14-576-011INSULATED FLEXIBLE
DUCT
(R -6 INSULATION)
INSULATED ROUND
COLLAR. SEAL
JOINT W /EPDXY & DU
MTL. ROUND FITTING
QUADRANT OPERATOR TO
BE OUTSIDE INSULATION —
PROVIDE INSULATION
GUARD AS REQUIRED
SUPPLY AIR. DUCT
R -6 INSULATION.
V
DRAWBAND
CONNECTOR
BENEATH INSULATION
PERFORATED DIFFUSER
MAXIMUN LENGTH OF FLEXIBLE DUCT
RUNOUT TO DIFFUSER TO BE 12 FEET.
NOTE: — HANGAR SIZE FOR FLEX —DUCT SHALL BE 1 -1/2" MIN. 22GAUGE
— DUCT SUPPLY /RETURN SHALL BE 1 -1/2" (R -6) FIBERGLASS
U.L. LISTED CLASS 1 AIR DUCT,
TYPICAL FLEXIBLE DUCT CONNECTION
N.T.S.
provide 1 /8"
steel straps around
the C /U's cabinet.
each way.
CONDENSI "
UNIT.
CONCRETE BASE
6' THICKNESS Y
SEAL ENTRANCE OF REFRIGERANT
LINES INTO P.V.C. PIPE I ^' 7
IMPERMEABLE, RESILIENT MATERIAL
SUCTION LINE W/ 1 -1/2"
ARMAFLEX INSULATION
& VAPOR BARRIER
FASTENED INSIDE C.U. TO SLAB W/ 4 -1/4 "0 x 1 -1/2" LONG
POWDERED ACTUATED PINS AS PER MANUFACTURER
SPECS. THRU NEOPRENE PADS, BETWEEN SLAB AND
CONDENSING UNIT.
POWER & CONTROL
LOCATION
NOTES:
1 —ALL C.U. SHALL BE ANCHORED
TO CONC. PADS & TO COMPLY
W/ 301.13 OF THE FMC
TO STAND 146 M.P.H. WIND
2— SECURE EXTERIOR AIR CONDITIONING
CONDENSING UNIT FOR THEFT
AS PER MIAMI —DADE COUNTY
ORDINANCE SECTION 8C -5
3 —THE CONDENSING UNIT SHALL BE
PLACED, AS TO MATCH THE FINISH FLOOR
LIQUID LINE
ELEVATION OF THE PROPOSED BUILDING.
W O INSULATION
4" 0 SCHEDULE
40 P.V.C. PIPE
INCREASE SIZE
AS REQUIRED BY
LENGTH AND ROUTING
CONDENSING UNIT
N.T.S.
DETAIL
GALV. MIN. 30 G.A. SHEET MTL.
EXHAUST
ROOF CAP
0
CIDz
ROOF TILE
o
0
2" X 4"
B LK'G.
4" DIA. MTL. DUCT
FROMDRYER AND OR TOILET EXHAUST VENT
DRYER 8c EXHAUST VENT ROOF CAP DETAIL
N.T.S.
z
O
0
Q
w
N
O
z
Q
LU
O
0
z
N
v
z
Um
U Q
�Cn
w
z
U
z
0
un
w
z
NOTE # 1:
- EXHAUST FAN 50 CFM.
2G GA, MIN. GALV. 5HEETMETAL 4 "0 26 GA. DRYER VENT
4 "0 VENT TERMINATE G" THRU ROOF, TERMINATE
ABOVE FINISH ROOF FG" ABOVE FINISH ROOF
PROVIDE A MIN. WORKING SPACE
CLEARANCE OF 4 ", ALONG THE SIDES,
BACK & TOP W/ A TOTAL WI
ENCLOSING SPACE BEING AT LEAST
WIDER THAN THE AIR HAND
CLOSET PARTITION WALL
BUILT —IN A.H.U. DISC.
