14-384-022
PRODUCED BY AN AUTODESK EDUCATIONAL PRODUCT SLICTRICAL SPECIFICATIONS I: GENERAL PLANS: WIRE 6 CABLES: THE GENERAL AND SPECIAL CONDITIONS AND REQUIREMENTS SHALL BE A PART OF THE WORK HEREBY SPECIFIED. THESE SPECIFICATIONS AND ACCOMPANYING PLANS ARE INTENDED TO PROVIDE FOR THE DM N E C PLETE FURNISHING AND INSTALLATION OF THE ELECTRICAL SYSTEMS. TO PROVIDE DRAWINGS ARE BASICALLY DIAGRAMS INTENDED TO DEPICT APPROXIMATELY EQUIPMENT LOCATIONS AND ARRANGEMENTS, NOT 10 SHOW EVERY All POWER CONDUCTORS SHAH BE COPPER. WIRING IN DUCTS, PLENUMS AND OTHER AIR HANDLING SPACES SHALL COMPLY WITH NEC ARTICLE MEANS TO FURNISH AND INSTALL MINOR DETAIL PLANS SHALL NOT BE SCALED TO DETERMINE EXACT LOCATION AND DIMENSIONS. 300.22, MINIMUM SIZE SHALL BE # 12 AWG FOR POWER WIRING AND # 16 AWG FOR CONTROL CIRCUITS. INSULATION SHALL BE GOOV THHN OR COMPLIANCE: INTERFERENCE: THWN FOR GENERAL USE AND COLOR CODED AS PER NEC AND TRADE STANDARDS. WORKMANSHIP, MATERIALS AND INSTALLATION SHAH BE IN STRICT ACCORDANCE WITH THE APPLICABLE EDITION OF THE FOLLOWING CODES: THE CONTRACTOR SHAH COORDINATE HIS WORK WITH OTHER TRADES SO THAT INTERFERENCE WITH EXISTING CONDITIONS. CONDUITS. PIPING, AND CABLES SHALL BE LABELED TO INDICATE DILATE CIRCUIT NUMBERS AND SOURCE. FLORIDA BUILDING CODE, NFPA -70 NATIONAL ELECTRICAL CODE, NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION NEMA . AMERICAN EQUIPMENT, AND ARCHITECTURAL AND STRUCTURAL MEMBERS IS AVOIDED. CONDUCTOR CALCULATIONS ARE BASED ON 75 ° C. NATIONAL STANDARDS INSTITUTE ANSI, UNDERWRITERS' LABORATORY. INC. AND OTHER APPLICABLE NATIONAL. STATE, AND LOCAL CODES AND TESTING: SWITCHGEAR, BREAKERS AND DISCONNECTS: PERTAINING REGULATIONS ESTABLISHED BY THE RULING AUTHORITY HAVING JURISDICTION. CONTRACTORS SHAH ALSO MEET THE REQUIREMENTS NO WORK SHAH BE ENCLOSED BEFORE All REQUIRED INSPECTIONS AND TESTS HAVE BEEN PERFORMED. ANY WORK PREMATURELY CLOSED SHAH WHEN SPECIFIED THE DISCONNECTS SHALL Q I L 6E U CK MAKE^ QUICK -BREAK ACTION, LOCKABLE TYPE. SERVICE DISCONNECT SHAH BE SERVICE OF OTHER STANDARDS WHERE SUCH REQUIREMENTS ARE MORE STRICT THAN THOSE STANDARDS CITED ABOVE. BE REOPENED FOR INSPECTION AND RESTORATION OF ALL WORK THEREBY SHALL BE AT THE CONTRACTOR'S EXPENSE. RATED AND HEAVY -DUTY TYPE. PROVIDE