13-1327-003N Note: NEC 705.10. - Place a permanent plaque or directory denoting all electrical power sources on or in the premises, shall be installed at each service equipment location and at locations of all electric power production sources capable of being interconnected. 2000A, 480V, 30 MAIN DISTRIBUTI ❑N PANEL. EXISTING 4 -1/0, 1 #6 F EX1911N --1 O 2" CONDUIT. RESTAURANT MAIN DISCONNECT LOCATED i 200A 3P INSIDE 1st FLOOR ELECTRICAL ROOM. I 200A 1 (SEE FLOOR PLAN) Icc: 42kA 48OV. 3POLE L - - --J NEW 4 -2/0, 1 #6 2" CONDUIT. LENGTH = 20 FEET RESTAURANT LOAD. ATS #3 NEMAI 200A A IS NO T 480V SEPARATELY DERIVED. 3PH (TYPICAL) Icc -63kA NEW 1 LOCATED AT BUILDING 7 I GROUND FLOOR FRONT DESK TO RSHOTE ANNDNCIATOR niBmS Bun.DING IWD -110 PANEL EDP. 25 3P 1 EXISTINGI L- — J ATS #i ATS IS NOT I SEPARATELY DERIVED. (TYPICAL) I I I I 480V 1cc�A NEMA1 L NEW_ J TO EXISTING EATER- CHARGI FACP C.B. #2. PANEL 'LEM'. NEW 4j ZnM (Cu) EXISTING. 3/4' CONDUIT. 2 #12THWN (Cu) EXISTING. (up to 4000') 3/4' CONDUIT. 2J12THWN (Cu) 3/4' CONDUIT. EXISTING 4- 500MCM, 1 #3 EXISTING 3" CONDUIT. 4 -1/0, 1 #6 2" CONDUIT. 225A FIRE PUMP CONTROL PANEL. 25 3P 1 EXISTINGI L- T - I EXISTING FIRE PUMP ATS #2 ATS IS NOT I SEPARATELY DERIVED. (TYPICAL) I 1 I 80V I 1c I NEMAL I EXISTINJ EXISTING 4 -4/0, 1#3 4" CONDUIT. EXISTING 4 -1/0, 1 #6 2" CONDUIT. LENGTH 20 FEET / I POWER SYSTEM RISER DIAGRAM. N.T.S. OPTIONAL STANDBY GENERATOR INFORMATION: MANUFACTURER: MTU. CAPACITY: 250kW /312kVA, 376A. 277/48OV, 30, 4 WIRES, 60Hz. Integral One 400A and one 200A 3 pole circuit breaker, 42kA ENGINE MANUFACTURER: MTU. FUEL: DIESEL #2. Fuel Consumption: At Power Rating: 100% ..... 18.5 gph 75% ..... 15.2 gph 50% ..... 11.0 gph GENERATOR MAXIMUM RUNNING TIME AT 100% WITH 1000 GALLONS DIESEL TANK IS: 544 HOURS. GENERATOR RATOR MAXIMUM RUNNING TIME AT 75% WITH 1000 GALLONS DIESEL TANK IS: 65.7 HOURS. GENERATOR MAXIMUM RUNNING TIME AT 50% WITH 1000 GALLONS DIESEL TANK IS: 90.9 HOURS. Diesel as Fuel. Recommended Fuel: Diesel #2 NEW STANDBY GENERATOR DIMENSIONS: SYSTEM DIMENSI ❑NS (L X W X H) 144 X 56 X 73 IN WEIGHT (DRY /LESS TANK) 3,078 KG (6,785 LB) OPEN POWER UNIT (OPU) Cj �ii - V SCOPE OF WORK: 1. BUILDING IS EXISTING AND HAS AN EXISTING 18OkW, 48OV, 30 STANDBY GENERATOR THAT IS GOING TO BE REPLACED BY NEW 250kW STANDBY GENERATOR. GENERATOR IS LOCATED AT 4th LEVEL PARKING GARAGE INSIDE A DEDICATED GENERATOR ROOM. EXISTING STANDBY GENERATOR PROVIDE POWER TO TWO SEPARATED AUTOMATIC TRANSFER SWITCHES. ONE 400 AMPS THAT FEED THE EMERGENCY DISTRIBUTION PANEL (ATS #1) THAT IS GOING TO BE REPLACED AS WELL AND AND A SECOND AUTOMATIC TRANSFER SWITCH THAT FEED THE FIRE PUMP CONTROLLER (ATS #2). 