PROVIDE CAP OFF
PERFORATION FOR V NT
PROVIDE FLOAT SWITCH AT
SECUNDARY DRAIN CONNE U
CONTROL OVERFLOW BY SHU
DOWN THE SYSTEM
AS PER FMC SECTION 307 ° N
NEW
>:��
MECHANICALLY
ATTACH PLENUM TO
TO AHU. FMC 603.7
REFRIGERANT
OVERHEAD
LINES
METAL STAND
FINISH FLOOR
I
2'
0
CONDITIONING SPLIT SYSTEM
EQUIPMENT SCHEDULE
a
A.H.0
LOCATION:
TOTAL CAPACITY, BTU HR.
18,700
I DRAFT DAMPER
NOTE: USE DESIGNATED EXHAUST FAN
OR APPROVED EQUAL
TOILET
RL & S
REFRIGERANT LIQUID
NET SENSIBLE LOAD, BTU HR. 14,000
& SUCTION PIPE
CFM
CUBIC FEET PER INUTE
2R0ELOW /couv�os°
NO N FOR CLARITY
TEMP CAT -II
NET LATENT, BTU HR.
4,700
UNDRY
THERMOSTAST
A#HU
DUCTWORK
AIR HANDER UNIT DETAIL
COOLING EER SEER
N.T.S.
CL.
v
z
Um
U Q
�Cn
w
z
U
z
0
un
w
z
NOTE # 1:
- EXHAUST FAN 50 CFM.
2G GA, MIN. GALV. 5HEETMETAL 4 "0 26 GA. DRYER VENT
4 "0 VENT TERMINATE G" THRU ROOF, TERMINATE
ABOVE FINISH ROOF FG" ABOVE FINISH ROOF
MANUFACTURER:
NEW
MODEL:
695
CFM:
I
AIR
CONDITIONING SPLIT SYSTEM
EQUIPMENT SCHEDULE
A /C#2
LOCATION:
TOTAL CAPACITY, BTU HR.
18,700
I DRAFT DAMPER
NOTE: USE DESIGNATED EXHAUST FAN
OR APPROVED EQUAL
TOILET
RL & S
REFRIGERANT LIQUID
NET SENSIBLE LOAD, BTU HR. 14,000
& SUCTION PIPE
CFM
CUBIC FEET PER INUTE
F
ROOM
TEMP CAT -II
NET LATENT, BTU HR.
4,700
UNDRY
THERMOSTAST
A#HU
DUCTWORK
DAC SONG
COOLING EER SEER
13.0 16.00
CL.
NEW
AXHAUST FAN
o&
MANUFACTURER
RHEEM
DENOTES AIR DISTRIBUTION DEVICE
STORAGE
DISTRIBUTION BOX
UC -\,F-
=
Q
i
�
�
w
J
z
=
Q:f
FINISH FLOOR AS NOTED
ROOM
DESIGNATION
AHU. 2
U
MODEL No: C /U, #2
14AJM
MODEL No: RHLL- HM2417
�
TOTAL KW.
3.0
6�
SUPPLY AIR, CFM
600
z
CONDENSER ENT. AIR F.
95°
EXTERNAL STATIC. IN. WC.
.30
�
COMPRESOR RLA -LRA
9/9-48
FAN SPEED
HIGH
FAN MOTOR FLA
1.9
W D
FAN MOTOR, HP.
1/4
LLj
z
MIN. CIRCUIT AMPS.
20/20
°
ELECTRIC HEATER KW.
5.0
�
MAX. FUSE AMPS.
20/20
VOLTS PHASE
208/240/10
o
VOLTS PHASE
10/60/208/230
W.D.
6X44
LINE: 3/4"
U
NET WEIGHT LBS.
140
' ' —D 100 CFM.
REFRIGERANT LINEISUID LINE:
3Y OR
v
z
Um
U Q
�Cn
w
z
U
z
0
un
w
z
NOTE # 1:
- EXHAUST FAN 50 CFM.
