PENETRATION FOR METAL PIPE /CONDUIT THROUGH CONCRETE FLOOR
ASSEMBLY BASED ON UL SYSTEM C -AJ -1001
METAL PIPE OR CONDUIT
CP -25 S/L CAULK
PENETRATING
STEEL SLEEVE
(OPTIONAL)
POINT OF C01
SECTION
2 1/2" MAX.
ANNULAR
SPACE
NOT USED
-
4 1/2" LIGHTWEIGHT OR NORMAL WEIGHT
CONCRETE (MIN.)
DAMMING MATERIAL (FIBERGLASS INSULATION
BACKER ROD OR MINERAL WOOL)
STEEL SLEEVE (OPTIONAL)
NOTES:
1. OPTIONAL STEEL SLEEVE 12" DIAM. OR SMALLER
SCHEDULE 40 OR HEAVIER STEEL PIPE SLEEVE
CAST INTO CONCRETE FLOOR. SLEEVE TO BE FLUSH
OR PROJECT 2" MAX FROM TOP SURFACE OF FLOOR.
2. PENETRATING ITEM TO BE: NOM. 20" DIAM. OR LESS
SCHEDULE IOS OR HEAVIER STEEL PIPE, NOM. 6" DIAM.
OR LESS RIGID STEEL CONDUIT, NOM. 6" DIAM. OR LESS
TYPE ••L" OR HEAVIER COPPER TUBING, NOM. 4" DIAM.
OR SMALLER CAST IRON PIPE. MAX ANNULAR SPACE
BETWEEN PIPE OR CONDUIT AND EDGE OF THROUGH
OPENING TO BE 2 1/2" OR LESS. MIN. ANNULAR SPACE
BETWEEN PIPE OR CONDUIT AND EDGE OF THROUGH
SPACE TO BE 0" (POINT OF CONTACT).
3. PIPE OR CONDUIT TO BE RIGIDLY SUPPORTED ON
BOTH SIDES OF FLOOR ASSEMBLY.
4. USE 1/2" MIN. CAULK DEPTH WHEN NOM. PIPE OR CONDUIT
IS 10 DIAM. OR LESS AND WHEN MAX ANNULAR SPACE
IS 1' OR LESS. USE CP -25 S/L CAULK.
5. USE 1" MIN. CAULK DEPTH WHEN NOM. PIPE OR CONDUIT
IS 10" DIAM. OR MORE, OR WHEN MAX. ANNULAR SPACE
IS 1" OR MORE. USE CP -25 S/L CAULK.
6. INSTALL FILL MATERIAL FLUSH WITH TOP OF FLOOR.
7. 40% CAULK SHRINKAGE MAY BE EXPECTED AFTER
INSTALLATION. FIRE RATING BASED ON WET INSTALLATION
DEPTH.
8. USE 1" MIN. PACKING MATERIAL FIBERGLASS INSULATION,
BACKER ROD, MINERAL WOOL, ALUMINA SILICA FIBER
BLANKET TIGHTLY PACKED ARE ACCEPTABLE. WHEN
PIPE OR CONDUIT SIZE IS 10" OR LESS OR WHEN MAX.
ANNULAR SPACE IS 1" OR LESS, TIGHTLY PACKED
CERAMIC FIBER BLANKET OR MINERAL WOOL BATT PACKING
MATERIAL MAY BE RECESSED MIN. 1/2" FROM BOTTOM
SURFACE OF FLOOR. USE CP -25 N/S WHEN FILLING
ANNULAR SPACE FROM BELOW.
9. RECOMMENDATIONS BASED ON PRODUCT PERFORMANCE
PER ASTM E -614 (UL 1479) FIRE TEST AND UL FIRE STOP
SYSTEM C -AJ -1001.
PENETRATION FIRESTOP FOR METAL PIPE /CONDUIT THROUGH GYP WALLBOARD PARTITION
ASSEMBLY BASED ON UL SYSTEM W -L -1001
PLAN
ONE OR TWO HOUR FIRE RATED
GYPSUM WALLBOARD ASSEMBLY
WOOD STUDS AT 16" O.C. OR
METAL STUDS AT 24" O.C. MAX
CAULK MATERIAL FORCED INTO ANNULAR
SPACE TO MAX EXTEND POSSIBLE AND
WITH 1/4" DIAM. BEAD APPLIED TO
PERIMETER OF PIPE OR CONDUIT AT ITS
EGRESS FROM WALL.
