System No. C -AJ -2419
F Rating - 3 Hr
T Rating - 0 Hr
1. Floor or Wall Assembly -- Min 4 -1/2 in. thick reinforced lightweight or normal weight (100 -150 pcf) concrete floor or min
5 in. thick reinforced lightweight or normal weight (100 -150 pcf) concrete wall. Wall may also be constructed of any UL
Classified Concrete Blocks *. Max diam of opening shall be 6 in.
See Concrete Blocks (CAZT) category in the Fire Resistance Directory for names of manufacturers.
2. Through Penetrants -- One nonmetallic penetrant centered within the firestop system. The annular space between pipe and
periphery of opening shall be nom 3/4 in. Pipe to be rigidly supported on both sides of the floor assembly. The following
types and sizes of non - metallic pipe may be used:
A. Polyvinyl Chloride (PVC) Pipe -- Nom 4 in. diam (or smaller) Schedule 40 solid core or cellular core PVC pipe for
use in closed (process or supply) or vented (drain, waste or vent) piping systems.
B. Chlorinated Polyvinyl Chloride (CPVC) Pipe -- Nom 4 in. diam (or smaller) SDR 13.5 CPVC pipe for use in closed
(process or supply) piping systems.
C. Acrylonitrile Butadiene Styrene (ABS) Pipe -- Nom 4 in. diam (or smaller) Schedule 40 solid core or cellular core
ABS pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems.
3. Firestop System -- The details of the firestop system shall be as follows:
*- -
- - in wide intumescent wrap The
A Fill Void or Cavity Mate
real Wrap Strip Nom 3 16 in. thick b 1 3 4
P
. P P / Y /
Y
wrap strip i s continuously wrapped around the outer circumference
of the pipe covering two times and slid into the
annular space. When multiple wrap strips are used to achieve the required total length, the ends are to be butted
end to end and held in place with tape. The bottom edge of the wrap strip shall be recessed 1/2 in. from the
bottom surface of the concrete floor. In walls, the wrap shall be installed on both surfaces of the wall such that
the exposed edge of the wrap strip is recessed 1/2 in. from
each side of the wall.
-- P 648 -E- W45/1-3/4' Wra Stri
CHEMICALS DIV OF HILTI INC C
HILT/ CONSTRUCTION p p
B. Fill, Void or Cavity Materials* - Sealant -- Min 1/2 in. thickness of fill material applied within the annulus, flush
with bottom surface of floor or both surfaces of wall.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC -- FS ONE Sealant
*Bearing the UL Classification Mark
D�1012==D=0® Reproduced by HILTI, Inc, Cs, Inc, of
Underwriters Laboratories, Inc.
FIRESTOP SYSTEMS Apn127,20135 C ® US
System No. C-AJ -2271
F Rating - 2 Hr 'a
T Rating -1 Hr
A W Rating - Class 1(See Item 3)
�► A
cCr•rrnu A_A
1. Floor or Wall Assembly - Min 2 -1/2 in. (64 mm) thick reinforced lightweight or normal weight (100 -150 pdor 1600 -2400 kghn3) concrete. Wall
may also be constructed of any UL Classified Concrete Blocks'. Maxdiam of opening is 7 in. (178 mm).
See Concrete Blocks (CAZT) category in the Fire Resistance Directory for names of manufadlirers.
2. Through Penetrants - One nonmetallic pipe or conduit to be installed concenbicalyoreceenbicalywitNn the firestop system. Annular space
between pipe or conduit and edge of opening to be min 0 in. (0 mm, point contact) and max 1/2 in. (13 mm). Pipe ormnduit to be rigidly
supported on both sides of floor - ceiling assembly. The following types and sizes of nonmetallic pipes or conduits maybe used:
A. Polyvinyl Chloride (PVC) Pipe - Nom 6 in. (152 mm) diam (or smaller) Schedule 40 solid orcellularcore PVC pipe for use in dosed (process
or supply) or vented (drain, waste orvent) piping systems.
B. Chlorinated Polyvinyl Chloride (CPVC) Pipe - Nom 6 in. (152 mm) diam (orsmaller) SDR13.5 CPVC pipe for use in dosed (process or
supply) piping systems.
C. Acrylonitrile Butadiene Styrene (ABS) Pipe - Nom 6 in. (152 mm) diam (or smaller) Schedule 40 solid orcellularcore ASS pipe for use in
dosed (process or supply) or vented (drain, waste orvent) piping systems.
D. Flame Retardant Polypropylene (FRPP) Pipe - Nom 6 in. (152 mm) diam (orsmaller) Sdhedule 40 FRPP pipe for use in dosed (processor
supply) or vented (drain, waste orvent) piping systems.
3. Fill, Void or Cavity Matenals' - Sealant- Required for systems with W Rating, butothenvise optional. Min 112 in. (13 mm) thickness of fill
material applied within the annulus, flush with top or bottom surface of floor. W Rating applies onywhen CP601S orCP 604 Sealant is used.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILT] INC - FS-ONE Sealant, CP 601S Sealant or CP 604 Sealant
3A. Packing Material (not shown) - Min 112 in. (13 mm) thickness of 4 pd (64 kg/m3) mineral wool bad insulation finely packed into annularspace
and recessed from the top surface of floor to accommodate the required thickness of fill material. Required cnlywhen CP 604 Sealant is used.
