12-952R-002System No. W -L -1222 F Ratings -1 and 2 Hr (See Item 1) T Ratings - 1/4, 314 and 1 Hr (See Item 2) r in L A Section A -A 1. Wall Assembly - The 1 or 2 hr fi re -rated gypsum board /stud wall assembly shall be constructed of the materials and in the manner specifi ed in the individual U300 or U400 Series Wall or Partition Design in the UL Fire Resistance Directory and shall include the following construction features: A. Studs - Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. (51 by 102 mm) lumber spaced 16 in. (406 mm) OC. Steel studs to be min 3 -1/2 in. (89 mm) wide and spaced max 24 in. (610 mm) OC. B. Gypsum Board' - Thickness, type, number of layers and fasteners as specifi ed in the individual Wall and Partition Design. Max diam of opening is 10-5/8 in. (270 mm). The hourly F Rating of the fi restop system is equal to the hourly fi re rating of the wall assembly in which it is installed. 2. Through Penetrant - One metallic pipe, conduit or tube to be installed eccentrically or concentrically within the fi restop system. Pipe, conduit or tubing may be installed at an angle not greater than 45 degrees from perpendicular. The annular space between the pipe, conduit or tube and the periphery of the opening shall be min 0 in. (0 mm, point contact) to max 2 in. (51 mm). Pipe, conduit or tube to be rigidly supported on both sides of the wall assembly. The following types and sizes of metallic pipes, conduits and tubes may be used: A. Steel Pipe - Nom 8 In. (203 mm) diam (or smaller) Schedule 5 (or heavier) steel pipe. B. Iron Pipe - Nom 8 in. (203 mm) diam (or smaller) cast or ductile iron pipe. C. Conduit- Nom 6 in. (152 mm) diam (or smaller) rigid steel conduit, nom 4 in. (102 mm) diam (or smaller) steel electrical metallic tubing (EMT) or nom 4 in. (102 mm) diam (or smaller) fl exible steel conduit. D. Copper Pipe - Nom 4 in. (102 mm) diam (or smaller) Regular (or heavier) copper pipe. E. Copper Tube - Nom 4 in. (102 mm) diam (or smaller) Type L (or heavier) copper tube. Type of Penetrant Max Diam T Rating Steel or iron pipe, steel conduit or EMT 2 in. (51 mm)1 hr Steel or iron pipe, steel conduit or EMT 8 in. (203 mm) 3/4 hr Copper pipe or tube 4 in. (102 mm) 114 hr 2A. Through Penetrating Product" - Flexible Metal Piping - As an alternate to Item 2, one nom 1 -1/4 in. (32 mm) diam (or smaller) steel fl exible metal pipe to be installed either concentrically or eccentrically within the fi restop system. The annular space between the pipe and the periphery of the opening shall be min 0 in. (0 mm, point contact) to max 2 in. (51 mm). Pipe to be rigidly supported on both sides of the wall assembly. LE A BUNDY CO. WARD MFG INC OMEGA FLEX INC TITEF X CORP, -Min 5/8 in. 16 mm thickness of fi II material applied within annulus fl ush 3. Fill, Void or Cavity Material ( ) pp , with both surfaces of wall assembly. At point contact location, min 1/4 in. (6 mm) diam bead of fi II material applied at metallic pipe /gypsum board interface on both surfaces of wall. SPECIFIED TECHNOLOGIES INC - SpecSeal LCI Sealant 0� System No. W- L-3169 F Ratings -1 and 2 Hr (See Item 1) T Ratings -1/4 and 3/4 Hr (See Item 2A) Section A -A 1. Wall Assembly - The 1 or 2 hr fi re -rated gypsum board/stud wall assembly shall be constructed of the materials and in the manner specifi ed in the individual U300 or U400 Series Wall or Partition Design in the UL Fire Resistance Directory and shall include the following construction features: A. Studs - Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. lumber spaced 16 in. OC. Steel studs to be min 3 -5/8 in. wide and spaced max 24 in. OC. B. Gypsum Board* - Thickness, type, number of layers and fasteners as specifi ed in the individual Wall and Partition Design. Max diam of opening is 5 in. The hourly F Rating of the fi restop system is equal to the hourly fi re rating of the wall assembly in which it is installed. 