DUAL ELEMENT, PROPERLY SIZED FUSES, AS PER MANUFACTURER'S RECOMMENDATIONS, FOR MOTORS OF WORKMANSHIP: FIELD CHANGES: ELECTRICALLY DRIVEN MECHANICAL EQUIPMENT. FIELD COORDINATE FUSE SIZE WITH EQUIPMENT NAMEPLATE BEFORE ACTUAL INSTALLATION. ALL WORK SHALL BE PERFORMED BY CONTRACTORS LICENSED IN THEIR RESPECTIVE DISCIPLINE. WORK SHALL BE DONE IN A FIRST CLASS MANNER. THE ELECTRICAL CONTRACTOR SHALL CONSULT THE ENGINEER BEFORE THE IMPLEMENTATION OF FIELD CHANGES, MODIFICATIONS OR ADDITIONS CIRCUIT BREAKERS IN POWER OR LIGHTING PANELBOARDS SHALL BE MOLDED CASE, BOLT -ON TYPE, OF QUICK -MAKE ACTION, THERMAL MAGNETIC FULLY OPERATIVE, AND TO THE ACCEPTANCE OF THE ARCHITECT AND THE ENGINEERS. CONTRACTOR SHALL PROVIDE FOR ALL NECESSARY LABOR COVERING ELECTRICAL EQUIPMENT. ELECTRICAL INSTALLATION, DISTRIBUTION OF THE ELECTRICAL LOADS, ELECTRICAL RISER OR SERVICE TRIP DEVICES. LOAD CENTER TYPE ELECTRICAL PANELS MAY BE USED WHERE SPECIFIED IN THE PLANS OR APPROVED BY THE ENGINEER. CIRCUIT AND MATERIAL REQUIRED FOR THE COMPLETION OF THE WORK INCLUDING BUT NOT LIMITED TO RELATED WORK SUCH AS CONNECTION OF EXISTING ENTRANCE THAT DEVIATES FROM THE ORIGINAL SIGNED, SEALED AND APPROVED ELECTRICAL PANS. BREAKERS IN LOAD CENTER TYPE ELECTRICAL PANELS SHALL BE MOLDED CASE, PLUG -IN TYPE, OF UUICK -MAKE ACTION, THERMAL MAGNETIC TRIP SYSTEMS. PROPOSED ELECTRICAL CHANGES, ADDITIONS AND MODIFICATIONS THAT DEVIATE FROM THE ORIGINAL SIGNED, SEALED PLANS ORIGINALLY DEVICES. UNLESS OTHERWISE NOTED ON THE PLANS, MINIMUM EQUIPMENT A.I.C. RMS SYMMETRICAL AMPERE RATING SHALL BE 10.000 AMPS AT MATERIALS: APPROVED BY THE BUILDING DEPT. WHICH ARE INTENDED TO BE INCLUDED BY THE ELECTRICAL CONTRACTOR IN ITS "AS- BUILT" DRAWINGS SHALL 120/240 VOLTS DR AS SPECIFIED IN THE PLANS. A.-CONTRACTOR SHALL PROVIDE ALL NEW MATERIALS OF AMERICAN MANUFACTURE, BEARING THE UNDERWRITER'S LABORATORY (UL) LABEL AS BE REVIEWED BY THE ENGINEER FOR A WRITTEN APPROVAL BEFORE THE CHANGES, MODIFICATIONS OR ADDITIONS ARE IMPLEMENTED. IHE ENGINEER WHEN BREAKERS ARE TO BE INSTALLED IN AN EXISTING PANELBOARD, THE NEW CIRCUIT BREAKER MUST MAINTAIN THE A.I.C. RATING TO EQUAL OR APPLICABLE. MATERIALS SHALL BE NEW, SUITABLE FOR THE APPLICATION AND ABOVE STANDARD QUALITY NORMALLY USED FOR THE PURPOSE AS SHALL NOT BE RESPONSIBLE AND WILL NOT INTEGRATE FIELD CHANGES INTO THE ORIGINAL PLANS THAT HAVE NOT BEEN CONSULTED AND EXCEED THAT OF THE EXISTING BREAKERS. MANUFACTURER SHALL BE SIEMENS, GE, SGUARE -D , WESTINGHOUSE OR EQUIVALENT. CALLED FOR ON PLANS. PRE- APPROVED BEFORE THEIR FIELD IMPLEMENTATION. EQUIPMENT IDENTIFICATION: B.