09-696-012
H.V.A.C. GENERAL NOTES : 1. USE VANE ELBOWS IN ALL CASES, SPLATTER DAMPERS WHERE INDICATED ON DRAWINGS AND CONTROLS IN ALL BRANCH DUCTS. 2. PROVIDE FIRE DAMPERS IN ALL DUCTS PENETRATING FIRE RATED CLGS.& EXCEEDING 100 IN. SQ. IN 100 FT. SQ. IN ALL DUCTS PENETRATING FIRE RATED WALLS AND PARTITIONS AND FLOOR OR ROOF SLABS AND AT FRESH AIR INTAKES (SEE PLANS). ALL FIRE DAMPERS SHALL BE RATED FOR USE IN CEILING ASSEMBLY SPECIFIED BY ARCHITECT. 3. ALL DUCT SIZES ARE CLEAR INSIDE DIMENSIONS. 4. SEAL ALL DUCTS IN AN APPROVED MANNER AND INSURE AGAINST LEAKAGE. 5. COORDINATE LOCATION OF CEILING DIFFUSERS, GRILLES, AND REGISTERS IN THE FIELD, WITH ELECTRITIAN, LIGHTS, AND ARCHITECTURAL ELEMENTS. 6. THIS CONTRACTOR SHALL COORDINATE ALL DUCT LOCATIONS WITH ALL TRADES SO THAT NO INTERFERENCES OCCUR. 7. THERMOSTAT LOCATIONS SHALL BE APPROVED BY OWNER AND ENGINEER BEFORE INSTALATION. 8. COMPLY WITH NFPA -90A AND ALL APPLICABLE CODES. THIS IS CONTRACTORS RESPONSIBILITY. 9. TERMINAL AIR DISTRIBUTION DEVICES SHALL BE TITUS AS FOLLOWS (C.R.) CEILING REGISTER 200AL SERIES WITH VOLUME CONTROL DAMPER OPERABLE THRU FACE OF DIFFUSER. (R.A.R.) RETURN AIR GRILL MODEL 4 -FL OR TXR. 10. ALL SUPPLY AND RETURN DUCTWORK SHALL BE OWENS CORNING FIBERGLASS (1.5" THICK) R -6 DUCTWORK MATERIAL TO BE VERIFIED WITH CEILING ASSEMBLY FIRE RATING. 11. ALL EXHAUST AND OUTSIDE AIR DUCTS SHALL BE GALVANIZED SHEET METAL CONSTRUCTED AND INSTALLED IN ACCORDANCE WITH ASHRAE AND SMACNA STANDARDS. 12. ALL OPENINGS IN BUILDING STRUCTURE, FOR DUCTWORK, TO BE 1" LARGER (ON ALL SIDES) THAN DUCT OUTSIDE DIMENSIONS. 13. RUN CONDENSATE DRAIN AS PER PLUMBING DRAWINGS. 14. PROVIDE 1" THICK (THROW -AWAY TYPE) FILTERS WITH EACH A/C UNIT. 15. IN GENERAL, DUCT OFFSETS HAVE NOT BEEN SHOWN. A/C CONTRACTOR TO COORDINATE THESE AS REQUIRED. 16. CONTRACTOR TO FURNISH SHOP DRAWINGS FOR DUCTWORK., AIR DEVICES, AND EXHAUST FANS. 17. MOUNT ALL EQUIPTMENT FOR WIND LOADS AND MOUNTING HEIGHTS AS REQUIRED BY LOCAL CODES. 18. BALANCE ALL AIR SYSTEMS AND SUBMIT TEST RESULTS PRIOR TO FINAL INSPECTION. HN.A.C. LEGEND YES 12' TQ TRANSFER GRILLE ACLU NR- COOLED CONDENSING UNIT (MIN-) - - - - - SUCTION CONNECTION am DETECTOR CLG. YID. CD CEILING SUPPLY DIFFUSER - - - - - - LIQUID CONNECTION CR CEILING SUPPLY REGISTER OA - - - - PROVIDE FACTORY NURR)CANE BRACKETS RETURN NR REGISTERS RA RETURN AR - OR STRAP UNIT AT EACH COW&-R TO SA SUPPLY NR ED - - - - WITHSTAND HURRICANE WNDS. OUTSIDE NR INTAKE QT THERMOSTAT - /- V44 BOLT ! UJ4S{•IER SAE GRADE 5 INSULATED SUCTION THERMOSTAT W/ REMOTE BULB SENSOR DUCTWORK TRANSITION - - -- W ASTM -A449 (TYP. OF 4) LINE (NO JONTS ALLOWED) VOLUME EXTRACTOR OBMVD OPPOSED BLADE MANUAL VOLUME DAMPER NO. SUPPLY