12" DIAM. OR SMALLER SCHEDULE 10S
OR HEAVIER STEEL PIPE, NOM. 6" DIAM.
OR SMALLER RIGID STEEL CONDUIT, 4"
DIAM. OR SMALLER STEEL E.M.T. CONDUIT
OR 1" DIAM. OR SMALLER FLEXIBLE STEEL
CONDUIT.
P -25 N/S CAULKING BY MINNESOTA MINING
I.
TO BE 3/16" OR LESS.
SED ON PRODUCT PERFORMANCE
1479) FIRE TEST AND UL FIRE STOP
PENETRATION FIRESTOP FOR 6" MAX. PVC PIPE THROUGH FIRE RATED CONC. FLOOR
ASSEMBLY BASED ON UL SYSTEM C -AJ -2001
p ° �
� e �
e e
n ° I°
4" DEEP STEEL COLLAR
W/ 1 1/4" W X 2" L ANCHOR
TABS OR FIELD FABRICATED
0.016" THICK (30 GAUGE)
GALV. SHEET STEEL IN
ACCORDANCE WITH INST.
SHEET SUPPLIED BY
WRAP SHEET MANUFACTURER
USE MIN. 2 - 1/2" WIDE BY
0.028" THICK STAINLESS
STEEL BAND CLAMPS
WITH WORM GEAR
TIGHTENING MECHANISM.
LOCATE CLAMP NEAR
MID OF EACH STRIP STACK
SECTION
ASSEMBLED STEEL COLLAR DETAIL
NOTES:
<tDIKH,IINU LULLAK
WND TABS
' ENETRATING ITEM
/4" MIN. BEAD OF CP -25 N/S
:AULK. APPLY TO PERIMETER OF
:OLLAR AT FLOOR CONNECTION.
6" (152 MM) MAX. PVC PIPE
FIRE RATED CONC. FLOOR 2 1/2" MIN.
1/4" ANNULAR SPACE
FS -195 R/R WRAP STRIP
2 STACKS (NOM. 4" STACK
HEIGHT) TIGHTLY WRAPPED
TOP EDGES BUTTED AGAINST
THE UNDERSIDE OF CONC.
4 a v
a °
I a a
1/4" X 1 1/2" MIN. STEEL EXP. BOLTS
W/ 1 1/4" DIAM. STEEL FENDER
WASHERS AT EA. ANCHOR TAB
CP -25 S/L OR CP -25 N/S
CAULK AT OUTER PERIMETER
ALUMINUM FOIL WRAP AROUND PIPE
2" MIN.
MAT WRAP - 6" WIDE STRIP
OF FLEXIBLE SHEET MATERIAL
FACED ON ONE SIDE W/
ALUM. FOIL (FOIL FACE EXPOSED)
OVERLAP 1/2" AT SEAM
SECURE IN PLACE W/ WIRE
TIES 4" O.C.
ALTERNATE: USE NOM. 1"
THICK HOLLOW CYLINDRICAL
HEAVY DENSITY (MIN. 3.5 PFC)
GLASS FIBER UNITS JACKETED
ON THE OUTSIDE WITH FOIL -
SCRIM- KRAFT. MIN. 6" LENGTH
OF PIPE COVERING INSTALLED
AROUND PIPE AT ITS EGRESS
FROM STEEL COLLAR ON
UNDERSIDE OF FLOOR. SECURE
COVERING TO PIPE NTH STEEL
WIRE TIES ® 4" O.C.
STEEL COLLAR DETAIL
REQ. LENGTH
1. WRAP THE PVC PIPE NTH ALUMINUM FOIL TAPE WHERE CAULK CONTACTS IT. CP -25 N/S MAY TEMPORARILY SOFTEN THE PLASTIC PIPE IF ALLOWED TO COME IN DIRECT CONTACT.
2. TIGHTLY WRAP 3 INDIVIDUAL LAYERS OF FS -195 R/R STRIPS AROUND PIPE. SECURE EACH WRAP WITH ALUMINUM FOIL TAPE OR APPROVED EQUIVALENT. INSURE ALL LAYERS OF
FS 195 R/R BUTT SECURELY AGAINST THE UNDERSIDE OF THE CONCRETE FLOOR. STAGGER BUTTED SEAMS BETWEEN LAYERS.
