14-925-001South Miami
Hospital
n Affiliate of Baptist Health Systems of South Florid
GENERAL NOTES
I.- CONTRACTOR IS BEING PROVIDED WITH COMPLETE SETS OF
DOCUMENTS. CONTRACTOR IS RESPONSIBLE FOR PROVIDING
SUBCONTRACTORS WITH COMPLETE SETS OF DRAWINGS. INTENT
IS FOR ALL SYSTEMS AND EQUIPMENT TO BE PROVIDED WITH
UTILITY CONNECTIONS AS REQUIRED FOR OPERATION.
EXAMPLE - IF A SINK IS SHOWN IN THE ARCHITECTURAL PLANS,
THE PLUMBING PLANS DO NOT SHOW A WATER OR DRAWINGS
CONNECTION THE ENGINEER WILL PROVIDE THE DESIGN DETAILS
IN ACCORDANCE WITH THE DESIGN CRITERIA FOR THE REST OF
THE INSTALLATIONS. CONTRACTOR IS RESPONSIBLE FOR PRO-
VIDING THE CONNECTION AT NO ADDITIONAL COST TO THE OW-
NER.
2.- CONTRACTOR IS RESPONSIBLE FOR VISITING THE SITE DURING
THE BIDDING PERIOD AND VERIFY THAT THE CONDITIONS ARE
AS DESCRIBED IN THE DOCUMENTS. DISCREPANCIES ARE TO
BE NOTED IN WRITING, AND NOTIFY ARCHITECT / ENGINEERS.
CONTRACTOR ACCEPTS CONDITIONS AS THEY ARE ON THE SITE,
AND MUST PROVIDE SYSTEMS AND WORK AS DESCRIBED IN THE
CONTRACT DOCUMENTS AT NO ADDITIONAL COST TO THE OWNER.
3.- DIMENSIONS PROVIDED ARE NOMINAL, NOT ACTUAL. THEY TAKE
AS A BASIS EXISTING WALLS. IF DISCREPANCIES ARE FOUND,
NOTIFY ARCHITECT IMMEDIATELY FOR COORDINATION. IF CON-
TRACTOR PROCEEDS, HE DOES SO AT HIS OWN RISK AND IS
RESPONSIBLE FOR ALL EXPENSES INCURRED, IF AT THE DISCRE _
TION OF THE OWNER OR THE ARCHITECT, THE WORK HAS TO BE
RE -DONE.
4.- SHUTDOWN OF UTILITIES; IF A SHUTDOWN OR ANY TYPE OF INTER-
FERENCE WITH EXISTING SYSTEMS IS ANTICIPATED, THE CONTRAC
TOR MUST NOTIFY THE OWNER, 72 HOURS IN ADVANCEAND OBTA-
IN APPROVAL IN WRITING PRIOR TO PROCEEDING.
5.- CONTRACTOR SHALL TAKE ALL NECESSARY PRECAUTIONS AND
USE ALL APPROPRIATE CONSTRUCTION METHODS / TECHNIQUES
TO PROTECT EXISTING UTILITIES AND OTHER PROPERTY NOT
NOTED FOR REMOVAL. CONTRACTOR SHALL BE RESPONSIBLE
FOR ANY DAMAGES INCURRED DURING CONSTRUCTION AND
SHALL REPAIR ANY DAMAGES AT NO EXPENSE TO THE OWNER.
6.- IF THERE IS A DISCREPANCY BETWEEN THE DRAWINGS AND THE
SPECIFICATIONS, THE CONTRACTOR IS TO OBTAIN CLARIFICATION
DURING THE BIDDING PERIOD. IF THE DISCREPANCY COMES UP
DURING THE CONSTRUCTION, IT IS ASSUMED THE CONTRACTOR BID
THE MOST EXPENSIVE WAY AND WILL DO THE WORK AS PER THE
DIRECTION OF THE OWNER /ARCHITECT AT NO ADDITIONAL COST
TO THE OWNER.
