09-424-015..... ��: '..i ' C!l •Rr ...... r. .....E --- _.... PENETRATION FOR METAL PIPE /CONDUIT THROUGH CONCRETE FLOOR ASSEMBLY BASED ON UL SYSTEM C -AJ -1001 METAL PIPE OR CONDUIT CP -25 S/L CAULK PENETRATING STEEL SLEEVE (OPTIONAL) POINT OF C01 SECTION 2 1/2" MAX. ANNULAR SPACE NOT USED - 4 1/2" LIGHTWEIGHT OR NORMAL WEIGHT CONCRETE (MIN.) DAMMING MATERIAL (FIBERGLASS INSULATION BACKER ROD OR MINERAL WOOL) STEEL SLEEVE (OPTIONAL) NOTES: 1. OPTIONAL STEEL SLEEVE 12" DIAM. OR SMALLER SCHEDULE 40 OR HEAVIER STEEL PIPE SLEEVE CAST INTO CONCRETE FLOOR. SLEEVE TO BE FLUSH OR PROJECT 2" MAX FROM TOP SURFACE OF FLOOR. 2. PENETRATING ITEM TO BE: NOM. 20" DIAM. OR LESS SCHEDULE IOS OR HEAVIER STEEL PIPE, NOM. 6" DIAM. OR LESS RIGID STEEL CONDUIT, NOM. 6" DIAM. OR LESS TYPE ••L" OR HEAVIER COPPER TUBING, NOM. 4" DIAM. OR SMALLER CAST IRON PIPE. MAX ANNULAR SPACE BETWEEN PIPE OR CONDUIT AND EDGE OF THROUGH OPENING TO BE 2 1/2" OR LESS. MIN. ANNULAR SPACE BETWEEN PIPE OR CONDUIT AND EDGE OF THROUGH SPACE TO BE 0" (POINT OF CONTACT). 3. PIPE OR CONDUIT TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF FLOOR ASSEMBLY. 4. USE 1/2" MIN. CAULK DEPTH WHEN NOM. PIPE OR CONDUIT IS 10 DIAM. OR LESS AND WHEN MAX ANNULAR SPACE IS 1' OR LESS. USE CP -25 S/L CAULK. 5. USE 1" MIN. CAULK DEPTH WHEN NOM. PIPE OR CONDUIT IS 10" DIAM. OR MORE, OR WHEN MAX. ANNULAR SPACE IS 1" OR MORE. USE CP -25 S/L CAULK. 6. INSTALL FILL MATERIAL FLUSH WITH TOP OF FLOOR. 7. 40% CAULK SHRINKAGE MAY BE EXPECTED AFTER INSTALLATION. FIRE RATING BASED ON WET INSTALLATION DEPTH. 8. USE 1" MIN. PACKING MATERIAL FIBERGLASS INSULATION, BACKER ROD, MINERAL WOOL, ALUMINA SILICA FIBER BLANKET TIGHTLY PACKED ARE ACCEPTABLE. WHEN PIPE OR CONDUIT SIZE IS 10" OR LESS OR WHEN MAX. ANNULAR SPACE IS 1" OR LESS, TIGHTLY PACKED CERAMIC FIBER BLANKET OR MINERAL WOOL BATT PACKING MATERIAL MAY BE RECESSED MIN. 1/2" FROM BOTTOM SURFACE OF FLOOR. USE CP -25 N/S WHEN FILLING ANNULAR SPACE FROM BELOW. 9. RECOMMENDATIONS BASED ON PRODUCT PERFORMANCE PER ASTM E -614 (UL 1479) FIRE TEST AND UL FIRE STOP SYSTEM C -AJ -1001. PENETRATION FIRESTOP FOR METAL PIPE /CONDUIT THROUGH GYP WALLBOARD PARTITION ASSEMBLY BASED ON UL SYSTEM W -L -1001 PLAN ONE OR TWO HOUR FIRE RATED GYPSUM WALLBOARD ASSEMBLY WOOD STUDS AT 16" O.C. OR METAL STUDS AT 24" O.C. MAX CAULK MATERIAL FORCED INTO ANNULAR SPACE TO MAX EXTEND POSSIBLE AND WITH 1/4" DIAM. BEAD APPLIED TO PERIMETER OF PIPE OR CONDUIT AT ITS EGRESS FROM WALL. 12" DIAM. OR SMALLER SCHEDULE 10S OR HEAVIER STEEL PIPE, NOM. 6" DIAM. OR SMALLER RIGID STEEL CONDUIT, 4" DIAM. OR SMALLER STEEL E.M.T. CONDUIT OR 1" DIAM. OR SMALLER FLEXIBLE STEEL CONDUIT. P -25 N/S CAULKING BY MINNESOTA MINING I. TO BE 3/16" OR LESS. SED ON PRODUCT PERFORMANCE 1479) FIRE TEST AND UL FIRE STOP PENETRATION FIRESTOP FOR 6" MAX. PVC PIPE