12-508-019ABBREVIATIONS /SUFFIXES
ELECTRICAL SYMBOL LEGEND
NOTE:
1. SYMBOLS IN DASHED LINE MEAN EXISTING.
2. ALL SYMBOLS MAY NOT BE USED.
A.F.F. ABOVE FINISHED FLOOR
A.F.G. ABOVE FINISHED GRADE
BD. BOARD
C. CONDUIT
CAB. CABINET
C.B. CIRCUIT BREAKER
CKT. CIRCUIT
E.A. EMPTY CONDUIT
E.W.C. ELECTRIC WATER COOLER
E EXISTING TO REMAIN
ER EXISTING RELOCATED
EMT ELECTRICAL METALLIC TUBING
F.A. FIRE ALARM
G.F.I. GROUND FAULT INTERRUPTER
GND. GROUND
HID HIGH INTENSIVE DISCHARGE
HPS HIGH PRESSURE SODIUM
I.G. ISOLATED GROUND
LT. LIGHT
LTG. LIGHTING
MCB MAIN CIRCUIT BREAKER
MLO MAIN LUGS ONLY
MT. MOUNT
MTG. HT. MOUNTING HEIGHT
N.E.C. NATIONAL ELECTRICAL CODE
N.I.G. NOT IN CONTRACT
NL NIGHT LIGHT
P.A. PUBLIC ADDRESS
PNL. PANEL
RECEPT. RECEPTACLE
S.D.B.C. SOFT DRAWN BARE COPPER
SW. SWITCH
U.O.N. UNLESS OTHERWISE NOTED
V.P. VAPOR PROOF
W.P. WEATHER PROOF (NEMA 3R ENCLOSURE)
X.P. EXPLOSION PROOF (CLASS TO MEET N.E.C.)
TVSS TRANSIENT VOLTAGE SURGE SUPPRESSION PANEL
CCTV CLOSED CIRCUIT TELEVISION
WAP WIRELESS ACCESS POINT
PTZ PAN - TILT -ZOOM CAMERA
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
LFMC LIQUID TIGHT FLEXIBLE METAL CONDUIT
NEMA NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION.
RMC RIGID METAL CONDUIT
AWG AMERICAN WIRE GAUGE
CO -THW COPPER WIRE WITH THERMOPLASTIC, HEAT RESISTANT,
MOISTURE RESISTANT CHARACTERISTICS
VOC VOLATILE ORGANIC COMPOUND
LIGHTING FIXTURES
FIRE ALARM DEVICES
FIRE ALARM PULL STATION (48" A.F.F.) SEMI FLUSH MOUNTED,
PROVIDE BREAKABLE GLASS COVER.
FIRE ALARM HORN WITH STROBE LIGHT (80 "A.F.F.) ADA
FIRE ALARM SPEAKER WITH STROBE LIGHT (80 "A.F.F.) ADA
FIRE ALARM MASS NOTIFICATION SPEAKER. CEILING MOUNTED
lef FIRE ALARM STROBE LIGHT - 75 CANDELA MIN. - (80 " A.F.F.) OR 6" BELOW
CEILING WHISHEVER IS LOWER, INSTALLATION SHALL COMPLY WITH A.D.A.,
t� 24V SMOKE DETECTOR (PHOTOELECTRIC TYPE).
`✓H SMOKE AND HEAT DETECTOR
a 24V FIXED TEMPERTURE 135° F THERMAL DETECTOR.
® 24V PHOTOELECTRIC DUCT DETECTOR.
FD DOOR HOLDER
FS FLOW SWITCH
TS TAMPER SWITCH
FACP FIRE ALARM CONTROL PANEL
POWER EQUIPMENT
EM HIGH VOLTAGE DISTRUBUTION PANELBOARD 277/480V
LOW VOLTAGE DISTRUBUTION PANELBOARD 120/208V
HIGH VOLTAGE PANELBOARD 277/48OV.
LOW VOLTAGE PANELBOARD 120/208V.
LC] HD FUSIBLE DISCONNECT OR CIRCUIT BREAKER. NEMA 3R WHEN OUTDOORS.
3 0 3 =NO.OF POLES, 60= SWITCH SIZE, 50 =FUSE, NF= NON - FUSED,
* =FUSE SIZE AS REQUIRED BY LOAD.
® MOTOR STARTER W /CONTROL XMFR, HOA SELECTOR SW. AND RED PILOT
LIGHT. NEMA SIZE BY MOTOR. PROVIDE NEMA 4 ENCLOSURE WHEN
OUTDOORS
t� COMBINATION MOTOR STARTER WITH DISCONNECT SWITCH OR CB. SAME
ENCLOSURE AND ACCESSORIES AS INDICATED ABOVE
® CONTACTOR. SAME ENCLOSURE AND ACCESSORIES AS STARTERS
FAN
.� MOTOR "2" WHEN SHOWN INDICATES HORSEPOWER
E TRANSFORMER
POWER DEVICES
04 DUPLEX RECEPT - 20 AMP NEMA 5 -20R (18" A.F.F.)
�i SINGLE RECEPT - 20 AMP NEMA 5 -20R (18" A.F.F.)
DUPLEX RECEPT. MOUNTED ABOVE COUNTER - 20 AMP NEMA 5 -20R
(44" A.F.F.) U.O.N.