7.- ABBREVIATIONS THROUGHOUT THE PLANS ARE THOSE IN COM-
MON USE, ARCHITECT WILL DEFINE INTENT OF ANY IN QUESTION.
8.- THE CONTRACTOR SHALL PROVIDE ALL NECESSARY TEMPORARY
BARRIERS, LIGHTING, COVERINGS, FIRE PREVENTION AND OTHER
EQUIPMENT TO PROTECT THE SAFETY OF ALL PERSONS AND THE
PROPERTY THROUGHOUT THE ENTIRE PERIOD OF THE CONSTRUC _
TION CONTRACT.
9.- THE CONTRACTOR SHALL VERIFY SIZES AND LOCATIONS OF ALL
OPENINGS FOR MECHANICAL, ELECTRICAL AND PLUMBING EQUIPMENT
WITH SUBCONTRACTORS, AS WELL AS SHOP DRAWINGS AS APPROVED
BY ARCHITECT, BEFORE PROCEEDING WITH THE WORK.
10.- ALL ITEMS USED IN CONSTRUCTION, BUT NOT SPECIFICALLY MENTIONED
HEREIN, SHALL CONFORM TO ALL LOCAL CODES AND STATE ORDINANCES
AS TO APPLICATION AND USE:.
Ii.- PROVIDE ELECTRIC INSULATION BETWEEN ALL DISSIMILAR METAL
AND ALSO BETWEEN CEMENT AND METAL.
12.- THE CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING ALL
PERMITS TO COMPLETE THE PROJECT.
I3.- CONTRACTOR TO REVIEW ALL EXISTING BUILDING SYSTEMS AS TO THEIR
COMPLIANCE WITH ALL LOCAL AGENCY REQUIREMENTS AND BRING ANY
NON - CONFORMING ITEMS TO ARCHITECT'S AND ENGINEER'S ATTENTION,
14.- GENERAL CONTRACTOR IS TO PROTECT EXISTING ADJACENT AREAS TO
WHERE WORK IS TO BE PERFORMED. ANY EXISTING MILLWORK,
EQUIPMENT DAMAGED DUE TO WORK PERFORMED SHALL BE REPAIRED/
REPLACED TO MATCH EXISTING (TYPICAL UNLESS OTHERWISE NOTED).
15.- DRAWINGS ARE SCHEMATIC SHOWING RELATIVE LOCATIONS AND
CONNECTIONS AND SHALL NOT BE SCALED AT ANY TIME.
16.- ALL WOOD BLOCKING WITHIN BUILDING STRUCTURE, SHALL BE FIRE -
RETARDANT TREATED AS PER SPECIFICATIONS.
17.- GENERAL CONTRACTOR SHALL INSPECT ALL EXISTING RATED WALLS /
PARTITIONS WITHIN SCOPE OF WORK AREA, CONTRACTOR SHALL UPGRADE
EXISTING PARTITIONS AS REQUIRED TO MAINTAIN THE INTEGRITY
OF THE DESIGNATED RATING.
18.- ELEVATION AND LEVELS;
A. ALL NUMERICAL ELEVATIONS ARE TO TOP OF CONCRETE SLAB.
UNLESS NOTED OTHERWISE.
19 ALL INTERIOR GYPSUM WALL BOARD IS 5/8' TYPE X G.W.B. ON METAL
STUDS OR FURRING CHANNELS UNLESS NOTED OTHERWISE, SIZES AS
DIMENSIONED ON FLOOR PLANS. SEE NOTES 9 FOR LOCATION OF
WATER RESISTANT G.W.B.
20.- PROVIDE WATER RESISTANT TYPE X G.W.B. IN ALL TOILETS,
AND JANITOR'S CLOSETS,
21.- BEFORE PATCHING ANY FIRE - RATED C.M.U. PARTITION, FILL ANY
EXPOSED CELLS SOLID WITH GROUT.
22.- PROVIDE FINISH WALL UNDER AND BEHIND ALL EQUIPMENT AND CASEWORK.