4. Firestop Device' -Firestop Collar - Firestop collar shall be installed in accordance with the accompanying installation instructions. Collarto be
installed and latched around the pipe and secured to underside of floor or both sides ofwall using andhorhocks provided with the collar. Minimum
two anchor hooks required for nom 1 -112 and 2 in. (38 and 51 mm) diam pipes. Minimum three anchor hooks required fornom 3 and 4 in. (76 and
102 mm) diam pipes. Minimum four anchor hooks required for 6 in. (152 mm) diam Pipes. The anchor hooks are lo be secured with min 114 in. (6
mm) diam by min 1 -1/4 in. (32 mm) long steel expansion bolts or min 0.145 in. (3.7 mm) diam by 1 -114 in. (32 mm) long powderactuated
fasteners utilizing a 1 -7/16 in. (37 mm) diam by 1116 in. (1.6 mm) thick steel washer. As altemates to the anchors specified above, Hilti 1/4 in. (6
mm) diam by 1 -1/4 in. (32 mm) long KWIK -CON II+ concrete screw anchor, Hilti 1/4 in. (6 mm) diam by 1 -314 in. (45 mm) tong KWIK -BOLT 3 steel
expansion anchor or Hilti X -DNI 27 P8 S15 powder actuated floor pin with integral nom 9/16 in. (15 mm) diam washer maybe used.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC - CP 643 50/1.5-N, CP 643 6312% CP 643 935-N, CP 643 9014"N and CP643
160/6'N. Firestop Collar
'Bearing the UL Classification Mark
Reproduced by HILTI, Inc. Courtesy of
Underwriters Laboratories, Ina V
Hilti Firestop Systems November 18, 2006 m
System No. W L -2284
F Rating -1 Hr
T Rating -1 Hr
Al
ecrrrnry A_A
1. Wall Assembly -- The 1 hr fire -rated gypsum board /stud wall assembly shall be constructed of the materials and in the
manner specified in the individual U300 or U400 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall
include the following construction features:
A Studs -- Wall framing shall consist of wood studs or steel channel studs. Wood studs to consist of 2 by 4 in. lumber
spaced 16 in. OC. Steel studs to be min 3 -1/2 in. wide and spaced max 24 in. OC.
B. Gypsum Board* -- Min 5/8 in, thick, 4 it wide with square or tapered edges. The gypsum wallboard type, thickness,
number of layers and orientation shall be as specified in the individual U300 or U400 Wall and Partition Design. Max
diam of opening is 4 in.
2. Through Penetrants -- One nonmetallic pipe to be centered within the firestop system. An annular space of 3/16 to 1/4 in.
is required within the firestop system. Pipe to be rigidly supported on both sides of wall assembly. The following types and
sizes of nonmetallic pipes may be used:
A Polyvinyl Chloride (PVC) Pipe -- Nom 3 in. diam (or smaller) Schedule 40 solid or cellular core PVC pipe for use in
closed (process or supply) or vented (drain, waste or vent) piping systems.
B. Chlorinated Polyvinyl Chloride (CPVC) Pipe -- Nom 3 in. diam (or smaller) SDR 13.5 CPVC pipe for use in closed
(process or supply) piping systems.
3. FII, Void or Cavity Material* -- Wrap Strip - Layers of intumescent wrap strip are continuously wrapped around the pipe with
ends held in place with tape. Wrap strip installed such that ends protrude nom. 1/8 in. beyond both surfaces of wall. Size
of wrap strip and number of layers are shown in table below.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILT] INC -- CP648 -E W25/1' or CP648 -E W45/1 -3/4' Firestop Wrap Strip
ProductDesignabon
Pipe
Numberof
Nom. Wrap Strip
SYMBOL
Diameter i n
Layers
Width (in.)
/ '
CP648 E -W251
1-1/2 and 2
1
1
CP648- E -W45/1 -314'
1 -112, 2 and 3
1
1 -3/4
A ill Void or Cavity Material* - Wrap Strip - -
( As an alternate to the wrap strip in Item 3 ) One layer of intumescent
wrap strip is tightly wrapped around the pipe with ends butted and held in place with integrated tape. Wrap strip
installed such that ends protrude
nom 1 / 8 in. beyond both surfaces of wall.
HILTI CONSTRUCTION CHEMICALS, DIV OF
HILTI INC -- CP648- S -1.5' US, CP648 -S -2' US, CP648 -S -3' US
*Bearing the UL Classification Mark
E===FJ= 0° Reproduced bysLab Ina Cs, Inc. of
Underwriters Laboratories, Inc.
FIRESTOP SYSTEMS Apn122, zoos C @us
System No. F -A -2089
F Rating - 3 Hr
T Rating - 0 Hr
W Rating - Class 1(See Item 313)
cCrrnnu A_A
1. Floor Assembly - Min 2-1/2 in. thick reinforced lightweight or normal weight (100.150 pd) concrete. Max diameter of opening is 5 in.
1A. Floor Assembly - (Optional - Not Shown) -The fire rated unprotected concrete and steel floorassemblyshall be constructed tithe materials
and in the manner specified in the individual D900 Series designs in the Fire Resistance Diredoryand as summarizes below:
A. Concrete - Min 2 -1/2 in. thick reinforced lightweight or normal weight (100 -150 pd) concrete.
B. Steel Floor and Form Units' - Composite or non - composite max 3 in. deep gaivsteel fluted unitsas specified in the individual Floor - Ceiling
Design.
2. Through Penetrants - One nonmetallic pipe to be installed concentrically or ecoentricellywithin theflrestop system. Annularspaee within the
firestop system is dependent upon the diam and type of penetrant used as tabulated in Item 3A Pipe lo be rigidly supported on both sides of floor
or wall assembly. The following types and sizes of nonmetallic pipes may be used:
A. Polyvinyl Chloride (PVC) Pipe - Nom 3 in. diam (or smaller) Schedule 40 solid or cellular core PVC for use in dosed (process or supply) or
vented (drain, waste or vent) piping systems.
B. Chlorinated Polyvinyl Chloride (CPVC) Pipe - Nom 3 in. diam (or smaller) SDR13.5 CPVC for use in dosed (process or supply) piping
systems.
