13-1327-004NEW GENSET TO BE MOUNTED ON SAME EXISTING 9 INCHES WIDE
GENERATOR ROOM CONCRETE SLAB. SEE DIMENSIONS AND DETAIL BELOW.
16.0"
128.0"
90,0"
56.0"
O O O O
FOUR 3/4" HILTI KWIK BOLT III
EXPANSION ANCHOR W /MIN. 6.5"
EMBEDMENT INTO CONCRETE PAD
0 EACH SIDE (TYPICAL)
Q 3/4" DIAMETER BASE MOUNTING HOLES
3/4" CONCRETE ANCHOR BOLT
< (4 REQUIRED EACH SIDE)
ry
0 0
GENERATOR ANCHORAGE
MOUNTING DETAIL
0
0
18.0"
USE MANUFACTURER DRAWINGS DIMENSIONS NOT THE
GENERATOR SPEC SHEET DIMENSIONS.
`0
In
144"
STANDBY GENERATOR BASE ANCHORAGE.
SCALE: 1/4 =1 " -0"
EXISTING
3/4" EXPANSION BOLT, ON SITE
ON
LENGTH: FIELD VERY � SLAB
L =810"
a
v
Q. 4
:4
a °
1- 200A,39
cn
L02
NEW STANDBY
d.
GENERATOR
4 a
oz
250kW
ui w
d' °
v
3
(RECOMMENDED)
4
o �
a
f
a a:
.4 °
DATE:
J.T.
9 -23 -13
SCALE:
REVISED BY:
AS NOTED
J.T.
PROJECT NUMBER:
20130923 -2
A.
NEW STANDBY GENERATOR
DIMENSIONS, ANCHORAGE AND
FUEL LINES DETAILS.
v
cd
4 d.4 °
LL
A d
s
I
9
co
04
4
d
CEO
CA
N
F— Z c°D
W Q
v
; "'
4
7
uj
s
.
d
11.
A
d
v
4
v 4
d
v
V
4
°
d•
4. -4
.1
4
° :a•
°
4 4
.° 4
3/4"0 HILTI KWIK GALVANIZED BOLT III EXPANSION
ANCHOR W /MIN. 6-1/2 1) EMBEDMENT INTO EXISTING
3,000PSI 9 INCH CONCRETE SLAB (EACH SIDE).
TENSION = 2,615
SHEAR = 41876
TO EXISTING
1000 GALLON
TANK AND PUMP AT
GROUND FLOOR
GENERATOR 1
PIPES ISOMETRIC
N.T.S.
ALL FUEL LINES AND
ANCHORAGES ARE
EXISTING.
0
FUEL PIPES.
PIPES ANCHORAGE DETAIL
TO CONCRETE SLAB WITH
UNISTRUT CHANNEL.
INSTALL LEGIBLE SIGN:
DO NOT SMOKE
IN THIS AREA"
h'U7'
EXISTING
DAY
TANK
PIPES
SUPPORT
(TYP)
SEE DETAIL
EXISTING DOUBLE DOORS
WITH AOUVERS _//
mmu 6,a
INSTALL LEGIBLE SIGN:
"DO NOT SMOKE
EXISTING IN THIS AREA"
GENERATOR
ROOM
PIPES
RUNS ABOVE
1- 400A,3P
GROUND
1- 200A,39
cn
L02
NEW STANDBY
EXISTING SPILL
GENERATOR
CONTAINING WALL
oz
250kW
ui w
480V
1" F.O.R.
3
EXISTING ,(LOUVERED
DOUBLE DOORS
3/4" F.O.S.
EXISTING
LOUVER
5„
EXISTING
LOUVER
WINDOW
(U
PIPES
SUPPORT
(nP)
SEE DETAIL
4th PARTIAL FLOOR PLAN.
EXISTING
LOUVERED
, WINDOW
cd
EXISTING LOUVER
NEW STANDBY GENERATOR AND EXISTING
GENERATOR ROOM REAL DIMENSIONS DRAWING.
PARTIAL 4th FLOOR PLAN.
�- SCALE: 1/4=11"-O"
ALL DRAWINGS AND WRITTEN MATERIAL APPEARING HEREIN CONSTITUTE THE ORIGINAL AND UMPUBLISHED WORK, AND SHALL NOT BE DUPLICATED, USED OR DISCLOSED WITHOUT THE EXPRESS WRITTEN CONSENT OF JAVIER TUCHMAN P.E. ENGINEER IS NOT RESPONSIBLE IF ANY CHANGES ARE MADE WITHOUT HIS APPROVAL.
N
F-
z
w
E
0
U .
T
z
0
U
W
0
W r
Q �
D r'
I
cV
z �
o a
N O
> Z T
w
c
�r,.", �^
PC, r-i m tn m
N M
/ 3 -9 n "t
L 00 ,
Z O 000 0 Ln
"
1�
� 1 M
DD N N
L.
C
O 0
LL
Z 0 E
WN m� 8
�W
E
d F- ». rn
., W U _ N Z Orr Y
Wc¢ -onrnO)o
ml 'L zW U?sA JLLVrn cti� cn
WV -iU) Z j rnaN
w o Y dw - O
1 QO -'��d �OC_C�U
o w�Ec
_¢
sh, I ~
WW z LL W E
riu1
W
a
PAGE NUMBER:
DETAILS -1 OF 1
a
cn
L02
a t=3
Q�
oz
ui w
I
z �
o �
a
f
DRAWN BY:
DATE:
J.T.
9 -23 -13
SCALE:
REVISED BY:
AS NOTED
J.T.
PROJECT NUMBER:
20130923 -2
PAGE TITLE:
NEW STANDBY GENERATOR
DIMENSIONS, ANCHORAGE AND
FUEL LINES DETAILS.
cd
0
LL
s
I
9
co
04
4",
c
co
CEO
CA
N
F— Z c°D
W Q
W
; "'
Q Q z
uj
riu1
W
a
PAGE NUMBER:
DETAILS -1 OF 1