12-952-022i{ is I',1 CEILING MOUNTED SMOKE /HEAT DETECTOR AUDIO ONLY 24" MIN HANDICAP DEVICES BEDROOM STROBE FIRE Ft� SYNCHRONIZE MORE THAN TWO APPLIANCES IN ANY FIELD OF VIEW MINIMUM OF 55' FROM EACH NFPA 72 2002 EDITION (SECTION 7.5.4.1.2(3)) NO LESS THAN 90" ABOVE FINISHED FLOOR NOR LESS THAN 6" BELOW FINISHED CEILING, WHICHEVER IS LOWER NFPA 72 2002 EDITION (SECTION 7.4.6.1) 80" MIN 96" MAX NFPA 72 2002 EDITION (SECTION 7.5.4) FINISHED FLOOR OPEN AREA SUPPORT 016 3' (MIN) AUDIO /VISUAL & VISUAL -ONLY DEVICES MANUAL PULL STATION O A/C SUPPLY /RETURN DIFFUSER --{ I Z/m rvz 42" MIN /54" MAX (NFPA) NFPA 72 2002 EDITION (SECTION 5.12.3,4) MOUNTING HEIGHT DETAIL ACCEPTED HERE - NEVER HERE • 4" WALL MOUNTED SMOKE /HEAT DETECTOR FINISHED WALL NOTE: MEASUREMENTS SHOWN ARE TO THE CLOSEST OF THE DETECTOR, SIDE WALL 12" (MAX) FIRE ALARM SYSTEM SEQUENCE OF OPERATION THE ACTUATION OF THE FIRE ALARM INITIATING DEVICES SHALL AUTOMATICALLY INITIATE THE FOLLOWING FUNCTIONS: A) MANUAL FIRE ALARM PULL STATION: 1. GENERATE AN AUDIBLE ALARM SIGNAL AT THE FIRE ALARM CONTROL PANEL. 2. GENERATE AN AUDIBLE ALARM SIGNAL SIMULTANEOUSLY ON DESIGNATED AREAS OF THE BUILDING BY MEANS OF HORN OR SPEAKER DEVICES. 3. GENERATE A VISUAL ALARM SIGNAL SIMULTANEOUSLY IN DESIGNATED AREAS OF THE BUILDING BY THE USE OF STROBE DEVICES, 4. INDICATE THE LOCATION OF THE ACTIVATED DEVICE BY DISPLAYING THE DEVICE LABEL AND ITS LOCATION ON THE FACP ALPHANUMERIC DISPLAY AND ON THE REMOTE ANNUNCIATOR (IF APPLICABLE). 5. TRANSMITS A "FIRE ALARM" SIGNAL TO THE DESIGNATED THIRD PARTY CERTIFIED CENTRAL STATION, B) SMOKE DETECTORS: 1. GENERATE AN AUDIBLE ALARM SIGNAL AT THE FIRE ALARM CONTROL PANEL. 2, GENERATE AN AUDIBLE ALARM SIGNAL SIMULTANEOUSLY ON DESIGNATED AREAS OF THE BUILDING BY MEANS OF HORN OR SPEAKER DEVICES, 3, GENERATE A VISUAL ALARM SIGNAL SIMULTANEOUSLY IN DESIGNATED AREAS OF THE BUILDING BY THE USE OF STROBE DEVICES. 4. INDICATE THE LOCATION OF THE ACTIVATED DEVICE BY DISPLAYING THE DEVICE LABEL AND ITS LOCATION ON THE FACP ALPHANUMERIC DISPLAY AND ON THE REMOTE ANNUNCIATOR (IF APPLICABLE). 5. TRANSMITS A "FIRE ALARM" SIGNAL TO THE DESIGNATED THIRD PARTY CERTIFIED CENTRAL STATION, C) DUCT DETECTORS: 1. GENERATE AN AUDIBLE "TROUBLE" ALARM SIGNAL AT THE FIRE ALARM CONTROL PANEL, 2. INDICATE THE LOCATION OF THE ACTIVATED DEVICE BY DISPLAYING THE DEVICE LABEL AND ITS LOCATION ON THE FACP ALPHANUMERIC DISPLAY AND ON THE REMOTE ANNUNCIATOR (IF APPLICABLE). 3. SHUT OFF THE AIR HANDLING UNIT AND A/C EQUIPMENT ASSOCIATED WITH THE DUCT DETECTOR. 4. TRANSMITS A "TROUBLE" SIGNAL TO THE DESIGNATED THIRD PARTY CERTIFIED CENTRAL STATION. D) DEVICES IN TROUBLE. OPENINGS OR GROUNDING OF ANY WIRE SHALL ACTIVATE A VISUAL AND AUDIBLE "TROUBLE" SIGNAL AT THE FIRE ALARM CONTROL PANEL AND SEND THE TROUBLE SIGNAL TO THE CENTRAL STATION, UQM- CONTRACTOR SHALL NOTIFY ENGINEER IF EXISTING FIRE ALARM SYSTEM SEQUENCE OF OPERATION IS DIFFERENT AS DESCRIBE ABOVE BEFORE INSTALLATION AND /OR MAKING ANY CHANGES TO THE EXISTING SYSTEM. - -1._J- - _.. {.a.