C. Acrylonitrile Butadiene Styrene (ABS) Pipe - Nom 3 in. diam (or smaller) Schedule 40 solid or cellular core PVC for use in dosed (process
or supply) or vented (drain, waste or vent) piping systems
D. Flame Retardant Polypropylene (FRPP) Pipe - Nom 3 in. diam (or smaller) Schedule 40 FRPP pipe for use in dosed (process or supply) or
vented (drain, waste orvent) piping system.
3. Firestop System - The firestop system shall consist of the following:
A. Fill, Void or Cavity Material' Wrap Strip - Nom 3116 in. thick by 1 -3/4 in. wide intumescentwmp strip. The layers of wrap strip are
continuously wrapped tightly around pipe with ends held in place with tape. Wrap strip installed recessed'/ in. from bottom surface of
concrete cover. The max diam of opening, max diam and type of penetrant, annular space within the firestop system and layers of wrap strip
required are tabulated below:
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC - CP648 -E W45/1 -3/4" Wrap Strip
B. Fill, Void or Cavity Materials' - Sealant - Min 114 in. thickness of fill material applied within the annulus directly on top of wrap strip, flush with
top surface of floor. W Rating applies onywhen CP 601S Sealant Is used.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILT] INC - FS-ONE Sealant or CP 601S Sealant
'Bearing the UL Class'dicalion Mark
Reproduced by HILTI, Inc Courtesyof
Underwriters Laboratories, Inc. V uL
Hilti Firestop Systems October 06, 2005 m
PLUMBING FIRE PENETRATION DETAILS
Scale: NTS
System No. C-AJ -1226
F RATING = MR.
T RATING = MR.
L Rating At Ambient- Less than 1 CFM1Sq Ft
L Rating At 400 F- 4 CFMISq Ft
mw.w.1
1. Floor or Wall Assembly -- Min 4 -1/2 in. thick reinforced lightweight or normal weight (100 -150
pcf) concrete. Wall may also be constructed of any UL Classified Concrete Blocks *. Max diam of
opening is 32 in.
2. Metallic Sleeve -- (Optional) Nom 32 in. diam (or smaller) Schedule 40 (or heavier) steel sleeve
cast or grouted into floor or wall assembly, flush with floor or wall surfaces or extending a max of 3
in. above floor or beyond both surfaces of wall.
3. Through - Penetrant -- One metallic pipe, tube or conduit to be installed either concentrically or
eccentrically within the firestop system. The annular space between penetrant and periphery of opening
shall be min 0 in. (point contact) to max 1 -7/8 in. Penetrant may be installed with continuous point
contact. Penetrant to be rigidly supported on both sides of floor or wall assembly. The following types
and sizes of metallic penetrants may be used:
A. Steel Pipe Nam 30 in. diam (or smaller) Schedule 10 (or heavier) steel pipe.
B. Iron Pipe Nom 30 in. diam (or smaller) cast or ductile iron pipe.
C. Copper Pipe -- Nom 6 in. diam (or smaller) Regular (or heavier) copper pipe.
D. Copper Tubing -- Nom 6 in. diam (or smaller) Type L (or heavier) copper tubing.
E. Conduit -- Nom 6 in. diam (or smaller) steel conduit.
F. Conduit -- Nom 4 in. diam (or smaller) steel electrical metallic tubing (EMT).
4. Firestop System -- The firestop system shall consist of the following:
-- f mineral wool batt insulation firm eked
A Packing Material Min 4 in. thickness of min 4 pcf IY Pa
9
in kin material to be recessed from to surface of floor or
into opening as a permanent form. Pac g at p
sleeve or from both surfaces of wall or sleeve as required to accommodate the required thickness of
fill material.
* --
- in thickness of fill material applied within the
B. Fill Void or Cavity Material* Sealant Min 1 4
tY
/ PP
annulus, flush with top surface of floor or sleeve or with both surfaces of wall or sleeve. At the point
I a min 1 4 in. diam bead of
or continuous contact locations between penetrant and concrete or sleeve, Pe � /
fill material shall be applied at the concrete or sleeve/ pipe penetrant interface on the top surface of
floor and on both surfaces of wall. HILT] CONSTRUCTION CHEMICALS, DIV OF
N
N
U
HILT] INC -- FS -One Sealant *Bearing the UL Classification Mark
��„SSIFj�o
Reproduced by HILTI, Inc. Coirteq of
FlRESTOP SYSTEMS Underwriters Laboratories, Ire.
October 30, 2003 C US Pope 1 of 1
System No. C -AJ -2342
F Rating - 3 Hr
T Rating - 0 Hr CJ
W Rating - Class 1(See Item 3B)
2
313 1
A A
3
SECTION A -A
1. Floor or Wall Assembly- Min 2 -1/2 in. (64 mm) thick reinforced lightweight or normal weight (100 -150 pcf or 1600 -2400 Wm3) concrete floor or
wall. Wall may also be constructed of any UL Classified Concrete Bkhde. Max diam of opening is 6 in.
See Concrete Blocks (CAZT) category in the Fire Resistance Diredmfor names ofmanufacturers.
2. Through Penetrants -One nonmetallic pipe to be installed concentrically or eccentrically within the firestop system. Annular space within the
firestop system is dependent upon the max diam and type of penetrant used as tabulated in Item 3A Pipe to be rigidly supported on both sides of
floor or wall assembly. The following types and sizes of nonmetallic pipes maybe used:
A. Polyvinyl Chloride (PVC) Pipe - Nom 4 in. (102 mm) diam (or smaller) Schedule 40 solid or cellular core PVC for use in dosed (process or
supply) or vented (drain, waste orvenl) piping systems.
B. Chlorinated Polyvinyl Chloride (CPVC) Pipe - Nom 4 in. (102 mm) diam (or smaller) SDR13.5 CPVC far use in dosed (process or supply) piping
systems.
