12-508-026System No. C -AJ -1226
F Rating — 3 Hr
T Rating — 0 Hr
L Rating At Ambient — Less Than 1 CFM /Sq Ft
L Rating At 400 F — 4 CFWSq Ft
A
SECTION A -A
1. Floor or Wall Assembly — Min 4 -1/2 in. thick reinforced lightweight or normal weight (100 -150 pcf) concrete.
Wall may also be constructed of any UL Classified Concrete Blocks *. Max diam of opening is 32 in.
2. Metallic Sleeve — (Optional) Nom 32 in. diam (or smaller) Schedule 40 (or heavier) steel sleeve cast or
grouted into floor or wall assembly, flush with floor or wall surfaces or extending a max of 3 in. above floor or
beyond both surfaces of wall.
2A. Sheet Metal Sleeve — (Optional) Max 6 in. diam, min 26 ga galy steel provided with a 26 ga galy steel
square flange spot welded to the sleeve at approx mid - height, or flush with bottom of sleeve in floors, and sized
to be a min of 2 in. larger than the sleeve diam. The sleeve is to be cast in place and may extend a max of 4 in.
below the bottom of the deck and a max of 1 in. above the top surface of the concrete floor.
2B. Sheet Metal Sleeve — (Optional) - Max 12 in. diam, min 24 ga galy steel provided with a 24 ga galy steel
square flange spot welded to the sleeve at approx mid - height, or flush with bottom of sleeve in floors, and sized
to be a min of 2 in. larger than the sleeve diam. The sleeve is to be cast in place and may extend a max of 4 in.
below the bottom of the deck and a max of 1 in. above the top surface of the concrete floor.
3. Through - Penetrant — One metallic pipe, tube or conduit to be installed either concentrically or eccentrically
within the firestop system. The annular space between penetrant and periphery of opening shall be min 0 in.
(point contact) to max 1 -7/8 in. Penetrant may be installed with continuous point contact. Penetrant to be rigidly
supported on both sides of floor or wall assembly. The following types and sizes of metallic penetrants may be
used:
A. Steel Pipe — Nom 30 in. diam (or smaller) Schedule 10 (or heavier) steel pipe.
B. Iron Pipe — Nam 30 in. diam (or smaller) cast or ductile iron pipe.
C. Copper Pipe — Nom 6 in. diam (or smaller) Regular (or heavier) copper pipe.
D. Copper Tubing — Nam 6 in. diam (or smaller) Type L (or heavier) copper tubing.
E. Conduit — Nom 6 in. diam (or smaller) steel conduit.
F. Conduit — Nom 4 in. diam (or smaller) steel electrical metallic tubing (EMT).
4. Firestop System — The firestop system shall consist of the following:
A. Packing Material — Min 4 in. thickness of min 4 pcf mineral wool batt insulation firmly packed into opening
as a permanent form. Packing material to be recessed from top surface of floor or sleeve or from both
surfaces of wall or sleeve as required to accommodate the required thickness of fill material.
B. Fill, Void or Cavity Material* — Sealant — Min 1/4 in. thickness of fill material applied within the annulus,
flush with top surface of floor or sleeve or with both surfaces of wall or sleeve. At the point or continuous
contact locations between penetrant and concrete or sleeve, a min 1/4 in. diam bead of fill material shall be
applied at the concrete or sleeve/ pipe penetrant interface on the top surface of floor and on both surfaces of
wall.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — FS-One Sealant
*Bearing the UL Classification Mark
Sl
Reproduced by HILTI, Inc. Courtesy of Fj��
Underwriters Laboratories, Inc. u
FIRESTOP SYSTEMS June 27, 2007 G O L Us
TWO INDUSTRIAL CONTROL RELAYS, ONE
N.O. AND ONE N.0 CONTACTOR. EACH IN
NEMA I ENCLOSURE. WESTINGHOUSE
TYPE 'BF' OR EQUAL, PROVIDED BY
CONTRACTOR.
TYPICAL EMERGENCY LIGHTING SWITCHING SCHEME DETAIL
SCALE: N.T.S.
SEQUENCE OF • - •Nl
1. UNDER NORMAL CONDITIONS EMERGENCY AND NORMAL LIGHTS SHALL OPERATE ON / OFF
AS A SINGLE SEQUENCE.
2. UNDER A POWER OUTAGE MODE, EMERGENCY FIXTURES ARE TO COME ON -LINE
AUTOMATICALLY REGARDLESS OR EIGHT SWITCH POSITION.
System No. W -L -1054
F Ratings -1 and 2 Hr (See Items 1 and 3)
T Rating - 0 Hr
L Rating At Ambient - Less Than 1 CFM /Sq Ft
L Rating At 400 F - 4 CFM /Sq Ft
SECTION A —A
1. Wall Assembly – The 1 or 2 hr fire -rated gypsum wallboard /stud wall assembly shall be constructed of
the materials and in the manner specified in the individual 0300 or 0400 Series Wall and Partition Designs
in the UL Fire Resistance Directory.
