12-508-013CONSTANT VOLUME T E R M I N A L U N I T S C H E D U L E AREA SERVED 1rd Floor DESIGN Roof AIR FLOW - CFM 6,750 MODEL SYMBOL SIZE CFM CFM MAX EH KW V / PH / HZ MANUFACT. ( *j NUMBER Y CV -1 m 8 550 900 2 Kw /2 Step 277/1/60 TITUS DESV CV -2 10 1050 1400 3 Kw /3 Step 277/1/60 TITUS DESV CV-3 12 1300 2000 4 Kw /3 Step 277 / 1166 �� TITUS DESV EXISTING RTU -1 (BEFORE DEMOLITION) AREA SERVED 1rd Floor LOCATION Roof AIR FLOW - CFM 6,750 OUTSIDE AIR - CFM 3,350 RETURN AIR - CFM 3,400 EXHAUST AIR - CFM 3,350 PRE - FILTER (PF) - FINAL FILTER (FF) 90% EFFICIENCY SMOKE DETECTOR EXIST. SMOKE DETECTOR ON SUPPLY NOTE: ADJUST THE EXISTING RTU # 1 CFM FROM 6,750 CFM TO 4,740 CFM TEMPORALLY. 1" X 22 ga. EXISTING RTU -1 (AFTER DEMOLITION) 1" X 22 ga. AREA SERVED 1 r Floor LOCATION Roof AIR FLOW - CFM 7,875 OUTSIDE AIR - CFM 3,350 RETURN AIR - CFM 4,525 EXHAUST AIR - CFM 3,350 PRE - FILTER (PF) - FINAL FILTER (FF) 90% EFFICIENCY SMOKE DETECTOR EXIST. SMOKE DETECTOR ON SUPPLY NOTE: THE RPM OF THE EXISTING RTU # 1 MUST BE ADJUSTED TO OBTAIN THE CFM REQUIRED ON THE SCHEDULE ABOVE. RTU -1 MUST BE SHUT DOWN ON FIRE ALARM MODE 12" X 12" EXISTING EXHAUST FAN (EF -2) (BEFORE DEMOLITION) 24" X 24" AREA SERVED Toilet & Soil RM 1rd Floor LOCATION ROOF AIR FLOW - CFM 520 1 1/2"X 16 ga. NOTES: 1. ADJUST THE EF -EAST CFM FROM 520 TO 440 CFM DURING THE CONSTRUCTION 1 1/2" X 16 ga. 1/2" LAY IN EXISTING EXHAUST FAN (EF -2) (AFTER DEMOLITION) 1" X 18 ga. AREA SERVED Toilet & Soil RM 1 rd Floor LOCATION ROOF AIR FLOW - CFM 520 NOTES: 1. THE RPM OF THE EXISTING EF -2 MUST BE ADJUSTED TO OBTAIN THE CFM REQUIRED ON THE SCHEDULE ABOVE 2. EXHAUST FAN (EF -2) MUST BE INTELOCKED WITH THE AHU -1 TO SHUT DOWN ON FIRE ALARM MODE FIXED AIR DISTRIBUTION SCHEDULE PAIR AT 10 FT. SPACING PAIR AT8 FT. SPACING PAIR AT5 FT. SPACING DESIGNATION DUCT PERIMETER A B STRAP C D MANUFACTURER (') STRAP TITUS TITUS 1" X 22 ga. TITUS TITUS MODEL NO. AND/ OR 1" X 22 ga. 12 ga. (0.106) 1" X 22 ga. 12 ga. (0.106) Pl2 = 72" 1" X 18 ga. 3/8" 1" X 20 ga. T MS -AA TMS -AA 1/4" 50FL 50FL CATALOG NO. 1" X 16 ga. 3/8" 1" X 18 ga. 3/8" 1" X 20 ga. 3/8" 1" X 22 ga. 114" 24" X 24" 12" X 12" 1/2" 24" X 24" 3/8" FRAME TYPE 3/8" 1" X 20 ga. 1/4" P/2 =168" 1 1/2"X 16 ga. SURFACE 1 1/2" X 16 ga. 1/2" LAY IN LAY I N 1" X 18 ga. LAY I N P2 = 192" NOT GIVEN 1/2" FIXED FIXED 1" X 16 ga. FIXED FIXED DEVICE TYPE P12 =193" UP SPECIAL ANALYSIS REQUIRED WHEN STRAPS ARE LAP JOINED USE