12-952R-002System No. W -L -1222
F Ratings -1 and 2 Hr (See Item 1)
T Ratings - 1/4, 314 and 1 Hr (See Item 2)
r in
L A
Section A -A
1. Wall Assembly - The 1 or 2 hr fi re -rated gypsum board /stud wall assembly shall be constructed of the materials
and in the manner specifi ed in the individual U300 or U400 Series Wall or Partition Design in the UL Fire Resistance
Directory and shall include the following construction features:
A. Studs - Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by
4 in. (51 by 102 mm) lumber spaced 16 in. (406 mm) OC. Steel studs to be min 3 -1/2 in. (89 mm) wide and spaced
max 24 in. (610 mm) OC.
B. Gypsum Board' - Thickness, type, number of layers and fasteners as specifi ed in the individual Wall and
Partition Design. Max diam of opening is 10-5/8 in. (270 mm).
The hourly F Rating of the fi restop system is equal to the hourly fi re rating of the wall assembly in
which it is installed.
2. Through Penetrant - One metallic pipe, conduit or tube to be installed eccentrically or concentrically within the
fi restop system. Pipe, conduit or tubing may be installed at an angle not greater than 45 degrees from perpendicular.
The annular space between the pipe, conduit or tube and the periphery of the opening shall be min 0 in. (0 mm, point
contact) to max 2 in. (51 mm). Pipe, conduit or tube to be rigidly supported on both sides of the wall assembly. The
following types and sizes of metallic pipes, conduits and tubes may be used:
A. Steel Pipe - Nom 8 In. (203 mm) diam (or smaller) Schedule 5 (or heavier) steel pipe.
B. Iron Pipe - Nom 8 in. (203 mm) diam (or smaller) cast or ductile iron pipe.
C. Conduit- Nom 6 in. (152 mm) diam (or smaller) rigid steel conduit, nom 4 in. (102 mm) diam (or smaller) steel
electrical metallic tubing (EMT) or nom 4 in. (102 mm) diam (or smaller) fl exible steel conduit.
D. Copper Pipe - Nom 4 in. (102 mm) diam (or smaller) Regular (or heavier) copper pipe.
E. Copper Tube - Nom 4 in. (102 mm) diam (or smaller) Type L (or heavier) copper tube.
Type of Penetrant Max Diam T Rating
Steel or iron pipe, steel conduit or EMT 2 in. (51 mm)1 hr
Steel or iron pipe, steel conduit or EMT 8 in. (203 mm) 3/4 hr
Copper pipe or tube 4 in. (102 mm) 114 hr
2A. Through Penetrating Product" - Flexible Metal Piping - As an alternate to Item 2, one nom 1 -1/4 in. (32 mm) diam
(or smaller) steel fl exible metal pipe to be installed either concentrically or eccentrically within the fi restop system. The
annular space between the pipe and the periphery of the opening shall be min 0 in. (0 mm, point contact) to max 2 in.
(51 mm). Pipe to be rigidly supported on both sides of the wall assembly.
LE A BUNDY CO. WARD MFG INC
OMEGA FLEX INC TITEF X CORP,
-Min 5/8 in. 16 mm thickness of fi II material applied within annulus fl ush
3. Fill, Void or Cavity Material ( ) pp ,
with both surfaces of wall assembly. At point contact location, min 1/4 in. (6 mm) diam bead of fi II material applied at
metallic pipe /gypsum board interface on both surfaces of wall.
SPECIFIED TECHNOLOGIES INC - SpecSeal LCI Sealant
0�
System No. W- L-3169
F Ratings -1 and 2 Hr (See Item 1)
T Ratings -1/4 and 3/4 Hr (See Item 2A)
Section
A -A
1. Wall Assembly - The 1 or 2 hr fi re -rated gypsum board/stud wall assembly shall be constructed of the materials and
in the
manner specifi ed in the individual U300 or U400 Series Wall or Partition Design in the UL Fire Resistance Directory and
shall include the following construction features:
A. Studs - Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4
in.
lumber spaced 16 in. OC. Steel studs to be min 3 -5/8 in. wide and spaced max 24 in. OC.