-SUPPLEMENTAL MATERIALS, PRODUCTS AND COMPONENTS NECESSARY TO COMPLY WITH THE INTENT OF THE CONTRACT DRAWINGS AND /OR THE INTEGRATION BY THE ENGINEER OF FIELD CHANGES, MODIFICATIONS AND ADDITIONS INTO THE ORIGINAL SET OF PLANS TO CREATE A FINAL OF PROVIDE MICARTA ENGRAVED NAMEPLATE (BLACK WITH WHITE LETTERING) FOR IDENTIFICATION OF SWITCHGEAR, BREAKERS, DISCONNECTS, SPECIFICATIONS, BUT NOT NOTED OR SPECIFIED ON THESE SECTIONS, SHAH BE PROVIDED BY THE CONTRACTOR AS REQUIRED FOR THE "AS- BUILT" PLANS IS NOT INCLUDED IN THE ORIGINAL CONTRACT AND SHALL BE CONSIDERED AN OPTIONAL ITEM. TRANSFORMERS, AND PANELBOARDS. COMPLETION OF THE WORK AT NO ADDITIONAL COST TO THE OWNER. PART 2- PRODUCTS CONNECTORS, LUGS AND SPLICES: C.-CONTRACTOR SHALL BE RESPONSIBLE FOR PROVISIONS AND COORDINATION OF DELIVERY OF MATERIALS. EQUIPMENT MARRED DURING PRODUCT QUALITY AND CONFORMANCE- SPLICES SHALL BE MADE WITH UL LISTED MECHANICAL PRESSURE AND SOLDERLESS CONNECTORS. BURNDY SERVICE TYPE OR APPROVED EQUAL SHIPMENT OR INSTALLATION SHALL BE TOUCHED UP AND REFINISHED TO FACTORY FINISH, REPLACED WHERE NOT ACCEPTABLE. ALL PRODUCTS SHALL BE NEW AND UNUSED. RECEIVED IN ORIGINAL CONTAINERS, INSTALLED AND TURNED OVER TO THE OWNER FREE OF DEFECTS, FEEDER SPLICES AND TERMINATIONS SHALL BE MADE MECHANICALLY USING COMPRESSION TYPE SLEEVES OR LUGS AND CONNECTION TO PANELS PERMITS AND INSURANCE: ALL PRODUCTS SHALL BE APPLIED IN ACCORDANCE WITH THE REQUIREMENT OF NEC. AND SWITCHES AS MANUFACTURED BY BURNDY OR THOMAS B BETTS. CONTRACTOR SHALL SECURE AND PAY FOR ALL PERMITS, FEES, TAXES, INSPECTIONS, TESTS, FINES AND OTHER ITEMS AS REQUIRED FOR THE ALL PRODUCTS SHALL BE UL LISTED FOR THE INTENDED APPLICATION. TAPE, CONNECTORS AND LUGS SHALL BE RATED THE SAME TEMPERATURE AND DUTY AS CABLE INSULATION AND SHALL BE SIZED FOR SPECIFIC INSTALLATION OF THE COMPLETE ELECTRICAL SYSTEMS AS OUTLINED HEREIN AND SHOWN ON PLANS. CONTRACTOR SHALL PROVIDE ALL REQUIRED