3. APPLY FIRE RESTRICTING COLLAR (3M RC -1 OR APPROVED EQ.). REMOVE ENOUGH OF THE RESTRICTING COLLAR TO MAKE ONE WRAP AROUND THE APPLIED FS -195 R/R WITH A
MINIMUM 1" OVERLAP. FIELD CUT TO FIT WITH MOUNTING TABS BENT AWAY FROM THE PIPE AT RIGHT ANGLES AND FLUSH WITH FLOOR.
WARNING:
EDGES OF RESTRICTING COLLAR ARE SHARP. HANDLE WITH CARE.
4. TIGHTLY SECURE RESTRICTING COLLAR AROUND PIPE WITH STEEL HOSE CLAMP CENTERED ON RESTRICTING COLLAR ASSEMBLY.
5. SECURE RESTRICTING COLLAR TO THE SLAB WITH 1 1/2" X 1/4" EXP. BOLTS. USE 1 1/4" DIAM. FENDER WASHERS ON THE MOUNTING TABS. SECURE ALL TABS.
6. FOLD RESTRICTING COLLAR SUPPORT TABS TO LOCK THE WRAP STRIPS IN PLACE.
7. AFTER INSTALLATION OF THE FIRST RESTRICTING COLLAR TO THE FLOOR, REPEAT STEP #2 BY BUTTING THE FS -195 R/R WRAP STRIP
AGAINST THE BOTTOM OF THE FIRST RESTRICTING COLLAR.
8. REMOVE ENOUGH RESTRICTING COLLAR MATERIAL TO MAKE THE SECOND COLLAR AND REPEAT STEP #3. INSTALL WITH MOUNTING TABS
STRAIGHT UP, SLIGHTLY BELOW THE FIRST RESTRICTING COLLAR HOSE CLAMP. APPLY THE HOSE CLAMP TO THE SECOND RESTRICTING
COLLAR ASSEMBLY LEAVE ENOUGH SLACK TO ALLOW REPOSITIONING OF THE COLLAR VERTICALLY. BEND SUPPORT TABS INWARD TO HOLD
THE WRAP IN PLACE. LOOSEN THE FIRST RESTRICTING COLLAR HOSE CLAMP TO ALLOW THE MOUNTING TABS OF THE SECOND RESTRICTING COLLAR TO PASS UNDER IT.
SLIDE THE SECOND RESTRICTING COLLAR UP WITH THE MOUNTING TABS UNDER THE FIRST RESTRICTING COLLAR HOSE CLAMP.
TIGHTEN THE SECOND RESTRICTING COLLAR HOSE CLAMP. TIGHTEN THE FIRST RESTRICTING COLLAR HOSE CLAMP AND BEND EVERY OTHER MOUNTING TAB OF THE SECOND
RESTRICTING COLLAR OVER THE FIRST RESTRICTING COLLAR HOSE CLAMP.
9. APPLY ONE WRAP OF 3M 3 -5A MAT, MINNESOTA MINING & MFG. CO. TYPE E -5A MAT, OR APPROVED EQ. 6" WIDTH MINIMUM AROUND THE PIPE, PROVIDE MINIMUM 1/2" OVERLAP. BUTT
THE MAT WRAP FLUSH TO THE SECOND RESTRICTING COLLAR ASSEMBLY. SECURE THE MAT WRAP WITH 18 SWIG MIN. TIE WIRES 1" FROM EACH END OF MAT. SEAL THE EDGE OF THE MAT
ABUTTING THE RESTRICTING COLLAR WITH 1/4" MIN. BEAD OF CP -25 N/S CAULK.
10. RECOMMENDATIONS BASED ON PRODUCT PERFORMANCE PER ASTM E -614 (UL 1479) FIRE TEST AND UL THROUGH - PENETRATION FIRESTOP SYSTEM #64.
PENETRATION FOR METAL PIPE /CONDUIT THROUGH CONCRETE WALL
ASSEMBLY BASED ON UL SYSTEM C -AJ -1001
METAL PIPE OR CONDUIT
CP -25 N/S CAULK
SECTION
PENETRATING ITEM
STEEL SLEEVE
(OPTIONAL)
POINT OF CONTACT
�1i3
ELEVATION
ANNULAR
SPACE
2 1/2" MAX.
DAMMING MATERIAL (FIBERGLASS INSULATION
BACKER ROD OR MINERAL WOOL)
STEEL SLEEVE (OPTIONAL)
FIRE RATED SOLID CONCRETE
OR CONCRETE BLOCK WALL
1. OPTIONAL STEEL SLEEVE 12" DIAM. OR SMALLER
SCHEDULE 40 OR HEAVIER STEEL PIPE SLEEVE
CAST INTO CONCRETE WALL. SLEEVE TO BE FLUSH
OR PROJECT 2" MAX FROM BOTH SURFACES OF WALL.