2. Cables - Max 4 -1/2 in. diam tight bundle of cables to be installed eccentrically or concentrically within the opening. The annular space between the cables and the periphery of the opening shall be min 0 in. (point contact) to max 1/2 in. Cable bundle to be rigidly supported on both sides of the fl oor or wall assembly. The following types and sizes of cables may be used: A. Max 200 pair No. 24 AWG (or smaller) copper conductor with polyvinyl chloride (PVC) insulation and jacketing material. B. Max 1/C No. 350 kcmil (or smaller) copper conductor cable with cross- linked polyethylene (XLPE) jacket. C. Max 7/C No. 12 AWG (or smaller) copper conductor power and control cables with XLPE or PVC insulation with XLPE or PVC jacket. D. Max 3/C No. 2/0 AWG (or smaller) copper or aluminum conductor SER cables with PVC insulation and jacket E. Max 3/C No. 2/0 AWG (or smaller) copper conductor PVC jacketed aluminum clad or steel clad TEK cable. F. Max 110/125 fi bar optic (F.O.) cable with PVC insulation and jacket. G. Max 3/C with ground No. 8 AWG (or smaller) copper conductor NM cable (Romex) with PVC insulation and jacket. H. Max RG /U coaxial cable with fl uorinated ethylene insulation and jacket. I. Max 4 pair No. 24 AWG (or smaller) copper conductor data cable with Hylar jacket and insulation. 2A. Through Penetrating Product' - As an alternate to the cables (Item 2), max 4 in. diam tight bundle of max 4/C No. 210 AWG (or smaller) aluminum or steel Armored Cable+ or Metal Clad Cable+ installed within the opening. Annular space between throughpenetrating products and periphery of opening to be min 0 in. (point contact) to max 1 in. Through penetrating product rigidly supported on both sides of fl oor or wall assembly. When Armored Cable or Metal Clad Cable is used, T Rating is 1/4 hr. AFC CABLE SYSTEMS INC 3. Fill, Void or Cavity Material' - Sealant - Min 5/8 in. thickness of fi II material applied within annulus, fl ush with both surfaces of wall assembly. Sealant to be forced into interstices of cable bundle to max ax extent possible. At point contact location, min 114 in. diam bead of fi II material applied at cable bundle /gypsum board interface on both surfaces of wall. SPECIFIED TECHNOLOGIES INC - SpecSeal LCI Sealant 'Bearing the UL Classifi cation Marking System No. W -L -5122 F Ratings -1 and 2 Hr (See Item 1) T Rating - 1/4 Hr �A 4 f 3 2 LA Section A -A 1. Wail Assembly - The 1 or 2 hr fi re-rated gypsum board /stud wall assembly shall be constructed of the materials and in the manner specifi ed in the individual U300 or U400 Series Wall or Partition Design in the UL Fire Resistance Directory and shall Include the following construction features: A. Studs - Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. lumber spaced 16 in. OC. Steel studs to be min 3 -5/8 in. wide and spaced max 24 in. OC. B. Gypsum Board' - Thickness, type, number of layers and fasteners as specifi ed in the individual Wall and Partition Design. Max diam of opening is 7 -112 in. The hourly F Rating of the fi restop system is equal to the hourly fi re rating of the wall assembly in which it is installed. 2. Through Penetrant - One metallic pipe or tube to be installed eccentrically or concentrically within the fi restop system. Pi pe o r t ube t o be rigidly su pp orted on both sides of the wall assembly. The followin g typ es and sizes of metallic pipes and tubes may be used: A. Steel Pipe - Nom 4 in. diam (or smaller) Schedule 5 (or heavier) steel pipe. B. Iron Pipe - Nom 4 in. diam (or smaller) cast or ductile iron pipe. C. Copper Pipe - Nom 2 in. diam (or smaller) Regular (or heavier) copper pipe. D. Copper Tube - Nom 2 in. diam (or smaller) Type L (or heavier) copper tube. 3. Tube Insulation - Plastics# - Nom 3/4 in. thick acrylonitrile butadiene/polyvinyl chloride (AB/PVC) fl exible foam furnished in the form of tubing. Annular space shall be min 0 in. (point contact) to