12-986-004IX6YT
HVAC GENERAL NOTES
1. ALL WORK SHALL CONFORM WITH ALL LOCAL, STATE, FEDERAL ORDINANCES AND BUILDING
9. SHOP DRAWINGS: CONTRACTOR SHALL FURNISH THE ENGINEER WITH SHOP DRAWINGS OF
CODES GOVERNING THE INSTALLATION OF THE MECHANICAL SYSTEM. IF WORK AS LAID OUT,
EQUIPMENT PRIOR TO PURCHASE FOR APPROVAL.
INDICATED OR SPECIFIED IS CONTRARY TO OR CONFLICTS WITH FIELD CONDITIONS, LOCAL
SA, S.A.,
ORDINANCES, BUILDING CODES AND REGULATIONS, THE CONTRACTOR SHALL REPORT IN
10. AT COMPLETION OF JOB THE MECHANICAL CONTRACTOR SHALL GIVE THE OWNER AN
WRITING TO THE ARCHITECT /ENGINEER BEFORE SUBMITTING A BID OR PROCEEDING WITH
AS —BUILT SET OF REPRODUCIBLE DRAWINGS SHOWING THE EXACT LOCATION OF ALL
WORK. THE ARCHITECT /ENGINEER WILL THEN ISSUE INSTRUCTIONS AS HOW TO PROCEED.
INSTALLATIONS.
2. THE DRAWINGS ARE TO BE CONSIDERED DIAGRAMMATIC, NOT NECESSARILY SHOWING IN
11. THE CONTRACTOR SHALL FURNISH ALL LABOR, MATERIAL AND EQUIPMENT
DETAIL OR TO SCALE ALL OF THE MINOR ITEMS. UNLESS SPECIFIC DIMENSIONS ARE SHOWN,
FOR A COMPLETE H.V.A.C. SYSTEM IN ACCORDANCE WITH THESE DRAWINGS. THE FLORIDA
THE STRUCTURAL, ARCHITECTURAL AND SITE CONDITIONS SHALL GOVERN THE EXACT
BUILDING CODE AND THE LATEST EDITION OF THE FOLLOWING
LOCATIONS. CONTRACTOR SHALL FOLLOW DRAWINGS IN LAYING OUT WORK, CHECK DRAWINGS
PUBLICATIONS:
OF ALL TRADES TO VERIFY SPACES IN WHICH WORK WILL BE INSTALLED AND MAINTAIN
a) ANS B91. MECHANICAL REFRIGERATION
MAXIMUM HEAD ROOM, AND SPACE CONDITIONS AT ALL POINTS. COORDINATE LOCATION OF
b) NFPA PAMPHLETS 90A & 91
DUCTWORK WITH OTHER TRADES, PARTICULARLY WHERE DUCTS RUN THROUGH STRUCTURAL
c) SMACNA
ELEMENTS. PROVIDE ALL NECESSARY SLEEVES BEFORE CONCRETE IS POURED. WHERE HEAD
d) ASHRAE
ROOM, OR SPACE CONDITIONS APPEAR INADEQUATE, ARCHITECT/ ENGINEER SHALL BE
N
NOTIFIED BEFORE PROCEEDING WITH INSTALLATION. THIS CONTRACTOR SHALL, WITHOUT EXTRA
12. ALL SUPPLY AIR CONDITIONING DUCTWORK SHALL BE 1%" STANDARD DUTY (R -6) FULL
CHARGE, MAKE FIELD MODIFICATION IN LAYOUT AS NEEDED TO PREVENT CONFLICT WITH WORK
REINFORCED FIBERGLASS WITH MANUFACTURE LOGO PRINTED ON THE VAPOR BARRIER WHEN
OF VARIOUS TRADES OR FOR PROPER EXECUTION OF THE WORK.
IN UNCONDITIONED SPACE, AND 3/4" STANDARD DUTY FOIL REINFORCED FIBERGLASS (R -4)
NO
WITH MANUFACTURE LOGO PRINTED ON THE VAPOR BARRIER IN CONDITIONED SPACE OR
3. EXAMINE ALL DRAWINGS CAREFULLY PRIOR TO SUBMITTING A BID. CONTRACTOR WILL BE
RETURN PLENUM SPACE. R -6 FLEXIBLE DUCTS ARE ACCEPTABLE AS SHOWN ON DRAWINGS.
