or rigid steel
conduit.
3. Fill, Void or Cavity Material* - Putty or Equivalent Sealant Material - Min 2 in. (51 mm)
thickness of fill material applied within the annulus, recessed % to 3/8 in. (6 to 10 mm from top
surface of floor or both surfaces of wall. In floors constructed of hollow -core precast concrete units, fill
material to be installed flush with both surfaces of assembly.
TREMCO INC. -- TREMstop Putty or Equivalent Material
*Bearing the UL Classification Mark
NEVER _j
HERE
WALL MOUNTED
SMOKE/HEAT-
DETECTOR
FINISHED
WALL
NOTE: MEASUREMENTS
SHOWN ARE TO THE
CLOSEST OF THE
DETECTOR.
SIDE WALL
12" (MAX)
9330 NW 13 ST.
DORAL FL 33172
PHONE 305 - 594 -2382
FAX 305 - 594 -2366
DRA,y�Nt iBX;,�
0
W
�••, • C N • •.may
Z
*• N
•p"
•
• 6
'
' 7a • A i'E OF
J
_
W
C)
PERMIT
SET
p 2016
MEP ENGINEERING DESIGNS Inc. HEREBY
RESERVE THEIR COPYRIGHTS TO THE IDEAS
AND DRAWINGS SHOWN. THESE DRAWINGS
ARE TO BE USED FOR THE PROJECT
STATED ONLY AND SHALL NOT BE USED OR
REPRODUCED FOR ANY OTHER PURPOSE
WHATSOEVER WITHOUT THE EXPRESSED
WRITTEN CONSENT. CONTRACTORS SHALL
VERIFY ALL DIMENSIONS AND SHALL NOT
RELY ON SCALED DIMENSIONS. NOTIFY THE
ENGINEER OF ANY DISCREPANCIES PRIOR
TO COMMENCING WORK.
REVISION DATE(S)
Q Miami -Dade 01/30/2013
A
A
PROJ. NO: DATE:
SHEET NO.:
FA -4
tJ Of 5 Sheets
0
W
Z
O
Q
J
_
W
C)
LJ
W
^ �
XI—ci
W
ch
F=
w
V J
Z
Z
oZ�
(<-
J
W
U)
n
W
C,
Q
U)
O
W
`D
U)
Z
W
U)
0
0
v
O
<
<
Z
W
J
~
Z
Q
W
W
-'
W
Z
W
o
L
W
IL
LiJ
U)
REVISION DATE(S)
Q Miami -Dade 01/30/2013
A
A
PROJ. NO: DATE:
SHEET NO.:
FA -4
tJ Of 5 Sheets
C.
W
O
J
_
C)
LJ
W
^ �
XI—ci
W
ch
F=
w
V J
Z
Z
oZ�
0
t'7
U)
n
W
00
Q
�
O
W
`D
O
~
N
v
O
REVISION DATE(S)
Q Miami -Dade 01/30/2013
A
A
PROJ. NO: DATE:
SHEET NO.:
FA -4
tJ Of 5 Sheets