SINGLE HANGER MAXIMUM ALLOWABLE LOAD THESE MINIMUM FASTENERS 12' j G26 STRAP LOUVERED LOUVERED 1" X 22 ga. - 260 lbs. LOUVERED LOUVERED FUNCTION 0.135"- 120 lbs. SUPPLY SUPPLY 0.162" - 160 lbs. RETURN EXHAUST PATTERN 23',24- SEE DRAWING SEE DRAWING B22 SEE DRAWING SEE DRAWING OPPOSED BLADE DAMPERS G26 YES YES 26',26- YES - NOTES: 2. TABLEALLOWS FOR DUCT W6GHT, 1 Ib. /ft2 INSULATION WBGHT AND NORMAL REINFORCEMENT AND TRAPEZEWBGHT, BUT NO EXTERNAL LOADS. 3. STRAPS ARE GALVANIZED STEEL; OTHER MATERIALS ARE UNCOATED STEEL. 4. ALLOWABLE LOADS FOR P/2 ASSUME THAT DUCTS ARE 16 GA. MAXIMUM, EXCEPT THAT WHEN MAXIMUM DUCT DIMENSION (W) 1. ( *) OR APPROVED EQUIVALENT BY TRANS, CARNES OR METALAIRE. 5. 12, 10, 8 ga. WIRE IS STEEL. OF BLACK ANNEALED, BRIGHT BASIC, OR GA LVA NIZED TY PE. D-26 2. ALL AIR DEVICES SHALL BE ALL ALUMINUM CONSTRUCTION AND FULLY GASKETED. 29',30- D-26 3. UNLESS OTHERWISE NOTED, FINISH OF ALL AIR DEVICES SHALL BE BAKED OFF - WHITE. 31% - 36" 4. FOR SQUARE NECK OUTLETS CONNECTED TO A ROUND FLEXIBLE OR RIGID DUCT, PROVIDE THE REQUIRED INSULATED SQUARE TO ROUND TRANSITION. 37" - 42" E-24 E-26 E-26 RECTANGULAR DUCT HANGERS MINIMUM SIZE MAXIMUM HALF OF PAIR AT 10 FT. SPACING PAIR AT8 FT. SPACING PAIR AT5 FT. SPACING PAIR AT4 FT. SPACING DUCT PERIMETER STRAP WIRFJROD STRAP WIRE TROD STRAP WIRE/ROD STRAP WIRFJROD P/2 = 30" 1" X 22 ga. 10 ga. (0.135) 1"X 22 ga. 10 ga. (0.135) 1" X 22 ga. 12 ga. (0.106) 1" X 22 ga. 12 ga. (0.106) Pl2 = 72" 1" X 18 ga. 3/8" 1" X 20 ga. 1/4" 1" X 22 ga. 1/4" 1" X 22 ga. 1/4" P/2 = 96" 1" X 16 ga. 3/8" 1" X 18 ga. 3/8" 1" X 20 ga. 3/8" 1" X 22 ga. 114" P12 =120" 1 1/2"X 16 ga. 1/2" 1" X 16 ga. 3/8" 1" X 18 ga. 3/8" 1" X 20 ga. 1/4" P/2 =168" 1 1/2"X 16 ga. 1/2" 1 1/2" X 16 ga. 1/2" 1" X 16 ga. 3/8" 1" X 18 ga. 3/8" P2 = 192" NOT GIVEN 1/2" 1 1/2"X 16 ga. 1/2" 1" X 16 ga. 3/8" 1 1/2" X 16 ga. 3/8" P12 =193" UP SPECIAL ANALYSIS REQUIRED WHEN STRAPS ARE LAP JOINED USE SINGLE HANGER MAXIMUM ALLOWABLE LOAD THESE MINIMUM FASTENERS 12' j G26 STRAP WIRE OR ROD (D(A. ) 1" X 18,20,22 ga. - TWO #10 OR ONE 1/4" BOLT 1" X 22 ga. - 260 lbs. 0.106"- 80 lbs. 1" X 16 ga. - TWO 1/4" DIA. BOLT 1" X 20 ga. - 320 lbs. 0.135"- 120 lbs. 1 1/2" X 16 ga. - TWO 3/8" DIA. BOLT 1" X 18 ga. - 420 lbs. 0.162" - 160 lbs. PLACE FASTENERS IN SERIES, NOT SIDE BY SIDE 1" X 16 ga. - 700 lbs. 1/4"- 260 lbs. 23',24- 1 1/2" X 16 ga. - 700 lbs. 3/8"- 680 lbs. B22 D­24 1/2" -1250 lbs. D-26 G26 5/8" - 2000 lbs. G26 26',26- 3/4" - 3000 lbs. NOTES: 1. DIMENSIONS OTHER THAN GAGES ARE IN INCHES. 