12-986R-001.3>C
ELECTRICAL
1.- OVERALL INSTALLATION: THE INSTALLATION SHALL COMPLY WITH THE NATIONAL ELECTRICAL
CODE (NEC), THE FLORIDA BUILDING CODE (FBC), AND ANY OTHER APPLICABLE FEDERAL, STATE
AND LOCAL CODES.
2.- COMPLIANCE: WORKMANSHIP, MATERIALS AND INSTALLATION SHALL BE IN STRICT ACCORDANCE
WITH THE APPLICABLE EDITION OF THE NEC, NFPA, NEMA, ASTM, OSHA, HRS HEALTH AGENCIES,
AND OTHER APPLICABLE NATIONAL, STATE, AND LOCAL CODES AND PERTAINING REGULATIONS
ESTABLISHED BY THE RULING AUTHORITY HAVING JURISDICTION. CONTRACTORS SHALL ALSO MEET
THE REQUIREMENTS OF OTHER STANDARDS WHERE SUCH REQUIREMENTS ARE MORE STRICT THAN
THOSE STANDARDS CITED ABOVE.
3.- MATERIALS: CONTRACTOR SHALL PROVIDE ALL NEW MATERIALS OF AMERICAN MANUFACTURE,
BEARING THE UNDERWRITER'S LABORATORY (UL) LABEL AS APPLICABLE.
4.- PERMITS AND INSURANCE: CONTRACTOR SHALL SECURE AND PAY FOR ALL PERMITS, FEES,
TAXES, INSPECTIONS, TESTS, FINES AND OTHER ITEMS AS REQUIRED FOR THE INSTALLATION OF
THE COMPLETE ELECTRICAL SYSTEMS AS OUTLINED HEREIN AND SHOWN ON PLANS. CONTRACTOR
SHALL PROVIDE ALL REQUIRED INSURANCE FOR PROTECTION AGAINST PUBLIC LIABILITY AND
PROPERTY DAMAGE FOR THE DURATION OF THE WORK.
5.- EXISTING CONDITIONS: BEFORE BIDDING, THE CONTRACTOR SHALL VISIT THE JOB SITE AND
ASCERTAIN ALL EXISTING CONDITIONS WHICH WILL AFFECT HIS WORK. FAILURE TO DO SO WILL
NOT BE ACCEPTED AS A REASON FOR REQUESTING EXTRA PAY WHERE THE EXISTING CONDITIONS
RESULT IN EXTRA MATERIALS OR ANY EXISTING CONDITIONS FOUND BY THE CONTRACTOR WHICH
WILL ADVERSELY AFFECT THE WORK SHALL BE IMMEDIATELY BE BROUGHT TO THE ATTENTION OF
THE ARCHITECT /ENGINEER. CORRECTION OF ANY DEFECTS SHALL BE COMPLETELY WITHOUT
ADDITIONAL CHARGE AND SHALL INCLUDE REPLACEMENTS OR REPAIR OF ANY OTHER PHASE OF
THE INSTALLATION WHICH MAY HAVE BEEN DAMAGED THEREBY.
6.- CUTTING AND PATCHING: MAJOR CUTTING, PATCHING & PAINTING REQUIRED BY THIS CONTRACT
WILL BE PERFORMED IN A NEAT AND WORKMANLIKE MANNER. ALL SURFACES SHALL BE RETURNED
TO ORIGINAL CONDITIONS AFTER THE INSTALLATION OF THE EQUIPMENT.
7. -THE ELECTRICAL INSTALLATION SHALL MEET ALL STANDARD REQUIREMENTS OF THE LOCAL
ELECTRIC UTILITY AND THE TELEPHONE COMPANY.
8. -LOAD DATA IS BASED ON INFORMATION PROVIDED TO THE ENGINEER AT THE TIME OF DESIGN.
ALL EQUIPMENT AND PANEL SIZES SHALL BE VERIFIED BEFORE ORDERING.