C. Acrylonitrile Butadiene Styrene (ABS) Pipe - Nom 4 in. (102 mm) diam (or smaller) Schedule 40 solid or cellular core ABS for use in dosed
(process or supply) or vented (drain, waste orvenQ piping systems.
D. Flame Retardant Polypropylene (FRPP) Pipe - Nom 4 in. (102 mm) diam (or smaller) Schedule 40 FRPP pipe for use in dosed (process or
supply) or vented (drain, waste orvenQ piping system.
3. Firestop System -The firestop system shall oonsistcf the following:
A. Fill, Void or Cavity Material' -Wrap Strip -Layers of intumescent wrap strip are continuously wrapped around the pipe with ends held in place
with tape. Wrap strip installed recessed max 1/4 in. (6 mm) from bottom surface of floor orfrom both surfaces of wall. Size of wrap strip and number
of layers for a given size penetrant are shown in table below.
HILT] CONSTRUCTION CHEMICALS, DNOF
HILTI INC - CP648 -E W25/1" or CP648 -E W4511 -3/4" Fimstop Wrap Strip
ZI Reproduced by HILTI, Inc. Courtesy ofS
Underwriters Laboratories, Inc. V V
Hiltil Firestop tems August 29,2007
P S Y Page-. 1 of 2
A-I
A---I
System No. W -L -1290
F Rating -1 and 2 Hr (See Item 1)
T Rating -0 Hr
L Rating at Ambient - Less than 1 CFM/Sq Ft
L Rating at 400° F - Less than 1 CFM /Sq Ft
J
3:
1. Wall Assembly -- The 1 or 2 hr fire rated gypsum board /stud wall assembly shall be constructed of the materials and in
the manner specified in the individual U300 or U400 Series Wall and Partition Designs in the UL Fire Resistance Directory and
shall include the following construction features.
A Studs -- The 1 or 2 hr fire rated gypsum board /stud wall assembly shall be constructed of the materials and in the
manner specified in the individual U300 or U400 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall
include the following construction features.
B. Gypsum Board * - -- Nom 5/8 in. thick, 4 ft wide with square or tapered edges. The gypsum board type, thickness, number
of layers, fastener type and sheet orientation shall be as specified in the individual U300 or U400 Series Design in the Fire
Resistance Directory. Max diam of opening is 5 in.
The hourly F and T Ratings of the firestop system are equal to the hourly fire rating of the wall assembly in which it is
installed.
2. Through Penetrant -- One metallic pipe, conduit or tubing installed concentrically or eccentrically within the firestop system.
Pipe, conduit or tubing may be installed at an angle not greater than 45 degrees from perpendicular. Pipe, conduit or tube to
be rigidly supported on both sides of wall assembly. The annular space between the pipe or tube and periphery of the opening
shall be min 0 in (point contact) to max 1/2 in. The following types and sizes of metallic pipes, conduit or tube may be used:
i -- i i r smaller Schedule 40 or heavier steel pipe.
A Steel Pipe Nom 4 n. dam o
P ( ) ( ) PP
B Iron Pi -- Nom 4 in. diam or smaller cast or ductile iron pipe.
B. Pe ( ) P Pe
C. Conduit -- Nom 4 in. diam (or smaller) steel electrical metallic tubing (EMT) or steel conduit.
D. Copper Tube Nom 4 in. diam (or smaller) Type L (or heavier) copper tube.
-- 4 in. diam or smaller Regular or heavier copper pipe.
E. Copper Pipe Nom ( ) g ( ) pp p Pie
*- -
3. Fill Void or Cavity atenal Sealant - Min 5 B in. thickness of fill material applied within the annulus flush with both
Y / PP
surfaces of wall. At the point contact location between pipe and wall, a min M in diam bead of fill material shall be applied at
P PP P
the pipe /wall interface.
HILTI CONSTRUCTION CHEMCIALS, DIV --
OF HILTI INC CP606 Flexible Firestop Sealant
*Bearing the UL Classification Mark
m Reproduced by HILTI, Inc. Courtesyof V" I FIFO
E==D= 0 Underwriters Laboratories, Inc,
FIRESTOP SYSTEMS June 03, 2005 C US
System No. C -AJ -2342
F Rating - 3 Hr a'
T Rating - 0 Hr
W Rating - Class 1 (See Item 3B)
Product Designation
Pipe Size in.
(mm)
Max Opening
Diam (in.)
PLUMBING
SYMBOL
LEGEND
Nom Wrap Strip
Width in. (mm)
CP648 -E W2511"
11/2(38)
3 (76)
3/16(4.8)
15/16(24)
1
1(25)
CP648 -E W4511 -3/4'
11/2(38)
3 (76)
3/16(4.6)
15/16(24)
->*_
GATE -VALVE
CP648 -E W25/1'
2 (51)
SYMBOL
DESCRIPTION
SYMBOL
DESCRIPTION
1(25)
CP648 -E W4511 -314'
J
VENT THRU ROOF (VTR)
3/16(4.8)
SANITARY PIPE
1
13/4(45)
/�
P -TRAP
4 (102)
3/16(4.8)
15/16(24)
1
CW
COLD WATER PIPE
3 (76)
5 (127)
-'
1 1/16(27)
2
13/4(45)
CP648 -E W4511 -3/4'
1 4 (102)
6 (152)
318 (10)
C
PIPING TURNING UP
13/4(45)1
MODEL- CST744SL
WATER HAMMER (SHOCK)
[Ed
- - - - - -
VENT PIPE
HW
HOT WATER PIPE
ARRESTOR.
�-
PIPING TURNING DOWN
-
COLD WATER PIPE
CONNECT TO EXISTING
CO
WALL CLEAN OUTS
LAVATORY
--
HOT WATER PIPE
1/2
1/2"
- VITREOUS CHINA, SELF - RIMMING
F.F.
