09-696-001FIRE REVIEW M2009008090 8/17/09 R. GONZALEZ
1. MUST PROVIDE A RESPONSE SHEET ADDRESSING EACH OF
THE COMMENTS & INDICATE THE SHEET IN WHICH ,
CORRECTION IS FOUND
2. INDICATE THE FLOOR ELEVATION ON BOTH SIDES OF DOORS - MAX w' - SCT.
7.2.1.3 -
3. STAIR LANDING DIMENSIONS IN THE DIRECTION OF TRAVEL SHALL BE AT LEAST -
THE WIDTH OF THE STAIRS - SCT. 7.2.2.3.2.3
4. STAIR TREADS NOT EXCEEDING 21" IN HEIGHT SHALL BE A MINIMUM OF 13" -
7.1.7.2.2
5. ALL NEW DOORS IN A MEANS OF EGRESS SHALL BE A MINIMUM OF 36" - SCT.
7.2.1.2.4 - (DOORS #B- C- D -E -F)
6. PROVIDE RAMP SLOPE
7. INDICATE IF THERE IS AN EXISTING FIRE SPRINKLER SYSTEM - IF SO INDICATE ON
PLANS THE LOCATION OF ALL NEW AND EXISTING HEADS
* ALL CODE REFERENCES MENTIONED IN THESE COMMENTS ARE FROM
FFPC/NFPA, FLORIDA FIRE PREVENTION CODE AND NFPA 101 LIFE SAFETY
CODE, UNLESS OTHERWISE NOTED..
• PROVIDE NEW SHEETS WITH ALL CORRECTIONS AND CHANGES
HIGHLIGHTED OR CLOUDED.
• RETURN VOIDED SHEETS WITH FIRE DEPT. STAMPS FOR COMPARISON, OR
FULL REVIEW FEE WILL BE ASSESSED
• COORDINATE ALL CORRECTIONS & CHANGES THROUGHOUT THE ENTIRE
SET OF PLANS.
* PROVIDE ALL INFORMATION ON THE PLANS
* FAST TRACK FOR REWORK