9.- CIRCUITS SHOWN ON PLANS ARE USED TO DETERMINE LOAD DATA AND PANEL SIZES. THE
CONTRACTOR SHALL PROVIDE CIRCUIT ROUTING TO SUIT THE JOB CONDITIONS.
10.- FURNISH AND INSTALL ALL FIXTURES AS CALLED FOR ON THE PLANS OR AS SELECTED BY
OWNER /ARCHITECT.
11. -ALL CONDUCTORS SHALL BE RUN IN CONDUIT, U.O.N.
12.- INSTALL 1/2" EMPTY CONDUIT TO ALL TELEPHONE /DATA OUTLETS. PROVIDE PULL WIRE.
13.- INTERFERENCE: THE CONTRACTOR SHALL COORDINATE HIS WORK WITH OTHER TRADES SO
THAT INTERFERENCE WITH EXISTING CONDITIONS, CONDUITS, PIPING, EQUIPMENT, ARCHITECTURAL
AND STRUCTURAL MEMBERS BE AVOIDED.
14.- PLANS: DRAWINGS ARE BASICALLY DIAGRAMS INTENDED TO DEPICT APPROXIMATELY
EQUIPMENT LOCATIONS AND ARRANGEMENTS, NOT TO SHOW EVERY MINOR DETAIL. PLANS SHALL
NOT BE SCALED TO DETERMINE EXACT LOCATION AND DIMENSIONS.
ELECTRICAL LEGEND
20 A., 120., V., DUPLEX RECEPTACLE,GROUNDING
TYPE, U.O.N. MOUNTED 18" A.F.F. OR
AS DIRECTED BY ARCHITECT.
$ 20A, 120V GFI DUPLEX RECEPTACLE.
® 250V SPECIAL PURPOSE RECEPTACLE.
*09- LIGHTING SWITCH ® 48" AFF.
� 3 -WAY LIGHTING SWITCH ® 48" AFF.
� SWITCH MOTOR RATE (60AMP).
0 PUSH BUTTON GARAGE OPENER.
[:1 SAFETY DISCONNECT SWITCH.
O ELECTRIC PANEL.
M EXHAUST FAN.
O SINGLE STATION SMOKE /CARBON MONOXIDE DETECTOR W /BATTE
BACKUP AND INTERCONNECTED. TIE TO BATHROOM CIRCUIT.
Tv TV OUTLET.
= PHONE OUTLET. PROVIDE MUD RING AND 3/4 "C
STUBBED ABOVE CEILING.
- SURFACE OR PENDANT MOUNTED FIXTURE.
WALL /PEDESTAL MOUNTED LIGHT.
c = ABOVE THE COUNTER.
WP = WEATHER PROOF.
E = EXISTING TO REMAIN.
TRory only to Cod
GENERAL NO TES
15. -ALL ELECTRICAL EQUIPMENT SHALL BE INSTALLED IN ACCESIBLE AREAS ONLY AND ABOVE
BASE FLOOD ELEVATION.
16.- CONTRACTOR IS RESPONSIBLE FOR PROVIDING ALL WIRING, BREAKER AND FUSES SIZES IN
ACCORDANCE WITH A/C EQUIPMENT NAMEPLATES, IF DIFFERENT FROM THOSE SPECIFIED ON
DRAWINGS, AS WELL AS ANY FEEDER CHANGES BEING AFFECTED BY THIS CHANGE. CONTRACTOR
SHALL MAKE ABOVE MENTIONED CHANGES AT NO EXTRA COST.
17.- ELECTRICAL CONTRACTOR SHALL COORDINATE WITH MECHANICAL CONTRACTOR TO PROVIDE ALL
REQUIRED J -BOXES AND CONDUITS FOR INSTALLATION OF CONTROL WIRING. LOW VOLTAGE
CONTROL WIRING AND THEIR TERMINATION IS THE RESPONSIBILITY OF THE MECHANICAL
CONTRACTOR.
18.- ELECTRICAL METER AND PANEL LOCATIONS SHOWN MAY VARY DEPENDING ON SERVICE
ENTRANCE LOCATION.