B. Gypsum Board* - Thickness, type, number of layers and fasteners as specifi ed in the individual Wall and Partition
Design.
Max diam of opening is 5 in. The hourly F Rating of the fi restop system is equal to the hourly fi re rating of the wall
assembly in which it is installed.
2. Cables - Max 4 -1/2 in. diam tight bundle of cables to be installed eccentrically or concentrically within the opening.
The annular space between the cables and the periphery of the opening shall be min 0 in. (point contact) to max 1/2 in.
Cable bundle to be rigidly supported on both sides of the fl oor or wall assembly. The following types and sizes of cables
may be used:
A. Max 200 pair No. 24 AWG (or smaller) copper conductor with polyvinyl chloride (PVC) insulation and jacketing
material.
B. Max 1/C No. 350 kcmil (or smaller) copper conductor cable with cross- linked polyethylene (XLPE) jacket.
C. Max 7/C No. 12 AWG (or smaller) copper conductor power and control cables with XLPE or PVC insulation with XLPE
or PVC jacket.
D. Max 3/C No. 2/0 AWG (or smaller) copper or aluminum conductor SER cables with PVC insulation and jacket
E. Max 3/C No. 2/0 AWG (or smaller) copper conductor PVC jacketed aluminum clad or steel clad TEK cable.
F. Max 110/125 fi bar optic (F.O.) cable with PVC insulation and jacket.
G. Max 3/C with ground No. 8 AWG (or smaller) copper conductor NM cable (Romex) with PVC insulation and jacket.
H. Max RG /U coaxial cable with fl uorinated ethylene insulation and jacket.
I. Max 4 pair No. 24 AWG (or smaller) copper conductor data cable with Hylar jacket and insulation.
2A. Through Penetrating Product' - As an alternate to the cables (Item 2), max 4 in. diam tight bundle of max 4/C No.
210 AWG (or smaller) aluminum or steel Armored Cable+ or Metal Clad Cable+ installed within the opening. Annular
space between throughpenetrating products and periphery of opening to be min 0 in. (point contact) to max 1 in. Through
penetrating product rigidly supported on both sides of fl oor or wall assembly. When Armored Cable or Metal Clad Cable
is used, T Rating is 1/4 hr. AFC CABLE SYSTEMS INC
3. Fill, Void or Cavity Material' - Sealant - Min 5/8 in. thickness of fi II material applied within annulus, fl ush with both
surfaces of wall assembly. Sealant to be forced into interstices of cable bundle to max ax extent possible. At point contact
location, min 114 in. diam bead of fi II material applied at cable bundle /gypsum board interface on both surfaces of wall.
SPECIFIED TECHNOLOGIES INC - SpecSeal LCI Sealant
'Bearing the UL Classifi cation Marking
System No. W -L -5122
F Ratings -1 and 2 Hr (See Item 1)
T Rating - 1/4 Hr
�A
4
f
3 2
LA
Section A -A
1. Wail Assembly - The 1 or 2 hr fi re-rated gypsum board /stud wall assembly shall be constructed of the
materials and in the manner specifi ed in the individual U300 or U400 Series Wall or Partition Design in the UL Fire
Resistance Directory and shall Include the following construction features:
A. Studs - Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2
by 4 in. lumber spaced 16 in. OC. Steel studs to be min 3 -5/8 in. wide and spaced max 24 in. OC.
B. Gypsum Board' - Thickness, type, number of layers and fasteners as specifi ed in the individual Wall and
Partition Design. Max diam of opening is 7 -112 in.
The hourly F Rating of the fi restop system is equal to the hourly fi re rating of the wall assembly in which it is
installed.