2. STANDBY GENERATOR HAS ONE STAND ALONE 1000 GALLONS DIESEL FUEL TANK LOCATED AT GROUND FLOOR AND ONE-2.5- GALLONS DAY TANK LOCATED INSIDE THE 4th FLOOR GENERATOR ROOM BOTH AR GO G TO REMAIN. 3. THE NEW PROPOSED STANDBY GENERATOR CAPACITY IS 250kW, 480V, 30. SHALL HAVE TWO SEPARATED CIRCUIT BREAKERS FACTORY ASSEMBLED, ONE 400AMPS, 3 POLES DOUBLE LUG EACH TERMINAL THAT ARE GOING TO BE INTERCONNECTED WITH NEW ATS #1 AND EXISTING ATS #2. SECOND 200A, 3 POLES CIRCUIT BREAKER IS GOING TO FEED EXISTING RESTAURANT ELECTRIC LOAD AND NEW 200A, "ATS #3 ". THE RESTAURANT HAS ONE 200A, 3 POLES MAIN DISCONNECT SWITCH. IN THIS PERMIT A NEW 200A, 3 POLES AUTOMATIC TRANSFER SWITCH (ATS #3) IS GOING TO BE INSTALLED TO PROVIDE THE RESTAURANT WITH BACK -UP POWER. NEW CONDUITS AND WIRES ARE GOING TO BE INSTALLED TO INTERCONNECT THE STANDBY GENERATOR WITH THE NEW RESTAURANT ATS #3. 4. ATS #1 & ATS #2 ELECTRIC LOADS REMAINS THE SAME. WIRING AND CONDUITS REMAIN THE SAME. 5. SEE FLOOR PLAN SECTIONS FOR LOCATIONS AND CONDUIT RUNS. 6. VOLTAGE DROP CALCULATIONS PROVIDED. 7. GENERATOR INSTALLATION SHALL COMPLY WITH NFPA 110.,/ 8. THE CLASSIFICATION OF THIS "STANDBY GENERATOR IS" IS: CLASS 54 (GENERATOR SET OPERATION HOURS IS LIMITED ONLY BY FUEL AVAILABILITY), TYPE 10 AND LEVEL 2 PER NFPA 110, CHAPTER 4. EMERGENCY POWER FOR EGRESS: POWER THAT MUST BE AVAILABLE WITHIN 10 - SECONDS AND MUST REMAIN AVAILABLE FOR 90 MINUTES SO THAT PEOPLE MAY EXIT A BUILDING SAFELY ACCORDING TO THE LIFE SAFETY CODE NFPA 110, CHAPTER 4.2, 4.3 AND 4.4. ADDITIONAL NOTES: a. EXISTING DOUBLE WALL ABOVE GROUND 1000 GLNS DIESEL FUEL TANK IS � U�� PHYSICALLY PROTECTED BY STEEL BOLLARDS AND A CONCRETE WALL. b. EXISTING FUEL SYSTEM AND /OR STORAGE SYSTEM SHALL COMPLY WITH NFPA--30 REQUIREMENTS. c. EXISTING GENERATOR ROOM HAS 2 HOURS FIRE RATED WITH 90 MIN. DOOR WITF CLOSER, NFPA 110 - 7.2.1.1 d. EXISTING FUEL LINES ARE PROVIDED WITH SIGNAGE AS PER NFPA 704.< e. GENERATOR ROOM HAS AN EXISTING EMERGENCY LIGHT BATTERY - POWERED AS PER NFPA 110 - 7.3.1. f. A COPY OF SPILLAGE METHOD ATTACHED TO DRAWINGS. g. THE "EPS" LEVEL WAS INDICATED ORIGINALLY INTO THE SCOPE OF WORK ITEM NUMBER 8. PLEASE MAKE REFERENCE OF IT. Restaurant Maximun Demand. 