Loading...
13-159-005rl PO a N 0 4 2 U_ I v r2 a N E rn N t 0 0 0 U_ v C N Q t 0 a N a 00 N Cp i 4 0 I 0 rn 0 I M 6 W Q Conduit 1014 � 14 1 JA i Is] � I el =k fil I W;'A � U.L. SYSTEM NO. WL1054 METAL PIPE THROUGH GYPSUM WALL ASSEMBLY F RATING = 1 -HR. OR 2 -HR. T RATING = 0 -HR. L RATING AT AMBIENT = LESS THAN 1 CFM /SQ. FT. L RATING AT 400 °F = LESS THAN 4 CFM /SQ. FT. FRONT VIEW SECTION A -A Rated Gypsum Wall -e Stop Sealant 1 4 Fire Stop Sealant Conduit 3 5 1. GYPSUM WALL ASSEMBLY (UL/ULC CLASSIFIED 0300 OR U400 SERIES) Stud Wall (1 -HR. OR 2 -HR. FIRE - RATING) (2 -HR. SHOWN). 2. [Not Shown] WOOD STUDS TO CONSIST OF NOMINAL 2" X 4" LUMBER STEEL STUDS TO BE MINIMUM 2 -1/2" WIDE. 3. PENETRATING ITEM TO BE ONE OF THE FOLLOWING: A. MAXIMUM 30" DIAMETER STEEL PIPE (SCHEDULE 10 OR HEAVIER) B. MAXIMUM 30" DIAMETER CAST IRON PIPE. C. MAXIMUM 6" NOMINAL DIAMETER COPPER PIPE. D. MAXIMUM 6" NOMINAL DIAMETER STEEL CONDUIT. E. MAXIMUM 4" NOMINAL DIAMETER EMT. 4. a. MINIMUM 5/8" DEPTH HILTI FS -ONE INTUMESCENT FIRESTOP SEALANT OR EQUIVALENT = 1 -HR. FIRE - RATING b. MINIMUM 1 -1/4" DEPTH HILTI FS -ONE FIRESTOP SEALANT OR EQUIVALENT = 2 -HR. FIRE - RATING 5. MINIMUM 1/2" BEAD HILTI FS -ONE FIRESTOP SEALANT OR EQUIVALENT FOR POINT OF CONTACT. NOTES: 1. MAXIMUM DIAMETER OF OPENING: A. 32 -1/4" FOR STEEL STUD WALLS. B. 14 -1/2" FOR WOOD STUD WALLS. 2. ANNULAR SPACE = MINIMUM 0 ", MAXIMUM 2 -1/4" 3. PIPE MAY BE INSTALLED WITH CONTINUOUS POINT OF CONTACT. 4. PIPE MAY BE INSTALLED AT AN ANGLE NOT GREATER THAN 45 DEG. FROM PERPENDICULAR INSTALLATION INSTRUCTIONS FOR UL NO. WL1054 STEP 1 - PREPARATION: ALL SURFACES MUST BE CLEAN,SOUND, DRY AND FROST FREE PRIOR TO APPLICATION OF FIRESTOPPING MATERIALS. STEP 2 - FIRESTOPPING SEALANT: APPLY A MINIMUM 5/8" OR 1 -1/4" DEPTH OF FS -ONE TOOL EXCESS SEALANT BEYOND PERIMETER OF THE SEAL UNDISTURBED FOR 48 HOURS. CONDUIT FIRESTOPPING DETAIL NOT TO SCALE T' CEILING MOUNTED SMOKE /HEAT DETECTOR 3' (MIN B'BEL CEILING 24" MIN HANDICAP AUDIO /VISUAL BEDROOM STROBE & VISUAL —ONLY Z DEVICES i SYNCHRONIZE MORE THAN TWO APPLIANCES IN ANY FIELD OF VIEW, SPACED A MINIMUM OF 50' FROM EACH OTHER IN ROOMS 80' x 80' OR GREATER. NFPA 72 2007 EDITION (SECTION 7.5.4.3.2) 80" MIN 96" MAX NFPA 72 2007 EDITION (SECTION 7.4.7.1) FINISHED FLOOR A/C SUPPLY DIFFUSER ) I ACCEPTED HERE IMPORTANT NOTE VERIFY EXACT MOUNTING REQUIREMENTS WITH MANUFACTURERS DATA SHEETS MANUAL PULL STATION FIRE PHONE JACK o 48" MAX (ADA) 42" MIN /54" MAX (NFPA) NFPA 72 2007 EDITION (SECTION 5.13.4) MAGNETIC DOOR HOLDER LESS 3" 6» DEVICE MOUNTING HEIGHTS SCALE: N.T.S. PENETRATION DETAIL # 2 SYSTEM No. C -AJ -1505 February 18, 2004 F Rating - 3 Hr T Rating - 3/4 Hr 