2G GA, MIN. GALV. 5HEETMETAL 4 "0 26 GA. DRYER VENT
4 "0 VENT TERMINATE G" THRU ROOF, TERMINATE
ABOVE FINISH ROOF FG" ABOVE FINISH ROOF
MANUFACTURER:
NEW
MODEL:
695
CFM:
I
SP:
0.10"
DRIVE:
DIRECT
LOCATION:
CEILING
NEW °
I DRAFT DAMPER
NOTE: USE DESIGNATED EXHAUST FAN
OR APPROVED EQUAL
TOILET
RL & S
REFRIGERANT LIQUID
& SUCTION PIPE
CFM
CUBIC FEET PER INUTE
F
ROOM
TEMP CAT -II
O.B.D.
L
UNDRY
THERMOSTAST
A#HU
DUCTWORK
DAC SONG
FLEXIBLE DUCT
z
CL.
NEW
AXHAUST FAN
o&
MANUAL VOLUME DAMPER
AO
DENOTES AIR DISTRIBUTION DEVICE
STORAGE
DISTRIBUTION BOX
UC -\,F-
UNDER CUT DOOR ABOVE
FINISH FLOOR AS NOTED
ROOM
40 CFM.
40 CF
W/D
6�
In
6X4
W D
N # 6 4
..
°
Cj
j=0q:i�L150-
4
/
W.D.
6X44
LINE: 3/4"
OX8 V'.D.4
60 CFM <'Q —
v
z
Um
U Q
�Cn
w
z
U
z
0
un
w
z
NOTE # 1:
- EXHAUST FAN 50 CFM.
2G GA, MIN. GALV. 5HEETMETAL 4 "0 26 GA. DRYER VENT
4 "0 VENT TERMINATE G" THRU ROOF, TERMINATE
ABOVE FINISH ROOF FG" ABOVE FINISH ROOF
EXHAUST FAN SCHEDULE
MANUFACTURER:
NEW
MODEL:
695
CFM:
I
SP:
0.10"
DRIVE:
DIRECT
LOCATION:
CEILING
NEW °
I DRAFT DAMPER
NOTE: USE DESIGNATED EXHAUST FAN
OR APPROVED EQUAL
TOILET
RL & S
REFRIGERANT LIQUID
& SUCTION PIPE
CFM
CUBIC FEET PER INUTE
F
ROOM
TEMP CAT -II
O.B.D.
L
UNDRY
THERMOSTAST
A#HU
DUCTWORK
DAC SONG
FLEXIBLE DUCT
z
CL.
NEW
AXHAUST FAN
o&
MANUAL VOLUME DAMPER
AO
DENOTES AIR DISTRIBUTION DEVICE
STORAGE
DISTRIBUTION BOX
UC -\,F-
UNDER CUT DOOR ABOVE
FINISH FLOOR AS NOTED
ROOM
40 CFM.
40 CF
W/D
6�
In
6X4
W D
N # 6 4
..
°
Cj
j=0q:i�L150-
4
/
W.D.
6X44
OX8 V'.D.4
60 CFM <'Q —
' ' —D 100 CFM.
�j rr jj r�
81-0
EXHAUST FAN SCHEDULE
MANUFACTURER:
NuTone
MODEL:
695
CFM:
70
SP:
0.10"
DRIVE:
DIRECT
LOCATION:
CEILING
ACCESORIES:
I DRAFT DAMPER
NOTE: USE DESIGNATED EXHAUST FAN
OR APPROVED EQUAL
AIR CONDITIONING LEGEND
SYMBOL
LEGEND
A.H.U.
AIR HANDLING UNIT
C.U.
CONDENSING UNIT
0. A.
OUTSIDE AIR
R/A
RETURN AIR
S. A.
SUPPLY AIR
W.S.A.
WALL SUPPLY AIR
C.S.A.
CEILING SUPPLY AIR
RL & S
REFRIGERANT LIQUID
& SUCTION PIPE
CFM
CUBIC FEET PER INUTE
M.V.D.
MANUAL VOLUME DAMPER
O.B.D.