200A. 3P Month NEW 2012 BREAKER FOR 400A. 3P 26 4� 2/0, 1 #6 RESTAURANT. BREAKER WITH I DOUBLE LUGS 2013 2 CONDUIT. -- --� -- LENGTH = 280 FEET OPTIONAL STANDBY SYSTEM SHALL BE 2013 April 19 IINTEGRAL !" - em 40 SUITABLE FOR THE MAXIMUM !'.AILABLE May 20 2013 SHORT - CIRCUIT CURI.LNT AT ITS TERMINALS. 21 2013 IJuly 3P 3P AL C.B. EXISTING MOP CIRCUIT BREAKER IS 42kA1C. 2013 August 24 TT Icr42kA September 20 2013 STANDBY I 2013 November I BATTERY GENERATOR CHARGER NEW 2812THWN +IBI2G-3/4'C STOP 2013 IDecember 0 AND sse 10 WP I Maximum 20.7 kW /day Demand HEATER � 11FK%W-40ft LOCATEC AT ;r D' FROM I 04 AVG (Cu) THE GENERATC-:'. GROUND COMPLY WITH I I - NFPA 110. GROUND GENERATOR METALLIC STRUCTURE AND TIE TO EXISTING GROUND CONNECTION. I I THE EMERGENCY GENERATOR' EXHAUST SHALL BE 10 FEET AWAY FROM ANY BUILDING 1 I OPENING TO PREVENT EXHAUST FUMES FROM GETTING INSIDE THE BUILDING. r/ OPENINGS INCLUDE: WINDOWS, DOORS, EAVE ROOF VENTS, WALL VENTS, ETC. I �--- -� OPTIONAL STANDBY GENERATOR LOCATED AT 4th FLOOR PARKIONG GARAGE INSIDE GENERATOR ROOM, POWER SYSTEM RISER DIAGRAM. N.T.S. OPTIONAL STANDBY GENERATOR INFORMATION: MANUFACTURER: MTU. CAPACITY: 250kW /312kVA, 376A. 277/48OV, 30, 4 WIRES, 60Hz. Integral One 400A and one 200A 3 pole circuit breaker, 42kA ENGINE MANUFACTURER: MTU. FUEL: DIESEL #2. Fuel Consumption: At Power Rating: 100% ..... 18.5 gph 75% ..... 15.2 gph 50% ..... 11.0 gph GENERATOR MAXIMUM RUNNING TIME AT 100% WITH 1000 GALLONS DIESEL TANK IS: 544 HOURS. GENERATOR RATOR MAXIMUM RUNNING TIME AT 75% WITH 1000 GALLONS DIESEL TANK IS: 65.7 HOURS. GENERATOR MAXIMUM RUNNING TIME AT 50% WITH 1000 GALLONS DIESEL TANK IS: 90.9 HOURS. Diesel as Fuel. Recommended Fuel: Diesel #2 NEW STANDBY GENERATOR DIMENSIONS: SYSTEM DIMENSI ❑NS (L X W X H) 144 X 56 X 73 IN WEIGHT (DRY /LESS TANK) 3,078 KG (6,785 LB) OPEN POWER UNIT (OPU) Cj �ii - V SCOPE OF WORK: 1. BUILDING IS EXISTING AND HAS AN EXISTING 18OkW, 48OV, 30 STANDBY GENERATOR THAT IS GOING TO BE REPLACED BY NEW 250kW STANDBY GENERATOR. GENERATOR IS LOCATED AT 4th LEVEL PARKING GARAGE INSIDE A DEDICATED GENERATOR ROOM. EXISTING STANDBY GENERATOR PROVIDE POWER TO TWO SEPARATED AUTOMATIC TRANSFER SWITCHES. ONE 400 AMPS THAT FEED THE EMERGENCY DISTRIBUTION PANEL (ATS #1) THAT IS GOING TO BE REPLACED AS WELL AND AND A SECOND AUTOMATIC TRANSFER SWITCH THAT FEED THE FIRE PUMP CONTROLLER (ATS #2). 