max 1 -1/2 in. See Plastics (QMFZ2) category in the Plastics Recognized Component Directory for names of manufacturers. Any Recognized Component tube insulation meeting the above specifi cations and having a UL 94 Flammability Classifi cation of 94-5VA may be used. 4. Fill, Void or Cavity Material' - Sealant - Min 5/8 in. thickness of fi II material applied within annulus, fl ush with both surfaces of wall assembly. At point contact location, min 1/4 in. diam bead of fi II material applied at insulated metallic pipe /gypsum board interface on both surfaces of wall. SPECIFIED TECHNOLOGIES INC - SpecSeal LCI Sealant 'Bearing the UL Classifi cation Marking NON RATED WALL S C A L E: 1 " =1' -0" 38" 5" NOM. OR 6" - 7"N 1. 1" 2 (1) LAYER 1/2" GYP. BD. ON EA. SIDE (TYPE AS PER APPLIED FINISH). 34" BATT INSULATION ATT. TO WALL BD. W/ WIRE STAPLES CONT. RUNNER FASTENED @ 24" AT STORAGE #001 :ONTINUE PARTITION UP TO U/S OF DECK AS PER RCP PLANS 1 NON -RATED - 3 5/8" STUD NON -RATED - 6" STUD AT BATHROOM SIDE 1/4" CERAMIC TILE ON 1/2" DUROCK (ONE OR BOTH SIDES AS REQUIRED) FINISH VARIES PER FLOOR FINISH PLANS: ID Y. , .. .............:. ,........... a EXIST. FLOOR SLAB NON - BEARING PARTITION NON RATED - 3 5/8" STUD @ 16" O.C. - (1) LAYER 1/2" GYP. BD. EACH SIDE - SOUND INSULATED AT WET ENVIRONMENTS (BATHROOM, JANITORS & 1A> SINK AREAS) SUBSTITUTE GYP. BD. LAYER WITH MOISTURE RESISTANCE GYP. BD. System No. HW -D -0079 Assembly Rating -1 and 2 Hr (See Item 2) Joint Width - 3/4 In. Maximum Class II Movement Capabilities - 25% Compression r-- A Q SECTI ❑N A -A 1. Floor Assembly - Min 4 -1/2 in. (114 mm) thick steel - reinforced lightweight or normal weight (100 -150 pcf or 1600 -2400 kg /m3) structural concrete. 2. Wall Assembly - The 1 or 2 hr fi re -rated gypsum board/stud wall assembly shall be constructed of the materials and in the manner described in the individual U400 0 0 r V4 0 Series Wall and Partition Design in the UL Fire Resistance Directory and shall include the following construction features: A. Steel Floor and Ceiling Runners - Floor and ceiling runners of wall assembly shall consist of galv steel channels sized to accommodate steel studs (Item 213) with min 1 -1/4 in. (32 mm) long fi anges. Ceiling runner secured to concrete fl oor slab with steel mason ry anchors h rs spaced max 24 in. (610 mm) OC. Al. Light Gauge Framing* - Clipped Ce ilin g Runner - As an alternate to the ceiling runner in Item 2A G i pped runner to consist of galv steel channel with clips preformed in track fl anges which positively engage the inside fl ange of the steel studs Item 213. Track sized to accommodate steel (Item 2B T - ( ) e s ee studs (e ). rack fl anges to be min 2 1/2 in. (64 mm) long. Clipped ceiling runner secured to concrete fl oor slab with steel masonry anchors spaced max 24 in. (610 mm) OC. TOTAL STEEL SOLUTIONS L L C - Snap Trak A2. Light Gauge Framing' - Slotted Ceiling Runner - As an alternate to the ceiling runner in Item 2A, ceiling runner to consist of gals steel channel with slotted fl anges sized to accommodate steel studs (Items 213). Ceiling runner secured to concrete fl oor slab with steel masonry anchors spaced max 24 in. (610 mm) OC. SLIPTRACK SYSTEMS INC - SLP -TRK A3. Light Gauge Framing" - Vertical Defl ection Ceiling Runner - As an alternate to the ceiling runner in Item 2A, vertical deft action ceiling runner to consist of gals steel channel with slotted vertical defl ection clips mechanically fastened within runner. Slotted clip provided with step bushings for permanent fastening of steel studs. Flanges sized to accommodate steel studs (Item 213). Vertical defl action ceiling runner secured to concrete fl oor slab with steel masonry anchors spaced max 24 in. (610 mm) OC. THE STEEL NETWORK INC - VertiTrack VTD358, VTD400, VTD600 and VTD800 A4. Light Gauge Framing' - Notched Ceiling Runner - As an alternate to the ceiling runners in Items 