NR FLOW VD VOLUME DAMPER SN arch �. for flood Iswl criteria RETURN AIR FLOW so T -..... -1I:- WE FLOOR PLAN ml� UNDER -CUT (DOOR) - FOR PIPE SIZES AHU NR HANDLING UNIT ODD- : ;. b' CONCRETE SLAB 4' BACK DRAFT CAMPER ❑s ® -1 ` PROVIDE PVC SLEEVE WITN 45 dog. LIGJID LINE . s1bm (NO JOINTS ALLOUJED) ' ''y AHU UNDER SLAB FOR 125 TONS TO 3 TONS. AND b' P.VC- FOR 326 TONS TO 5 TONS. CONDENSING UNIT MOUNTING DETAIL N.T.S. 3/4 18 HN.A.C. LEGEND YES NO TQ TRANSFER GRILLE ACLU NR- COOLED CONDENSING UNIT DG DOOR GRILLE ® am DETECTOR CLG. YID. CD CEILING SUPPLY DIFFUSER ®-'- DUCT SMOKE DEIEIIIDR CR CEILING SUPPLY REGISTER OA OUTSIDE NR RAR RETURN NR REGISTERS RA RETURN AR ER EX HAUETT NR REGISTERS SA SUPPLY NR ED EXHAUST NR GRILLE ON OUTSIDE NR INTAKE QT THERMOSTAT -R- ItEFRIG. PIPING ONSUL SUCTION Alt LIQUID) QT THERMOSTAT W/ REMOTE BULB SENSOR DUCTWORK TRANSITION F.D. A FIRE DMMPER W/ ACCESS DOOR VOLUME EXTRACTOR OBMVD OPPOSED BLADE MANUAL VOLUME DAMPER NO. SUPPLY NR FLOW VD VOLUME DAMPER -+r- RETURN AIR FLOW so SPTmER DAMPER W.M.S. WIRE MESH SCREEN ml� UNDER -CUT (DOOR) S.R. SIDEWALL REGISTER AHU NR HANDLING UNIT ODD- AUTOMATIC LOINERE DAMPER BDD BACK DRAFT CAMPER ❑s ® MOTION DETECTOR SWITCH CO2 SENSOR H.V.4r- DESIGN REGRAREMENTSt YES NO DUCT SMOKE DETECTOR AIR COOLED X FIRE DAVROWS) !PIPES ABOVEr 0 ;GROUND X SMOKE DAMPERIS) X FIRE RATED ENCLOSURE X FIRE RATED ROOF / CEILING ASSEMBLY MAX X FIRE STOPPING CAPACITY (MBTH) X SMOKE CONTROL UNIT X IN H. P. F.L.A. AIR CONDITIONING SYSTEMS SCHEDULE -) AIR HANDLING UNIT AIR COOLED COND. UNIT SYSTEM !PIPES ABOVEr 0 ;GROUND E.S.P. ELECTRIC HEATING COMPRESSOR TOTAL MAX MOD. WT. CAPACITY (MBTH) w UNIT C.F.M. IN H. P. F.L.A. MODEL UNIT FUSE NO. LBS. ELEC. SEER NO. O A H2O KW STAGE F.L.A. F.L.A. SIZE COND TOT. SEN AHU 1 1485 05 3/4 18 10.0 1 06 TujE E 199 26 45 4 219 525 39.1 24OV.I# 15D 300 13PS AI000A to y NOTES: 1. OUTSIDE AIR DESIGN CONDITIONS: 91 FDB - 79 FWB. 2. PROVIDE HEATING AND COOLING PROGRAMMABLE THERMOSTAT ON SUBBASE WITH FAN ON - OFF SWITCH. 3. SIZE AND RUN REFRIGERANT PIPING AS PER MANUFACTURER'S RECOMMENDATION. 4. PROVIDE VIBRATION ISOLATION WITH RUBBER IN SHEAR PADS. 5. INSULATE REFRIGERANT SUCTION LINE WITH 3/4" ARMAFLEX. 6. INSTALL CHEMICAL DRYER AND STRAINER IN REFRIGERANT LIQUID LINE. 7. PROVIDE BUILT -IN DISCONNECT TO AIR HANDLING UNITS. 8. PROVIDE EXTREME HURRICANE CUPS WITH ALL UNITS. »s HANG DUCT AS PER THE LATEST SMAACNA STANDARDS. FOR DUCTS FRO!'