09-700-001KEY • N (6th FLOOR)
REVISICNS'
1 —FIRE ALARM SYSTEM SHALL BE U.L. LISTED AND NFPA 72 APPROVED AND
COMPATIBLE.
2 —RISER INTERCONNECTIONS ARE DIAGRAMMATIC ONLY.
3 —TOTAL ACTIVE AREA: 7.260 SO. FT.
4 —FIRE ALARM SYSTEM TO BE "POWER LIMITED ".
5 —THE INSTALLATION SHALL COMPLY WITH NFPA 70 CHAPTER 760
6 —ALL WIRING AND CONDUIT SIZE SHALL BE IN ACCORDANCE WITH
MANUFACTURER RECOMMENDATION, LOCAL CODES AND NFPA.
7 —ALL CONDUCTORS SHALL BE SOLID OR STRANDED COPPER.
8— MAXIMUM CONDUIT FILLS TO BE 40%. MINIMUM RACEWAY SIZE
9— SYSTEM SHALL BE GROUNDED ACCORDING TO MANUFACTURER
SPECIFICATION AND NEC ARTICLE 250.
10 —ALL FIRE WALL PENETRATION SHALL BE MADE WITH APPROVED (NEC)
ELECTRICAL TUBING AND SEALED WITH A U.L. LISTED FIRE STOPPER. (SEE
FIRE STOP DETAIL).
11 —THE 120V AC POWER FEED FOR THE FIRE PANEL MUST BE FROM A
DEDICATED CIRCUIT AND THE BREAKER MUST BE IDENTIFIED FIRE ALARM
CIRCUIT AND HAVE A LOCK ON IT.
12— VISUAL ALARM PER ANSI A117.1, 4.26, AND ADA APPROVED. WALL
MOUNTS 80" A.F.F. TO BOTTOM OF STROBE LENS.
13 —ALL NEW WIRING INSTALLED IN DUCTS, PLENUMS AND OTHER SPACES
USED FOR ENVIRONMENTAL AIR SHALL BE TYPE FPLP, AS PER NEC
(NATIONAL ELECTRIC CODE) ARTICLE 760 -61.
14 —ALL N.A.C. WIRING SHALL BE CLASS "B" (STYLE "Y"). EIGHT ZONES, 6
CLASS B (STYLE A) AND 2 CLASS A (STYLE D). THE MODEL 5210
PROVIDES THE 5207 WITH EIGHT ADDITIONAL CLASS B (STYLE A) ZONES.
15—HO"/STROBES SHALL BE LOCATE AS PER WFPA 72, CRWTER 7.
16— STROBE LIGHT CIRCUITS SHALL BE SYNCHRONIZED AT 1 HZ PER ADA AND
NFPA 72.
17— UNLESSm-0T11ERWlSE NOTED - ALL - CEILING HEIGHTS DO NOT EXCEED 10' -0"
AND ALL:..CEI INGS- •ARE-�FLAT.
18— FURNITURE AND EQUIPMENT SHALL. NOT EXCEED 72" IN HEIGHT WHERE
PLACED ALONG THE PATH OF VISUAL SIGNALS.
19— IS CLASSIFIED -AS REMOTE SUPERVISING STATION FIRE
AL.ARM..SYSTEW
20 —THE SYSTEM SHALL HAVE BATTERY BACK UP FOR 24 HRS IN STANDBY
MODE AND 5 MINUTES IN ALARM.
THIS IS AN i O•
• i 7 BUtDiNG
i
E: DENOTE EXISTING DEVICE If
N: DENOTE NEW DEVICE
FIRE ALARM
LEGEND
I.M
SCALE
DESCRIPTION
•i
' R'
+ •
J
RRE ALARM CONTROL PANEL
DATE:
Zom
MOM
REMOTE ANNUNCIATOR `
•
REMOTE POWER SUPPLY
.rl
•
PHOTOELECTRIC SMOKE DETECTOR
SYSTEM
SENSOR
Q ,
CONVENTIONAL DUCT DETECTOR
SYSTEM
S S •-
DH100AC •
CONVENTIONAL PULL STATION
+` 'O= •
_
STROBE LIGHT WALL MOUNT (1 5/75cd,
75cd)
11 SYSTEM
SENSOR
+- `+e +
'
.,
TAMPER SVITCH
•
WATERFLOW SWITCH
' +
BACKFLOW P -
_ • -
+
E: DENOTE EXISTING DEVICE If
N: DENOTE NEW DEVICE
INFORMATION: OWNER
. s # D SUNSET LLC.
1660 N.E. MAW GARDEN DR_ SUITE 8
NORTH
IIALCIO
FIRE • CONTRACTORS
•• r `
•
7234 N.W. 66TH STREET
R.ORIDA 33166
TEL (305) 592-4U7
FAX: (305) 592-9977
..
QUALIFIER:
DATE: DANIEL R. FERNANDEZ,,,
0r? Vo
DRAWN
I.M
SCALE
0
•i
to
J
w
DATE:
Zom
om
LLI
•
.rl
•
it
..
Coll
INFORMATION: OWNER
. s # D SUNSET LLC.
1660 N.E. MAW GARDEN DR_ SUITE 8
NORTH
IIALCIO
FIRE • CONTRACTORS
•• r `
•
7234 N.W. 66TH STREET
R.ORIDA 33166
TEL (305) 592-4U7
FAX: (305) 592-9977
..
QUALIFIER:
DATE: DANIEL R. FERNANDEZ,,,
0r? Vo
DRAWN
I.M
SCALE
PROD. NO.
DATE:
07/20/09
ml
m