19. -ALL LIGHTING FIXTURES TO BE SELECTED BY THE OWNER /ARCHITECT, U.O.N. AND SHALL BE
INSTALLED BY THIS CONTRACTOR.
20.- BALANCE ALL PHASES AT EACH PANEL AND MDP /SERVICE MAINS.
21. -CHECK AVAILABLE ELECTRICAL SERVICE CHARACTERISTICS WITH THE LOCAL POWER COMPANY
PRIOR TO ORDERING ANY EQUIPMENT. INFORM THE ARCH /ENGINEER IF IT IS DIFFERENT FROM
WHAT IS SHOWN ON PLANS.
22.- ELECTRICAL CONTRACTOR SHALL ASSURE THAT ALL FEATURES OF SERVICE COMPLY WITH THE
POWER COMPANY'S REQUIREMENTS AND SHALL MAKE ALL NECESSARY ARRANGEMENTS WITH POWER
COMPANY FOR SERVICE. ALL EQUIPMENT NOT FURNISHED AND /OR INSTALLED BY THE POWER CO.
IS TO BE FURNISHED AND INSTALLED BY THE ELECTRICAL CONTRACTOR.
23.- U.O.N., COORDINATE REQUIRED A.I.C. RATINGS WITH POWER COMPANY.
24. -WHERE MORE THAN ONE DEVICE IS INDICATED AT ANY LOCATION, THESE SHALL BE GANGED
UNDER ONE COMMON COVER.
25.- QUANTITY AND LOCATION OF ELECTRICAL, TELEPHONE /DATA & TV OUTLETS, LIGHTS AND LIGHT
CONTROLS, SHALL BE ADJUSTED TO SUIT THE OWNER'S REQUIREMENTS AS PER OWNER /ARCHITECT
INSTRUCTIONS. SAID ARRANGEMENTS SHALL NOT BE IN CONFLICT WITH APPLICABLE CODES.
26.- ELECTRICAL CONTRACTOR SHALL VERIFY REQUIREMENTS, EXACT LOCATIONS, TYPE AND
ARRANGEMENT OF OUTLETS FOR ALL ELECTRICAL FIXTURES, APPLIANCES AND EQUIPMENT, PRIOR
TO INSTALLATION.
27.- PROVIDE A TYPEWRITTEN DIRECTORY FOR EACH ELECTRICAL PANEL.
28.- CONTRACTOR SHALL FURNISH AS -BUILT DRAWINGS TO THE OWNER UPON COMPLETION OF
WORK AND PRIOR TO FINAL PAYMENT.
29.- OUTLET BOXES SHALL BE PRESSED STEEL IN DRY LOCATIONS, CAST ALLOY WITH THREADED
HUBS IN WET /DAMP LOCATIONS AND SPECIAL ENCLOSURES AS REQUIRED FOR OTHER CLASSIFIED
AREAS AND SHALL CONFORM TO NEMA STANDARDS. PLASTIC BOXES MAY BE USED WHERE
PERMITTED UNDER APPLICABLE CODES AND ORDINANCES.
30. -ALL DISCONNECT SWITCHES SHALL BE SIZED BY NEC REQUIREMENTS TO ACCOMODATE THE
EQUIPMENT SERVED, INCLUDING REJECTION CLIPS AND FUSES, WHEN APPLICABLE. SWITCHES
SHALL BE HP RATED, QUICK -MAKE, QUICK - BREAK, IN NEMA 1 ENCLOSURES FOR INDOOR AND
NEMA 3R FOR OUTDOOR.
CIRCUIT SEE PLAN WIRE 12 BRKR 20 AMP
SMOKE DETECTOR -�
KITCHEN OR
BATHROOM LIGHT
SWITCH
120V
PHASE CONDUCTOR
SMOKE DETECTOR CONNECTION DETAIL
PHASE: 10
BY -
�1 2 -20 -13
OPL
NEW SUBPANEL "Bn
Many Lariga
Scale
MAKE: SIEMENS
MAKE: SIEMENS
VOLTAGE: 120/240 v
VOLTAGE: 120/240 v
Q
J
L'-
Q
Z
Z
Q
TYPE: G203OLl150CU
°
`0
00
TYPE: G203OLl150CU
PANEL AMPS: 70 Amps
(BRANCH BREAKERS TYPE QP, 10KAIC)
(BRANCH BREAKERS TYPE
QP, 10KAIC)
MAIN BREAKER: 125 AMP
Ckt
No.