FIRST FLOOR
FD
FLOOR DRAIN
UG
UNDERGROUND
MODEL No. LT401
REQUIREMENTS WHEN COUNTERTOP INSTALLED 34" FROM FINISHED FLOOR
S.F.
SECOND FLOOR
CD
CONDENSATE DRAIN PIPE
SELF - RIMMING
AND LAVATORY INSTALLED 2" MIN. FROM FRONT EDGE.
FAUCET= ZURN MODEL 281101
FU
FIXTURE UNITS
KITCHEN SINK
1 -1/4"
2
1/2
DCV
DOUBLE CHECK VALVE
-18 GAUGE STAINLESS STEEL.
** MODEL ELUHAD 2115
- SINGLE BOWL DESIGN.
FW
FILTERED WATER
BACKFLOWPREVENTER;
HEWC
ELECTRIC WATERCOOLER
2
1 -1/2
1/2
__
ELKAY MODEL EZSTLSC
CA
COMPRESSOR SYSTEM PIPING
HANDICAP
VA
VACUUM SYSTEM PIPING
®
FLOOR CLEAN -OUT
ANSI /NSF61 COMPLIANT
PLUMBING FIRE PENETRATION DETAILS
Scale: NTS
System No. C-AJ -1226
F RATING = MR.
T RATING = MR.
L Rating At Ambient- Less than 1 CFM1Sq Ft
L Rating At 400 F- 4 CFMISq Ft
mw.w.1
1. Floor or Wall Assembly -- Min 4 -1/2 in. thick reinforced lightweight or normal weight (100 -150
pcf) concrete. Wall may also be constructed of any UL Classified Concrete Blocks *. Max diam of
opening is 32 in.
2. Metallic Sleeve -- (Optional) Nom 32 in. diam (or smaller) Schedule 40 (or heavier) steel sleeve
cast or grouted into floor or wall assembly, flush with floor or wall surfaces or extending a max of 3
in. above floor or beyond both surfaces of wall.
3. Through - Penetrant -- One metallic pipe, tube or conduit to be installed either concentrically or
eccentrically within the firestop system. The annular space between penetrant and periphery of opening
shall be min 0 in. (point contact) to max 1 -7/8 in. Penetrant may be installed with continuous point
contact. Penetrant to be rigidly supported on both sides of floor or wall assembly. The following types
and sizes of metallic penetrants may be used:
A. Steel Pipe Nam 30 in. diam (or smaller) Schedule 10 (or heavier) steel pipe.
B. Iron Pipe Nom 30 in. diam (or smaller) cast or ductile iron pipe.
C. Copper Pipe -- Nom 6 in. diam (or smaller) Regular (or heavier) copper pipe.
D. Copper Tubing -- Nom 6 in. diam (or smaller) Type L (or heavier) copper tubing.
E. Conduit -- Nom 6 in. diam (or smaller) steel conduit.
F. Conduit -- Nom 4 in. diam (or smaller) steel electrical metallic tubing (EMT).
4. Firestop System -- The firestop system shall consist of the following:
-- f mineral wool batt insulation firm eked
A Packing Material Min 4 in. thickness of min 4 pcf IY Pa
9
in kin material to be recessed from to surface of floor or
into opening as a permanent form. Pac g at p
sleeve or from both surfaces of wall or sleeve as required to accommodate the required thickness of
fill material.
* --
- in thickness of fill material applied within the
B. Fill Void or Cavity Material* Sealant Min 1 4
tY
/ PP
annulus, flush with top surface of floor or sleeve or with both surfaces of wall or sleeve. At the point
I a min 1 4 in. diam bead of
or continuous contact locations between penetrant and concrete or sleeve, Pe � /
fill material shall be applied at the concrete or sleeve/ pipe penetrant interface on the top surface of
floor and on both surfaces of wall. HILT] CONSTRUCTION CHEMICALS, DIV OF
N
N
U
HILT] INC -- FS -One Sealant *Bearing the UL Classification Mark
��„SSIFj�o
Reproduced by HILTI, Inc. Coirteq of
FlRESTOP SYSTEMS Underwriters Laboratories, Ire.
October 30, 2003 C US Pope 1 of 1
System No. C -AJ -2342
F Rating - 3 Hr
T Rating - 0 Hr CJ
W Rating - Class 1(See Item 3B)
2
313 1
A A
3
SECTION A -A
1. Floor or Wall Assembly- Min 2 -1/2 in. (64 mm) thick reinforced lightweight or normal weight (100 -150 pcf or 1600 -2400 Wm3) concrete floor or
wall. Wall may also be constructed of any UL Classified Concrete Bkhde. Max diam of opening is 6 in.
See Concrete Blocks (CAZT) category in the Fire Resistance Diredmfor names ofmanufacturers.
2. Through Penetrants -One nonmetallic pipe to be installed concentrically or eccentrically within the firestop system. Annular space within the
firestop system is dependent upon the max diam and type of penetrant used as tabulated in Item 3A Pipe to be rigidly supported on both sides of
floor or wall assembly. The following types and sizes of nonmetallic pipes maybe used:
A. Polyvinyl Chloride (PVC) Pipe - Nom 4 in. (102 mm) diam (or smaller) Schedule 40 solid or cellular core PVC for use in dosed (process or
supply) or vented (drain, waste orvenl) piping systems.
B. Chlorinated Polyvinyl Chloride (CPVC) Pipe - Nom 4 in. (102 mm) diam (or smaller) SDR13.5 CPVC far use in dosed (process or supply) piping
systems.