OPPOSED BLADE DAMPER
0
THERMOSTAST
A#HU
DUCTWORK
®- -�_'F.D
FLEXIBLE DUCT
z
SUPPLY AIR DIFUSSER
z
AXHAUST FAN
—�
MANUAL VOLUME DAMPER
AO
DENOTES AIR DISTRIBUTION DEVICE
D O
DISTRIBUTION BOX
UC -\,F-
UNDER CUT DOOR ABOVE
FINISH FLOOR AS NOTED
.' C
� � a
D
0 '
K
R.A.G. ,'
v
i
w a - - - - --
I r
EX I ST. O • D/V11
- BATHROOM L ----- J
T EMAIN
EXIST.
EXIST.
BATHROOM
THROOM
BEDROOM TO REMAIN
TO REMAIN
CLOSET REF.
TO REMAIN
/
EXIST.
BEDROOM
TO REMAIN
I /
NEW CONC.
SLAB
EXIST.
BEDROOM
TO REMAIN
NEW FAMILY
ROOM
_
100 CFM.
4— I —D
® 10X8 C.D.
TO REMAIN
r---- - - - - -- 1
0 0
0 O
MECHANICAL PLAN
i
n
6" 0
EXIST.
LIVING ROOM
TO REMAIN
AHU
#1
0
7
0
H.V. A. C. NOTES: -- - - - = -�
1. ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH MECHANICAL OF "F.B.C." 2010
LATEST EDITION AND ALL OTHER PERTAINING CODES.
2. ALL WORK SHALL BE PERFORMED BY A LICENSED MECHANICAL CONTRACTOR,
WORK TO BE IN THE ACCEPTANCE OF THE OWNER AND THE ENGINEER
3. THE CONTRACTOR SHALL HAVE VISITED THE JOB SITE BEFORE BIDDING AND FAILURE
TO DO SO WILL NOT BE ACCEPTED AS A REASON FOR REQUESTING EXTRA PAY
IN THE EVENT THAT THE EXISTING CONDITIONS RESULT IN EXTRA MATERIALS OR LABOR.
4. ALL WORK SHALL BE COORDINATED WITH OTHER TRADES TO AVOID INTERFERENCE WITH
THE PROGRESS OF MECHANICAL CONSTRUCTION, ANY EXISTINGCONDITION FOUND AND /OR
DISCREPANCIES FOUND BY THE CONTRACTOR SHALL BE BROUGHT TO THE ATTENTION
OF THE OWNER AND ENGINEER
5. INSULATE REFRIGERANT SUCTION PIPING WITH 1/2" CLOSED CELL POLYETHYLENE
PRE - MOLDED PIPE INSULATION
6. UNDERGROUND CONDENSE DRAIN LINE SHALL BE 2" DIA. MINIMUM
7. ALL REFRIGERANT COMPRESSORS SHALL BE WARRANTED FOR A MINIMUM OF 5 YEARS
AFTER DATE OF ACCEPTANCE OF THE PROJECT.
8. ALL EQUIPMENT AS PER MANUFACTURER RECOMMENDATIONS TO ELIMINATE ANY EQUIPMENT
NOISE AND VIBRATION
9. AFTER THE SYSTEM IS INSTALLED CONTRACTOR SHALL CONDUCT AN OPERATIVE TEST
FOR APPROVAL AND ACCEPTANCE BY THE OWNER /ENGINEER SHALL BE GUARANTEED FOR
A PERIOD OF 1 YEAR FROM THE DATE OF FINAL ACCEPTANCE THEREOF AGAINST DEFECTIVE
MATERIALS AND WORKMANSHIP.
10. ALL EXHAUST DUCTS SHALL BE CONSTRUCTED OF SHEET METAL, TERMINATE OUTSIDE
THE BUILDING, AND BE EQUIPPED WITH A BACK DRAFT DAMPER
11. DUCTS FROM TOILET ROOMS SHALL DISCHARGE TO THE OUTSIDE OF THE BUILDING, SHALL
BE TERMINATED NOT LESS THAN 6" ABOVE THE FINISHED ROOF SURFACE AND SHALL
BE SCREENED WITH A CORROSION RESISTANT MATERIAL HAVING A MESH SIZE NOT LARGER
THAN 1/2 ". (SEE DTL. FOR GOOSE NECK OR RAIN CAP ON ROOF TERMINATION)
12. CLOTHES DRYERS EXHAUST DUCTS OR VENTS SHALL COMPLY WITH MANUFACTURE'S INSTAL-
LATION INSTRUCTIONS, BE CONSTRUCTED OF A MIN. 26 GAUGE METAL PIPE, HAVING A
SMOOTH INTERIOR SURFACE WITH JOINTS RUNNING IN THE DIRECTION OF THE AIR FLOW.
