14-384-018TYP. SECURE W/ 1/8" STAINLESS STEEL CABLE
OR STRAPS ANCHOR TO SLAB IN A CRISSCROSS
PATTERN OVER UNIT.
3/8" BOLTS, NUTS 8 WASHERS
SEE DETAIL "B"
WEATHER HOOD
PIPE INSULATION
PITCH PAN
BUILT-UP ROOF
20"x 31/2"
REFRIG. PIPES
ONDENSING UNITS
ALUMA STAND, AL. PIPE FRAME 9
SUPPORT DADE CO. PROD. APP.
98-1206.01
FLASH AND SEAL TO ROOF (BY
ROOF CONTRACTOR)
WELD
REF. LINES DOWN TO AIR HANDLER -BOLT THRU CONC, W/ 1/2" BOLTS, NUTS 8
IN CHASE WASHERS 8 STEEL PLATE 1/4" THICK TO STAND
WINDS OVER 150 MPH
CONDENSING UNIT INSTALLATION DETAIL SCHEME
N.T.S.
GALV. SHEET METAL HOOD W/
WEATHERTIGHT SEAMS AND
WELDED SKIRT
GALV. SHEET METAL OR FLEX-TUBE COLLAR
SLOPE PIPES AWAY FROM HOOD
GALV. FASTENERS APPROX. 6" D.C.
NOTE:
PIPING HOOD PROVIDED BY THIS CONTRACTOR FLASHING BY ROOFING
CONTRACTOR.
ROOF PENETRATION DETAIL FOR REFRIGERANT PIPES
N.T.S.
STRUCT JO
SEE DETAIL
HANGER STRAP 11/2".
FOR DUCTS OVER 48"
WIDE, FASTEN UNDER
BOTTOM OF DUCT
CONCRETE BEAM OR
CONCRETE SLAB.
LOW PRESSURE DUCT
DUCT SIZE
HANGER SIZE
MAX. SPACING
UP THRU 2 S.F.
11/2" x 1/16"
81-011
2 THRU 4 S.F.
11/2" x 1/8"
81-01,
4 THRU ID S.F.
111/2" x 1/8"
6,-D"
OVER 10 S.F.
111/2" x 1/8"
4'-D"
ti
EZ-TRAP SERIES 200 FLOAT
SWITCH TO SHUT-DOWN PVC OVERFLOW
EQUIP. AS PER FMC. 301.13 DRAIN LINE
REMOVABLE CAP 314"
PERFORATED !!
_F
VENT CAP —IA
SLOPE 1/8"/
SLOPE 12"MIN. UNION
A/C UNIT
DRAIN PAN
3/4" MIN. fiO3'MIN.
CONDENSATE DRAIN TRAP DETAIL.
N.T.S
-11/2" MIN. STRAP, 26 G.
offli 11117 mull"
EXPANSION SHIELDS
(2" EMBEDMENT)
N.T.S.
,HANGER
STRAPS
GO" MAXIMUM UNLESS FOOT OF STRAP IS
PLACED UNDER A BOTTOM
REINFORCEMENT I
SCREWS '—"
SCREWS MAY
BE OMITTED IF
HANGER LOOPS
P
k
7' 7-
T7 i (7 m P' 17 r',- T. L17- AF,(�""CT. T HE C,JTRb S Rz�:"r-_
WCIO OR MODEL B-100 L
OR 0-68 WALL CAP
BACKDRAFT DAMPER
1/4" BIRD SCREEN
RUST RESISTANT
MIN. EL V. 10'-0"
ABOVE GRADE
PROPOSED B"ff EXHAUST G.M.D.
(26 GAUGE) TO A NON CORROSIVE
WALL CAP. (300 CFM)
MIAMI TECH, INC. MN-ASWCB OR
APPROVED EGUALPROVIDE INSECT
SCREEN AND BACK DR-
Ak F
T
DA
MPER.
-----------
-
PROPOSED 4"H EXHAUST G.M.D. \
(Z,B GAUGE} - --T dMN 0 4 -E-- DR. Rb SI V E
Wk CAP. (50 CFM)
MI AM[ TECH, INC. MWASIVE Obi - ---------
APPROVED EgUAL OV16E INSECT
SCREEN AND BACK D A , AMPER.
4"OIA. S/M 26 GA.
EXHAUST DUCT
STRUCTURE
CEILING FAN.
CEILING
WN
/ GRILLE\ �
I 103 1, Fill 163 m 1111.1111
-2 5T
5T _\
REFRIGERANT LINES--
THRU ATTIC SPACE
(SUCTION-
..........
40
91
B" O/A GMD UP TO ROOF
-GAP. PROVIDE BIRD SCREEN
----- - ------ -
,AND BACKDRAFT DAMPER.
OUTSIDE AIR INTAKE SHALL BE LOCATED A MINIMUM OF IDA"
HORIZONTALLY FROM ANY HAZARDOUS OR NOXIOUS
CONTAMINANT SOURCE. SUCH AS VENTS, STREETS, ALLEYS,
PARKING LOTS AND LOADING DOCKS
PROPOSED SITE/ROOF PLAN
MANUEL A. CID, P.E.
LIC. #45176
STATE OF FLORIDA
PROFESSIONAL ENGINEER
14448 SW 173 STREET, MIAMI FL. 33177
PHONE NO. (305) 951-2080
0:10
CANDELA + PARTNERS, LLC
ARCHITECTURE + PLANNING + INTERIORS
H I L A R 1 0 F. C A N D E L A, F A I A
MAURICE H. CANDELA . DESIGN
5940 SOUTHWEST 73RD STREET SUITE 200
SOUTH MIAMI, FLORIDA 33143 P.305.666,7788
WWW. CA N D E LAAN D PA R T N E R S , C 0 M
H I L A R 1 0 F. CAN DELA, FAIA
A R C H I T E C T: A R 0 0 0 4 3 7 6
seal:
MIRACLE
S P A
6 2 0 8
SOUTH DIXIE
H I G H W A Y
consultant:
Date:
01.13.2014
Drawn by:
R.A.
Checked By:
M.C.
Scale:
AS SHOWN
Project No:
C.14.1001
Revisions
No. Date Description