2A through 2A3, notched ceiling runners to consist of C- shaped galv steel channel with notched return fl anges sized to accommodate steel studs (Item 213). Notched ceiling runner secured to concrete fl oor slab with steel masonry anchors spaced max 24 in. (610 mm) OC. DENMAR STEEL INC - Type SCR B. Studs- Steel studs to be min 3 -1/2 in. (89 mm) wide. Studs cut 1/2 in. (13 mm) to 3/4 in. (19 mm) less in length than assembly height with bottom nesting in and resting on fl oor runner and with top nesting in ceiling runner without attachment. When deft ection channel (Item 3A) is used, steel studs attached to ceiling runner with sheet metal screws located 1/2 in. (13 mm) below the bottom of the deft ection channel. When slotted ceiling runner (Item 2A2) is used, steel studs secured to slotted ceiling runner with No. 8 by 1/2 in. (13 mm) long wafer head steel screws at midheight of slot on each side of wall. When vertical defl action ceiling runner (Item 2A3) is used, steel studs secured to slotted vertical defl ection clips, through bushings, with steel screws at midheight of each slot. Stud spacing not to exceed 24 in. (610 mm) OC. C. Gypsum Board' - Gypsum board sheets installed to a min total thickness of 518 in. (16 mm) and 1 -114 in. (32 mm) on each side of wall for 1 and 2 hr fi re rated assemblies, respectively. Wall to be constructed as specifi ad in the individual Wall and Partition Design in the UL Fire Resistance Directory, except that a nom 314 in. (19 mm) gap shall be maintained between the top of the gypsum board and the bottom surface of the fl oor. In addition, the top row of screws shall be installed into the steel studs 1/2 to 1 in. (13 to 25 mm) below the bottom edge of the ceiling runner flange. The hourly fi re rating of the joint system is dependent on the hourly fi re rating of the wall assembly in which it is installed. 3. Joint System - Max separation between bottom of fl oor and top of wall is 3/4 in. (19 mm). The joint system is designed to accommodate a max 25 percent compression om ression from its installed width. The joint system m consists of the 9 P P J Y following: A. Forming Material - (Optional, Not Shown) - In 2 hr fi re rated wall assemblies, polyethylene backer rod, mineral wool batt insulation or fi berglass batt insulation friction fi t into joint opening. B. Fill, Void or Cavity Material' - Sealant - Min 1/2 in. (13 mm) thickness of fi II material applied within joint opening on both sides of wall, fl ush with both surfaces of wall. As an option in 1 hr fi re rated walls, bond breaker tape applied to ceiling channel (Item 2A) prior to Installation of fi II material. SPECIFIED TECHNOLOGIES INC - SpecSeal ES Sealant `Bearing the UL Classifi cation Mark Reproduced courtesy of Underwriters Laboratories, Inc. EXISTING CMU WALL FURRING S C A L E: 1 " =1' -0" NON RATED & 2HR EXISTING CONCRETE WALL BOTTOM OF SLAB FINISHED CLG. AS PER RCP PLANS 1/2" GYP. BD. ON 7/8" STL. CHANNEL AT 24 FURRING INTERIOR SIDE: 1 -1/2" MTL FURRING CF WHERE E -BOXES (COC ELECTRICAL) FLOOR FINISH 8, BASE ROOM FINISH SCHEDU EXISTING FLOOR SLAB O 12 HR FIRE RATED EXISTING 8" CONCRETE WALL EXISTING CONCRETE WALL 2 NON RATED FURRING WALL AT WET ENVIRONMENTS (BATHROOM, JANITORS & 2A > SINK AREAS) SUBSTITUTE GYP. BD. LAYER WITH MOISTURE RESISTANCE GYP. BD. System No. W- L-5121 F Ratings -1 and 2 Hr (See Item 1) T Rating -1 Hr Section A -A 1. Wall Assembly - The 1 or 2 hr fl re -rated gypsum board/stud wall assembly shall be constructed of the materials and in the manner specifi ed in the individual U300 or U400 Series Wall or Partition Design in the UL Fire Resistance Directory and shall include the following construction features: A. Studs - Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. lumber spaced 16 in. OC. Steel studs to be min 3 -5/8 in. wide and spaced max 24 in. OC. B. Gypsum Board' - Thickness, type, number of layers and fasteners as specifi ed in the individual Wall and Partition Design. Max diam of opening is 12 in. The hourly F Rating of the fi restop system is equal to the hourly fi re rating of the wall assembly in which it is installed. 