RACEWAYS: CONDUCTORS INSTALLED. INSURANCE FOR PROTECTION AGAINST PUBLIC LIABILITY AND PROPERTY DAMAGE FOR THE DURATION OF THE WORK ALL CLASS I POWER 020V AND ABOVE) SHALL BE INSTALLED IN RACEWAYS. BOXES, FITTINGS AND COVERS EXISTING CONDITIONS - EMT: SHALL BE USED FOR INTERIOR SPACES WHERE NOT EXPOSED TO PHYSICAL DAMAGE. FITTINGS SHALL BE STEEL OR DIE CAST. CONDUITS FOR DEVICES AND OUTLET BOXES CONCEALED UTILIZE GALVANIZED STEEL BOXES, MINIMUM 1 -1/2" DEPTH. UTILIZE BOXES SIZED IN ACCORDANCE BEFORE BIDDING, THE CONTRACTOR SHALL VISIT THE JOB SITE. TAKE THE NECESSARY MEASUREMENTS, VERIFY THE EXACT LOCATION OF BUILDING, SHAH BE USED FOR RACEWAYS CONCEALED IN WALLS, ABOVE CEILINGS OR IN CONCEALED SPACES. WITH NEC VOLUMETRIC REQUIREMENTS OR AS SPECIFIED ON THE DRAWINGS. LOCATION OF THE ELECTRICAL ROOM, DISTANCE BETWEEN THE ELECTRICAL ROOM AND LOCATION OF PANELS, UTILITIES AND ASCERTAIN ALL ENT MAY BE USED AS LONG AS ITS USE AND INSTALLATION COMPLIES WITH THE NEC ARTICLE 362. FOR JUNCTION BOXES AND PULL BOXES UTILIZE GALVANIZED SHEET STEEL. WITH PROTECTIVE PRIMING COAT AND FINISH COAT OF ENAMEL ON ALL EXISTING CONDITIONS WHICH WILL AFFECT HIS WORK IN ORDER TO PROVIDE FOR AN INTELLIGENT BID. FAILURE TO DO SO WILL NOT BE ACCEPTED - RMC AND IMC: RIGID METAL CONDUIT SHALL BE USED IN EXPOSED LOCATIONS UP TO 5 FEET ABOVE FINISHED FLOOR. HOT- DIPPED GALVANIZED SIDES. MINIMUM J -BOXES SIZES SHALL BE IN ACCORDANCE TO NEC AND NO LESS IN THICKNESS THAN NEC STANDARD FOR DIMENSIONS OF AS A REASON FOR REQUESTING EXTRA PAY WHERE THE EXISTING CONDITIONS RESULT IN EXTRA MATERIALS OR LABOR. ANY EXISTING CONDITIONS INCLUDING THREADS. PROVIDE FOR HAZARDOUS LOCATIONS, EXTERIOR LOCATIONS, WHERE EXPOSED TO PHYSICAL DAMAGE AND FOR ELBOWS INTO CABINETS. FOUND BY THE CONTRACTOR WHICH WILL ADVERSELY AFFECT THE WORK SHALL BE IMMEDIATELY BE BROUGHT TO THE ATTENTION OF THE THE GROUND OR THE SLAB. INSTALL ELLS AND RISERS STUBBED UP 6 INCHES FROM CONCEALED SLAB RUNS DR 48 INCHES ABOVE GROUND WHERE WIRING DEVICES ARCHITECT /ENGINEER. EXPOSED ON WALL RUNS BELOW THE SLAB OR FINISHED EXTERIOR GRADE SHALL BE PAINTED WITH TWO (2) COATS OF BITUSMATIC PAINT UP TO A RECEPTACLES: DUPLEX RECEPTACLES SHALL BE HUBBELL HEAVY DUTY OR APPROVED EQUAL 12OV, 20A, 3W, GROUNDED. COLOR SHALL BE