REQUIRED TO FURNISH, INSTALL AND /OR CONNECT WITH APPROPRIATE SERVICES ALL
�
ED
z
PLUMBING ITEMS SHOWN ON ANY OF THE ARCHITECTURAL, AIR CONDITIONING, ELECTRICAL AND
13. ALL EXHAUST AIR DUCTWORK SHALL BE CODE GAGE GALVANIZED SHEET METAL.
SPRINKLER DRAWINGS WITHOUT ADDITIONAL EXPENSE TO THE OWNER. IF DISCREPANCIES,
Q
CONFLICTS, INTERFERENCE OR OMISSIONS OCCUR BETWEEN DRAWINGS, NOTIFY IN WRITING THE
14. DUCT SIZES SHOWN ARE NET FREE AREA.
ARCHITECT /ENGINEER IN AMPLE TIME TO PERMIT REVISIONS BEFORE THE BIDS ARE
F-1
SUBMITTED.
15. ALL AIR DEVICES (DIFFUSERS, REGISTERS, AND GRILLES) SHALL BE ALL
CD
ALUMINUM CONSTRUCTION, WITH EXPOSED SURFACE CHEMICALLY TREATED TO
4. INSTALL MATERIALS AND EQUIPMENT IN A NEAT AND FIRST CLASS WORKMANLIKE MANNER.
RECEIVE PAINT TO MATCH COLOR OF AIRGUIDE OR APPROVED EQUAL.
THE OWNER RESERVES THE RIGHT TO DIRECT REMOVAL AND REPLACEMENT OF ITEMS WHICH,
IN HIS OPINION, DO NOT PRESENT A NEAT AND WORKMANLIKE APPEARANCE. REMOVAL AND
16. PROVIDE TURNING VANES AT ALL ELBOWS. PROVIDE MULTIPLE VANE EXTRACTORS OR
REPLACEMENT IS TO BE DONE IMMEDIATELY WHEN DIRECTED BY THE OWNER IN WRITING,
SPLITTERS WITH CONTROL RODS AT ALL OUTLETS CONNECTED CLOSER THAN TWO DUCT
AT THE SOLE EXPENSE OF CONTRACTOR.
DIAMETERS TO MAIN SUPPLY DUCT AND WHERE SHOWN ON DRAWINGS. PROVIDE ALL
`0
NECESSARY ACCESS PANELS TO CONTROL VALVES, DAMPERS, ETC.
5. START OF WORK BY CONTRACTOR SHALL BE CONSIDERED AS ACCEPTANCE BY HIM OF
ALL CLAIMS OR QUESTIONS AS TO SUITABILITY OF THE WORK OF OTHER. TRADES OR OTHER
17. REFRIGERANT PIPING SHALL BE SEAMLESS COPPER TYPE "L" HARD OR SOFT DRAWN OR
CONTRACTORS TO RECEIVE HIS WORK. THIS CONTRACTOR SHALL REMOVE AND REPLACE, AT
ACR COPPER TUBING WITH WROUGHT COPPER SOLDER JOINT FITTINGS. SOLDER SHALL BE
HIS EXPENSE, ALL MECHANICAL WORK WHICH MAY HAVE TO BE REMOVED BECAUSE OF
95/5, APPLIED WITH SUITABLE FLUX. INSULATE REFRIGERANT SUCTION PIPING WITH 3/4"
INTERFERENCE WITH OTHER TRADES.
FIRE RESISTANT FOAM PLASTIC OR CLOSED CELL POLYETHYLENE PRE — MOLDED PIPE
6. THIS CONTRACTOR SHALL OBTAIN AND PAY ALL INSURANCE, FEES, PERMITS, ASSOCIATION
INSULATION.
DUES, ROYALTIES AND TAXES OF WHATEVER NATURE SHALL APPLY TO THIS WORK. HE SHALL
18. ALL CONTROL WIRING SHALL BE THE RESPONSIBILITY OF THE MECHANICAL
ALSO PAID ALL THE INSPECTION FEES AS MAY BE REQUIRED BY LAW OR ORDINANCE AND
SUB — CONTRACTOR. MECHANICAL SUB CONTRACTOR TO FURNISH ALL MOTORS, STARTERS,
SHALL KEEP THE OWNER HARMLESS FROM ANY DAMAGE AND EXPENSE ARISING FROM ANY
AND RELAYS, ETC.
VIOLATION OF LAWS, RULES OR ORDINANCES.
7. PROVIDE MEANS "FURNISH AND INSTALL ".
19. FOR INSTALLATION OF ANY ROOF OR WALL MOUNTED EQUIPMENT REFER TO
ARCHITECTURAL STRUCTURAL ENGINEERING DRAWINGS.
8. DO A COMPLETE JOB, EVERYTHING CONNECTED, READY FOR USE.
1 IV 1 VI \L It 1 . VLI 1\11 11 IL L/\IJ IIIYV V/'ll \r\VL flll\ JVI 1 L-1
PICTURE # 2 : HOUSE RETURN AIR GRILL
CClory on1V to Cued
HVAC LEGEND
® F SUPPLY AIR DIFFUSERS (SEE
SCHEDULE) DUCT TO MATCH NECK
SIZE TYP.
toxe NEW DUCT (WIDTH X DEPTH)
pT PROGRAMMABLE THERMOSTAT
AIR FLOW DIRECTION (ARROWS
DENOTE 1 WAY, 2 WAY, ETC., SEE
PLANS)
RETURN OR EXHAUST, SEE PLANS.