2. STANDBY GENERATOR HAS ONE STAND ALONE 1000 GALLONS DIESEL FUEL TANK LOCATED AT GROUND FLOOR AND ONE-2.5- GALLONS DAY TANK LOCATED INSIDE THE 4th FLOOR GENERATOR ROOM BOTH AR GO G TO REMAIN. 3. THE NEW PROPOSED STANDBY GENERATOR CAPACITY IS 250kW, 480V, 30. SHALL HAVE TWO SEPARATED CIRCUIT BREAKERS FACTORY ASSEMBLED, ONE 400AMPS, 3 POLES DOUBLE LUG EACH TERMINAL THAT ARE GOING TO BE INTERCONNECTED WITH NEW ATS #1 AND EXISTING ATS #2. SECOND 200A, 3 POLES CIRCUIT BREAKER IS GOING TO FEED EXISTING RESTAURANT ELECTRIC LOAD AND NEW 200A, "ATS #3 ". THE RESTAURANT HAS ONE 200A, 3 POLES MAIN DISCONNECT SWITCH. IN THIS PERMIT A NEW 200A, 3 POLES AUTOMATIC TRANSFER SWITCH (ATS #3) IS GOING TO BE INSTALLED TO PROVIDE THE RESTAURANT WITH BACK -UP POWER. NEW CONDUITS AND WIRES ARE GOING TO BE INSTALLED TO INTERCONNECT THE STANDBY GENERATOR WITH THE NEW RESTAURANT ATS #3. 4. ATS #1 & ATS #2 ELECTRIC LOADS REMAINS THE SAME. WIRING AND CONDUITS REMAIN THE SAME. 5. SEE FLOOR PLAN SECTIONS FOR LOCATIONS AND CONDUIT RUNS. 6. VOLTAGE DROP CALCULATIONS PROVIDED. 7. GENERATOR INSTALLATION SHALL COMPLY WITH NFPA 110.,/ 8. THE CLASSIFICATION OF THIS "STANDBY GENERATOR IS" IS: CLASS 54 (GENERATOR SET OPERATION HOURS IS LIMITED ONLY BY FUEL AVAILABILITY), TYPE 10 AND LEVEL 2 PER NFPA 110, CHAPTER 4. EMERGENCY POWER FOR EGRESS: POWER THAT MUST BE AVAILABLE WITHIN 10 - SECONDS AND MUST REMAIN AVAILABLE FOR 90 MINUTES SO THAT PEOPLE MAY EXIT A BUILDING SAFELY ACCORDING TO THE LIFE SAFETY CODE NFPA 110, CHAPTER 4.2, 4.3 AND 4.4. ADDITIONAL NOTES: a. EXISTING DOUBLE WALL ABOVE GROUND 1000 GLNS DIESEL FUEL TANK IS � U�� PHYSICALLY PROTECTED BY STEEL BOLLARDS AND A CONCRETE WALL. b. EXISTING FUEL SYSTEM AND /OR STORAGE SYSTEM SHALL COMPLY WITH NFPA--30 REQUIREMENTS. c. EXISTING GENERATOR ROOM HAS 2 HOURS FIRE RATED WITH 90 MIN. DOOR WITF CLOSER, NFPA 110 - 7.2.1.1 d. EXISTING FUEL LINES ARE PROVIDED WITH SIGNAGE AS PER NFPA 704.