IVORY # CUTTING AND PATCHING: POINT 2" ABOVE GRADE /SLAB. 5352 OR AS SPECIFIED IN PLANS. ISOLATED GROUND RECEPTACLES SHALL BE PROVIDED AS PER PLAN. GFI RECEPTACLES SHALL BE PROVIDED AS MAJOR CUTTING, PATCHING AND PAINTING REQUIRED BY THIS CONTRACT WILL BE PERFORMED IN A NEAT AND WORKMANLIKE MANNER. ALL - PVC SCHEDULE 40: MAY BE USED WHERE CONDUIT IS RUN IN CONCRETE SLABS OR 12" BELOW THE SLAB OR WHERE BURIED 24" BELOW FINISHED PER PLANS. SURFACES SHALL BE RETURNED TO ORIGINAL CONDITION AFTER THE INSTALLATION OF THE EQUIPMENT. GRADE OR 30" UNDER VEHICULAR TRAFFIC AREAS. GROUNDING AND BONDING GUARANTEES: PVC JACKETED FLEXIBLE METAL CONDUIT: MAY BE USED FOR MOTORS OR EXTERIOR EQUIPMENT CONNECTIONS, OUTSIDE LOCATIONS, WHERE GROUNDING AND BONDING SHALL COMPLY WITH NEC 250. ALL METALLIC RACEWAYS SHALL BE GROUNDED AND BONDED AS PER NEC ARTICLE 259. AFTER THE SYSTEM IS INSTALLED, THE CONTRACTOR SHALL CONDUCT AN OPERATIVE TEST FOR APPROVAL AND ACCEPTANCE BY THE EXPOSED TO MOISTURE. NON- METALLIC RACEWAYS SHALL BE PROVIDED WITH A GROUNDING CONDUCTOR SIZED AS PER NEC ARTICLE 250.122. ARCHITECT /OWNER. UNLESS THERE IS A WRITTEN CONTRACT SPECIFYING OTHERWISE, THE ENTIRE ELECTRICAL WORK. INCLUDING PARTS AND - UNDERGROUND RUNS: UNDERGROUND RUNS SHALL BE PROVIDED WITH A YELLOW RIBBON TAPED ALONG THE TRENCH G" BELOW GRADE FOR PROVIDE A SEPARATE EQUIPMENT GROUNDING CONDUCTOR "GREEN WIRE" IN ALL SUB- FEEDERS CIRCUITS AND ALSO IN ISOLATED GROUND BRANCH LABOR, SHALL BE GUARANTEED FUR A PERIOD OF ONE (1) YEAR FROM THE DATE OF FINAL WRITTEN ACCEPTANCE THEREOF AGAINST DEFECTIVE RACEWAY IDENTIFICATION. CIRCUITS AND IN BRANCH CIRCUITS WHERE NON - METALLIC CONDUIT IS USED, MATERIALS, CONSTRUCTION AND WORKMANSHIP - FLEXIBLE METAL CONDUIT: MAY BE USED INSIDE CABINETS. FLEXIBLE CONDUITS SHALL BE LIMITED TO 6 FEET IN LENGTH OR AN EQUIPMENT PROVIDE ISOLATED GROUND SYSTEM FOR ALL DATA AND COMMUNICATION EQUIPMENT LOAD. CIRCUITS AND LOADS: GROUNDING CONDUCTOR SHALL BE PROVIDED WITH THE BRANCH CIRCUIT CONDUCTORS AS PER NEC. MAY BE USED WITH LIGHTING FIXTURES, NEUTRAL ON THE SECONDARY OF A TRANSFORMER MUST BE GROUNDED AS PER NEC ARTICLES 25929(9) AND 250.30. THE CIRCUIT NUMBERS SHOWN ON THE PLANS ARE USED TO CALCULATED CIRCUIT LOADING. BREAKERS AND PANEL SIZE. THE CONTRACTOR