(3)4 QUAD - PLEX RECEPT - 20 AMP NEMA 5 -20R (18" A.F.F.)
® DUPLEX RECEPT FLUSH FLOOR MOUNTED - 20 AMP NEMA 5 -20R
SPECIAL PURPOSE RECEPT (18" A.F.F.)
A, B, C A - 250V, 30A, 4W
B - 25OV, 50A, 4W.
C - 25OV, 50A, 5W.
Q JUNCTION BOX
{ WALL MOUNTED JUNCTION BOX
■� FLOOR MOUNTED JUNCTION BOX UNDER RAISED FLOOR FOR CONNECTION
J TO WIREMOLD PLUG STRIP MOUNTED AT RACKS AND FURNITURE BY A
HARDWIRE FLEXIBLE CONNECTION BY ELECTRICAL CONTRACTOR.
PB PULL BOX
S SINGLE POLE SWITCH - 20 AMP (48" A.F.F.)
S3 THREE WAY SWITCH - 20 AMP (48" A.F.F.)
S4 FOUR WAY SWITCH - 20 AMP (48" A.F.F.)
SD DIMMER SWITCH 2000 WATTS 48" A.F.F.)
SF FAN SPEED CONTROL (48" A.F.F.)
SK KEY OPERATED SWITCH - 20 AMP (48" A.F.F.)
SP SINGLE POLE SWITCH WITH PILOT LIGHT - 20 AMP(48" A.F.F.)
Sm MOTOR RATED SWITCH (ONE, TWO OR THREE POLE AS REQUIRED)
ST TIME CONTROL SWITCH
SOS OCCUPANCY SENSOR SINGLE POLE SWITCH - 20 AMP. (42" AFF).
® LTG. TRANSFER RELAY.
DATA, COMMUNICATIONS AND SECURITY
V TELEPHONE & DATA OUTLET (4 "x 4 "x 2 1/2" OUTLET BOX) (18" A.F.F.)
® TELEPHONE & DATA OUTLET FLUSH FLOOR MOUNTED
0 TELEPHONE OUTLET (4 "x 4"x 2 1/2" OUTLET BOX)(18" A.F.F.)
® TELEPHONE OUTLET FLUSH FLOOR MOUNTED
V, PUBLIC TELEPHONE (48" A.F.F.)
Vw WALL MOUNTED TELEPHONE OUTLET (60 "A.F.F.)
Q CLOCK (8' -0" AFF)
® TERMINAL CABINET - TYPE INDICATED
® TELEPHONE TERMINAL BACK BOARD
a CLOSE CIRCUIT TV MONITORS
Q RADIO REMOTE
PAGER SPEAKER
Czz CCTV CAMERA
is W INTERCOM STATION (WALL MTD) -3GANG BOX @ 4' -0"
iC D INTERCOM (DOOR STATION) SAME AS WALL MTD
!C INTERCOM @ 4' -0" A.F.F.
F0 CAN STATIONS @ 2'-6" A.F.F. (U.N.O.)
WALL MOUNTED TV OUTLET.
DOOR BELL PUSH BUTTON
6BB DOOR BELL CHIME
K® SECURITY SYSTEM KEYPAD
R SECURITY SYSTEM CARD READER
® SECURITY SYSTEM MOTION DETECTOR
7 SECURITY SYSTEM DOOR STRIKE
SECURITY SYSTEM DOOR CONTACT
PS POWER SUPPLY
NURSE CALL
LIGHTING FIXTURE IDENTIFICATION. SEE SCHEDULE
Q
HID OR FLUORESCENT DOWN LIGHT
Q
ACCENT TYPE LIGHT FIXTURE
(�
HID OR FLUORESCENT WALL MOUNTED LIGHT FIXTURE
Q,
RECESSED / LAY -IN MOUNTED FLUORESCENT LIGHT FIXTURE
®
SURFACE OR PENDANT MOUNTED FLUORESCENT LIGHT FIXTURE
WALL MOUNTED FLUORESCENT LIGHT FIXTURE
1---)
SURFACE OR PENDANT MOUNTED FLUORESCENT STRIP
HID DOWN LIGHT ON NIGHT LIGHT CIRCUIT & EQUIPPED WITH RESTRIKE SYSTEM
HID WALL MOUNTED LIGHT FIXTURE ON NIGHT LIGHT CIRCUIT
RECESSED /FLUORESCENT LIGHT FIXTURE ON EMERGENCY CIRCUIT OR
EMERGENCY BATTERY PACT.
®
SURFACE MOUNTED FLUORESCENT LIGHT FIXTURE ON LIGHT CIRCUIT OR
EMERGENCY BATTERY PACT
e
EXIT LIGHT
WALL MOUNTED EXIT LIGHT SHADED QUADRANT INDICATES NUMBER OF FACES.
--
ARROWS AS SHOWN OR REQUIRED.
UNIT EQUIPMENT BATTERY BACKUP EMERGENCY LIGHT
COMBINATION EXIT / EMERGENCY LIGHT WITH BATTERY BACKUP.
LANDSCAPE LIGHT FIXTURE
O-E]
POLE MOUNTED SINGLE SITE LIGHTING FIXTURE
0<>O
POLE MOUNTED DOUBLE SITE LIGHTING FIXTURE
CEILING MOUNTED OCCUPANCY SENSOR. INCLUDE POWER PACK AS REQUIRED.
PP
OCCUPANCY SENSOR POWER PACK.