EXHAUST FAN
E EXISTING TO REMAIN
R EXISTING TO BE RELOCATED
AHU AIR HANDLING UNIT
CU
SCHEDULE
CONDENSING UNIT
RA, R.A.,
R/A
RETURN AIR
SA, S.A.,
S/A
SUPPLY AIR
TA, T.A.,
T/A
TRANSFER AIR
UC
BROAN
DOOR UNDERCUT (1" TYP.)
RAG
S50U
RETURN AIR GRILLE
SAG
50
SUPPLY AIR GRILLE
FAN
SCHEDULE
FAN DESIGNATION
10- 10- 10
EF -1
AREA SERVED
W
TOILET
LOCATION
Q
J
�
CEILING
MANUFACTURER
BROAN
MODEL NO.
CD
�
CO
S50U
TOTAL AIR (CFM)
50
E.S.P. INCHES OF WATER
0.125
SONES
I—
0.5
H.P. (A =AMP - W =WATTS
`D
0.15
VOLT -PH -HZ
N
120 -1 -60
DRIVE
D
DIRECT
BACKDRAFT DAMPER
a
U
NO
INTERLOCK
L0
°
LIGHT SWITCH
REMARKS:
1. ALTERNATE MANUFACTURERS OF EQUAL OR BETTER
QUALITY MAY BE SUBMITTED FOR APPROVAL.
2. UNLESS OTHERWISE NOTED ALL FANS SHALL BE
EQUIPPED WITH SAFETY DISCONNECT SWITCH.
NEW 3' THEMOFIN TO 1
SOFFIT VENT THR
MECHANICAL PLAN SC: 1/4"
OSCARIP08ADA
ARCHITECT
AR 0016550
9231 SW 12 ST.
Miami Fl. 33174
305 -554 1094
786- 6835155
Fax: 305 - 5541134
ARENCO@AOL.COM
REVISION BY
ALL CONCEPTS, DESIGNS, ARRANGEMENTS,
DRAWINGS AND SPECIFICATIONS ARE OWNED
AND ARE THE PROPERTY OF THIS OFFICE
AND WERE CREATED, INVOLVED AND DEVEL-
OPED FOR USE ON AND IN CONJUCTION
WITH THE SPECIFIC PROJECT. NO IDEA,
DESIGN, ARRANGEMENT OR PLAN SHALL BE
USE BY OR DISCLOSE TO ANY PERSON,
FIRM OR CORPORATION FOR ANY PURPOSE
WITHOUT THE WRITTEN PERMISSION OF:
OSCAR A. POSADA ARCHITECT.
Drawn by
O.P
N
10- 10- 10
File
Many Lariga
W
AS SHOWN
Job No
Q
J
�
Q
Z
Z
�
Q
W
=
CD
�
CO
F-i
Q
W
I—
_
`D
Q�
I—
N
LIJ
D
L�J
I
a
U
ED
_
I-
ly
2:
:
L0
°
Ld
0
Q
Q
00
Lr)
3
�
ED
z
L,J
o
L3
Q
CL
F-1
CD
ci�
(LI
`0
ALL CONCEPTS, DESIGNS, ARRANGEMENTS,
DRAWINGS AND SPECIFICATIONS ARE OWNED
AND ARE THE PROPERTY OF THIS OFFICE
AND WERE CREATED, INVOLVED AND DEVEL-
OPED FOR USE ON AND IN CONJUCTION
WITH THE SPECIFIC PROJECT. NO IDEA,
DESIGN, ARRANGEMENT OR PLAN SHALL BE
USE BY OR DISCLOSE TO ANY PERSON,
FIRM OR CORPORATION FOR ANY PURPOSE
WITHOUT THE WRITTEN PERMISSION OF:
OSCAR A. POSADA ARCHITECT.
Drawn by
O.P
Date
10- 10- 10
File
Many Lariga
Scale
AS SHOWN
Job No
2010012
Sheet M 1
MECHANICAL PLAN
° ° °�pQODODDD00p00
o° 0 F FL
0 A 0 °0000000 �
° �°
v °° p °
45v .0 06N 00
o �o
7-tA
� 00
ca E * ° O /°
a o . o ti
°e o ° 2a o
° V o
s° � o AR. 0018550 �o
°° o
00 0 � O
°00.00000
° °°o��EDD D o g o ° °oo