- .._.._ FIRE ALARM SPECIFICATIONS : 1. INSTALLATION SHALL BE IN ACCORDANCE WITH THE 2008 EDITION OF NFPA 70, 2002 NFPA 72, FLORIDA BUILDING CODE, FLORIDA FIRE PREVENTION CODE AND ALL LOCAL RULES AND REGULATIONS, 2, ALL EQUIPMENT SHALL BE IDENTIFIED, COMPATIBLE AND LISTED FOR THE APPLICATION BEING USED, ALL EQUIPMENT MUST HAVE AN UNIQUE IDENTIFICATION NUMBER, 3. CONTRACTOR SHALL PROVIDE ALL REQUIRED PERMITS, 4, MINIMUM CONDUIT SIZE WILL BE 3/4 ". MAX CONDUIT FILL SHALL BE 40 %, 5. CONTRACTOR SHALL WARRANTEE ALL WORKMANSHIP AND MATERIALS FOR A MINIMUM OF ONE YEAR FROM FINAL INSPECTION. 6. CONTRACTOR SHALL REPORT ANY DISCREPANCIES TO THE ENGINEER FOR CLARIFICATION. 7. CONTRACTOR SHALL INVESTIGATE THE PROJECT SITE AND ALL EXISTING SYSTEMS PRIOR TO BIDDING AND CONSTRUCTION, 8. SUBMIT SHOP DRAWINGS TO TO CITY /FIRE MARSHALL FOR APPROVAL PRIOR TO ROUGH -IN, AND TO ENGINEER FOR REVIEW. 9, VERIFY LOCATION OF ALL DEVICES WITH FIRE MARSHALL AND OWNER REPRESENTATIVE AT ROUGH -IN, 10, PROVIDE AND INSTALL ALL 'FIRE MARSHALL APPROVED' SIGNAL TRANSMISSION EQUIPMENT FOR MUNICIPAL TIE-IN. COORDINATE WITH FIRE DEPARTMENT. 11, THIS IS A PROTECTED PREMISES REMOTE SUPERVISING STATION FIRE ALARM SYSTEM, USING A TWO PHONE DIALER AT FIRE ALARM CONTROL PANEL (FACP), FACP MUST SERVES THE PROTECTED PREMISES AND INDICATES THE "ALARM" SENDING A SIGNAL TO THE CENTRAL STATION THRU A DIALER AND VIA NOTIFICATION APPLIANCES INSIDE THE PROTECTED PREMISES. 12. FIRE ALARM CONTROL PANEL SHALL BE CROSS LISTED AND COMPATIBLE WITH OTHER COMPONENTS USED 13, ALL INITIATING AND INDICATION CIRCUITS MUST BE SUPERVISED. 14, ALL NEW CONDUITS MUST BE' CONCEALED IN WALLS. 15. EVACUATIONS SIGNALS SHALL BE TEMPORAL IN ACCORDANCE WITH NFPA 72 3- 7.2(A) AND ANSI 53.41. 16, CIRCUIT BREAKER SUPPLYING POWER TO THE FIRE ALARM PANEL AND COMPONENTS NEED TO BE CLEARLY MARKED WITH RED PAINT, 17. SIZE GUTTERS ND JUNCTIONS BOXES ACCORDING TO 314.28 AND 314.71 OF "NEC" (NFPA 70), 18. POWER UP AND POWER DOWN OF THE FIRE ALARM PANEL MUST BE DONE IN THE PROPER SEQUENCE: POWER DOWN: DISCONNECT BATTERY AND THEN TURN OFF THE AC POWER AT THE BREAKER. POWER UP: TURN ON THE AC POWER AT THE BREAKER AND THEN CONNECT THE BATTERY, NOTE' DO NOT DISCONNECT THE AC POWER FEED FROM THE TERMINAL BLOCK TO DISCONNECT POWER. 19. THE SOUND LEVEL OF ALL NOTIFICATION DEVICES SHALL BE AT LEAST 15dbA ABOVE THE EQUIVALENT SOUND LEVEL OR 5 DBA ABOVE THE MAXIMUM I SOUND LEVEL HAVING A DURATION OF AT LEAST 60 SECONDS, MEASURED 5 FT. ABOVE THE FLOORIIN THE OCCUPIED AREA, 20, BATTERY BACK -UP SHALL BE PROVIDED FOR 24 HOURS STANDBY AND 15 MINUTES IN ALARM. 21, FIRE ALARM SYSTEM MUST BE ADDRESSABLE. 