THROUGH FIRE RATED CONC. FLOOR ASSEMBLY BASED ON UL SYSTEM C -AJ -2001 p ° � � e � e e n ° I° 4" DEEP STEEL COLLAR W/ 1 1/4" W X 2" L ANCHOR TABS OR FIELD FABRICATED 0.016" THICK (30 GAUGE) GALV. SHEET STEEL IN ACCORDANCE WITH INST. SHEET SUPPLIED BY WRAP SHEET MANUFACTURER USE MIN. 2 - 1/2" WIDE BY 0.028" THICK STAINLESS STEEL BAND CLAMPS WITH WORM GEAR TIGHTENING MECHANISM. LOCATE CLAMP NEAR MID OF EACH STRIP STACK SECTION ASSEMBLED STEEL COLLAR DETAIL NOTES: <tDIKH,IINU LULLAK WND TABS ' ENETRATING ITEM /4" MIN. BEAD OF CP -25 N/S :AULK. APPLY TO PERIMETER OF :OLLAR AT FLOOR CONNECTION. 6" (152 MM) MAX. PVC PIPE FIRE RATED CONC. FLOOR 2 1/2" MIN. 1/4" ANNULAR SPACE FS -195 R/R WRAP STRIP 2 STACKS (NOM. 4" STACK HEIGHT) TIGHTLY WRAPPED TOP EDGES BUTTED AGAINST THE UNDERSIDE OF CONC. 4 a v a ° I a a 1/4" X 1 1/2" MIN. STEEL EXP. BOLTS W/ 1 1/4" DIAM. STEEL FENDER WASHERS AT EA. ANCHOR TAB CP -25 S/L OR CP -25 N/S CAULK AT OUTER PERIMETER ALUMINUM FOIL WRAP AROUND PIPE 2" MIN. MAT WRAP - 6" WIDE STRIP OF FLEXIBLE SHEET MATERIAL FACED ON ONE SIDE W/ ALUM. FOIL (FOIL FACE EXPOSED) OVERLAP 1/2" AT SEAM SECURE IN PLACE W/ WIRE TIES 4" O.C. ALTERNATE: USE NOM. 1" THICK HOLLOW CYLINDRICAL HEAVY DENSITY (MIN. 3.5 PFC) GLASS FIBER UNITS JACKETED ON THE OUTSIDE WITH FOIL - SCRIM- KRAFT. MIN. 6" LENGTH OF PIPE COVERING INSTALLED AROUND PIPE AT ITS EGRESS FROM STEEL COLLAR ON UNDERSIDE OF FLOOR. SECURE COVERING TO PIPE NTH STEEL WIRE TIES ® 4" O.C. STEEL COLLAR DETAIL REQ. LENGTH 1. WRAP THE PVC PIPE NTH ALUMINUM FOIL TAPE WHERE CAULK CONTACTS IT. CP -25 N/S MAY TEMPORARILY SOFTEN THE PLASTIC PIPE IF ALLOWED TO COME IN DIRECT CONTACT. 2. TIGHTLY WRAP 3 INDIVIDUAL LAYERS OF FS -195 R/R STRIPS AROUND PIPE. SECURE EACH WRAP WITH ALUMINUM FOIL TAPE OR APPROVED EQUIVALENT. INSURE ALL LAYERS OF FS 195 R/R BUTT SECURELY AGAINST THE UNDERSIDE OF THE CONCRETE FLOOR. STAGGER BUTTED SEAMS BETWEEN LAYERS. 3. APPLY FIRE RESTRICTING COLLAR (3M RC -1 OR APPROVED EQ.). REMOVE ENOUGH OF THE RESTRICTING COLLAR TO MAKE ONE WRAP AROUND THE APPLIED FS -195 R/R WITH A MINIMUM 1" OVERLAP. FIELD CUT TO FIT WITH MOUNTING TABS BENT AWAY FROM THE PIPE AT RIGHT ANGLES AND FLUSH WITH FLOOR. WARNING: EDGES OF RESTRICTING COLLAR ARE SHARP. HANDLE WITH CARE. 4. TIGHTLY SECURE RESTRICTING COLLAR AROUND PIPE WITH STEEL HOSE CLAMP CENTERED ON RESTRICTING COLLAR ASSEMBLY. 5. SECURE RESTRICTING COLLAR TO THE SLAB WITH 1 1/2" X 1/4" EXP. BOLTS. USE 1 1/4" DIAM. FENDER WASHERS ON THE MOUNTING TABS. SECURE ALL TABS. 6. FOLD RESTRICTING COLLAR SUPPORT TABS TO LOCK THE WRAP STRIPS IN PLACE. 7. AFTER INSTALLATION OF THE FIRST RESTRICTING COLLAR TO THE FLOOR, REPEAT STEP #2 BY BUTTING THE FS -195 R/R WRAP STRIP AGAINST THE BOTTOM OF THE FIRST RESTRICTING COLLAR. 