2. TABLEALLOWS FOR DUCT W6GHT, 1 Ib. /ft2 INSULATION WBGHT AND NORMAL REINFORCEMENT AND TRAPEZEWBGHT, BUT NO EXTERNAL LOADS. 3. STRAPS ARE GALVANIZED STEEL; OTHER MATERIALS ARE UNCOATED STEEL. 4. ALLOWABLE LOADS FOR P/2 ASSUME THAT DUCTS ARE 16 GA. MAXIMUM, EXCEPT THAT WHEN MAXIMUM DUCT DIMENSION (W) IS OVER60" THAN P/2 MAXIMUM IS 1.25 in. 5. 12, 10, 8 ga. WIRE IS STEEL. OF BLACK ANNEALED, BRIGHT BASIC, OR GA LVA NIZED TY PE. ARCHITECT: BERMELLO AJAMIL & PARTNERS, INC. - - - - - - - - Architecture Engineering Planning - Interior Design Landscape Architecture --- w - --- - 2601 South Bayshore Drive 10th Floor Miami, Florida 33133 (305) 859 -2050 Fax (305) 860 -3700 LOUIS J. AGUIRRE & ASSOCIATES, P.A. Consulting Engineers 9150 South Dodeland Blvd. • Suite 900 Miami . Florida 33156 . EB0000924 Telephone 305.670.0141 Facsimile 305.670.0144 www,l iaa a Project No.: 22007 " - ,h 4 `1 ETNA CAL: , -' �GI SE AIVg`. CEN PERMIT SET 4/13/2012 REVISIONS: PROJECT NAME: SMH- HYPERBARIC CHAMBER PROJECT ADDRESS: 7400 S.W. 62nd Ave. South Miami, Florida 33143 KEY PLAN MINIMUM HANGER SIZES FOR ROUND DUCTS DUCT MAXIMUM WIRE ROD STRAP DIAMETER SPACING DIAMETER GAGE NO. 10 DN 12' ONE 12 ga. 1/4" 1" x 22 ga 250 rnn DN 3.7 m ONE 2.75 mm. 6.4 rnm 25.4 X 0.85 mm 11" - 18" 12' TWO 12 ga. OR ONE 8 ga. 1/4" 1" x 22 ga 460 mm 3.7 m ONE 4.27 nvn. 6.4 mm 25.4 X 0.85 mm 19" - 24" 12' TWO 10 ga. 1/4" 1" x 22 ga 610 mm 3.7 m TWO 3.51 mm, 6.4 mm 25.4 X 0.85 mm 25" - 36" 12' TWO 8 ga. 3/8" 1" x 20 ga 900 mm 3.7 m TWO 2.7 mrn. 9.5 mm 25.4 X 1.00 mm 37'- 50" 12' C-26 TWO 3/8" TWO 1" X 20 ga. B-26 1270 rrm 3.7 m TWO 9.5 mm TWO 25.4 X 1.00 rnn 51" - 60" 12' G26 TWO 3/8" TWO 1" X 18 ga. G26 1520 mm 3.7 m TWO 9.5 mm TWO 25.4 X 1.31 mm 6111-84, 12' j G26 TWO 3/8" TWO 1" X 16 ga. 2130 rrin 3.7 m 21 ", 22" TWO 9.5 mm TWO 25.4 X 1.61 mm NOTES. 1. STRAPS ARE GALVANIZED STEEL; RODS ARE UNCOATED OR GALVANIZED STEEL; WIRE IS BLACK ANNEALED, BRIGHT BASIC, OR GALVANIZED STEEL. ALL ARE ALTERNATIVES. 2. TABLE ALLOWS FOR CONVENTIONAL WALL THICKNESS, AND JOINT SYSTEMS PLUS ONE LB /SF INSULATION WBGHT. IF HEAVIER DUCTS ARE TO BE INSTALLED, ADJUST RANGER SIZES TO BE WITHIN THBR LOAD LIMITS. HANGER SPACING MAY READJUSTED BY SPECIAL ANALYSIS. ARCHITECT: BERMELLO AJAMIL & PARTNERS, INC. - - - - - - - - Architecture Engineering Planning - Interior Design Landscape Architecture --- w - --- - 