MAY MOIORS, TRANSFORMERS AND VIBRATING EQUIPMENT CONNECTIONS IN LENGTH NO EXCEEDING 6 FEET. WATERTIGHT FLEXIBLE CONDUIT SHALL BE ' MODIFY CIRCUIT NUMBERING AND PROVIDE CIRCUIT ROUTINGS TO SUIT THE JOB CONDITIONS. LOAD DATA IS BASED UPON INFORMATION SUPPLIED USED FOR MOTORS OR EXTERIOR EQUIPMENT CONNECTIONS. BY THE OWNER AT THE TIME OF DESIGN. ALL EQUIPMENT AND PANEL SIZES SHAH BE VERIFIED BEFORE ORDERING. LOADS ON ALL PANELS SHALL BE HAIR REMOVAL -I 17 BALANCED BETWEEN PHASES. WHEN REQUIRED THE CONTRACTOR SHALL ADJUST PANEL SCHEDULE TO OBTAIN PROPER BALANCING OF ALL PHASES. o 18 DRYER TO FPL OPEN DELTA BANK 120/240V 39` OUTSIDE BUILDING DISTRI6. LINE GUTTER 12" x 12" x 6' :........ - .._._..._. ...... __. _ ........... ...... _..., .._......... ...__..... ............. _...... ............. ........ MAIN I OF 2 I .. - MAIN f OF 2 I FUSES € ! x FUSES 300 AMPS I K -7 400 AMPS METER CAN i I 39 s ° E .. ............. .._._ ...__. — ........... 22 KA PAC 22 KA IAC i "' 39 39 KIOJIN RESTAURANT :.. :. -... .......... . 1- #3/0 Cu TO FOUNDATION STEEL REBAR 1 - 0/0 Cu 70'-D" MIN LONG � 4- 590 MCM THWN IN 3" METAL COND. © 0 . E -2 I SCALE: NTS TYPE: LOAD CENTER 39 NEW PANEL "A" M.L.G. 200 A RATING SERVICE :120/240 V, 4 WIRE LA.0 : 2Z.000 A MOUNTING SURFACE LOCATION: SEE PLAN DISTRIB. GUTTER ID" x 10" x 41" POLES TRIP. i WIRE REMARKS CKT. A 8 06 6"240 I REMARKS BAY I....._..30 ...._;_. HOUSE I POLES ..........._. UNIFORM I: I _.... I .... -._. I HOUSE NEI 6 SHOES € MAIN 8 150A I� I 150A . 21 39 € :.. _. : 19 ---------- 3 3/4" LOAD GUTTER 2 6000 I HOUSE I HOUSE REMARKS PANEL -I PANEL -2 3 MLO MLO 120 V 19 IDDA IODA 249 V 19 I 19 I... _... 19 I .._ © 0 . E -2 I SCALE: NTS TYPE: LOAD CENTER 39 NEW PANEL "A" M.L.G. 200 A RATING SERVICE :120/240 V, 4 WIRE LA.0 : 2Z.000 A MOUNTING SURFACE LOCATION: SEE PLAN VOLT. AMPS. POLES TRIP. COND. WIRE REMARKS CKT. A 8 CKT. C REMARKS WIRE COND. TRIP^ POLES VOLT. AMPS. 7000 2 50 3/4° EF -2 (1/2HP) AHU -1 1 ° 2 A/C -I #8 3/4" 40 2 6000 A B CKT. REMARKS WIRE COND. 3 0 4 120 V 19 2000 va 249 V 19 I 7000 2 50 3/4 °' 2 AHU -2 5 120 V Ia 0 6 A/C 2 #8 3/4" 40 0 I/2 " #12 RECEPTACLES 3 0 7 o 8 ISO 1275 I 20 1/2 " 1 #12 1 EF -I 9 ol 1 10 W.N. TITAN 120 #6 1 /2 "' 60 I 1275 1 20 1/2" #12 NOT 120V LOAD 11 0 12 8 LIGHTING