8. REMOVE ENOUGH RESTRICTING COLLAR MATERIAL TO MAKE THE SECOND COLLAR AND REPEAT STEP #3. INSTALL WITH MOUNTING TABS STRAIGHT UP, SLIGHTLY BELOW THE FIRST RESTRICTING COLLAR HOSE CLAMP. APPLY THE HOSE CLAMP TO THE SECOND RESTRICTING COLLAR ASSEMBLY LEAVE ENOUGH SLACK TO ALLOW REPOSITIONING OF THE COLLAR VERTICALLY. BEND SUPPORT TABS INWARD TO HOLD THE WRAP IN PLACE. LOOSEN THE FIRST RESTRICTING COLLAR HOSE CLAMP TO ALLOW THE MOUNTING TABS OF THE SECOND RESTRICTING COLLAR TO PASS UNDER IT. SLIDE THE SECOND RESTRICTING COLLAR UP WITH THE MOUNTING TABS UNDER THE FIRST RESTRICTING COLLAR HOSE CLAMP. TIGHTEN THE SECOND RESTRICTING COLLAR HOSE CLAMP. TIGHTEN THE FIRST RESTRICTING COLLAR HOSE CLAMP AND BEND EVERY OTHER MOUNTING TAB OF THE SECOND RESTRICTING COLLAR OVER THE FIRST RESTRICTING COLLAR HOSE CLAMP. 9. APPLY ONE WRAP OF 3M 3 -5A MAT, MINNESOTA MINING & MFG. CO. TYPE E -5A MAT, OR APPROVED EQ. 6" WIDTH MINIMUM AROUND THE PIPE, PROVIDE MINIMUM 1/2" OVERLAP. BUTT THE MAT WRAP FLUSH TO THE SECOND RESTRICTING COLLAR ASSEMBLY. SECURE THE MAT WRAP WITH 18 SWIG MIN. TIE WIRES 1" FROM EACH END OF MAT. SEAL THE EDGE OF THE MAT ABUTTING THE RESTRICTING COLLAR WITH 1/4" MIN. BEAD OF CP -25 N/S CAULK. 10. RECOMMENDATIONS BASED ON PRODUCT PERFORMANCE PER ASTM E -614 (UL 1479) FIRE TEST AND UL THROUGH - PENETRATION FIRESTOP SYSTEM #64. PENETRATION FOR METAL PIPE /CONDUIT THROUGH CONCRETE WALL ASSEMBLY BASED ON UL SYSTEM C -AJ -1001 METAL PIPE OR CONDUIT CP -25 N/S CAULK SECTION PENETRATING ITEM STEEL SLEEVE (OPTIONAL) POINT OF CONTACT �1i3 ELEVATION ANNULAR SPACE 2 1/2" MAX. DAMMING MATERIAL (FIBERGLASS INSULATION BACKER ROD OR MINERAL WOOL) STEEL SLEEVE (OPTIONAL) FIRE RATED SOLID CONCRETE OR CONCRETE BLOCK WALL 1. OPTIONAL STEEL SLEEVE 12" DIAM. OR SMALLER SCHEDULE 40 OR HEAVIER STEEL PIPE SLEEVE CAST INTO CONCRETE WALL. SLEEVE TO BE FLUSH OR PROJECT 2" MAX FROM BOTH SURFACES OF WALL. 2. PENETRATING ITEM TO BE: NOM. 20" DIAM. OR LESS SCHEDULE 10S OR HEAVIER STEEL PIPE, NOM. 6" DIAM. OR LESS RIGID STEEL CONDUIT, NOM. 6" DIAM. OR LESS TYPE "L" OR HEAVIER COPPER TUBING, NOM. 4" DIAM. OR SMALLER CAST IRON PIPE. MAX ANNULAR SPACE BETWEEN PIPE OR CONDUIT AND EDGE OF THROUGH OPENING TO BE 2 1/2" OR LESS. MIN. ANNULAR SPACE BETWEEN PIPE OR CONDUIT AND EDGE OF THROUGH SPACE TO BE 0" (POINT OF CONTACT). 3. PIPE OR CONDUIT TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF WALL ASSEMBLY. 4. USE 1/2" MIN. CAULK DEPTH WHEN NOM. PIPE OR CONDUIT IS 10 DIAM. OR LESS AND WHEN MAX ANNULAR SPACE IS 1" OR LESS. USE CP -25 N/S CAULK. 5. USE 1" MIN. CAULK DEPTH WHEN NOM. PIPE OR CONDUIT IS 10" DIAM. OR MORE, OR WHEN MAX. ANNULAR SPACE IS 1" OR MORE. USE CP -25 N/S CAULK. 6. INSTALL FILL MATERIAL (CAULK) FLUSH WITH AND ON BOTH SIDES OF WALL ASSEMBLY SURFACE. 7. 40% CAULK SHRINKAGE MAY BE EXPECTED AFTER INSTALLATION. FIRE RATING BASED ON WET INSTALLATION DEPTH. 