2. PENETRATING ITEM TO BE: NOM. 20" DIAM. OR LESS
SCHEDULE 10S OR HEAVIER STEEL PIPE, NOM. 6" DIAM.
OR LESS RIGID STEEL CONDUIT, NOM. 6" DIAM. OR LESS
TYPE "L" OR HEAVIER COPPER TUBING, NOM. 4" DIAM.
OR SMALLER CAST IRON PIPE. MAX ANNULAR SPACE
BETWEEN PIPE OR CONDUIT AND EDGE OF THROUGH
OPENING TO BE 2 1/2" OR LESS. MIN. ANNULAR SPACE
BETWEEN PIPE OR CONDUIT AND EDGE OF THROUGH
SPACE TO BE 0" (POINT OF CONTACT).
3. PIPE OR CONDUIT TO BE RIGIDLY SUPPORTED ON
BOTH SIDES OF WALL ASSEMBLY.
4. USE 1/2" MIN. CAULK DEPTH WHEN NOM. PIPE OR CONDUIT
IS 10 DIAM. OR LESS AND WHEN MAX ANNULAR SPACE
IS 1" OR LESS. USE CP -25 N/S CAULK.
5. USE 1" MIN. CAULK DEPTH WHEN NOM. PIPE OR CONDUIT
IS 10" DIAM. OR MORE, OR WHEN MAX. ANNULAR SPACE
IS 1" OR MORE. USE CP -25 N/S CAULK.
6. INSTALL FILL MATERIAL (CAULK) FLUSH WITH AND
ON BOTH SIDES OF WALL ASSEMBLY SURFACE.
7. 40% CAULK SHRINKAGE MAY BE EXPECTED AFTER
INSTALLATION. FIRE RATING BASED ON WET INSTALLATION
DEPTH.
8. USE 1" MIN. PACKING MATERIAL FIBERGLASS INSULATION,
BACKER ROD, MINERAL WOOL, ALUMINA SILICA FIBER
BLANKET TIGHTLY PACKED ARE ACCEPTABLE.
RECESS PACKING MATERIAL FROM WALL SURFACE
AS REQUIRED TO ACCOMOOATE THE REQUIRED THICKNESS
OF CAULK.
9. RECOMMENDATIONS BASED ON PRODUCT PERFORMANCE
PER ASTM E -614 (UL 1479) FIRE TEST AND UL FIRE STOP
SYSTEM C -AJ -1001.
SYSTEM NO. W -L -2003
(FORMERLY SYSTEM NO. 148)
F RATINGS - 1 AND 2 HR (SEE ITEM 3)
T RATINGS - 1 AND 2 HR (SEE ITEM 3)
L RATING AT AMBIENT - 7 CFM /SQ FT (SEE ITEM 38)
L RATING AT 400 F - LESS THAN 1 CFM /SQ FT (SEE ITEM 313)
i A
1. WALL ASSEMLBY - The 1 or 2 hr fire -rated gypsum wallboard /stud wall assembly shall be constructed of the materials and in the manner described
in the individual U300 or U400 Series Wall or Partition Design in the UL Fire Resistance Directory and shall include the following construction features:
A. STUDS - Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. lumber spaced 16 in.
OC with nom 2 by 4 in. lumber end plates and cross braces. Steel studs to be min 3 -sib in. wide by 1 -%in. deep channels spaced max 24 in.
O.C.
B. WALLBOARD. GYPSUM* - in. thick, 4 ft wide with square or tapered edges. The gypsum wallboard type, thickness, number of layers, fastener
type and sheet orientation shall be as specified in the individual U300 or U400 Series Design in the UL Fire Resistance Directory. Max diam of
pening is 3 -Y6 in.
2• THROUGH PENETRANTS - One nonmetallic pipe or conduit to be centered in the through opening. The annular space between pipe or conduit and
periphery of opening shall be min X in. and max % in. Pipe or conduit to be rigidly supported on both sides of the floor - ceiling assembly. The
following types and sizes of nonmetallic pipes or conduits may be used:
A. POLYVINYL CHLORIDE (PVC) PIPE - Nom 2 in. diam (or smaller) Schedule 40 solid core PVC pipe for use in closed (process or supply) or vented
(drain, waste or vent) piping system.