I 20 1/2" #12 EF -2 13 o 14 WASHER #12 1/2" 20 1 1500 20 1 1285 1 SPARE 15 0 16 SPARE o 12 WATER FOUNTAIN #12 ' 20 HAIR REMOVAL -I 17 o 18 DRYER #10 I/2" 30 2 5000 #12 1/2" 20 19 0 20 /2" #12 MICROWAVE 15 o 2 20 I/2°' #12 1 HAIR REMOVAL -3 21 o 22 HAIR REMOVAL -2 #12 1/2" 20 2 1 1440 0 IS SPARE 23 o 24 1 20 1/2" #12 REFRIGERATOR 25 0 26 SUB - PANEL'S' #4 1" 80 17904 189 1 20 1/2" #12 GFI RECEP BATH 27 ol 1 28 SPARE NOT 120VLOAD 29 1 ol 30 NOT 120VLOAD 36O I 20 1/2°' #12 PEDICURE CHAIR RECEP 31 o 1 1 32 GFI RECEP COUNTER #12 1/2" 20 1 36D I 20 1/2" #12 PEDICURE CHAIR RECEP 33 ol 1 34 SIGN OUTLET #12 1/2" 20 1 1500 FEEDER: 2 - # 4 THWN NOT 120V LOAD 35 lo 1 36 NOT 120V LOAD 360 1 20 1/2" #12 PEDICURE CHAIR RECEP 37 o 38 RECEPTACLES #12 1/2" 20 1620 1260 I 20 1/2 " #12 RECEPTACLES 39 0 1 40 1 RECEPTACLES #12 1/2" 20 1 1080 NOT 120V LOAD 41 Iol 42 1 NOT 120V LOAD FEEDER: 3 - # 3/0 THWN I- # 3/0 THWN NEUTRAL IN 2" METAL CONDUIT I- # 8 Cu E.G.C. TYPE: LOAD CENTER 19 B419 va WATER HEATER TITAN -120 R.A. REFRIGERATOR M.C. M.L.O. :100 A RATING 12060 va SERVICE :129/240 V. 3 WIRE ZELTIQ LIGHT BASED HAIR REMOVAL MACHIN -3 NEW SUB -PANEL "B" PEDICURE CHAIRS 1030 va I.A.0 :10.090 A MOUNTING SURFACE EF -I (IHP) IQ EF -2 (1/2HP) 120 V 19 LOCATION: SEE PLAN AMPS. POLES TRIP. COND. WIRE REMARKS CKT. A B CKT. REMARKS WIRE COND. TRIP. POLES AMPS. 120 V 19 2000 va 249 V 19 I RECEPTACLES i 0 2 RECEPTACLES 120 V Ia 1496 va 75% = 13842 va I 0 I/2 " #12 RECEPTACLES 3 0 4 ROD R C GF ISO 1275 LIGHTING 5 0 6 712 1275 1 20 1/2" #12 LIGHTING 7 0 8 LIGHTING 720 720 I 120 1/2" #12 LIGHTING 9 ID LIGTHING #12 I/2" 20 1 1285 1 20 1/2" #12 LTG HT NG II o 12 WATER FOUNTAIN #12 ' 20 RECEPTACLES 130 14 FLUOR LIGHTS #12 1/2" 20 I 79 /2" #12 MICROWAVE 15 o 16 RECEP DATA CENTER 720 600 1 29 1/2" #12 LIGHTING 17 0 IS SPARE SPARE 19 ol 20 SPARE SPARE 21 22 SPAR SPARE 23 0 24 SPARE Continuous Load x 1.25 = 8444 VA Receptacle load = 5760 VA (first IU,000VA 1@ 100 %, remainder 9 50 %) 25% of Largest Motor = OVA Other Loads = 3790 VA FEEDER: 2 - # 4 THWN 1714 VA 17994/240= 75 AMPS I- # 4 THWN NEUTRAL IN I" METAL CONDUIT SITE PLAN SCALE: 1/64" = V -0" LOAD CALCULATION: ( PANEL'A') LIGTHING LOAD: BAY AREA: 2245 x 3.0 = 6735 va SIGN LOAD: RECEPTACLES LOAD: (NEC 220.13) EQUIPMENT