2601 South Bayshore Drive 10th Floor Miami, Florida 33133 (305) 859 -2050 Fax (305) 860 -3700 LOUIS J. AGUIRRE & ASSOCIATES, P.A. Consulting Engineers 9150 South Dodeland Blvd. • Suite 900 Miami . Florida 33156 . EB0000924 Telephone 305.670.0141 Facsimile 305.670.0144 www,l iaa a Project No.: 22007 " - ,h 4 `1 ETNA CAL: , -' �GI SE AIVg`. CEN PERMIT SET 4/13/2012 REVISIONS: PROJECT NAME: SMH- HYPERBARIC CHAMBER PROJECT ADDRESS: 7400 S.W. 62nd Ave. South Miami, Florida 33143 KEY PLAN RECTANGULAR DUCT REINFORCEMENT SCALE: AS SHOWN 2" W.G. STATIC POS. OR NE M NO REINFORCEMENT REQUIRED REINFORCEMENT CODE FOR DUCT GAGE NO. DRAWING TITLE: RENFORCBM4T SPACING OPTIONS SCHEDULES DUCT DIM. 10' 1 8' 6' 1 5' 1 4' 1 3' 2 -1/2' 1 2' 10" dn. 26 ga. NOT REQUIRED 11-,12' 24 ga. B-26 B-26 B-26 B-26 B-26 B-26 B -26 13',14- 22 ga. B-24 B-26 B-26 B-26 B-26 B-26 B-26 15',16' 20 ga. 0-22 G24 G24 C-26 G26 G26 B-26 B -26 17-,18- 20 ga. G22 G24 G24 G26 G26 G26 G26 B -26 19',20- 18 ga. G20 j 0-22 G24 j G26 G26 j G26 G26 G26 21 ", 22" 16 ga. D-20 D-22 D•24 D-26 G26 0-26 G26 C-26 23',24- 16 ga. E-20 B22 D­24 0.26 D-26 G26 G26 G26 26',26- E-20 F -18 F -18 G-16 NOT DESIGNED E-22 E-20 F-20 G-18 K16 1-16 EL 24 E-22 E-22 F-20 G-18 1-18 1.16G E16G D-26 E-24 E-24 F-22 G-20 1-20 K18G 1-18G J-16H D-26 D-26 E-26 E-24 F-24 G-22 K20G H-18G 1-18G 1-18G J-1$H G26 G26 G26 27,28- D-26 G26 G26 29',30- D-26 D•26 G26 31% - 36" E-26 D-26 D-26 37" - 42" E-24 E-26 E-26 43" - 48" F-24 FL 24 E-24 49 "-54" G-24 FL 24 F -24 55"- 60" G-22 G-24 F -24 61% 72" H-22G K22G H-24 73% 84" 1-20G 1-22G 1­22G 86% 96" 1�181­1 1-20H 1­22H 97" - 108" K 18H J-18H 1­18H 109" - 120" K-181 J-181 ARCHITECT: BERMELLO AJAMIL & PARTNERS, INC. - - - - - - - - Architecture Engineering Planning - Interior Design Landscape Architecture --- w - --- - 2601 South Bayshore Drive 10th Floor Miami, Florida 33133 (305) 859 -2050 Fax (305) 860 -3700 LOUIS J. AGUIRRE & ASSOCIATES, P.A. Consulting Engineers 9150 South Dodeland Blvd. • Suite 900 Miami . Florida 33156 . EB0000924 Telephone 305.670.0141 Facsimile 305.670.0144 www,l iaa a Project No.: 22007 " - ,h 4 `1 ETNA CAL: , -' �GI SE AIVg`. CEN PERMIT SET 4/13/2012 REVISIONS: PROJECT NAME: SMH- HYPERBARIC CHAMBER PROJECT ADDRESS: 7400 S.W. 62nd Ave. South Miami, Florida 33143 KEY PLAN SHEET NO. M6.6 WN1 COMM. NO. 40068 SCALE: AS SHOWN DATE: 04/13/2011 DRAWN: AP CHECKED: CADD FILE: V/22007 -MEP DRAWING TITLE: SCHEDULES HVAC SHEET NO. M6.6 WN1