2. Through Penetrant - One metallic pipe or tube to be installed eccentrically or concentrically within the fi restop
system. Pi pe o r t ube t o be rigidly su pp orted on both sides of the wall assembly. The followin g typ es and sizes of
metallic pipes and tubes may be used:
A. Steel Pipe - Nom 4 in. diam (or smaller) Schedule 5 (or heavier) steel pipe.
B. Iron Pipe - Nom 4 in. diam (or smaller) cast or ductile iron pipe.
C. Copper Pipe - Nom 2 in. diam (or smaller) Regular (or heavier) copper pipe.
D. Copper Tube - Nom 2 in. diam (or smaller) Type L (or heavier) copper tube.
3. Tube Insulation - Plastics# - Nom 3/4 in. thick acrylonitrile butadiene/polyvinyl chloride (AB/PVC) fl exible
foam furnished in the form of tubing. Annular space shall be min 0 in. (point contact) to max 1 -1/2 in.
See Plastics (QMFZ2) category in the Plastics Recognized Component Directory for names of manufacturers. Any
Recognized Component tube insulation meeting the above specifi cations and having a UL 94 Flammability Classifi
cation of 94-5VA may be used.
4. Fill, Void or Cavity Material' - Sealant - Min 5/8 in. thickness of fi II material applied within annulus, fl ush with
both surfaces of wall assembly. At point contact location, min 1/4 in. diam bead of fi II material applied at insulated
metallic pipe /gypsum board interface on both surfaces of wall.
SPECIFIED TECHNOLOGIES INC - SpecSeal LCI Sealant
'Bearing the UL Classifi cation Marking
NON RATED WALL
S C A L E: 1 " =1' -0"
38"
5" NOM.
OR
6"
-
7"N
1. 1"
2
(1) LAYER 1/2" GYP. BD. ON
EA. SIDE (TYPE AS PER APPLIED
FINISH).
34" BATT INSULATION
ATT. TO WALL BD. W/ WIRE STAPLES
CONT. RUNNER FASTENED @ 24"
AT STORAGE #001
:ONTINUE PARTITION
UP TO U/S OF DECK
AS PER RCP PLANS
1 NON -RATED - 3 5/8" STUD
NON -RATED - 6" STUD
AT BATHROOM SIDE 1/4" CERAMIC
TILE ON 1/2" DUROCK (ONE OR BOTH
SIDES AS REQUIRED)
FINISH VARIES PER FLOOR FINISH
PLANS: ID
Y.
, .. .............:. ,...........
a EXIST. FLOOR SLAB
NON - BEARING PARTITION
NON RATED - 3 5/8" STUD @ 16" O.C. - (1) LAYER 1/2" GYP.
BD. EACH SIDE - SOUND INSULATED
AT WET ENVIRONMENTS (BATHROOM, JANITORS &
1A> SINK AREAS) SUBSTITUTE GYP. BD. LAYER WITH MOISTURE
RESISTANCE GYP. BD.
System No. HW -D -0079
Assembly Rating -1 and 2 Hr (See Item 2)
Joint Width - 3/4 In. Maximum
Class II Movement Capabilities - 25% Compression
r-- A Q
SECTI ❑N A -A
1. Floor Assembly - Min 4 -1/2 in. (114 mm) thick steel - reinforced lightweight or normal weight (100 -150 pcf or 1600 -2400
kg /m3) structural concrete.
2. Wall Assembly - The 1 or 2 hr fi re -rated gypsum board/stud wall assembly shall be constructed of the materials and
in the manner described in the individual U400 0 0
r V4 0 Series Wall and Partition Design in the UL Fire Resistance
Directory and shall include the following construction features:
A. Steel Floor and Ceiling Runners - Floor and ceiling runners of wall assembly shall consist of galv steel channels
sized to accommodate steel studs (Item 213) with min 1 -1/4 in. (32 mm) long fi anges. Ceiling runner secured to
concrete fl oor slab with steel mason ry anchors h rs spaced max 24 in. (610 mm) OC.
Al. Light Gauge Framing* - Clipped Ce ilin g Runner -
As an alternate to the ceiling runner in Item 2A G i pped runner to
consist of galv steel channel with clips preformed in track fl anges which positively engage the inside fl ange of the steel
studs Item 213. Track sized to accommodate steel (Item 2B T -
( ) e s ee studs (e ). rack fl anges to be min 2 1/2 in. (64 mm) long.