8. USE 1" MIN. PACKING MATERIAL FIBERGLASS INSULATION, BACKER ROD, MINERAL WOOL, ALUMINA SILICA FIBER BLANKET TIGHTLY PACKED ARE ACCEPTABLE. RECESS PACKING MATERIAL FROM WALL SURFACE AS REQUIRED TO ACCOMOOATE THE REQUIRED THICKNESS OF CAULK. 9. RECOMMENDATIONS BASED ON PRODUCT PERFORMANCE PER ASTM E -614 (UL 1479) FIRE TEST AND UL FIRE STOP SYSTEM C -AJ -1001. SYSTEM NO. W -L -2003 (FORMERLY SYSTEM NO. 148) F RATINGS - 1 AND 2 HR (SEE ITEM 3) T RATINGS - 1 AND 2 HR (SEE ITEM 3) L RATING AT AMBIENT - 7 CFM /SQ FT (SEE ITEM 38) L RATING AT 400 F - LESS THAN 1 CFM /SQ FT (SEE ITEM 313) i A 1. WALL ASSEMLBY - The 1 or 2 hr fire -rated gypsum wallboard /stud wall assembly shall be constructed of the materials and in the manner described in the individual U300 or U400 Series Wall or Partition Design in the UL Fire Resistance Directory and shall include the following construction features: A. STUDS - Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. lumber spaced 16 in. OC with nom 2 by 4 in. lumber end plates and cross braces. Steel studs to be min 3 -sib in. wide by 1 -%in. deep channels spaced max 24 in. O.C. B. WALLBOARD. GYPSUM* - in. thick, 4 ft wide with square or tapered edges. The gypsum wallboard type, thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual U300 or U400 Series Design in the UL Fire Resistance Directory. Max diam of pening is 3 -Y6 in. 2• THROUGH PENETRANTS - One nonmetallic pipe or conduit to be centered in the through opening. The annular space between pipe or conduit and periphery of opening shall be min X in. and max % in. Pipe or conduit to be rigidly supported on both sides of the floor - ceiling assembly. The following types and sizes of nonmetallic pipes or conduits may be used: A. POLYVINYL CHLORIDE (PVC) PIPE - Nom 2 in. diam (or smaller) Schedule 40 solid core PVC pipe for use in closed (process or supply) or vented (drain, waste or vent) piping system. B. RIGID NONMETALLIC CONDUIT ++ - Nom 2 in. dicm (or smaller)(Sshedule 40 or 80) PVC conduit installed in accordance with Article 347 of the National electric Code (NFPA No. 70). C. CHLORINATED POLYVINYL CHLORIDE (CPVC ) PIPE - Nom 2 in. diam (or smaller) SDR17 CPVC pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems. D. CELLULAR CORE POLYVINYL CHLORIDE (ccPVC) Pipe - Nom 2 in. diam (or smaller) Schedule 40 cellular core PVC pipe for use in closed (process or supply) or vented (drain, waste or vent) piping system. E. ACRYL ONITRIL E BUTADIENE STYRENE (ABS) Pipe - Nom 2 in, diam (or smaller) Schedule 40 solid core ABS pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems. F. CELLULAR ULAR CORE ACRYLONITRILE BUTADIENE STYRENE (ccABS) Pipe - Nom 2 in, diam (or smaller) Schedule 40 cellular core ABS pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems. 3• FIRESTOP SYSTEM - Installed symmetrically on both sides