2. Through Penetrant - One metallic pipe or tube to be installed eccentrically or concentrically within the fi restop system. Pipe or tube to be rigidly supported on both sides of the wall assembly. The following types and sizes of metallic pipes and tubes may be used: A. Steel Pipe - Nom 6 in. diam (or smaller) Schedule 5 (or heavier) steel pipe. B. Iron Pipe - Nom 6 in. diam (or smaller) cast or ductile iron pipe. C. Copper Pipe - Nom 4 in. diam (or smaller) Regular (or heavier) copper pipe. D. Copper Tube - Nom 4 in. diam (or smaller) Type L (or heavier) copper tube. 3. Pipe Coverings - One of the following types of pipe coverings shall be used: A. Pipe and Equipment Covering Materials' - Nom 2 in. thick hollow cylindrical heavy density (min 3.5 pcf) glass fiber units jacketed on the outside with an all service jacket. Longitudinal joints sealed with metal fasteners or factoryapplied self - sealing lap tape. Transverse joints secured with metal fasteners or butt tape supplied with the product. The annular space between the insulated through penetrant and periphery opening shall be min 0 in. (point contact) to max 1 -1/2 in. See Pipe and Equipment Covering Materials (BRGU) category in the Building Materials Directory for names of manufacturers. Any pipe covering material meeting the above specifi cations and bearing the UL Classification Marking with a Flame Spread Index of 25 or less and a Smoke Developed Index of 50 or less may be used. B. Pipe Covering Materials' - Nom 2 in. thick unfaced mineral fi bar pipe insulation sized to the outside diam of pipe or tube. Pipe Insulation secured with min No. 8 AWG steel wire spaced max 12 in. OC. The annular space between the insulated through penetrant and periphery opening shall be min 0 in. (point contact) to max 1 -1/2 in. IIG MINWOOL L L C - High Temperature Pipe Insulation 1200, High Temperature Pipe Insulation BWT or HighTemperature Pipe Insulation Therrnaloc. C. Sheathing Material' - Used in conjunction with Item 3B. Foil- scrim -kraft or all service jacket material shall be wrapped around the outer circumference of the pipe insulation (Item 313) with the kraft side exposed. Longitudinal joints and transverse joints sealed with metal fasteners or butt tape. See Sheathing Materials (BVDV) category in the Building Materials Directory for names of manufacturers. Any sheathing material meeting the above specifi cations and bearing the UL Classifi cation Marking with a Flame Spread Index of 25 or less and a Smoke Developed Index of 50 or less may be used. 4. Fill, Void or Cavity Material* - Sealant - Min 5/8 in. thickness of fi II material applied within annulus, fl ush with both surfaces of wall assembly. At point contact location, min 1/4 in. diam bead of fi II material applied at insulated metallic pipe /gypsum board interface on both surfaces of wall. SPECIFIED TECHNOLOGIES INC - SpecSeal LCI Sealant 1 HR - UL DESIGN No. U419 S C A L E: 1 " =1' -0" UNDERSIDE OF EXISTING STRUCTURE FIRE -RATED SEALANT EACH SIDE GYP. BOARD TO 1/2" BELOW BOTTOM STRUCTURE EACH SIDE SEE REFLECTED CEILING PLAN - FOR CEILING HEIGHTS AND TYPES (1) LAYER 5/8" FIRE -RATED GYP. BD. ON EA. SIDE 3 1" STEEL STUDS W/ 32" BATT INSULATION ATT. TO WALL BD. W/ WIRE STAPLES CONT. RUNNER FASTENED @ 24" O.C. FIRE -RATED SEALANT EACH SIDE FLOOR FINISH & BASE PER ROOM FINISH SCHEDULE GYP. BD.MTL. STUD CHASE PARTITION NON RAT C = - - FOR APPLIED WALL FINISH OVER - GYP. BD. SEE FINISH SCHEDULE 8JOR INTERIOR ELEVATIONS 5" 38 2 1/2"W. 1 3/8" LEGS. & 1/4" GALV. STEEL STUDS @ 16 O.C. .......... ... ..: ,. EXIST. LOO SLAB NON - BEARING PARTITION < > 3 1 HR RATED - 3 5/8" STUD @ 16" O.C. System No. W -L -7060 F Ratings -1 and 2 Hr (See Item 