Clipped ceiling runner secured to concrete fl oor slab with steel masonry anchors spaced max 24 in. (610 mm) OC.
TOTAL STEEL SOLUTIONS L L C - Snap Trak
A2. Light Gauge Framing' - Slotted Ceiling Runner - As an alternate to the ceiling runner in Item 2A, ceiling runner
to consist of gals steel channel with slotted fl anges sized to accommodate steel studs (Items 213). Ceiling runner
secured to concrete fl oor slab with steel masonry anchors spaced max 24 in. (610 mm) OC.
SLIPTRACK SYSTEMS INC - SLP -TRK
A3. Light Gauge Framing" - Vertical Defl ection Ceiling Runner - As an alternate to the ceiling runner in Item 2A,
vertical deft action ceiling runner to consist of gals steel channel with slotted vertical defl ection clips mechanically
fastened within runner. Slotted clip provided with step bushings for permanent fastening of steel studs. Flanges
sized to accommodate steel studs (Item 213). Vertical defl action ceiling runner secured to concrete fl oor slab with
steel masonry anchors spaced max 24 in. (610 mm) OC.
THE STEEL NETWORK INC - VertiTrack VTD358, VTD400, VTD600 and VTD800
A4. Light Gauge Framing' - Notched Ceiling Runner - As an alternate to the ceiling runners in Items 2A through
2A3, notched ceiling runners to consist of C- shaped galv steel channel with notched return fl anges sized to
accommodate steel studs (Item 213). Notched ceiling runner secured to concrete fl oor slab with steel masonry
anchors spaced max 24 in. (610 mm) OC.
DENMAR STEEL INC - Type SCR
B. Studs- Steel studs to be min 3 -1/2 in. (89 mm) wide. Studs cut 1/2 in. (13 mm) to 3/4 in. (19 mm) less in length
than assembly height with bottom nesting in and resting on fl oor runner and with top nesting in ceiling runner without
attachment. When deft ection channel (Item 3A) is used, steel studs attached to ceiling runner with sheet metal
screws located 1/2 in. (13 mm) below the bottom of the deft ection channel. When slotted ceiling runner (Item 2A2)
is used, steel studs secured to slotted ceiling runner with No. 8 by 1/2 in. (13 mm) long wafer head steel screws at
midheight of slot on each side of wall. When vertical defl action ceiling runner (Item 2A3) is used, steel studs secured
to slotted vertical defl ection clips, through bushings, with steel screws at midheight of each slot. Stud spacing not to
exceed 24 in. (610 mm) OC.
C. Gypsum Board' - Gypsum board sheets installed to a min total thickness of 518 in. (16 mm) and 1 -114 in. (32 mm)
on each side of wall for 1 and 2 hr fi re rated assemblies, respectively. Wall to be constructed as specifi ad in the
individual Wall and Partition Design in the UL Fire Resistance Directory, except that a nom 314 in. (19 mm) gap shall
be maintained between the top of the gypsum board and the bottom surface of the fl oor. In addition, the top row of
screws shall be installed into the steel studs 1/2 to 1 in. (13 to 25 mm) below the bottom edge of the ceiling runner
flange. The hourly fi re rating of the joint system is dependent on the hourly fi re rating of the wall assembly in
which it is installed.
3. Joint System - Max separation between bottom of fl oor and top of wall is 3/4 in. (19 mm). The joint system is
designed to accommodate a max 25 percent compression om ression from its installed width. The joint system m consists of the
9 P P
J Y
following:
A. Forming Material - (Optional, Not Shown) - In 2 hr fi re rated wall assemblies, polyethylene backer rod, mineral
wool batt insulation or fi berglass batt insulation friction fi t into joint opening.