WIRING
BRANCH CIRCUIT OR FEEDER WIRING IN CONDUIT. NO TICKS INDICATES 2 # 12
CONDUCTORS & 1 # 12 GROUND IN 3/4" CONDUIT. TICK MARKS WHEN SHOWN,
INDICATES NUMBER OF # 12 CONDUCTORS IF OTHER THAN THREE, (j) INDICATES
GROUND. CONDUIT LARGER THAN 3/4" & CONDUCTOR LARGER THAN # 12 SHALL BE
AS INDICATED.
HOME RUN TO PANEL "A" = PANEL DESIGNATION, 1,3,5 = CIRCUIT NUMBERS.
U.O.N. MINIMUM SIZE OF 3/4 "C AND MAXIMUM OF THREE CIRCUITS PER
A-135
HOMERUN. (DEDICATED NEUTRAL FOR EACH HOT WIRES MUST BE PROVIDED)
FLEXIBLE CONDUIT
CONDUIT RUN CONCEALED IN CEILING OR WALLS
-
CONDUIT RUN UNDERGROUND OR IN SLAB
- - - -
CONDUIT RUN EXPOSED
C
CAPPED CONDUIT
- I- -#--1-
SYSTEM AND /OR EQUIPMENT GROUNDING CONDUCTOR
1I�--
GROUNDING ELECTRODE & CONDUCTOR SYSTEM
^S
CONDUIT SEAL
FIRE ALARM DEVICES
FIRE ALARM PULL STATION (48" A.F.F.) SEMI FLUSH MOUNTED,
PROVIDE BREAKABLE GLASS COVER.
FIRE ALARM HORN WITH STROBE LIGHT (80 "A.F.F.) ADA
FIRE ALARM SPEAKER WITH STROBE LIGHT (80 "A.F.F.) ADA
FIRE ALARM MASS NOTIFICATION SPEAKER. CEILING MOUNTED
lef FIRE ALARM STROBE LIGHT - 75 CANDELA MIN. - (80 " A.F.F.) OR 6" BELOW
CEILING WHISHEVER IS LOWER, INSTALLATION SHALL COMPLY WITH A.D.A.,
t� 24V SMOKE DETECTOR (PHOTOELECTRIC TYPE).
`✓H SMOKE AND HEAT DETECTOR
a 24V FIXED TEMPERTURE 135° F THERMAL DETECTOR.
® 24V PHOTOELECTRIC DUCT DETECTOR.
FD DOOR HOLDER
FS FLOW SWITCH
TS TAMPER SWITCH
FACP FIRE ALARM CONTROL PANEL
POWER EQUIPMENT
EM HIGH VOLTAGE DISTRUBUTION PANELBOARD 277/480V
LOW VOLTAGE DISTRUBUTION PANELBOARD 120/208V
HIGH VOLTAGE PANELBOARD 277/48OV.
LOW VOLTAGE PANELBOARD 120/208V.
LC] HD FUSIBLE DISCONNECT OR CIRCUIT BREAKER. NEMA 3R WHEN OUTDOORS.
3 0 3 =NO.OF POLES, 60= SWITCH SIZE, 50 =FUSE, NF= NON - FUSED,
* =FUSE SIZE AS REQUIRED BY LOAD.
® MOTOR STARTER W /CONTROL XMFR, HOA SELECTOR SW. AND RED PILOT
LIGHT. NEMA SIZE BY MOTOR. PROVIDE NEMA 4 ENCLOSURE WHEN
OUTDOORS
t� COMBINATION MOTOR STARTER WITH DISCONNECT SWITCH OR CB. SAME
ENCLOSURE AND ACCESSORIES AS INDICATED ABOVE
® CONTACTOR. SAME ENCLOSURE AND ACCESSORIES AS STARTERS
FAN
.� MOTOR "2" WHEN SHOWN INDICATES HORSEPOWER
E TRANSFORMER
POWER DEVICES
04 DUPLEX RECEPT - 20 AMP NEMA 5 -20R (18" A.F.F.)
�i SINGLE RECEPT - 20 AMP NEMA 5 -20R (18" A.F.F.)
DUPLEX RECEPT. MOUNTED ABOVE COUNTER - 20 AMP NEMA 5 -20R
(44" A.F.F.) U.O.N.
(3)4 QUAD - PLEX RECEPT - 20 AMP NEMA 5 -20R (18" A.F.F.)
® DUPLEX RECEPT FLUSH FLOOR MOUNTED - 20 AMP NEMA 5 -20R
SPECIAL PURPOSE RECEPT (18" A.F.F.)
A, B, C A - 250V, 30A, 4W
B - 25OV, 50A, 4W.
C - 25OV, 50A, 5W.
Q JUNCTION BOX
{ WALL MOUNTED JUNCTION BOX
■� FLOOR MOUNTED JUNCTION BOX UNDER RAISED FLOOR FOR CONNECTION
J TO WIREMOLD PLUG STRIP MOUNTED AT RACKS AND FURNITURE BY A
HARDWIRE FLEXIBLE CONNECTION BY ELECTRICAL CONTRACTOR.
PB PULL BOX
S SINGLE POLE SWITCH - 20 AMP (48" A.F.F.)
S3 THREE WAY SWITCH - 20 AMP (48" A.F.F.)
S4 FOUR WAY SWITCH - 20 AMP (48" A.F.F.)
