12-508-018STF 45` anr�GUrr HVAC DUCT CONSTRUCTION STANDARDS ALL DUCTWORK MUST COMPLY WITH SMACNA HVAC CONSTRUCTION STANDARD AS FOLLOWS: MEDIUM PRESSURE DUCTWORK: 3 "W.G. LOW- PRESSURE DUCTWORK: 2"W.G. DUCTWORK DOWNSTREAM FROM VAV BOXES: 2"W.G. BRANCH NTS AIRL FLOW SHEET METAL MAIN SUPPLY TRUNK TYPICAL TRANSITION MAX. 200 ANGLE VOLUME DAMPER W/ LOCKING DEVICE SHEET METAL BRANCH DUCT CAV BOX CONTROL DIAGRAM (Al) DO- Heating Stages Air Flow Sensor Aa CAV damper actuator i Room Temp Sensor a CAV Sequence of operations: Run Conditions - Scheduled:The unit shall run according to a user definable time schedule in the following modes: • Occupied Mode: The unit shall maintain A 72 °F (adj.) cooling setpoint. A 68 °F (adj.) heating setpoint. • Unoccupied Mode (night setback): The unit shall maintain A 78 °F (adj.) cooling setpoint. A 62 °F (adj.) heating setpoint. Flow Control: The unit supplies a constant volume of supply air to the space. The controller monitors the air velocity sensor and modulates the supply air damper to maintain the supply air volume at both modes (occupied and unoccupied) Electric Heating Stages:The controller shall measure the space air temperature and stage the heating to maintain its heating setpoint. To prevent short cycling, there shall be a user definable (adj.) delay between stages, and each stage shall have a user definable (adj.) minimum runtime. Alarms shall be provided as follows: . High /Low Zone Temp GENERAL NOTES: -CAV boxes shall be connected to existing BAS. -Space sensors located as per plans. -CAV manufacture to provide factoring mounting and wirring of DDC CAV box controller. -The air flow sensors are provided by CAV manufacture. CONSTANT VOLUME BOX —1 __ 1 .11 — 1 \ ^_ -1 A A 1^ 1 ".'^ r AMIC FIBER BLANKET FRAME 2 HINGE POS. 2 FRAME 3 HINGE POS. 3 A /"1l1� - A n 1r1 ,�..`SS DOOR DETAIL N.T.S. DUCT ACCESS DOORS AND PANELS DOOR SIZE NO. HINGES NO. LOCKS METAL GAGE FRAME DOOR BACK 12" X 12" 2 1 - S 24 26 26 2" W.G. STATIC AND LESS 16" X 20" 2 2-S 22 24 26 24" X24" 3 2-S 22 22 26 3" W.G. STATIC 12" X 12" 2 1 - S 22 22 26 16" X20" 2 1 - S, 1 - T, 1 - B 20 20 26 24" X 24" 3 2 - S, 1 - T, 1 - B 20 20 24 4" W.G. TO 10" W.G. 12" X 12"' 2 2 - S, 1 - T, 1 - B 20 20 26 16" X 20" 3 1 - S, 1 - T, 1 - B 20 18 24 24" X2411 1 3 2 -S, 2 -T, 2 -B 18 18 24 S = SIDE OPPOSITE HINGES, T = TOP, B = BOTTOM CONSTRUCTION AND AIRTIGHTNESS MUST BE SUITABLE FOR THE DUCT PRESSURE CLASS USED. THESE ILLUSTRATIONS DO NOT PRECLUDE THE USE OF OTHER METHODS AND HARDWARE. # 10 SHEET METAL - SCREWS. WOOL BATTING ALL SIDES 1 -1/2" X 1 -1/2" X 16 GAUGE STEEL RETAINING ANGLES &.919 SONG X 16 GAUL- t - _ mm - STEEL SLEEVE CENTS ED IN DUCT OPENING II I 1 12" M Il II II II ,--26 gauge min steel kNKET -L DUCT PENETRATION THROUGH FIRE PARTITION N.T.S. * FIRE DAMPER EXCEPTION PER FBC 607.5.3 SYSTEM NO. W -L -7178 F Ratings - 1 and 2 Hr (See Item 1) T Rating - 3/4 Hr L Rating At Ambient - Less Than 1 CFM /sq ft L Rating At 400 F - Less Than 1 CFM /sq ft W A OC-_k. I IVIN AA-H 1. WALL ASSEMBLY. THE 1 OR 2 HR FIRE -RATED GYPSUM BOARD /STEEL STUD WALL ASSEMBLY SHALL BE CONSTRUCTED OF THE MATERIALS AND IN. THE MANNER DESCRIBED IN THE INDIVIDUAL U400 OR V400 SERIES WALL AND PARTITION DESIGN IN THE UL FIRE RESISTANCE DIRECTORY