3 A 1 a d LAD-`�' SECTION A -A 1. Floor or Wall Assembly - Min 4 -1/2 in. 114 mm) thick reinforced lightweight or normal weight (100 -150 pcf (1600 -2400 kg /cu meter structural concrete. Floor may also be constructed of any min 6 in. 152 mm) thick UL Classified hollow -core Precast Concrete Wall may also be constructed of any UL Classified Concrete Blocks". Max diam of opening is 3 in. (76 mm). See Precast Concrete Units (CFTV) and Concrete Block (CAZT) categories in the Fire Resistance Directory for names of manufacturers. 2. Through Penetrants One metallic pipe, conduit or tubing to be installed within the firestop system. The annular space shall be min 3/8 10 mmto max 3/4 in. 19 mm). Pipe, conduit or tubing to be rigidly supported on both sides of floor or wall assembly. The following types and sizes of metallic pipes, conduits or tubing may be'used: A. Steel Pipe Nom 1 -1/2 in. (38 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe. B. Conduit Nom 1 -1/2 in. (38 mm) diam (or smaller) steel electrical metallic tubing or rigid steel conduit. 3. Fill, Void or Cavity Material* - Putty or Equivalent Sealant Material - Min 2 in. (51 mm) thickness of fill material applied within the annulus, recessed % to 3/8 in. (6 to 10 mm from top surface of floor or both surfaces of wall. In floors constructed of hollow -core precast concrete units, fill material to be installed flush with both surfaces of assembly. TREMCO INC. — TREMstop Putty or Equivalent Material *Bearing the UL Classification Mark 4` NEVER HERE WALL MOUNTED SMOKE /HEAT DETECTOR FINISHED WALL NOTE: MEASUREMENTS SHOWN ARE TO THE CLOSEST OF THE DETECTOR. 4` SIDE WALL 12" (MAX) S �• 01.7% 9330 NW 13 ST. DORAL FL 33172 PHONE 305- 594 -2382 FAX 305- 594 -2366 DRAWN BY: 4 •� r 0 ,,7 6 - 0. ' m ©2M MEP ENGINEERING DESIGNS Inc. HEREBY RESERVE THEIR COPYRIGHTS TO THE IDEAS AND DRAWINGS SHOWN. THESE DRAWINGS ARE TO BE USED FOR THE PROJECT STATED ONLY AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PURPOSE WHATSOEVER WITHOUT THE EXPRESSED WRITTEN CONSENT. CONTRACTORS SHALL VERIFY ALL DIMENSIONS AND SHALL NOT RELY ON SCALED DIMENSIONS. NOTIFY THE ENGINEER OF ANY DISCREPANCIES PRIOR TO COMMENCING WORK. REVISION DATE(S) A Miami -Dade 01/29/2013 A2 A PROJ. NO: DATE: SHEET NO.: FA -4 5 at 5 0 O Z Q Q LL J_ W Q C10 J f.— J W LLI p <C c a (0 Z W U) 7 o CK Z O - �^ J o V 00 CV Q F— C� < <C Z H J Q W Z W Z W W O Uj 1AJ 0 IL U) REVISION DATE(S) A Miami -Dade 01/29/2013 A2 A PROJ. NO: DATE: SHEET NO.: FA -4 5 at 5 O Q O LL W 0 o C10 J /�J w LLI c`) F_ U ` (0 Z U) J 7 o CK Z O - �^ J o V 00 CV Q C) N W NW N` w REVISION DATE(S) A Miami -Dade 01/29/2013 A2 A PROJ. NO: DATE: SHEET NO.: FA -4 5 at 5