C. Acrylonitrile Butadiene Styrene (ABS) Pipe - Nom 4 in. (102 mm) diam (or smaller) Schedule 40 solid or cellular core ABS for use in dosed
(process or supply) or vented (drain, waste orvenQ piping systems.
D. Flame Retardant Polypropylene (FRPP) Pipe - Nom 4 in. (102 mm) diam (or smaller) Schedule 40 FRPP pipe for use in dosed (process or
supply) or vented (drain, waste orvenQ piping system.
3. Firestop System -The firestop system shall oonsistcf the following:
A. Fill, Void or Cavity Material' -Wrap Strip -Layers of intumescent wrap strip are continuously wrapped around the pipe with ends held in place
with tape. Wrap strip installed recessed max 1/4 in. (6 mm) from bottom surface of floor orfrom both surfaces of wall. Size of wrap strip and number
of layers for a given size penetrant are shown in table below.
HILT] CONSTRUCTION CHEMICALS, DNOF
HILTI INC - CP648 -E W25/1" or CP648 -E W4511 -3/4" Fimstop Wrap Strip
ZI Reproduced by HILTI, Inc. Courtesy ofS
Underwriters Laboratories, Inc. V V
Hiltil Firestop tems August 29,2007
P S Y Page-. 1 of 2
A-I
A---I
System No. W -L -1290
F Rating -1 and 2 Hr (See Item 1)
T Rating -0 Hr
L Rating at Ambient - Less than 1 CFM/Sq Ft
L Rating at 400° F - Less than 1 CFM /Sq Ft
J
3:
1. Wall Assembly -- The 1 or 2 hr fire rated gypsum board /stud wall assembly shall be constructed of the materials and in
the manner specified in the individual U300 or U400 Series Wall and Partition Designs in the UL Fire Resistance Directory and
shall include the following construction features.
A Studs -- The 1 or 2 hr fire rated gypsum board /stud wall assembly shall be constructed of the materials and in the
manner specified in the individual U300 or U400 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall
include the following construction features.
B. Gypsum Board * - -- Nom 5/8 in. thick, 4 ft wide with square or tapered edges. The gypsum board type, thickness, number
of layers, fastener type and sheet orientation shall be as specified in the individual U300 or U400 Series Design in the Fire
Resistance Directory. Max diam of opening is 5 in.
The hourly F and T Ratings of the firestop system are equal to the hourly fire rating of the wall assembly in which it is
installed.
2. Through Penetrant -- One metallic pipe, conduit or tubing installed concentrically or eccentrically within the firestop system.
Pipe, conduit or tubing may be installed at an angle not greater than 45 degrees from perpendicular. Pipe, conduit or tube to
be rigidly supported on both sides of wall assembly. The annular space between the pipe or tube and periphery of the opening
shall be min 0 in (point contact) to max 1/2 in. The following types and sizes of metallic pipes, conduit or tube may be used:
i -- i i r smaller Schedule 40 or heavier steel pipe.
A Steel Pipe Nom 4 n. dam o
P ( ) ( ) PP
B Iron Pi -- Nom 4 in. diam or smaller cast or ductile iron pipe.
B. Pe ( ) P Pe
C. Conduit -- Nom 4 in. diam (or smaller) steel electrical metallic tubing (EMT) or steel conduit.
D. Copper Tube Nom 4 in. diam (or smaller) Type L (or heavier) copper tube.
-- 4 in. diam or smaller Regular or heavier copper pipe.
E. Copper Pipe Nom ( ) g ( ) pp p Pie
*- -
3. Fill Void or Cavity atenal Sealant - Min 5 B in. thickness of fill material applied within the annulus flush with both
Y / PP
surfaces of wall. At the point contact location between pipe and wall, a min M in diam bead of fill material shall be applied at
P PP P
the pipe /wall interface.
HILTI CONSTRUCTION CHEMCIALS, DIV --
OF HILTI INC CP606 Flexible Firestop Sealant
*Bearing the UL Classification Mark
m Reproduced by HILTI, Inc. Courtesyof V" I FIFO
E==D= 0 Underwriters Laboratories, Inc,
FIRESTOP SYSTEMS June 03, 2005 C US
System No. C -AJ -2342
F Rating - 3 Hr a'
T Rating - 0 Hr
W Rating - Class 1 (See Item 3B)
Product Designation
Pipe Size in.
(mm)
Max Opening
Diam (in.)
Annular Space
Min in (mm)
Annular Space
Max in. (mm)
Number of
Layers
Nom Wrap Strip
Width in. (mm)
CP648 -E W2511"
11/2(38)
3 (76)
3/16(4.8)
15/16(24)
1
1(25)
CP648 -E W4511 -3/4'
11/2(38)
3 (76)
3/16(4.6)
15/16(24)
1
1 3/4 (45)
CP648 -E W25/1'
2 (51)
31/2(89)
3/16(4.8)
15/16(24)
1
1(25)
CP648 -E W4511 -314'
2 (51)
31/2(89)
3/16(4.8)
15/16(24)
1
13/4(45)
CP648 -E W4511 -3/4'
3 (76)
4 (102)
3/16(4.8)
15/16(24)
1
13/4(45)
CP648 -E W4511 -314'
3 (76)
5 (127)
318 (10)
1 1/16(27)
2
13/4(45)
CP648 -E W4511 -3/4'
1 4 (102)
6 (152)
318 (10)
11/8(29)1
2
13/4(45)1
Al. Fill, Void or Cavity Material' - Wrap Strip - (As an alternate to the wrap strip in Item 3A) - One layer of intumescent wrap strip is oontinuousy
wrapped around the pipe with ends butted and held in place with integrated tape. Wrap strip installed recessed max 1/4 in. (6 mm) from top surface
of floor or from both surfaces of wall. Size of wrap strip for a given size penetrant are shown in the table below.