AND SHALL INCLUDE THE FOLLOWING CONSTRUCTION FEATURES: A. A. STUDS . WALL FRAMING SHALL CONSIST OF MIN 3 -1/2 IN. (89 MM) WIDE STEEL CHANNEL STUDS SPACED MAX 24 IN. (610 MM) OC. - ADDITIONAL STEEL STUDS SHALL BE USED TO COMPLETELY FRAME THE OPENING. B. B. GYPSUM BOARD* - 5/8 IN. (16 MM) THICK, 4 FT (1.22 M) WIDE WITH SQUARE OR TAPERED EDGES. THE GYPSUM BOARD TYPE, THICKNESS, NUMBER OF LAYERS, FASTENER TYPE AND SHEET ORIENTATION SHALL BE AS SPECIFIED IN THE INDIVIDUAL U400 OR V400 SERIES DESIGNS IN THE UL FIRE RESISTANCE DIRECTORY. MAX AREA OF OPENING IS 540 SQ IN. (0.35 M2) WITH A MAX DIM OF 30 IN. (762 MM). THE HOURLY F RATING OF THE FIRESTOP SYSTEM IS EQUAL TO THE HOURLY FIRE RATING OF THE WALL ASSEMBLY IN WHICH IT IS INSTALLED. 2. STEEL DUCT - MAX 24 BY 12 IN. (610 BY 305 MM) NO. 26 GAUGE (OR HEAVIER) STEEL DUCT TO BE INSTALLED WITHIN THE FRAMED OPENING. MIN CLEARANCE BETWEEN DUCT AND EDGE OF FRAMED OPENING IN WALL IS 3 IN. (76 MM). STEEL DUCT TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF THE WALL ASSEMBLY. 3. BATTS AND BLANKETS* -NOM 2 IN. (51 MM) THICK LIGHT DENSITY (MIN 3/4 PCF OR 12 KG /M3) GLASS FIBER BLANKET INSULATION JACKETED ON THE OUTSIDE WITH A FOIL - SCRIM -KRAFT FACING. LONGITUDINAL AND TRANSVERSE JOINTS SEALED WITH FOIL - SCRIM -KRAFT TAPE. NOM ANNULAR SPACE BETWEEN INSULATED STEEL DUCT AND PERIPHERY OF OPENING TO BE 1 IN. (25 MM). SEE BATTS AND BLANKETS (BKNV) CATEGORY IN THE BUILDING MATERIALS DIRECTORY FOR NAMES OF MANUFACTURERS. ANY BATT OR BLANKET MEETING THE ABOVE SPECIFICATIONS AND BEARING THE UL CLASSIFICATION MARKING WITH A FLAME SPREAD VALUE OF 25 OR LESS AND A SMOKE DEVELOPED VALUE OF 50 OR LESS MAY BE USED. 4. FIRESTOP SYSTEM - THE FIRESTOP SYSTEM SHALL CONSIST OF THE FOLLOWING: A. PACKING MATERIAL - (OPTIONAL, NOT SHOWN) - POLYETHYLENE BACKER ROD, MINERAL WOOL BATT INSULATION OR FIBERGLASS BATT INSULATION FRICTION FITTED INTO ANNULAR SPACE. PACKING MATERIAL TO BE RECESSED FROM BOTH SURFACES OF WALL AS REQUIRED TO ACCOMMODATE THE REQUIRED THICKNESS OF FILL MATERIAL. B. FILL, VOID OR CAVITY MATERIAL* - SEALANT - BOTH SURFACES OF THE WALL. SPECIFIED TECHNOLOGIES INC - SPECSEAL SERIESS SSS SEALANT OR SPECSEAL LCI SEALANT *BEARING THE UL CLASSIFICATION MARK ARCHITECT: BERMELLO AJAMIL & PARTNERS, INC. Architecture Engineering Planning Interior Design Landscape Architecture 2601 South Bayshore Drive 10th Floor Miami, Florida 33133 (305) 859 -2050 Fax (305) 860 -3700 LOUIS J. AGUIRRE & ASSOCIATES, P.A. Consulting Engineers 9150 South Dodeland Blvd. * Suite 900 Miami * Florida 33156 * EB0000924 Telephone 305.670.0141 Facsimile 305.670.0144 www.l laol2a,com Project No.: 22007 10120TI . PERMIT SET 4/13/2012 REVISIONS: PROJECT NAME: SMH- HYPERBARIC CHAMBER PROJECT ADDRESS: 7400 S.W. 62nd Ave. South Miami, Florida 33143 HT91=1 COMM. NO. 40068 SCALE: AS SHOWN DATE: 04/1312011 DRAWN: AP CHECKED: CADD FILE: v/22007 -MEP DRAWING TITLE: CONTROLS AND DETAILS HVAC MMANK"o 1171 �I� r ' � N � 6 10120TI . PERMIT SET 4/13/2012 REVISIONS: PROJECT NAME: SMH- HYPERBARIC CHAMBER PROJECT ADDRESS: 7400 S.W. 62nd Ave. South Miami, Florida 33143 HT91=1 COMM. NO. 40068 SCALE: AS SHOWN DATE: 04/1312011 DRAWN: AP CHECKED: CADD FILE: v/22007 -MEP DRAWING TITLE: CONTROLS AND DETAILS HVAC MMANK"o 1171 �I� r