MAIN BREAKER: 70 AMP
SPEC
Ckt
USE
SPEC
VOLT
BKR
WIRE
COND
VA
PH
VA
COND
WIRE
BKR
VOLT
SPEC
USE
Ckt
q
B
No.
120
20
12
AMP
AWG
SIZE
Q
1,500
SIZE
AWG
AMP
120
SMALL APPLIANCE
No.
1
A.H.U. #1 **
240
50
6
RM
8,184
4,186
3/4
10
25
240
NCL
C.U. 1 **
2
3
.l.
41
ry
-
11,
1
•L
4
5
NEW BEDROOM LIGHTS & RECEPTACLES
120
15
14
RM
s
*
RM
14
15
120
NEW BEDROOM LIGHTS & RECEPTACLES
6
7
INEW BEDROOM LIGHTS & RECEPTACLES
120
15
14
RM
*
1,500
RM
12
20
120
SPACE
8
9
1
240
30
8
RM
5,000
1,500
RM
12
20
120
REFRIGERATOR
10
* SEE Load CALCULATION
41
.L
*
** VERIFY NAME PLATE
14
15
120
GENERAL RECEPTACLES
14
15
GENERAL UGHTS & RECEPTACLES
120
GFI = GROUND FAULT INTERRUPTER.
14
RM
*
1,500
RM
12
20
120
NCL = NON CONCURRENT LOAD.
SMALL APPLIANCES
16
17
GENERAL UGHTS & RECEPTACLES
120
15
14
RM
*
RM = ROMEX.
5,000
RM
10
30
240
CLOTHES DRYER
18
19
NOTE -1:
ALL 120 -VOLT, SINGLE - PHASE, 15- AND 20- AMPERE BRANCH CIRCUITS SUPPLYING OUTLETS
INSTALLED IN DWELLING UNIT FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,PARLORS, LIBRARIES,
DENS, BEDROOMS,
SUN ROOMS, RECREATION ROOMS, CLOSETS, HALLWAYS, OR SIMILAR ROOMS OR AREAS SHALL BE
PROTECTED BY A LISTED ARC FAULT CIRCUITINTERRUPTER,
COMBINATION -TYPE, INSTALLED TO PROVIDE PROTECTION OF THE BRANCH CIRCUIT. (2008 NEC.
210.12B
NOTE -2:
IN ALL AREAS SPECIFIED IN NOTE -1, ALL 125 -VOLT, 15 AND 20 AMPERE RECEPTACLES
SHALL BE LISTED TAMPER RESISTANT RECEPTACLES.
ELECTRICAL PLAN
SC: 1/4 if
PHASE: 10
BY -
�1 2 -20 -13
OPL
EXISTING PANEL ��A��
Many Lariga
Scale
MAKE: SIEMENS
Job No
VOLTAGE: 120/240 v
Sheet E 1
ELECTRICAL PLAN
Q
J
L'-
Q
Z
Z
Q
TYPE: G203OLl150CU
°
`0
00
PANEL AMPS: 125 Amps
z
(BRANCH BREAKERS TYPE QP, 10KAIC)
MAIN BREAKER: 125 AMP
Ckt
No.
USE
SPEC
VOLT
BKR
AMP
WIRE
AWG
COND
SIZE
VA
Mn
N
VA
COND
SIZE
WIRE
AWG
BKR
AMP
VOLT
SPEC
USE
Ckt
No.