HILT] CONSTRUCTION CHEMICALS, DIV OF
HILTI INC - CP648- S -1.5- US, CP648 -S -2- US, CP648 -S-3' US or CP648-S -4' US Wrap Strip
Product Designation
Pipe Size
Max Opening
AnnularSpace
AnnularSpace
Nom Wrap Strip
Nom Wrap
Strip Thick in.
Nom Wrap
Strip Width in.
in.(mm)
Diann (in.)
Min in. (mm)
Max in. (mm)
Length in. (mm)
(mm)
(mm)
CP648- S -1.5' US
11/2(38)
3 (76)
3/16(4.8)
15/16(24)
6 5 (165)
0.18 (4.6)
1(25)
CP648S -2" US
2 (51)
3112 (89)
3/16(4.8)
15/16(24)
8 (203)
0.18 (4.6)
1 (25)
CP648S -3' US
3 (76)
4 (102)
3/16 (4.8)
5/16 (8)
11.5 (292)
0.18 (4.6)
13/4 (45)
CP648S4' US
1 4 (102)
6 (152)
3/8 (10)
11/8(29)1
15.1(384)
0.36(9)1
13/4(45)
Al. Fill, Void or Cavity Material' -Wrap Strip - (As an alternate to the wrap strip in Item 3A) - One layer of intumescent wrap strip is continuously
wrapped around the pipe with ends butted and held in place with integrated tape. Wrap strip installed recessed max 114 in. (6 mm) from by surface
of floor or from both surfaces of wall. Size of wrap strip for a given size penetrant are shown in the table below.
HILTI CONSTRUCTION CHEMICALS, DIV OF
HILTI INC - CP648- S -1.5' US, CP648 -S -2' US, CP648 -S-3' US or CP64&S-4" US Wrap Strip
B. Fill, Void or Cavity Material' - Sealant - Min 1/4 in. (6 mm) thickness of fill material applied within the annulus, flush with top surface of floor of
both surfaces of wall. W Rating applies only when CP 601S or CP 604 sealant is used.
HILTI CONSTRUCTION CHEMICALS, DIV OF
HILTI INC - FS -ONE Sealant, CP 601S SealantorCP 604 Sealant
C. Packing Material (not shown) - Min 1/2 in. (13 mm) thickness of 4 pd (64 kg/m3) mineral wool badinsulation flnnlypacred into annularspace
and recessed from the top surface of floor to accommodate the required thickness of till material. Required onywhen CP 604 Sealant is used.
'Bearing the UL Classification Mark
SIF��Reproduced by HILTI, Inc Courtesy of V
Underwriters Laboratories, Inc.
Hilti Firestop August 29, 2007
P Y stems ® Page: 2 of 2
* *COORDINATE FINAL FIXTURE WITH ARCHITECT / OWNER BEFORE BID THE PROJECT
151 SEVILLXAVENUE; 361TE 26G
CORAL GABLES, FL 33134
OFFICE: (305) 442 -1188
FAX: (305) 445 -1509
WWW. ADCINTERNATIONAL.NET
STATE OF FLORIDA AR- 0010536
RAYMUNDO FEITO, R.A. AA- CO01315
Architect * SeaUSignature
�sRn ExpANSlo�v
SUNSET PROFE S-SIONAL BLDG
6280 SUNSET DR
SUITE li 0
i
FKey Plan - Scope of Work Area
Z KEY PLAN LEGEND
:AREAAT WHICH
. %nay nom!
THE SCOPE OF
Y
b
:WORK WILL BE
PERFORMED.
�vH
S U
S
N
H
H : 5
N.I.C. AREA
a'
wHgaabH.�'s�
:i
S
CONSTRUCTION NOTE
f. ° ^�:' > rrrwy *'•'" "'• ""b'4••4bbb4'¢b-1:��� THE CONTRACTOR, BY VIRTUE OF
SIGNING THE CONTRACT,
� *,�* ^* *,, ,`),.b;•%.;,;;,� ACKNOWLEDGES THAT HE AND
a X . ALL HIS SUBCONTRACTORS HAVE
r y SATISFIED THEMSELVES AS TO
N
y THE NATURE AND LOCATION OF
THE WORK. THE GENERAL AND
tk LOCAL CONDITIONS INCLUDE, BUT ARE NOT RESTRICTED TO THOSE
BEARING UPON, ACCESS POINTS
AND POINTS OF CONNECTION TO
THE SITE, THE CONFORMATION
AND CONDITIONS OF THE WORK
r y ' AREA; AND THE CHARACTER OF
EQUIPMENT AND DEVICES NEEDED
PRELIMINARY TO AND DURING THE
i PERFORMANCE OF THE WORK.
FAILURE ON THE PART OF THE
# CONTRACTOR TO COMPLETELY OR
PROPERLY EVALUATE ANY
FACTORS OF COSTS PRIOR TO
y... BIDDING SHALL NOT FORMA BASIS
FOR ADDITIONAL COMPENSATION
Y IF HE IS AWARDED THE CONTRACT.
Date & Issue Description Drawn By Checked By
Z
Z
Z
g
CL
•
W
lY
V
W
%
2
lY
Q Date & Issue Description Drawn By Checked By
Project Number Client Name
OS032 PROMED PROPERI IES
Description Client Address
PLUMBING FIRE PENETRATION DETAILS Ib°b NE MIAMI GARDENS DR
SUITE 8
Scale N. MIAMI BEACH, FL 33115
AS SHOWN Client Phone Number
(305) 941 -WW
CAD File Name
G:V2Proje3cteV2200Sh /2ADG1/2MRA EXPANSION
Consultant * Seal/Signature
ENGIN EKING
z DE I '' •
J RP,
61.
r�
V tom• ..� cn 4 -' '
Z 21 SW 102 Ct. Miaxr6? 4 �
_ Office: (786) 863- 1' • • • •''
Fax: (305) 220 -519 t
CIO pgengineerdesign®bellsouth.net
P=5mO
0. STATE OF FLORIDA
LUIS O. PEREZ, PE P.E. No. 62586
PLUMBING FIXTURE SCHEDULE
SOIL/
COLD
HOT
MANUFACTURER
MARK
FIXTURE
WASTE
VENT
WATER
WATER
MODEL No.