LOAD WATER FOUNTAIN B419 va WATER HEATER TITAN -120 R.A. REFRIGERATOR M.C. ZELTIQ LIGHT BASED HAIR REMOVAL MACHIN -1 12060 va ZELTIQ LIGHT BASED HAIR REMOVALMACHIN -2 10000 va 9 100% = ZELTIQ LIGHT BASED HAIR REMOVAL MACHIN -3 PEDICURE CHAIRS 1030 va DRYER WASHER MACHINE EF -I (IHP) IQ EF -2 (1/2HP) 120 V 19 A/C LOAD C I00%: A/C UNIT -I 5500 va A/C COMPRESSOR -1 6.0 KW 240 V HEATER ELEMENT -I 7.0 KW 240 V A/C UNIT -2 720 va A/C COMPRESSOR -2 6.0 KW 240 V HEATER ELEMENT -2 7.0 KW 240 V 6735 va x 1.25 = B419 va Drawn by: R.A. 1500 va M.C. 18D x 67 = 12060 va Project No: 10000 va 9 100% = IOOOOva REAMINED 2060 R 50 %= 1030 va 20949 va IQ HIGH LEG 120 V 19 1200 ve 240 V 19 5500 va 5500 va 120 V 19 1200 va 240 V 19 720 va 720 va 240 V 19 720 va 720 va 240 V 19 720 va 720 va 120 V 19 2000 va 249 V 19 2590 va 2500 va 120 V 19 1500 va 120 V Ia 900 va 120 V Ia 1496 va 75% = 13842 va 7620 va 19 19 3500 va 3500 va 19 13 3500 va 3500 va 7000 va 70DO va MOTOR LOAD: (NEC 430 -24) LARGE MOTOR 9 25 %: 54DOx 9.25 = 1350 va TOTAL LOAD: 43141/ 249 = 189 AMPS (PHASE A AND B) 14620 / 249 = 61 AMPS (PHASE C) Ia= 18DA Ib= ISOA Ic= GIA PETCO �. SCOPE OF WORK BLDG ELEC ROOM ............................... . --- ------- --- ........... I . .... 2 OF 5' UNIFORMS AND SHOES�� _ . KYOJIN JAPANESE BUFFET :....... ...'..._ I p v .... ... .... ...— ¢:r -n.._ ......_ -+_.., -•._£'c m.v n.., r.I .. _._. -. .[a,.,a e. a \P +tnT :?r^ rer Fr`C "V `. P� t¢°' }.1�7 T' ' 07 !.r - ' _ ''^ r-• . r-•^.•,n!— +_•® 11711 1!1 :n., -:.. n +'..... _ _.. ,--,.- .- .... .-. __. ..._ ._.. ..._ _ _._ . ...... ......_... II a en -_I MANUEL A. CID, P.E. LIC. #45176 STATE OF FLORIDA PROFESSIONAL ENGINEER 14448 SW 173 STREET, MIAMI FL. 33177 PHONE NO. (305) 951 -2080 my CANDELA + PARTNERS, LLC ARCHITECTURE + PLANNING + INTERIORS H I L A R 1 0 F. C A N D E L A, F A I A M A U R I C E H. CANDELA . DESIGN 5940 SOUTHWEST 73RD STREET SUITE 200 SOUTH MIAMI, FLORIDA 33143 P.305.6663788 WWW. CAN DELAANDPARTNERS.00M H I L A R 1 0 F. C A N D E L A, F A I A A R C H IT E C T: AROp04376 seal: "0 C n m v w MIRACLE-" S P AD C O m ul X m v 6 2 O 8o SOUTH D IXI Eo H I G H WAY> M 0 —i consultant: Date: 01.13.2014 Drawn by: R.A. Checked BY: M.C. Scale: AS SHOWN Project No: C ^14.1001 Revisions No. Date Description