A
B
1
GENERAL UGHTS & RECEPTACLES
L,J
LD
Q
�
Q
120
20
12
RM
1,200
Q
1,500
RM
12
20
120
SMALL APPLIANCE
2
3
RANGE **
240
60
6
RM
9,600
s
RM
4
70
240
`D
SUBPANEL "8" **
4
5
.f,
N!,
ry
11,
1
11,
6
7
1 DISHWASHER **
120
20
12
RM
1,200
*
RM
14
15
120
GENERAL RECEPTACLES
8
9
GENERAL UGHTS
120
15
14
RM
*
1,500
RM
12
20
120
SMALL APPLIANCES
10
11
WATER HEATER
240
30
8
RM
5,000
1,500
RM
12
20
120
REFRIGERATOR
12
13
41
.L
*
RM
14
15
120
GENERAL RECEPTACLES
14
15
GENERAL UGHTS & RECEPTACLES
120
15
14
RM
*
1,500
RM
12
20
120
SMALL APPLIANCES
16
17
GENERAL UGHTS & RECEPTACLES
120
15
14
RM
*
5,000
RM
10
30
240
CLOTHES DRYER
18
19
CLOTH WASHER
120
20
12
RM
1,500
11,
14,
20
21
SPACE
1,000 *
RM
12
20
120
NEW BATHROOM RECEPTACLE GFI
22
23
24
* SEE Load CALCULATION
Load Calculation Calculation
** VERIFY NAME PLATE
As per N.E.0 Art. 220.30 Section B.
GFI = GROUND FAULT INTERRUPTER.
1,657 sqf x 3 va /sqf = 4,971 va
Other Loads = 26,800 va
NCL = NON CONCURRENT LOAD.
Subtotal = 31,771 va
RM = ROMEX.
First 10,000 va ® 100% = 10,000
va
Rest 21,771 va ® 40% = 8,708 va
Subtotal = 18,708
va
A/C Load = 8,184 va
Total VA = 26,892 va
Panel Load = 26,892/240 = 112 Amps
A/C CALCULATIONS
240V -10
\ ►'
COMPRESSOR: 16.7 AMP HEATER: 7,200 VA
CONDENSER FAN: 0.74 AMP
EVAP. BLOWER: 4.1 AMP EVAP. BLOWER: 4.1 A x 240 V = 980 VA
21.54 AMP
TOTAL VA = 21.54 A x 240 V = 5,170 VA TOTAL HEATER = 8,184 VA
SELECT LARGER NON CONCURRENT A/C LOAD: 8,184VA
.r`
OSCRRIPOSRDA
ARCHITECT
AR 0016550
9231 SW 12 ST.
Miami Fl. 33174
305 -554 1094
786- 6835155
Fax: 305 - 5541134
ARENCO ®AOL.COM
REVISION
BY -
�1 2 -20 -13
OPL
File
Many Lariga
DESIGNS, ARRANGEMENTS,
SPECIFICATIONS ARE OWNED
ROPERTY OF THIS OFFICE
1TED, INVOLVED AND DEVEL-
BE
USE BY OR DISCLOSE
FIRM OR CORPORATIO:
WITHOUT THE wRriTEl
OSCAR A. POSADA
Drawn by
O•P
N
10- 10- 10
File
Many Lariga
Scale
Li
Job No
2010012
Sheet E 1
ELECTRICAL PLAN
Q
J
L'-
Q
Z
Z
Q
r1l
L,_J
=
°
`0
00
z
L U
S
W
F-
N
L,J
D
L d
I
.y
Z
ED
U
O
0
-
F--
r
�
Q
n
°
L,J
LD
Q
�
Q
00
In
3
o
Z
LLJ
z
�
=
L7
Q
c--
H
°
N
`D
ry
DESIGNS, ARRANGEMENTS,
SPECIFICATIONS ARE OWNED
ROPERTY OF THIS OFFICE
1TED, INVOLVED AND DEVEL-
BE
USE BY OR DISCLOSE
FIRM OR CORPORATIO:
WITHOUT THE wRriTEl
OSCAR A. POSADA
Drawn by
O•P
Date
10- 10- 10
File
Many Lariga
Scale
AS SHOWN
Job No
2010012
Sheet E 1
ELECTRICAL PLAN