DESCRIPTION
IN.
IN.
IN.
IN.
** TOTO
-ADA COMPLIANT, CONTEMPORARY, HIGH PROFILE DESIGN
-G -MAX TECHNOLOGY. POWERFUL, QUIET FLUSH EVERY TIME
WC
TANK TYPE, HANDICAP
3-
2"
1/2"
__
DRAKE CLOSE COUPLED
-WIDE, 2 -J" COMPUTER DESIGNED TRAPWAY
FLOOR MOUNTED
MODEL- CST744SL
-LARGE WATER SURFACE.LOW CONSUMPTION (1.6GPF)
[Ed
- SIPHON JET FLUSHING ACTION
-TANK COVER, FITTINGS, CHROME PLATED TRIP LEVER , LESS SEAT
LAVATORY
1 -1/4"
2
1/2
1/2"
- VITREOUS CHINA, SELF - RIMMING
LAV
(HANDICAP)
** TOTO
- MEETS THE AMERICAN DISABILITIES ACT GUIDELINES AND ANSI A117.1
MODEL No. LT401
REQUIREMENTS WHEN COUNTERTOP INSTALLED 34" FROM FINISHED FLOOR
SELF - RIMMING
AND LAVATORY INSTALLED 2" MIN. FROM FRONT EDGE.
FAUCET= ZURN MODEL 281101
- INSULATE TRAP AND HW AND CW LINES
K -SK
KITCHEN SINK
1 -1/4"
2
1/2
1/2"
ELKAY
-18 GAUGE STAINLESS STEEL.
** MODEL ELUHAD 2115
- SINGLE BOWL DESIGN.
FAUCET= AMERICAN STANDARD MODEL #6424
HEWC
ELECTRIC WATERCOOLER
2
1 -1/2
1/2
__
ELKAY MODEL EZSTLSC
-WALL MOUNT WATER COOLER, BARRIER -FREE ACCESS ( ADULT & CHILD)
[61
HANDICAP
ANSI /NSF61 COMPLIANT
* *COORDINATE FINAL FIXTURE WITH ARCHITECT / OWNER BEFORE BID THE PROJECT
151 SEVILLXAVENUE; 361TE 26G
CORAL GABLES, FL 33134
OFFICE: (305) 442 -1188
FAX: (305) 445 -1509
WWW. ADCINTERNATIONAL.NET
STATE OF FLORIDA AR- 0010536
RAYMUNDO FEITO, R.A. AA- CO01315
Architect * SeaUSignature
�sRn ExpANSlo�v
SUNSET PROFE S-SIONAL BLDG
6280 SUNSET DR
SUITE li 0
i
FKey Plan - Scope of Work Area
Z KEY PLAN LEGEND
:AREAAT WHICH
. %nay nom!
THE SCOPE OF
Y
b
:WORK WILL BE
PERFORMED.
�vH
S U
S
N
H
H : 5
N.I.C. AREA
a'
wHgaabH.�'s�
:i
S
CONSTRUCTION NOTE
f. ° ^�:' > rrrwy *'•'" "'• ""b'4••4bbb4'¢b-1:��� THE CONTRACTOR, BY VIRTUE OF
SIGNING THE CONTRACT,
� *,�* ^* *,, ,`),.b;•%.;,;;,� ACKNOWLEDGES THAT HE AND
a X . ALL HIS SUBCONTRACTORS HAVE
r y SATISFIED THEMSELVES AS TO
N
y THE NATURE AND LOCATION OF
THE WORK. THE GENERAL AND
tk LOCAL CONDITIONS INCLUDE, BUT ARE NOT RESTRICTED TO THOSE
BEARING UPON, ACCESS POINTS
AND POINTS OF CONNECTION TO
THE SITE, THE CONFORMATION
AND CONDITIONS OF THE WORK
r y ' AREA; AND THE CHARACTER OF
EQUIPMENT AND DEVICES NEEDED
PRELIMINARY TO AND DURING THE
i PERFORMANCE OF THE WORK.
FAILURE ON THE PART OF THE
# CONTRACTOR TO COMPLETELY OR
PROPERLY EVALUATE ANY
FACTORS OF COSTS PRIOR TO
y... BIDDING SHALL NOT FORMA BASIS
FOR ADDITIONAL COMPENSATION
Y IF HE IS AWARDED THE CONTRACT.
Date & Issue Description Drawn By Checked By
Z
Z
Z
g
CL
•
W
lY
V
W
%
2
lY
Q Date & Issue Description Drawn By Checked By
Project Number Client Name
OS032 PROMED PROPERI IES
Description Client Address
PLUMBING FIRE PENETRATION DETAILS Ib°b NE MIAMI GARDENS DR
SUITE 8
Scale N. MIAMI BEACH, FL 33115
AS SHOWN Client Phone Number
(305) 941 -WW
CAD File Name
G:V2Proje3cteV2200Sh /2ADG1/2MRA EXPANSION
Consultant * Seal/Signature
ENGIN EKING
z DE I '' •
J RP,
61.
r�
V tom• ..� cn 4 -' '
Z 21 SW 102 Ct. Miaxr6? 4 �
_ Office: (786) 863- 1' • • • •''
Fax: (305) 220 -519 t
CIO pgengineerdesign®bellsouth.net
P=5mO
0. STATE OF FLORIDA
LUIS O. PEREZ, PE P.E. No. 62586