SD DIMMER SWITCH 2000 WATTS 48" A.F.F.)
SF FAN SPEED CONTROL (48" A.F.F.)
SK KEY OPERATED SWITCH - 20 AMP (48" A.F.F.)
SP SINGLE POLE SWITCH WITH PILOT LIGHT - 20 AMP(48" A.F.F.)
Sm MOTOR RATED SWITCH (ONE, TWO OR THREE POLE AS REQUIRED)
ST TIME CONTROL SWITCH
SOS OCCUPANCY SENSOR SINGLE POLE SWITCH - 20 AMP. (42" AFF).
® LTG. TRANSFER RELAY.
DATA, COMMUNICATIONS AND SECURITY
V TELEPHONE & DATA OUTLET (4 "x 4 "x 2 1/2" OUTLET BOX) (18" A.F.F.)
® TELEPHONE & DATA OUTLET FLUSH FLOOR MOUNTED
0 TELEPHONE OUTLET (4 "x 4"x 2 1/2" OUTLET BOX)(18" A.F.F.)
® TELEPHONE OUTLET FLUSH FLOOR MOUNTED
V, PUBLIC TELEPHONE (48" A.F.F.)
Vw WALL MOUNTED TELEPHONE OUTLET (60 "A.F.F.)
Q CLOCK (8' -0" AFF)
® TERMINAL CABINET - TYPE INDICATED
® TELEPHONE TERMINAL BACK BOARD
a CLOSE CIRCUIT TV MONITORS
Q RADIO REMOTE
PAGER SPEAKER
Czz CCTV CAMERA
is W INTERCOM STATION (WALL MTD) -3GANG BOX @ 4' -0"
iC D INTERCOM (DOOR STATION) SAME AS WALL MTD
!C INTERCOM @ 4' -0" A.F.F.
F0 CAN STATIONS @ 2'-6" A.F.F. (U.N.O.)
WALL MOUNTED TV OUTLET.
DOOR BELL PUSH BUTTON
6BB DOOR BELL CHIME
K® SECURITY SYSTEM KEYPAD
R SECURITY SYSTEM CARD READER
® SECURITY SYSTEM MOTION DETECTOR
7 SECURITY SYSTEM DOOR STRIKE
SECURITY SYSTEM DOOR CONTACT
PS POWER SUPPLY
NURSE CALL
�s
NURSE CALL STAFF STATION 48" AFF
T
NURSE CALL TOILET EMERGENCY STATION 48" AFF
NURSE CALL DOME LIGHT, CEILING MOUNTED
FN CMS
NURSE CALL MASTER STATION
=EPO
EMERGENCY OFF BUTTON 48 "A.F.F.
GENERAL NOTES:
1. SITE INVESTIGATION: PRIOR TO BIDDING THE CONTRACTOR SHALL VISIT THE JOBSITE AND
BECOME ACQUAINTED WITH ALL OF THE EXISTING CONDITIONS WHICH WILL AFFECT HIS WORK.
FAILURE TO DO SO WILL NOT BE ACCEPTED AS A REASON FOR REQUESTING EXTRA PAY WHERE
THE EXISTING CONDITION RESULTS IN EXTRA MATERIAL OR LABOR. THE CONTRACTOR SHALL
SUBMIT IN HIS BID AN AMOUNT THAT WOULD BE SET ASIDE FOR UNIDENTIFIED ITEMS.
2. ALL WORK SHALL BE PERFORMED BY A LICENSED ELECTRICAL CONTRACTOR IN A FIRST CLASS
MANNER AND SHALL BE A COMPLETED AND FULLY OPERATIVE TO THE ACCEPTANCE OF THE
OWNER, GENERAL CONTRACTOR AND ENGINEER.
3. THE CONTRACTOR SHALL FURNISH ALL LABOR, MATERIALS AND EQUIPMENT NECESSARY FOR
THE COMPLETE INSTALLATION OF THE ELECTRICAL SYSTEMS, ALL IN ACCORDANCE WITH
THESE CONSTRUCTION DOCUMENTS. ALL WORK PERFORMED UNDER THIS CONTRACT SHALL
COMPLY WITH THE FLORIDA BUILDING CODE 2010 AND NFPA CODES INCLUDING, BUT NOT
LIMITED TO NFPA 70 - (2008 NEC), NFPA 72 - 2007 (FIRE ALARM) AND NFPA 101 -2009 - LIFE
SAFETY CODE, NFPA 99 - 2005.
4. THIS CONTRACTOR SHALL PAY FOR ALL FEES, INSPECTIONS, TESTS, FINES, ETC., AS REQUIRED.
5. MINIMUM STANDARDS: THE MATERIAL, EQUIPMENT, INSTALLATIONS, AND WORKMANSHIP
FURNISHED UNDER THIS SECTION SHALL CONFORM AT LEAST TO THE REQUIREMENTS OF THE
REGULATING AGENCIES AS LISTED IN ITEM (3) ABOVE.
6. RESPONSIBILITIES: CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING A COMPLETE
INSTALLATION OF THE RACEWAY SYSTEM, EQUIPMENT AND WIRING IN ACCORDANCE WITH THE
CONTRACT DOCUMENTS.