< e. GENERATOR ROOM HAS AN EXISTING EMERGENCY LIGHT BATTERY - POWERED AS PER NFPA 110 - 7.3.1. f. A COPY OF SPILLAGE METHOD ATTACHED TO DRAWINGS. g. THE "EPS" LEVEL WAS INDICATED ORIGINALLY INTO THE SCOPE OF WORK ITEM NUMBER 8. PLEASE MAKE REFERENCE OF IT. Restaurant Maximun Demand. Year Month Max Demand (kW) 2012 December 26 2013 January 19 2013 February 19 2013 March 18 2013 April 19 2013 May 20 2013 jJune 21 2013 IJuly 21 2013 August 24 2013 September 20 2013 October 0 2013 November 0 2013 IDecember 0 Maximum 20.7 kW /day Demand RESTAURANT YEAR MAXIMUM DEMAND = 26kW /DAY AS PER UTILITY POWER STATEMENTS (SEE ATTACHED STATEMENTS). RESTAURANT MAXIMUM DEMAND CALCULATIONS TO BE DONE WITH ADDITIONAL. 25% OF ACTUAL MAXIMUM DEMAND. 26kW x 1.25 = 32.5 kW /DAY MAXIMUM REQUIRED AMPERES = 32.5kW/1.73xO.48VxO.8 = 48.9A EXISTING BUILDING STANDBY GENERATOR CAPACITY IS: 180kW. NEW PROPOSED STANDBY GENERATOR CAPACITY IS 250kW. EXISTING 180kW + NEW 48.9 kW = 229 kW NEW CAPACITY = 250kW -229kW = 21 kW SPARE CAPACITY. RESTAURANT NEW FEEDER VOLTAGE DROP CALCULATION: RESTAURANT DEMAND = 32.5kW AMPERES # 480V, 30 = 48.9A DISTANCE FROM GENERATOR TO NEW ATS #3 = 280 FEET. WIRE TO RUN: 4 -2/0, 1 #6 GROUND IN 2" C. ree ase ree re rcu'3ts 7 Drop (30 °C) = 2K x L x I X­0866' 0 866 = 25 8 x 280 x 391 X 0 866 = D 66360 K - Conductor reslslNEy - 12 9 for aW% anpaclty 8 11 for -50% arrpacity copper, L - One w ay length of conductors In feet, I - Oevice(s) total rated current In apps Eater wire size (with slash) (le. 12/, 1/, 2/0, 500/ - see Table) 2! D - Conductor cross section (Automatically Inserted) 66360.. cm One way length of conductors in feet - 280 R Total full load circuit current - 39.1 A Circuit Voltage - 480 V (//q." GENERAL ELECTRICAL NOTES (ODIERAL NOTES ARE PROVIDED AS A BASIC DESCRIPTION OF THE EXTENT AND OUAIiTY EXPECTED 01 THIS PROJECT. IF A CONFUCT D0314 BLI EEN - THESE GENERAL NOTES A'J THE REMAINDER OF THE CONTRACT DOCUMENTS THE SPECIFICATIONS, PLANS AND DETAILS VILL OOVFRN.) ENTIRE INSTALLATION SHALL BE IN ACCORDANCE WITH THE 2008 NATIONAL_ ELECTRICAL CODE (NEC) AND THE LATEST EDITIONS OF ALL LOCAL CGDFS, �} RUB -AND ORDINANCES HAVING JURISDICTION. ALL ELECTRICAL EQUIPMENT, DEVICES, WIRE, ETC., SHALL BE LISTED, FOR INTENDED USE, WITH UNDERWRITER'S LABORATORIES INC. (U.L.), WHERE STANDARDS HAVE BEEN ESTABLISHED BY U.L. ALL CONDUIT RISERS SHALL BE RIGID GALVANIZED STEEL (RGS) EMT OR PVC. WHERE CONDUIT BENDS UPWARD FROM UNDERGROUND TO ABOVE GROUND, OR FROM UNDERGROUND TO FLUSH FLOOR TURN UP AT SWITCHBOARDS AND OTHER FLOOR MOUNTED ELECTRICAL EQUIPMENT, USE AN APPROVED PVC TO RGS COUPLER, AS REQUIRED. RGS CONDUITS SHALL EXTEND A MINIMUM OF 457.2MM (18 ") BELOW GRADE. ALL CONDUIT RUNS