of wall assembly. The hourly F and T Ratings for the firestop system are equal to the hourly fire rating of the wall assembly in which it is installed. The details of the firestop system shall be as follows. A. FILL. , VOID OR CAVITY MATERIALS* - WRAP STRIP - Nom Y4 in. thick intumescent elastomeric material faced on one side with aluminum foil, supplied in 2 in. wide strips. Nom 2 in, wide strip thightly wrapped around nonmetallic pipe (foil side out) with seam butted. Wrap strip layer securely bound with steel wire or aluminum foil tape and slid into annular space approx 1 -Y4in. such that approx 3/4 in. of the wrap strip proturdes from the wall surface. MINNESOTA MINING & MFG CO - FS -195+ B. FILL • VOID OR CAVITY MATERIALS* - CAULK OR PUTTY - Min % in. thickness of caulk or putty applied into annular space between wrap strip and periphery of opening. A nom Y4 in. diam bead of caulk or putty to be applied to the wrap strip /wall interface and to the exposed edge of the wrap strip layers approx Y4 in. from the wall surface. MINNESOTA MINING & MFG CO - CP 25WB+ CAULK OR MPS -2+ PUTTY. (NOTE: L Ratings apply only when Type CP -25 WB+ caulk is used.) C. FOIL TAPE - (NOT SHOWN) - Nom 4 in. wide. 3 mil thick aluminum tape wrapped around pipe prior to the installation of the wrap strip (Item 3A). Min of one wrap, flush with both sides of wall and proceeding outward. Tape is not required for pipes sown in Items 2A, 2B and 2C. *Bearing the UL Classification Marking gl - i tlAa DESON cackle N# ,.,k „« «, <,,,�'• 151 SEu'LA -A. V -00I=, SUTS -�00 = - -- CORAL GABLES, FL 33134 OFFICE: (305) 442 -1188 FAX: (305) 445 -1509 WWW. ADCINTERNATIONAL.NET TIVE << Q f E I O STATE OF FLORIDA AR- V001105�6 RAYMUNDO FEITO, R.A. AA- C001315 Architect • Seal/Signature MRA EXPANSION SUNSET PROFESSIONAL BLDG 6280 SUNSET DR E SUITE 600 E i SOUTH MIAMI FL ......................................................................................................................................................... ............................... : Date Issue Description Drawn By Checked By 04 -13 -09 LANDLORD REVIEW ER ER 04 -27 -09 PERMIT ISSUE ER ER Z Z a......................................................................................................................................................... ............................... Date $Issue Description Drawn By Checked By ........................................................................................................................................................... ............................... Project Number Client Name 09032 PROMED PROPERTIES Description Client Address 1696 NE MIAMI GARDENS DR SUITE 8 Scale N. MIAMI BEACH, FL 33179 NONE Client Phone Number (305) 947 -8800 CAD File Name FIRE PENETRATION DETAILS Consultant • Seal/Signature 9.0