7. GUARANTEE: THE CONTRACTOR /SUB - CONTRACTOR SHALL FURNISH A WRITTEN GUARANTEE
THAT ALL WORK EXECUTED UNDER THIS CONTRACT SHALL BE FREE FROM DEFECTS OF
WORKMANSHIP AND MATERIALS FOR A PERIOD OF ONE YEAR FROM THE DATE OF FINAL
ACCEPTANCE AND THAT HE, AT HIS OWN EXPENSE, WILL REPAIR OR REPLACE ALL WORK
WHICH BECOMES DEFECTIVE DURING THE TIME OF THE GUARANTEE.
8. ALL EQUIPMENT, SYSTEMS AND SYSTEM COMPONENTS SHALL BE FROM THE SAME
MANUFACTURER AND SHALL BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURERS
RECOMMENDATIONS AND SPECIFICATIONS.
9. VERIFY ALL DIMENSIONS WITH ARCHITECTURAL PLANS PRIOR TO ANY FABRICATIONS OR
INSTALLATION.
10. OBTAIN FULL INFORMATION REGARDING PECULIARITIES AND LIMITATIONS OF SPACE AVAILABLE
FOR INSTALLATION OF THE EQUIPMENT AND MATERIALS UNDER CONTRACT, AND PROVIDE
READY ACCESSIBILITY TO ELECTRICAL EQUIPMENT, INCLUDING ANY PART OF SYSTEM
REQUIRED TO BE REACHED FOR MAINTENANCE AND OPERATIONS.
11. PROVIDE ACCURATE LAYOUT, GRADES AND ELEVATIONS. TAKE PROPER PRECAUTIONS TO
PROTECT WORK AND EQUIPMENT FROM DAMAGE.
12. PROVIDE CODE APPROVED FIRE STOPPING AT ALL CONDUIT PENETRATIONS THROUGHOUT
BUILDING CONSTRUCTION TO MAINTAIN FIRE, SMOKE AND SOUND RATING. FIRE SEAL ALL
PENETRATIONS. SEAL TELECOMMUNICATION SLEEVES AFTER CABLES HAVE BEEN INSTALLED.
13. RACEWAYS AND FITTINGS: CONDUIT RUNS SHALL BE CONCEALED IN CEILING SPACES AND
WALL PARTITIONS. NO CONDUIT SHALL BE EXPOSED IN INTERIOR SPACES EXCEPT FLEXIBLE
CONNECTION TO WIRE MOLDS. CONCEALED CONDUITS ARE TO BE EMT. SURFACE MOUNTED
RACEWAYS (WIRE MOLD) ARE TO BE INSTALLED IN SOLID WALLS ONLY. THE MINIMUM CONDUIT
SIZE IS TO BE 1/2 ". ALL CONDUITS AND RACEWAYS SHALL BE METAL.
14. THIS CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATION WITH OTHERS AS WELL AS
PROVIDING TEMPORARY POWER.
15. VERIFY EQUIPMENT SIZES, VOLTAGE AND CURRENT CHARACTERISTICS, ETC., BEFORE THE
ORDERING OF ANY EQUIPMENT AND PRIOR TO ROUGHING -IN FOR EQUIPMENT TO BE SUPPLIED
TO OTHERS. NOTIFY ENGINEER OF ANY CONFLICT.
16. PROVIDE COMPLETE POWER CIRCUIT WIRING AND CONNECTIONS FOR EACH AND EVERY ITEM
OF PERMANENT MECHANICAL EQUIPMENT. PRIOR TO ANY ROUGH -IN, COORDINATE WITH HVAC
AND PLUMBING EQUIPMENT NAME PLATE TO OBTAIN CORRECT WIRE SIZE AND OVERCURRENT
PROTECTION RATING. IF THE NAME PLATE LABEL REQUIRES THE OVERCURRENT PROTECTION
DEVICE TO BE FUSES, PROVIDE A FUSED SWITCH WITH PROPER SIZE FUSES AT THE
EQUIPMENT LOCATION.
17. CONDUCTOR: ALL CONDUCTOR WIRE AND CABLE SHALL CONSIST OF 98% CONDUCTIVITY
COPPER. ALL CABLES SHALL BE SINGLE CONDUCTOR, 600 VOLT, THERMOPLASTIC INSULATION,
SUITABLE FOR CONTINUOUS OPERATION AT 75 DEGREES C. CONDUCTOR TEMPERATURE IN
BOTH WET AND DRY LOCATIONS. THESE CABLES SHALL BE N.E.C. INSULATION CLASSIFICATION
TYPE THWNITHHN. MINIMUM SIZE SHALL BE #12. ALL CONDUCTOR INSULATION SHALL BE
COLOR CODED MAINTAINING THE INTEGRITY OF THE EXISTING INSTALLATION. COLORED
INSULATION SHALL BE USED FOR AWG SIZES #10 AND SMALLER AND APPROVED COLOR TAPES
SHALL BE USED FOR AWG SIZES #8 AND LARGER. ALL POWER AND CONTROL CIRCUITS SHALL
CARRY EQUIPMENT GROUNDING CONDUCTOR SIZED PER NEC 250 -122.
18. THE NATURE OF THIS TYPE OF CONSTRUCTION POSES SPECIAL PROBLEMS FOR THE DESIGN
ENGINEER AS WELL AS THE CONTRACTOR, EVERY EFFORT HAS BEEN MADE BY THE ENGINEER
TO SHOW AND VERIFY WHERE POSSIBLE THE LOCATION OF THE EXISTING ELECTRICAL SYSTEM.