ARE SHOWN DIAGRAMMATIC. EXACT ROUTING SHALL BE DETERMINED IN THE FIELD, UNLESS OTHERWISE NOTED. WIRE WAYS SHALL BE SIZED AS REQUIRED, PER NEC, UNLESS OTHERWISE NOTED. CONTRACTOR SHALL VERIFY CIRCUIT PROTECTIVE DEVICE RATING FOR EQUIPMENT PRIOR TO CONSTRUCTION. CONTRACTOR TO PROVIDE ALL LABOR, MATERIALS AND SUPERVISION NECESSARY TO ACCOMPLISH THE WORK AS SHOWN AND /OR NOTED ON THE DRAWINGS. CONTRACTOR SHALL VISIT THE JOB SITE AND VERIFY ALL CONDITIONS, LOCATIONS, DIMENSIONS AND COUNTS AS SHOWN AND /OR NOTED ON THE DRAWINGS. THIS SHALL INCLUDE ANY AND ALL FABRICATIONS PRIOR TO INSTALLATION. CONTRACTOR SHALL GUARANTEE ALL MATERIALS AND WORKMANSHIP FREE FROM DEFECTS FOR A PERIOD OF NOT LESS THAN ONE YEAR FROM DATE OF ACCEPTANCE, UNLESS INDICATED OR SPECIFIED OTHERWISE. CORRECTION OF ANY DEFECTS SHALL BE COMPLETED WITHOUT ADDITIONAL CHARGE AND SHALL INCLUDE REPLACEMENT OR REPAIR OF ANY OTHER PHASE OF THE INSTALLATION WHICH MAY HAVE BEEN DAMAGED THEREBY. ALL REQUIRED INSURANCE SHALL BE PROVIDED FOR PROTECTION AGAINST PUBLIC LIABILITY AND PROPERTY DAMAGE FOR THE DURATION OF THE WORK. CONTRACTOR SHALL KEEP ALL AREAS IN WHICH WORK IS BEING PERFORMED, FREE FROM DEBRIS AT ALL TIMES AND SAID AREAS SHALL BE LEFT BROOM CLEAN AT THE END OF EACH WORKING DAY. IT SHALL BE UNDERSTOOD THAT ALL WORK PERFORMED SHALL BE DONE BY A LICENSED CONTRACTOR AND IN A FIRST -CLASS WORKMANLIKE MANNER. SAID CONTRACTOR SHALL MEET ALL REQUIREMENTS SET FORTH BY ANY LOCAL ORDINANCE AND GOVERNING AUTHORITIES. COORDINATE ALL ELECTRICAL SITE WORK WITH ALL OTHER TRADES CONTRACTORS. ALL ELECTRICAL EQUIPMENT SHALL BE RAINTIGHT WHERE EXPOSED TO THE WEATHER. ALL FLEX CONDUITS CONNECTED TO SUCH EQUIPMENT SHALL BE LIQUID TIGHT. THE ELECTRICAL CONTRACTOR SHALL FURNISH A COMPLETE SET OF AS -BUILT DRAWINGS, SHOWING ALL CHANGES AND DEVIATIONS TO THE ARCHITECT /ENGINEER PRIOR TO COMPLETION OF THE PROJECT. EQUIPMENT SHALL BE OF MATERIALS SUITABLE FOR AND NEMA RATED FOR THE ENVIRONMENT IN WHICH THEY ARE TO BE INSTALLED. FURNISH AND INSTALL CONDUCTORS TO MATCH BUILDING COLOR CODE. IF THERE IS NO BUILDING CODE, THE FOLLOWING COLOR CODING SHALL BE ADHERED TO: NEUTRAL -- WHITE PHASE A -- BLACK PHASE B -- RED PHASE C -- BLUE PHASE C -- ORANGE (HI -LEG IF EXISTING) GROUND -- GREEN ALL OTHER SYSTEMS SHALL BE INSTALLED UTILIZING DIFFERENT COLOR WIRING TO SEPARATE EACH SYSTEM. ALL EQUIPMENT TO BE INSTALLED