B. Fill, Void or Cavity Material' - Sealant - Min 1/2 in. (13 mm) thickness of fi II material applied within joint opening
on both sides of wall, fl ush with both surfaces of wall. As an option in 1 hr fi re rated walls, bond breaker tape applied
to ceiling channel (Item 2A) prior to Installation of fi II material.
SPECIFIED TECHNOLOGIES INC - SpecSeal ES Sealant
`Bearing the UL Classifi cation Mark
Reproduced courtesy of Underwriters Laboratories, Inc.
EXISTING CMU WALL FURRING
S C A L E: 1 " =1' -0"
NON RATED & 2HR EXISTING CONCRETE WALL
BOTTOM OF SLAB
FINISHED CLG. AS
PER RCP PLANS
1/2" GYP. BD. ON 7/8"
STL. CHANNEL AT 24
FURRING INTERIOR SIDE:
1 -1/2" MTL FURRING CF
WHERE E -BOXES (COC
ELECTRICAL)
FLOOR FINISH 8, BASE
ROOM FINISH SCHEDU
EXISTING FLOOR SLAB
O
12 HR FIRE RATED EXISTING
8" CONCRETE WALL
EXISTING CONCRETE WALL
2 NON RATED FURRING WALL
AT WET ENVIRONMENTS (BATHROOM, JANITORS &
2A > SINK AREAS) SUBSTITUTE GYP. BD. LAYER WITH
MOISTURE RESISTANCE GYP. BD.
System No. W- L-5121
F Ratings -1 and 2 Hr (See Item 1)
T Rating -1 Hr
Section A -A
1. Wall Assembly - The 1 or 2 hr fl re -rated gypsum board/stud wall assembly shall be constructed of the
materials and in the manner specifi ed in the individual U300 or U400 Series Wall or Partition Design in the UL
Fire Resistance Directory and shall include the following construction features:
A. Studs - Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom
2 by 4 in. lumber spaced 16 in. OC. Steel studs to be min 3 -5/8 in. wide and spaced max 24 in. OC.
B. Gypsum Board' - Thickness, type, number of layers and fasteners as specifi ed in the individual Wall and
Partition Design. Max diam of opening is 12 in.
The hourly F Rating of the fi restop system is equal to the hourly fi re rating of the wall assembly in which it is
installed.
2. Through Penetrant - One metallic pipe or tube to be installed eccentrically or concentrically within the fi
restop system.
Pipe or tube to be rigidly supported on both sides of the wall assembly. The following types and sizes of metallic
pipes and tubes may be used:
A. Steel Pipe - Nom 6 in. diam (or smaller) Schedule 5 (or heavier) steel pipe.
B. Iron Pipe - Nom 6 in. diam (or smaller) cast or ductile iron pipe.
C. Copper Pipe - Nom 4 in. diam (or smaller) Regular (or heavier) copper pipe.
D. Copper Tube - Nom 4 in. diam (or smaller) Type L (or heavier) copper tube.
3. Pipe Coverings - One of the following types of pipe coverings shall be used:
A. Pipe and Equipment Covering Materials' - Nom 2 in. thick hollow cylindrical heavy density (min 3.5 pcf)
glass fiber units jacketed on the outside with an all service jacket. Longitudinal joints sealed with metal fasteners
or factoryapplied
self - sealing lap tape. Transverse joints secured with metal fasteners or butt tape supplied with the product. The
annular space between the insulated through penetrant and periphery opening shall be min 0 in. (point contact)
to max 1 -1/2 in. See Pipe and Equipment Covering Materials (BRGU) category in the Building Materials
Directory for names of manufacturers. Any pipe covering material meeting the above specifi cations and bearing
the UL Classification Marking with a Flame Spread Index of 25 or less and a Smoke Developed Index of 50 or
less may be used.
B. Pipe Covering Materials' - Nom 2 in. thick unfaced mineral fi bar pipe insulation sized to the outside diam of
pipe or tube. Pipe Insulation secured with min No. 8 AWG steel wire spaced max 12 in. OC. The annular space
between the
insulated through penetrant and periphery opening shall be min 0 in. (point contact) to max 1 -1/2 in. IIG
MINWOOL L L C - High Temperature Pipe Insulation 1200, High Temperature Pipe Insulation BWT or
HighTemperature Pipe Insulation Therrnaloc.