THE MAJOR PORTION OF THE ELECTRICAL SYSTEMS ARE AS SHOWN ON THE DRAWINGS.
HOWEVER, MINOR DEVIATIONS MAY BECOME EVIDENT AS THE JOB PROGRESSES. NO
ADVANTAGE IS TO BE TAKEN BY THE CONTRACTOR BECAUSE OF THESE MINOR DIFFERENCES.
19. CORRECTION OF ANY DEFECTS, REPAIRS OR DAMAGE DURING CONSTRUCTION AS WELL AS
ANY MINOR CHANGES IN OUTLET LOCATIONS SHALL BE MADE WITHOUT ADDITIONAL COST.
20. GUTTERS, PULL BOXES, ETC., SHALL BE GALVANIZED STEEL SIZED PER NATIONAL ELECTRICAL
CODE, ARTICLE 312, MADE OF MATERIAL SUITABLE FOR THE ENVIRONMENTAL CONDITIONS
PRESENT.
21. ALL FLOORS, WALLS AND ROOF PENETRATIONS SHALL BE PROPERLY SEALED -OFF. IF FIRE
RATED, AN APPROVED FIRE RETARDANT SEAL SHALL BE USED.
22. ALL WRING SHALL BE IN RACEWAY.
A. INDOORS - USE THE FOLLOWING WIRE METHODS:
• EXPOSED: EMT
• CONCEALED: EMT
• CONNECTION TO VIBRATION EQUIPMENT (INCLUDING TRANSFORMERS AND HYDRAULIC,
PNEUMATIC, ELECTRIC SOLENOID, OR MOTOR - DRIVEN EQUIPMENT): FMC, EXCEPT IN
WET OR DAMP LOCATIONS USE LFMC.
• DAMP OR WET LOCATIONS: RIGID STEEL CONDUIT.
• BOXES AND ENCLOSURES: NEMA 250, TYPE I, EXCEPT AS FOLLOWS:
DEMOLITION NOTES:
1. ALL WORK HEREIN DESCRIBED AND SHOWN ON DRAWINGS AND REQUIRED TO MAKE
PROJECT COMPLETE IN EVERY ASPECT, PLUS ANY AND ALL PATCHING NECESSARY
SHALL BE DONE TO THE COMPLETE SATISFACTION OF THE ARCHITECT I ENGINEER AND /
OR OWNER AND SHALL BE ACCOMPLISHED IN STRICT ACCORDANCE WITH THE DRAWINGS
AND SPECIFICATIONS. ALL MATERIALS SHALL MATCH EXISTING WHERE APPLICABLE AND
ALL CONSTRUCTION AND ALTERATION LEFT IN NEW CONDITION.
2. ALL ITEMS TO BE REMOVED SHALL BE REMOVED WITH UTMOST CARE AND WITHOUT
DAMAGE, AND THOSE ITEMS NOT DESIGNATED TO BE REUSED SHALL BE DELIVERED TO
THE OWNER OR DISPOSED OF AS PER HIS WRITTEN INSTRUCTIONS.
3. ALL ALTERATIONS, DEMOLITION AND REMOVAL, CUTTING AND PATCHING AND OTHER
WORK NECESSARY FOR CONSTRUCTION OF THIS CONTRACT SHALL BE PERFORMED
WITHOUT ADDITIONAL COST TO THE OWNER. THIS SHALL INCLUDE REMOVAL,
REROUTING, ETC. OF ALL ELECTRICAL ITEMS REQUIRED TO COMPLETE INSTALLATION
INTENDED.
4. PATCH OR REPLACE ALL DAMAGED FLOOR, WALL, CEILING, ETC. SURFACES ALTERED TO
ACCOMMODATE THE NEW CONSTRUCTION. PATCHED SURFACES SHALL MATCH EXISTING
ADJACENT SPACES.
5. ALL CUTTING, PATCHING, DEMOLITION, REPAIRING, REPLACING, ECT. NECESSARY UNDER
THIS CONTRACT WILL BE COORDINATED BY THE GENERAL CONTRACTOR. WHERE
APPLICABLE COORDINATE WORK WITH UTILITY COMPANIES. LOCAL AND STATE
AUTHORITIES HAVING JURISDICTION, OWNERS REPRESENTATIVE AND ALL APPLICABLE
CODES.
6. WHERE ALTERATIONS TAKE PLACE IN OCCUPIED AREAS, CONTRACTOR SHALL CLEAN UP
DAILY AND NOISE SHALL BE KEPT TO A MINIMUM.
B. DAMP OR WET LOCATIONS: NEMA 250, TYPE 3R STEEL. - „ m
C. DAMP OR WET LOCATIONS: 250, TYPE 4, NONMETALLIC.
• UNDERGROUND RNC (SINGLE RUN OR GROUPED).
D. SEALING FITTINGS SHALL BE INSTALLED AT FOLLOWING POINTS, AND ELSEWHERE AS SH6MN- "
• WHERE REQUIRED BY THE NEC. -
23. THESE DRAWINGS ARE A GUIDE FOR THE INSTALLATION OF THE RACEWAY SYSTEM AND
EQUIPMENT. THEY ARE INTENDED TO SHOW THE GENERAL ARRANGEMENT, DESIGN AND
EXTENT OF THE WORK AND ARE PARTLY DIAGRAMMATIC. THE CONTRACTOR IS RESPONSIBLE
FOR PROVIDING A COMPLETE AND FUNCTIONAL INSTALLATION.