22, SYSTEM SHALL HAVE A REMOTE SUPERVISION STATION MONITORING SERVICE, COORDINATE INTERCONNECTION (PHONE /INITERNET) WITH CLIENT, NOTES Z SCOPE OF WORK: 1. BUILDING HAS AN EXISTING FIRE ALARM SYSTEM. WORK CONSIST OF BUILD -OUT OF TENANT SPACE ONLY. 2, SEE PLANS FOR', LOCATION AND QUANITITY OF DEVICES TO BE INSTALLED. ALL DEVICES ARE NEW UNLESS OTHERWISE NOTICED iAS EXISTING OR RELOCATED. 3. RECONNECT ALLY EXISTING AND /OR RELOCATED !DEVICES TO THE FIRE ALARM SYSTEM. 4, EXISTING FIRE ALARM SYSTEM SEQUENCE OF OPERATION AND CIRCUITS CLASS & STYLE SHALL REMAIN THE SAME, I 5, CONTRACTOR STALL TEST ALL EXISTING FIRE ALARM DEVICES AND REPAIR /REPLACE WITH NEW AS REQUIRED, 6, FIRE ALARM SYSTEM SHALL RE POWER LIMITED I AS PER NEC 760 AND UL 864 REQUIREMENTS, NOTIFY ENGINEER IF EXISTING FIRE ALARM SYSTEM IS NOT POWER LIMITED. 7. CONTRACTOR SHALL PROVIDEi,'SHOP DRAWINGS, I RISER, BATTERY CALCULATIONS AND CUT SHEETS AND SUBMIT TO BUILDING DEPARTMENT FOR CONSTRUCTION PERMIT REVIEW AND APPROVAL. SHOP DRAWINGS SHALL BE IN CONFORM WITH ALL' REQUIREMENTS OF NFPA -72, 2002 EDITION. 8, ALL NEW DEVICES SHALL BE COMPATIBLE WITH j THE EXISTING FIRE ALARM SYSTEM. 9. ALL VISUAL NOT FICATION APPLIANCES SHALL BE 75cd MINIMUM. CONTRACTOR TO REPLACE ANY EXISTING DEVICE IF LESS THAN 75cd WITHIN THIS SCOPE OF WORK. 10. PROVIDE RE- CERTIFICATION OF SYSTEM AFTER ,COMPLETION, 11. FIRE ALARM CIRCUITS SHALL BE AS FOLLOW: I 11.1. INITIATING DEVICES SHALL, BE CLASS 'B', STYLE 'C', 11.2. SIGNALING LINE CIRCUITS ,SHALL BE CLASS :'B', STYLE W. 11.3, NOTIFICATION CIRCUITS SHALL BE CLASS 'B', STYLE 'Y'. 11.4. CONTRACTOR SHALL NOTIFY ENGINEER IF EXISTING FIRE ALARM CIRCUITS CLASS AND STYLE ARE NOT AS DESCRIBED ABOVE BEFORE INSTALLATION AND /OR MAKING ANY CHANGES TO THE EXISTING SYSTEM. 12, FOR REFERENCE, BUILDING IS SPRINKLER, THESE PLANS ARE FOR BUILDING DEPARTMENT REVIEW ONLY, THEY ARE NOT TO BE CONSTRUED AS CONSTRUCTION DOCUMENTS UNTIL ALL BUILDING DEPARTMENT APPROVALS ARE OBTAINED. DO `use be subm .I.t-, d fear zz sl € aPPr(v 41'(0 i ti' lo- u-sIty .'`ire De na %'tip'" 1 i . App },,,• - Dale EIRE ALARM LEGEND ® PULL STATION t2 SMOKE DETECTOR �2 DUCT SMOKE DETECTOR O HEAT DETECTOR �Q 75cd MULTI - CANDELA STROBE 18175cd MULTI - CANDELA HORN /STROBE Rr REMOTE TEST STATION - Ne , Am FIRE ALARM LAYOUT PLAN Scale: 1/4" = V -0" PROJECT #:1245 Ofer Stark, AIA Licer,se #A, 996 i % L•J F- Q J O z w M O W F- T LU N� L.L 0 LLI O J z LL C-C U C O Q N 2E FIRE ALARM LAYOUT PLAN Project No: 6280603 L Al t °4B I FAm 1 0 ANt O't 9C-OL0WELL lta ' ■ OSCAR _`a ISj�BELEN, PE - tLIC #+ 66481 O O O O O f; M M M c� V '6 t � `A � lRV � M Drawn By: OS Checked By: OS Date 07 -23 -2012 Revisions L•J F- Q J O z w M O W F- T LU N� L.L 0 LLI O J z LL C-C U C O Q N 2E FIRE ALARM LAYOUT PLAN Project No: 6280603 L Al t °4B I FAm 1 0 ANt O't 9C-OL0WELL lta ' ■ OSCAR _`a ISj�BELEN, PE - tLIC #+ 66481