SHALL BE NEW AND INSTALLED AS PER MANUFACTURER'S RECOMMENDATIONS SO AS NOT TO VOID ANY WARRANTY. STORE ALL EQUIPMENT ABOVE GROUND IN A DRY, COVERED AREA TO PROTECT FROM MOISTURE AND DAMAGE. IF EQUIPMENT IS DAMAGED, THE CONTRACTOR IS TO PROVIDE A NEW REPLACEMENT AT NO ADDITIONAL COST TO THE OWNER. OPTIONAL STANDBY GENERATOR GENERAL NOTES: a) The generator set and its components are prototype- tested, factory- built, and production - tested. Type of fuel: DIESEL. < ' b) The generator set accepts rated load in one step. c) All three phos- units are rate at 0.8 power factor. d) A 10% overload capacity is available for one hour in twelve for Prime Power Rating. e) Ratings are in accordance with ISO- 8528/1, overload power in accordance with ISO- 3046/1, BS 5514. f) NEMA MG1, IEEE, and ANSI standards compliance for temperature rise and motor starting. More information can be obtained from OPTIONAL STANDBY generator specification sheet model number: DS250D6SRA provided in this set of drawings. LEGEND SYMBOLS: ATS :AUTOMATIC TRANSFER SWITCH. �B :JUNCTION BOX :ELECTRIC PANEL sTO :EMERGENCY SHUT —OFF CONTROL WP D:3 POLES FUSED DISCONNECT SWITCH XXAR AR DENOTES AMP RATING OF SWITCH XXAF AF DENOTES AMP FUSE SIZE ® :ELECTRIC METER M.D.P.: MAIN DISTRIBUTION PANEL. CB: CIRCUIT BREAKER WP: WEATHER PROOF E EXISTING =BATTERY—POWERED EMERGENCY LIGHT ALL DRAWINGS AND WRITTEN MATERIAL APPEARING HEREIN CONSTITUTE THE ORIGINAL AND UMPUBLISHED WORK, AND SHALL NOT BE DUPLICATED, USED OR DISCLOSED WITHOUT THE EXPRESS WRITTEN CONSENT OF JAVIER TUCHMAN P.E. ENGINEER IS NOT RESPONSIBLE IF ANY CHANGES ARE MADE WITHOUT HIS APPROVAL. , Iln'AC�' s I'y'iLAA, I -DzkDE COU,jN T Y I Mi-E DEPARTME,11T N F- z w s 0 U Z 0 W 0 W w r- r a ti o r- I CV T z 0 Q N O > z w X r 1 L c,4 06 I-- r n tD N M I -�� N 1174 1 M � .L 00 Z o 0000 in LL, 00 O Al l6D . c 0-0 0 &1 z i E l Z I WIMP - C.� (v of -j W E a_ I- 0) .I W (3 - z C" Z . No 6-C N ZCULU 0to 0 2)U?I.Ca 0 L� ZW U} _jLvrn clime F W V J cn z -- o) r 04 W 0 `R -620 3) 0 0 1 QW-'Q 80EIGa wU 2U) o 'w'� E � of C4 = Q H ~ W W - w L1 c.S -� dN- -i- o a „o o z w '~ -� O z 3 V) LL- U-1 CV U DRAWN BY: DATE: J.T. 9 -23 -13 SCALE: REVISED BY: AS NOTED J.T. PROJECT NUMBER: 20130923 -2 PAGE TITLE: GENERATOR, SUBBASE DIESEL FUEL TANK INFORMATION & NOTES. C6 0 LL yI 00 Z CD � co 00 w � Q, W W W r r. z b IrIIII 111 p z t1 P = U o! w Q PAGE NUMBER: E -2OF2