24. CIRCUIT NUMBERS ARE FOR IDENTIFICATION PURPOSES ONLY. THE CONTRACTOR IS
RESPONSIBLE FOR CORRECTLY PHASING THE CIRCUITS IN THE PANEL AND SHALL BALANCE
THE LOAD ON THE PHASES UNDER NORMAL OPERATING CONDITIONS. PROVIDE TYPE WRITTEN
PANEL BOARD DIRECTORIES IN EXISTING PANEL BOARD DIRECTORIES. UPDATE ALL
DIRECTORIES IN EXISTING PANEL BOARDS AFFECTED BY THIS PROJECT ELECTRONICALLY
TRACING ALL CIRCUITS.
25. ANY DEVIATION FROM THESE DRAWINGS AND SPECIFICATIONS MUST BE AUTHORIZED IN
WRITING FROM THE ENGINEERS OFFICE. THE CONTRACTOR SHOULD BE HELD LIABLE FOR ANY
DEVIATIONS WITHOUT SUCH AUTHORIZATION.
26. ALL POWER AND LIGHTING CIRCUITS SHALL HAVE A GREEN EQUIPMENT GROUNDING
CONDUCTOR SIZED AS PER NEC 250 -122. NEUTRAL CONDUCTOR SHALL BE 10 AWG (MINIMUM
CU -THW) IN ALL MULTICIRCUIT BRANCH CIRCUITS.
27. PROVIDE NYLON PULL STRINGS IN ALL EMPTY CONDUITS FOR FUTURE USE.
28. COLOR CODING FOR CONDUCTORS: *
A. WIRING FOR 120/208 VOLT SYSTEM SHALL BE CODED AS FOLLOWS:
PHASE A - BLACK
PHASE B - RED
PHASE C - BLUE
NEUTRAL - WHITE
GROUND -GREEN
B. WIRING FOR 277/480 VOLT SYSTEM SHALL BE CODED AS FOLLOWS:
PHASE A - YELLOW
PHASE B - BROWN
PHASE C - ORANGE
NEUTRAL - GRAY
GROUND - GREEN
C. COLORS ON CONDUCTOR 6 AWG AND SMALLER SHALL BE AN INTEGRAL PART OF INSULATION.
ON CONDUCTOR 4 AWG AND LARGER CONDUCTORS, EITHER COLOR CODING TAPE OR PAINTED
WITH TWO COATS OF CORRECT COLOR PAINT AT ALL TERMINALS AND CONNECTION POINTS.
* UNLESS OTHERWISE REQUIRED BY APPLICABLE CODE.
29. ANY WORK NOT SHOWN OR SPECIFICALLY MENTIONED ON THESE PLANS BUT CONSIDERED
NECESSARY FOR COMPLETION OF WORK IN THE PROPER MANNER SHALL BE PROVIDED BY THE
CONTRACTOR WITHOUT ADDITIONAL CHARGE.
30. CONTRACTOR SHALL VERIFY SPACE CONDITIONS AND DIMENSIONS AT JOB SITE PRIOR TO
FABRICATION AND INSTALLATION OF MATERIALS AND EQUIPMENT. ELECTRICAL CONTRACTOR
IS TO COORDINATE HIS WORK WITH THE ARCHITECT BEFORE ROUGH INSTALLATION OF ALL
OUTLETS (LIGHTS, RECEPTACLES, SWITCHES, PULL BOXES, ETC.) FOR EXACT LOCATION.
31. ALL ELECTRICAL EQUIPMENT SUCH AS PANELS, PULUJ- BOXES, FEEDERS, ETC. SHALL BE
PROPERLY IDENTIFIED WITH A PERMANENT LABEL AFFIXED TO THE EQUIPMENT. IDENTIFY
CIRCUIT IN PANELS BY MEANS OF A TYPED, PLASTIC COVERED DIRECTORY.
32. SPOT PAINT CONDUITS AND BOXES. IDENTIFY CONDUITS WITHIN 6 INCHES (6 ") OF BOX OR
ENCLOSURE. USE ONLY COLOR CODE IN COMPLIANCE WITH USER REQUIREMENTS UPON
COMPLETION.
33. ALL SERVICE INTERRUPTIONS AND ALL REMOVAL AND DISPOSAL WORK SHALL BE SCHEDULED
AND COORDINATED WITH THE AUTHORIZED REPRESENTATIVE OF THE OWNER.
34. CONTRACTOR SHALL SECURE AND PAY FOR ALL PERMITS, FEES, TAXES, INSPECTIONS, TESTS
AND OTHER ITEMS AS REQUIRED INSURANCE FOR PROTECTION AGAINST PUBLIC LIABILITY AND
PROPERTY DAMAGE FOR THE DURATION OF THE WORK.
35. CONTRACTOR SHALL MAINTAIN A COMPLETE SET OF PRINTS FOR INDICATING ALL CHANGES AS
THE CONTRACTOR PROGRESSES. AT THE COMPLETION OF THE WORK, THE CONTRACTOR
SHALL DELIVER A SET OF AS -BUILT DRAWINGS TO THE OWNER IN REPRODUCIBLE MATERIAL.