13. VENTILATION DUCTWORK SHALL BE GALVANIZED STEEL WITH GAUGES DUCT CONSTRUCTION
BRACING AND SUSPENSION IN ACCORDANCE WITH THE RECOMMENDATIONS SET IN THE
LATEST EDITION OF THE ASHRAE GIDE AND SMACNA STANDARDS
810 I
--D160 CFM.
z
O
Q
Ir
0
w
U)
O
02
CL
0 z
Q
PROP. NEW
EXIST. CU -2
'
WASH. MACH. I--
O
& DRYER EXIST, z
TO REMAIN .RELOCATED
Ln
EXIST.
GARAGE
TO REMAIN
CU -1
z y
Cn
z
Z Z Z
jo��yx O
OF
w w
w wc`aw Zo F�w-'z
00 <MN � Z a
U. 0000N�
tu b° � .gnu
°� w>Z izom °omL >�
0.W0w �2t9
OwOOO O
Z OLL ZCU V O aQg05M yz(a aW
aLz o0 .
° °� zwa`ino w
zLQWa U
% �
ii wagAo7<90
( ¢�WW P O uZ N OO a =
O OZO°Q
zdHu.2050-o
R~aM, ZW2 W6O-O �¢WWVOg m V
OFW U
8 5gaua WRD2=i�d
r
UK -3Zt3U i
PROVIDE A MIN. WORKING
1" 1 10 "X10" %
5PACE CLEARANCE OF 4 ",
R.A.G. ,'
ALONG THE 51DE5, BACK
TOP W1 A TOTAL WIDTH OF THE
-" NEW
ENCL05ING 5PACE BEING AT
LEAST 12" WIDER THAN THE
AIR HANDLER.
Q
A5 PER F.B.C. 11305.1.1
10
.D
A#HU
N E W
100 CFM. Q-
2
BEDROOM
b
810 I
--D160 CFM.
z
O
Q
Ir
0
w
U)
O
02
CL
0 z
Q
PROP. NEW
EXIST. CU -2
'
WASH. MACH. I--
O
& DRYER EXIST, z
TO REMAIN .RELOCATED
Ln
EXIST.
GARAGE
TO REMAIN
CU -1
z y
Cn
z
Z Z Z
jo��yx O
OF
w w
w wc`aw Zo F�w-'z
00 <MN � Z a
U. 0000N�
tu b° � .gnu
°� w>Z izom °omL >�
0.W0w �2t9
OwOOO O
Z OLL ZCU V O aQg05M yz(a aW
aLz o0 .
° °� zwa`ino w
zLQWa U
% �
ii wagAo7<90
( ¢�WW P O uZ N OO a =
O OZO°Q
zdHu.2050-o
R~aM, ZW2 W6O-O �¢WWVOg m V
OFW U
8 5gaua WRD2=i�d
r
�
In
INTERIOR WORKAND
ADDITION TO EXIST.
SINGLE FAMILY RESIDENCE
SITE ADDRESS:
6201 SW 80 ST.
MIAMI, FLORIDA
OWNER:
MR. AJAY PANDEY AND
MRS. PARUL SHAH
AGUDELO
ARCHITECT P.A.
A.A.26002013
4841 NW 107 Ct.
Doi FI. 33178
Phone #:
(786) 738 -8236
e -mail address:
netl
SEAL:
STATE QF FLORIDA
GERMAN A.; PLIDELO
ARCHITECT.FOR THE FIRM
LICENSE # AR- 0091594