2. Through - Penetrants – One metallic pipe, conduit or tubing to be installed either concentrically or
eccentrically within the firestop system. The annular space shall be min 0 in, to max 2 -1/4 in. Pipe may
be installed with continuous point contact. Pipe, conduit or tubing may be installed at an angle not greater
than 45 degrees from perpendicular. Pipe, conduit or tubing to be rigidly supported on both sides of wall
assembly. The following types and sizes of metallic pipes, conduits or tubing may be used:
A. Steel Pipe -- Nom 30 in diam (or smaller) Schedule 10 (or heavier) steel pipe.
B. Iron Pipe – Nom 30 in. diam (or smaller) cast or ductile iron pipe.
C. Conduit – Nom 4 in diam (or smaller) steel electrical metallic tubing or 6 in. diam steel conduit,
D. Copper Tubing – Nom 6 in. diam (or smaller) Type L (or heavier) copper tubing.
E. Copper Pipe – Nom 6 in. diam (or smaller) regular (or heavier) copper pipe.
3. Fill, Void or Cavity Material* – Sealant – Min 5/8 in, thickness of fill material applied within the
annulus, flush with both surfaces of wall. At the point or continuous contact locations between pipe and
wall, a min 1/2 in. diam bead of fill material shall be applied at the pipe wall interface on both surfaces
of wall.
HILT[ CONSTRUCTION CHEMICALS, DIV OF
HILTI INC – FS -One Sealant
*Bearing the UL Classification Mark
UL
Reproduced HILTI, Inc. Courtesy of
Underwriters Laboratories, Inc.
FlRESTOP SYSTEMS December 4, 2002 C US
STUB UP AS
NOTED (TYP)
STAINLESS STEEL WALL PLATE, SINGLE
GANG, SINGLE JACK, WITH LUGS-FGR r ry
WALL PHONE MOUNTING. PROVIDE WITH
6W STAINLESS STEEL WALL PHONE'
PLATE, MOLEX WNC- 00029. TERMINATE
PAIRSS 1 AND 2 USOC STYLE ON PINS 2,
3, 4 AND 5 AND LEAVE PAIRS 3 AND 4
UNTERMINATED WITH SLACK STORED IN
BOX. TERMINATE ALL PAIRS ON 66
BLOCK IN CER - SEE VOICE SINGLE LINE
DIAGRAM.
WALL PHONE OUTLET - TYPICAL DETAIL
SCALE: N.T.S.
n
I
•a
CO KEY NOTES:
A TWO PORT ANGLED FACEPLATE.
LASER PRINTED LABEL INDICATING
OUTLET IDENTIFIER
G LASER PRINTED LABEL
D SNAP -IN BLACK TAB
ADHESIVE LAVEL (BROTHER P- TOUCH),
MOUNT TO INSIDE OF FACEPLATE.
TOP PLATE1 "°" OF WALL
COMMUNICATION OUTLET CO
I� CEILING GRID
RAIL (TYP.)
—
II 1� I F
CEILING TILE (TYP.) II
FLUSH MOUNT
COMMUNICATIONS
OUTLET TYPICAL.
0
CO.IOI.A
CO.IOI.A I
00
00
N
CO KEY NOTES:
V FOUR PORT ANGLED FACEPLATE.
LASER PRINTED LABEL INDICATING
OUTLET IDENTIFIER
�C LASER PRINTED LABEL
SNAP -IN BLACK TAB
E ADHESIVE LAVEL (BROTHER P- TOUCH),
MOUNT TO INSIDE OF FACEPLATE.
OF 3/4" CONDUIT UP CEILING SPACE OR
ABOVE CEILING AREA.
FOUR (4) CABLES UP TO CORRESPONDING
VOICE / DATA PATCH PANEL IN NEW
TELECOM ROOM.
COMMUNICATION OUTLET (CO)
SCALE: N.T.S.
4
ARCHITECT:
BERMELLO AJAMIL & PARTNERS, INC.
Architecture Engineering Planning
Interior Design Landscape Architecture
2601 South Bayshore Drive 10th Floor
Miami, Florida 33133
(305) 859 -2050 Fax (305) 860 -3700
Lll2d
LOUIS J. AGUIRRE & ASSOCIATES. P.A.
Consulting Engineers
9150 South Dadeland Blvd. ® Suite 900
Miami « Florida 33156 • EB0000924
Telephone 305.670.0141
Facsimile 305.670,0144
www.11oo aR com
Project No.: 22007
PERMIT SET
4/13/2012
REVISIONS:
PROJECT NAME:
SMH- HYPERBARIC CHAMBER
PROJECT ADDRESS:
7400 S.W. 62nd Ave.
South Miami, Florida 33143
KEY PLAN
COMM. NO.
40068
SCALE:
AS SHOWN
DATE:
04/13/2011
DRAWN:
AP
CHECKED:
CADD FILE:
v/220074,1EP
DRAWING TITLE:
DETAILS ELECTRICAL
SHEET NO. I
ETI
a