CONTRACTOR SHALL STAMP AS -BUILT ON THE PLANS (EACH SHEET), PRINT, DATE, AND SIGN
WITH INK.
36. CONTRACTOR IS RESPONSIBLE FOR REPLACING ALL PARTITION, FLOOR CEILING, CONDUIT
PENETRATIONS, AND ANY OTHER EXISTING CONDITION AFFECTED BY THIS PROJECT. UPON
COMPLETION, RE -PAINT ALL AFFECTED SURFACES MATCHING SURROUNDING COLOR.
37. TELECOM RACEWAYS, EMPTY BOXES AND PULL STRINGS TO BE INSTALLED BY ELECTRICAL
CONTRACTOR. WIRING AND WIRING DEVICES AND FINAL CONNECTION IS TO BE BY OWNER.
38. DUPLEX RECEPTACLES, LIGHT SWITCHES AND WIRING DEVICES SHALL BE ENGRAVED
INDICATING PANEL AND CIRCUIT NUMBERS.
39. DEVICES AND COVER PLATES ON EMERGENCY CIRCUITS SHALL BE RED, OTHERWISE DEVICE
AND COVER PLATE TO BE IVORY TO MATCH BALANCE OF BUILDING.
40. WIRING AND GROUNDING IN ALL PATIENT AREAS SHALL BE INSTALLED IN COMPLIANCE WITH
NBC ARTICLE #517 -13.
7. NONE OF THE SERVICES TO EXISTING BUILDINGS SHALL BE DISRUPTED IN ANY WAY
EXCEPT WITH THE WRITTEN PERMISSION OF THE OWNER.
8. ALL EQUIPMENT PRESENTLY "HOT" AND REQUIRED TO BE MAINTAINED SHALL BE
RETURNED TO THIS CONDITION AFTER PERFORMING THE CHANGES TO EXISTING
BUILDING. REROUTE CONDUITS AND EXTEND OR REPLACE CIRCUITS AS REQUIRED.
PERFORM WORK AT CONVENIENCE OF OWNER.
9. WHERE DEVICES ARE SHOWN TO BE REMOVED ON PLANS, REMOVE ALL ASSOCIATED
WIRING AND CONDUIT BACK TO THE SOURCE OR MAINTAIN CONTINUITY OF THE CIRCUIT
IF OTHER LOADS ARE SERVED FROM THE SAME CIRCUIT. CONSOLIDATE PARTIALLY
LOADED CONVENIENCE RECEPTACLE CIRCUITS TO MAXIMIZE SPACE MADE AVAILABLE AT
THE PANEL BOARD. TRACE CONSOLIDATED CIRCUITS TO VERIFY THAT THE TOTAL LOAD
DOES NOT EXCEED 1920 VOLT AMPERES.
10. THE CONTRACTOR SHALL BE FULLY RESPONSIBLE FOR ANY DAMAGE TO EXISTING
BUILDING AND TO CONTENTS THEREOF INCLUDING MACHINERY, FURNITURE, EQUIPMENT,
ETC. AND DAMAGED TO BUILDINGS OR CONTENTS THEREOF DUE TO CONTRACTOR
OPERATIONS, SHALL BE REPAIRED OR REPLACED AT DIRECTION OF
ARCHITECT /ENGINEER, AND /OR OWNER, THE CONTRACTOR, AT NO EXTRA COST TO THE
OWNER.
11. CONNECTION TO EXISTING STRUCTURES OR SYSTEMS SHALL BE MADE IN SUCH A
MANNER THAT AS LITTLE TIME AS ABSOLUTELY POSSIBLE WILL BE TAKEN, AND
CONTRACTOR WILL BE REQUIRED TO COORDINATE FULLY WITH OWNER IN CONNECTION
WITH CONVENIENCE AND SAFETY OF ALL PERSONS INVOLVED, INCLUDING EMPLOYEES.
12. CONTRACTOR SHALL COORDINATE ALL WORK WITH OWNER TO DETERMINE OWNER'S
REQUIREMENTS REGARDING ACCESS, TIME OF WORK, PROTECTION OF EXISTING
CONDITIONS, ETC.
ARCHITECT:
BERMELLO AJAMIL & PARTNERS, INC.
Architecture Engineering Planning
Interior Design Landscape Architecture
2601 South Bayshore Drive 10th Floor
Miami, Florida 33133
(305) 859 -2050 Fax (305) 860 -3700
L9
LOUIS J. AGUIRRE & ASSOCIATES. P.A.
Consulting Engineers
9150 South Dadeland Blvd. • Suite 900
Miami • Florida 33156 • EB0000924
Telephone 305.670.0141
Facsimile 305.670.0144
www.l jaa ap com
Project No.: 22007
• f e
-_J
x ELECTIAL .:-
`t ARJO D. PAZ05 ?�.
ICE(V_E °52078'
PERMIT SET
4/13/2012
REVISIONS:
PROJECT NAME:
SMH- HYPERBARIC CHAMBER
PROJECT ADDRESS:
7400 S.W. 62nd Ave.
South Miami, Florida 33143
10
COMM. NO. 40068
SCALE: AS SHOWN
DATE: 04/13/2011
DRAWN: AP
CHECKED:
CARD FILE: V/22007 -MEP
DRAWING TITLE:
LEGEND, GENERAL
AND DEMOLITION
NOTES ELECTRICAL
SHEET NO.
1 1