- . _- -- _. ._. - •- - - - - -- SPAI 19 TH 8' -9 31 TN "pm,%s11Rf aic 10%1&. METHODS OF HANGING DUCTS DETAIL OR *m AIR DUCT I METAL ROUND FITTING QUAD��,,dd��''�� OPERATOR TO BE OUTSIDE M JLATION. PROVIDE INSULATION GUARD WHERE NECESSARY !DAMPER UJI ARE NOTEDA F- NSULATED FLEX DUCT SEAL JOINT UnTN DUCT SEALER T LIOS PREVENT CONDENSATION. �- C8ILRJG DIFFUSER OR RETURN REGISTER FLEXIBLE DUCT CONNECTION DETAIL N.T.S. `- SUPPLY AIR DUCT CONNECT SUPPLY PLENUM TO FRAME OF AHU WITH ANGLE IRON SUPPORTS. -AIR HANDLING UNIT PROVIDE 4' CLE,4RANM ALL AROUND WIT. REFRIGERANT LINES RFORATED CAP �- CONDENSATE DRAIN NEOPF406 PAD VIBRATION ISOLATER I'XPXV4'STEEL ANGLE FRAME FLOOR STRUCTURE A.H.U. MOUNTING [DETAIL_ N.TB. 1.5" MINIM UM IUM SPACING SUPPORTS 61} , --------------------------------------------- - ------------------------- w / lenum �2)6" RD. !PIPES ABOVEr 0 ;GROUND : /P enum CD 6" 6" ��1 � �`G 9 "X9" w • X IL (100 CF RD. 6" RD. ' 0 C -1 - - ------ - - - - -- ........ CD 12 "X12" (300 CFM) '<- CD 12 "X12" (2) 6" RD. (280 CFM) AHU MTD ON AN ADJUSTABLE (2) 6" RD. MTL. STAND. PROVIDE A SHT. MTL PAN AT FLOOR W /FLOAT SWITCH. PROVIDE 4" - ALL AROUND UNI' CLEA 10 "X8 0 RAG 12 "X12" w /plenum CD 6"X6" CD 6 _ ' 0 CFM (80 C, M) 4" RD. RAG 9x9 ' 6" RDA w /plen,lm 0 0 (2)6" 14D.0 COUNTER PASS THRU ....................._._X F1- ------------------ - --------- d .........................44 i ------------------------------------------ - - - -�' I I. ................... ................. ........ ...... c� Nl art `WIRE 1.5 MINIMUM WIRE MAX. SACS 1/2' /Ft BETWEEN SUPPORTS. IN GENERAL FLEX. INSTALLATION TO COMPY W/F.M.C. 603.=x' bb SUPPORT SYSTEM MUST NOT DAMAGE DUCT OR CAUSE OUT OF ROUND SHAPE. FLEXIBLE DUCT SUPPORTS KT.L r {( 9 "• 10 "X8 C ,•i11tiyl•>2will 15 PLP X 20 CFM /PLP= 300 --------------------- - - - - -- ----------------------------------------- - - - - -- CFM. INSULATED 9 RD. SHT. MTL. 12 "X12" GRILLE IN OVERHANG W /W.M.S. ....................................... .. ......................................................................... RAG 12 "X12" w / lenum �2)6" RD. !PIPES ABOVEr 0 ;GROUND AC .................. CD 12 "X12" F (200 CFM) w ------:'-REFRIG. PIPES UP TO CLG. 16 "X3.25" SHT MTL DN. TO FIL S: 1 1 /8" LEVEL W/V.D. L• 3/8" AG 12 "X12 "T CD 9 "X9" h © w ! lenurr� x(170 CFM) 2)6" R' 8" RD. - -- -------------- © " RD. ff LO DER FAN NUTONE LS n.. 80, 80 CFM, 120V -RAO 12 "X1 T " " W/41- RD. DUCT © W. lenum CD 6 X� UP TO ROOFCAP . .. . ....... .....:------------------ .....................(.80-...C% W /WAS © ; 6 RD. CD 9 "X9" 12 "X10 (1_ 4 CFM) 6" R . A/C FLOOR PLAN. Scale: 1/4" = 1' -0" s T �USTAVO SOLANO, P.E. '� : � `mechanical / electrical � J;'` ..t►���� consulting engineer fla. registration #: 3 4 9 2 3 1' 7410 -B sm. 48th. ST., miami, fl. 33155 it e l. ( 3 0 5) 6 6 5 - 6 1 5 1 O O S 0 Z gi r 2 7-7 0 = o� 11-- LLI AC N H A� N� 4 Cq ZLL d� 3: FN Lu O z r ID?RAWN my go ' DATE 02- -2000 z Q 0 0 1 LL- U Q amc" No AC -1 on Comm NO w T2