B. RIGID NONMETALLIC CONDUIT ++ - Nom 2 in. dicm (or smaller)(Sshedule 40 or 80) PVC conduit installed in accordance with Article 347 of the
National electric Code (NFPA No. 70).
C. CHLORINATED POLYVINYL CHLORIDE (CPVC ) PIPE - Nom 2 in. diam (or smaller) SDR17 CPVC pipe for use in closed (process or supply) or vented
(drain, waste or vent) piping systems.
D. CELLULAR CORE POLYVINYL CHLORIDE (ccPVC) Pipe - Nom 2 in. diam (or smaller) Schedule 40 cellular core PVC pipe for use in closed (process
or supply) or vented (drain, waste or vent) piping system.
E. ACRYL ONITRIL E BUTADIENE STYRENE (ABS) Pipe - Nom 2 in, diam (or smaller) Schedule 40 solid core ABS pipe for use in closed (process or
supply) or vented (drain, waste or vent) piping systems.
F. CELLULAR ULAR CORE ACRYLONITRILE BUTADIENE STYRENE (ccABS) Pipe - Nom 2 in, diam (or smaller) Schedule 40 cellular core ABS pipe for use in
closed (process or supply) or vented (drain, waste or vent) piping systems.
3• FIRESTOP SYSTEM - Installed symmetrically on both sides of wall assembly. The hourly F and T Ratings for the firestop system are equal to the
hourly fire rating of the wall assembly in which it is installed. The details of the firestop system shall be as follows.
A. FILL. , VOID OR CAVITY MATERIALS* - WRAP STRIP - Nom Y4 in. thick intumescent elastomeric material faced on one side with aluminum foil,
supplied in 2 in. wide strips. Nom 2 in, wide strip thightly wrapped around nonmetallic pipe (foil side out) with seam butted. Wrap strip layer
securely bound with steel wire or aluminum foil tape and slid into annular space approx 1 -Y4in. such that approx 3/4 in. of the wrap strip
proturdes from the wall surface.
MINNESOTA MINING & MFG CO - FS -195+
B. FILL • VOID OR CAVITY MATERIALS* - CAULK OR PUTTY - Min % in. thickness of caulk or putty applied into annular space between wrap strip and
periphery of opening. A nom Y4 in. diam bead of caulk or putty to be applied to the wrap strip /wall interface and to the exposed edge of the
wrap strip layers approx Y4 in. from the wall surface.
MINNESOTA MINING & MFG CO - CP 25WB+ CAULK OR MPS -2+ PUTTY. (NOTE: L Ratings apply only when Type CP -25 WB+ caulk is used.)
C. FOIL TAPE - (NOT SHOWN) - Nom 4 in. wide. 3 mil thick aluminum tape wrapped around pipe prior to the installation of the wrap strip (Item
3A). Min of one wrap, flush with both sides of wall and proceeding outward. Tape is not required for pipes sown in Items 2A, 2B and 2C.
*Bearing the UL Classification Marking
gl -
i tlAa DESON
cackle N# ,.,k „« «, <,,,�'•
151 SEu'LA -A. V -00I=, SUTS -�00 = - --
CORAL GABLES, FL 33134
OFFICE: (305) 442 -1188
FAX: (305) 445 -1509
WWW. ADCINTERNATIONAL.NET
TIVE
<< Q f E I O
STATE OF FLORIDA AR- V001105�6
RAYMUNDO FEITO, R.A. AA- C001315
Architect • Seal/Signature
MRA EXPANSION
SUNSET PROFESSIONAL BLDG
6280 SUNSET DR E
SUITE 600
E
i
SOUTH MIAMI FL
......................................................................................................................................................... ............................... :
Date Issue Description Drawn By Checked By
04 -13 -09 LANDLORD REVIEW ER ER
04 -27 -09 PERMIT ISSUE ER ER
Z
Z
a......................................................................................................................................................... ...............................
Date $Issue Description Drawn By Checked By
........................................................................................................................................................... ...............................
Project Number
Client Name
09032
PROMED PROPERTIES
Description
Client Address
1696 NE MIAMI GARDENS DR
SUITE 8
Scale
N. MIAMI BEACH, FL 33179
NONE
Client Phone Number
(305) 947 -8800
CAD File Name
FIRE PENETRATION
DETAILS
Consultant • Seal/Signature
9.0