09-696-001FIRE REVIEW M2009008090 8/17/09 R. GONZALEZ 1. MUST PROVIDE A RESPONSE SHEET ADDRESSING EACH OF THE COMMENTS & INDICATE THE SHEET IN WHICH , CORRECTION IS FOUND 2. INDICATE THE FLOOR ELEVATION ON BOTH SIDES OF DOORS - MAX w' - SCT. 7.2.1.3 - 3. STAIR LANDING DIMENSIONS IN THE DIRECTION OF TRAVEL SHALL BE AT LEAST - THE WIDTH OF THE STAIRS - SCT. 7.2.2.3.2.3 4. STAIR TREADS NOT EXCEEDING 21" IN HEIGHT SHALL BE A MINIMUM OF 13" - 7.1.7.2.2 5. ALL NEW DOORS IN A MEANS OF EGRESS SHALL BE A MINIMUM OF 36" - SCT. 7.2.1.2.4 - (DOORS #B- C- D -E -F) 6. PROVIDE RAMP SLOPE 7. INDICATE IF THERE IS AN EXISTING FIRE SPRINKLER SYSTEM - IF SO INDICATE ON PLANS THE LOCATION OF ALL NEW AND EXISTING HEADS * ALL CODE REFERENCES MENTIONED IN THESE COMMENTS ARE FROM FFPC/NFPA, FLORIDA FIRE PREVENTION CODE AND NFPA 101 LIFE SAFETY CODE, UNLESS OTHERWISE NOTED.. • PROVIDE NEW SHEETS WITH ALL CORRECTIONS AND CHANGES HIGHLIGHTED OR CLOUDED. • RETURN VOIDED SHEETS WITH FIRE DEPT. STAMPS FOR COMPARISON, OR FULL REVIEW FEE WILL BE ASSESSED • COORDINATE ALL CORRECTIONS & CHANGES THROUGHOUT THE ENTIRE SET OF PLANS. * PROVIDE ALL INFORMATION ON THE PLANS * FAST TRACK FOR REWORK T. =,