1) T Rating -1/2 Hr c- A Section A-A 31" BATT INSULATION ATT. TO WALL BD. W/ WIRE STAPLES SEALANT BOTH SIDES 1. Wall Assembly - The 1 or 2 hr fi re-rated gypsum board/stud wall assembly shall be constructed of the materials and in the manner specifi ed in the individual U300, U400 or V400 Series Wall or Partition Design in the UL Fire Resistance Directory and shall include the following construction features: A. Studs - Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. (51 by 102 mm) lumber spaced 16 in. (406 mm) OC. Steel studs to be min 3-1/2 in. (89 mm) wide and spaced max 24 in. (610 mm) OC. Additional horizontal framing members installed to form a rectangular box around the steel duct (Item 2). B. Gypsum Board - Thickness, type, number of layers and fasteners as specifi ed in the individual Wall and Partition Design. When wood studs are used, interior of through opening to be lined with sheets of gypsum board around entire periphery to a total thickness of 5 in. 1 mm or 1 -1 4 in. 2 mm for 1 or 2 hr wall assemblies, p p ry /8 (6 ) / (3 ) a asse b es, respectively. Max area of opening is 952 s in. 0.61 m2 with a max dim of 32 in. 813 mm . P 9 q ( ) ( ) The hourly F Rating of the fi restop system is equal to the hourly fi re rating of the wall assembly in which it is installed. 2. Steel Duct - Max 24 by 30 in. (610 by 762 mm) No. 26 gauge (or heavier) galv steel duct installed eccentrically or concentrically within opening. Annular space between duct and periphery of opening to be min 0 in. ( 0 mm , Po int contact) to max 2 in. (51 mm). Duct to be rigidly supported on both sides of the wall assembly. 3. Firestop System - The fi restop system shall consist of the following: A. Packing Material - (Optional, Not Shown) - Mineral wool batt Insulation, foam backer rod or glass fi bar insulation installed as a permanent form to facilitate installation of fi II material (Item 313). B. Fill, Void or Cavity Material' - Sealant - Min 5/8 in. (16 mm) thickness of fi II material applied within annulus, fl ush with both surfaces of wall assembly. At point contact location, min 1/4 in. (6 mm) diam bead of fi II material applied at steel ductigypsum board interface on both surfaces of wall. SPECIFIED TECHNOLOGIES INC - SpecSeal LCI Sealant C. Retaining Angles - Min 16 gauge galv steel angles sized to lap onto duct a min of 2 in. (51 mm) and to lap onto wall around periphery of opening a min of 1 in. (25 mm). Angles attached to all four sides of steel duct on both surfaces of wall with No. 10 (or larger) steel sheet metal screws located 1 in. (25 mm) from each end and spaced max 4 in. (102 mm) OC. FAI 22" VARIES 22" T_ AS PER RCP PLANS AT BATHROOM SIDE I1 /4" CERAMIC TILE ON 1/2" DUROCK (ONE OR BOTH SIDES AS REQUIRED) 2HR RATED SHAFT WALL 2 HR - UL DESIGN No. U415 SCALE: 1 " =1' -0" 3" CAVITY SHADOWLINE RUNNER, 25 MSG GALV STEEL, FASTENED @ 24 "O.C. MAX. 1" THICK GYPSUM WALLBOARD LINER PANELS. 2 1/2" I- SHAPED MTL. - STUDS, 25 MSG GALV. STEEL @ 24-O.C. MINERAL WOOL OR GU` FIBER BATTS. (2) LAYERS 5/8" THICK, TYPE "X" GYPSUM BOAI SHAFT SIDE FLOOR RUNNER 25 GA. CHAN., 1" + 2" UNEQ. LE UNDERSIDE OF SLAB AT 2 HR. RATED WALLS, CLG. AS PER RCP PLANS FIRE STOP ALL GAPS. SEE FIRESTOP DTLS 1►�IFE :I=0s>w�vt9l:4 FINISH VARIES PER FLOOR FINISH PLANS FLOOR SLAB NON - BEARING PARTITION ofrY or SOU r� B(/ILDING DtPp -r. STUCTUR! �ECTfp� l � M O �.,clrs O 00 O �1 N� rm M c ,, \. V < QJ r0 V Liz CML M �l i Drawn By: OS Checked By: OS • V Date 06-15 -2012 Revisions 1 11.13.2012 a Z O Z aw >a X o� � � o O c=n � J oQ LL N 2 to LCPL G r till eka M r'*, . .r� .DTI SCHEDULES 4' r f Project No: 61806 Am6; 'J619b ' se 9 ) 96 z' r M O �.,clrs O 00 O �1 N� rm M c ,, \. V < QJ r0 V Liz CML M �l i Drawn By: OS Checked By: OS • V Date 06-15 -2012 Revisions 1 11.13.2012 a Z O Z aw >a X o� � � o O c=n � J oQ LL N 2 to LCPL G r till eka M r'*, . .r� .DTI SCHEDULES 4' r f Project No: 61806 Am6;