C. Sheathing Material' - Used in conjunction with Item 3B. Foil- scrim -kraft or all service jacket material shall be
wrapped around the outer circumference of the pipe insulation (Item 313) with the kraft side exposed.
Longitudinal joints and transverse joints sealed with metal fasteners or butt tape.
See Sheathing Materials (BVDV) category in the Building Materials Directory for names of manufacturers. Any
sheathing material meeting the above specifi cations and bearing the UL Classifi cation Marking with a Flame
Spread Index of 25 or less and a Smoke Developed Index of 50 or less may be used.
4. Fill, Void or Cavity Material* - Sealant - Min 5/8 in. thickness of fi II material applied within annulus, fl ush
with both surfaces of wall assembly. At point contact location, min 1/4 in. diam bead of fi II material applied at
insulated metallic
pipe /gypsum board interface on both surfaces of wall.
SPECIFIED TECHNOLOGIES INC - SpecSeal LCI Sealant
1 HR - UL DESIGN No. U419
S C A L E: 1 " =1' -0"
UNDERSIDE OF EXISTING
STRUCTURE
FIRE -RATED SEALANT EACH SIDE
GYP. BOARD TO 1/2" BELOW BOTTOM
STRUCTURE EACH SIDE
SEE REFLECTED CEILING PLAN -
FOR CEILING HEIGHTS AND TYPES
(1) LAYER 5/8" FIRE -RATED GYP.
BD. ON EA. SIDE
3 1" STEEL STUDS W/
32" BATT INSULATION ATT. TO WALL BD.
W/ WIRE STAPLES
CONT. RUNNER FASTENED @ 24" O.C.
FIRE -RATED SEALANT EACH SIDE
FLOOR FINISH & BASE PER
ROOM FINISH SCHEDULE
GYP. BD.MTL. STUD CHASE PARTITION
NON RAT C = - -
FOR APPLIED WALL FINISH OVER -
GYP. BD. SEE FINISH SCHEDULE
8JOR INTERIOR ELEVATIONS
5"
38 2 1/2"W. 1 3/8" LEGS. & 1/4" GALV.
STEEL STUDS @ 16 O.C.
.......... ... ..: ,. EXIST. LOO SLAB
NON - BEARING PARTITION
< >
3 1 HR RATED - 3 5/8" STUD @ 16" O.C.
System No. W -L -7060
F Ratings -1 and 2 Hr (See Item 1)
T Rating -1/2 Hr
c- A
Section A-A
31" BATT INSULATION
ATT. TO WALL BD. W/ WIRE STAPLES
SEALANT BOTH SIDES
1. Wall Assembly - The 1 or 2 hr fi re-rated gypsum board/stud wall assembly shall be constructed of the materials
and
in the manner specifi ed in the individual U300, U400 or V400 Series Wall or Partition Design in the UL Fire Resistance
Directory and shall include the following construction features:
A. Studs - Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by
4 in. (51 by 102 mm) lumber spaced 16 in. (406 mm) OC. Steel studs to be min 3-1/2 in. (89 mm) wide and spaced
max 24 in. (610 mm) OC. Additional horizontal framing members installed to form a rectangular box around the
steel duct (Item 2).
B. Gypsum Board - Thickness, type, number of layers and fasteners as specifi ed in the individual Wall and
Partition Design. When wood studs are used, interior of through opening to be lined with sheets of gypsum board
around entire periphery to a total thickness of 5 in. 1 mm or 1 -1 4 in. 2 mm for 1 or 2 hr wall assemblies,
p p ry /8 (6 ) / (3 ) a asse b es,
respectively. Max area of opening is 952 s in. 0.61 m2 with a max dim of 32 in. 813 mm .
P 9 q ( ) ( )
The hourly F Rating of the fi restop system is equal to the hourly fi re rating of the wall assembly in
which it is installed.
2. Steel Duct - Max 24 by 30 in. (610 by 762 mm) No. 26 gauge (or heavier) galv steel duct installed eccentrically or
concentrically within opening. Annular space between duct and periphery of opening to be min 0 in. ( 0 mm ,
Po int
contact) to max 2 in. (51 mm). Duct to be rigidly supported on both sides of the wall assembly.
3. Firestop System - The fi restop system shall consist of the following:
A. Packing Material - (Optional, Not Shown) - Mineral wool batt Insulation, foam backer rod or glass fi bar
insulation installed as a permanent form to facilitate installation of fi II material (Item 313).
B. Fill, Void or Cavity Material' - Sealant - Min 5/8 in. (16 mm) thickness of fi II material applied within annulus,
fl ush with both surfaces of wall assembly. At point contact location, min 1/4 in. (6 mm) diam bead of fi II material
applied at steel ductigypsum board interface on both surfaces of wall.
SPECIFIED TECHNOLOGIES INC - SpecSeal LCI Sealant
C. Retaining Angles - Min 16 gauge galv steel angles sized to lap onto duct a min of 2 in. (51 mm) and to lap onto
wall around periphery of opening a min of 1 in. (25 mm). Angles attached to all four sides of steel duct on both
surfaces of wall with No. 10 (or larger) steel sheet metal screws located 1 in. (25 mm) from each end and spaced
max 4 in. (102 mm) OC.
FAI
22" VARIES 22"
T_
AS PER RCP PLANS
AT BATHROOM SIDE I1 /4" CERAMIC
TILE ON 1/2" DUROCK (ONE OR
BOTH SIDES AS REQUIRED)
2HR RATED SHAFT WALL
2 HR - UL DESIGN No. U415
SCALE: 1 " =1' -0"
3" CAVITY SHADOWLINE
RUNNER, 25 MSG GALV
STEEL, FASTENED @
24 "O.C. MAX.
1" THICK GYPSUM
WALLBOARD LINER
PANELS.
2 1/2" I- SHAPED MTL. -
STUDS, 25 MSG GALV.
STEEL @ 24-O.C.
MINERAL WOOL OR GU`
FIBER BATTS.
(2) LAYERS 5/8" THICK,
TYPE "X" GYPSUM BOAI
SHAFT SIDE
FLOOR RUNNER 25 GA.
CHAN., 1" + 2" UNEQ. LE
UNDERSIDE OF SLAB
AT 2 HR. RATED WALLS,
CLG. AS PER RCP PLANS
FIRE STOP ALL GAPS.
SEE FIRESTOP DTLS
1►�IFE :I=0s>w�vt9l:4
FINISH VARIES PER
FLOOR FINISH PLANS
FLOOR SLAB
NON - BEARING PARTITION
ofrY or SOU r�
B(/ILDING DtPp -r.
STUCTUR!
�ECTfp�
l �
M O
�.,clrs O
00
O
�1
N�
rm
M
c ,, \.
V <
QJ
r0
V
Liz
CML
M
�l
i
Drawn By: OS
Checked By: OS •
V
Date 06-15 -2012
Revisions
1 11.13.2012
a
Z
O
Z
aw
>a
X o�
� �
o
O c=n �
J oQ
LL N 2
to
LCPL
G
r till
eka
M
r'*,
. .r�
.DTI
SCHEDULES
4'
r
f
Project No: 61806
Am6;
'J619b
' se 9 ) 96
z' r
M O
�.,clrs O
00
O
�1
N�
rm
M
c ,, \.
V <
QJ
r0
V
Liz
CML
M
�l
i
Drawn By: OS
Checked By: OS •
V
Date 06-15 -2012
Revisions
1 11.13.2012
a
Z
O
Z
aw
>a
X o�
� �
o
O c=n �
J oQ
LL N 2
to
LCPL
G
r till
eka
M
r'*,
. .r�
.DTI
SCHEDULES
4'
r
f
Project No: 61806
Am6;