23.- LOCATION AND SIZE OF CEILING AND WALL ACCESS PANELS SHALL BE
DETERMINED BY THE POSITION OF VALVES AND OTHER MECHANICAL AND
ELECTRICAL ITEMS WHICH REQUIRE ACCESS. THE CONTRACTOR SHALL
COORDINATE WITH ALL TRADES. THE ARCHITECT SHALL REVIEW AND
APPROVE ALL FINAL LOCATIONS OF ACCESS PANELS PRIOR TO
INSTALLATION.
24.- THERE SHALL BE NO BACK - TO BACK ELECTRICAL TELEPHONE
OR OTHER OUTLETS.
25.- ALL VERTICAL PIPING AND COLUMNS, EXPOSED IN ROOMS SHALL BE
FURRED WITH METAL STUDS AND DRY WALL AND FINISHED TO MATCH
ADJACENT WALLS, UNLESS NOTED OTHERWISE, EXCEPTIONS:
A. ELECTRIC CLOSETS C. MECHANICAL ROOMS
B. TELEPHONE CLOSETS D. STAIRS
26.- WHERE HVAC OR OTHER MECHANICAL, ELECTRICAL AND PLUMBING ITEMS
PENETRATE PARTITIONS, STUDS SHALL BE BRACED AND FRAMED TO
STRUCTURE AS REQUIRED TO PROVIDE ADEQUATE SUPPORTS. ALL
PENETRATIONS THROUGH RATED WALLS SHALL BE SEALED TO PROVIDE
FIRE, SMOKE AND / OR ACOUSTICAL ISOLATION OF SPACES WITH
APPROPRIATE FIRE S.T.0 MATERIAL.
27.- SEE INTERIOR ELEVATIONS FOR FINISHES AND FINISH DETAILS FOR INTERIOR
SPACES. SEE ARCHITECTURAL REFLECTED CEILING PLANS FOR
ACOUSTICAL TILE FINISH.
28.- SEE ARCHITECTURAL REFLECTED CEILING PLANS FOR LOCATION OF
CEILING MOUNTED MECHANICAL, ELECTRICAL FIXTURES.
29.- STAGGER JOINTS VERTICALLY AND HORIZONTALLY IN ALL G.W.B. PARTITIONS
EA. SIDE OF PARTITION, JOINTS STAGGERED MINIMUM 2' -0 ",
UNLESS OTHERWISE NOTED.
30. CONTRACTOR SHALL CONFIRM THAT ALL EXISTING EXPOSED
STEEL COMPLIES WITH N.F,P.A FIRE PROTECTION REQUIRE-
MENTS. CONTRACTOR SHALL PROVIDE ALL NECESSARY INSULA-
TION /FIRE PROTECTIVE COATINGS.
31. CONTRACTOR TO SUBMIT ALL SHOP DRAWINGS TO ARCHITECT AND
THE BUILDING DEPARTMENT FOR APPROVAL. (ELEVATOR, TRUSSES,
WINDOWS, ETC.)
32, CONTRACTOR REQUIRED TO PULL SEPARATE DEMOLITION PERMIT.
SMH BREAST CEN R XPANSION
SOUTH MIAMI HOSPITAL , MEDICAL ARTS BUILDING
6200 S.W. 72 STREET
TEL: (786) 596 -8386
EB0000924
LOUIS J. AGUIRRE & ASSOCIATES P.A.
CONSULTING ENGINEERS
9150 SOUTH DADELAND BLVD. SUITE 900
MIAMI, FLORIDA 33156
TELEPHONE: (305) 670 -0141
FAX: (305) 670 -0144
E -MAIL ADDRESS: GRALMAIL@LLJAAPA.COM
SOUTH MIAMI, FLORIDA 33143
Fax: (786) 596 -2901
0 d 0 0
r c h i t e c t s
FLORIDA LICENSE *AA0002689
2100 PONCE DE LEON BLVD. SMITE 1170, CORAL GABLES, FL 33134
Td (305)265 -7177 Fax: (305)262 -8435
LUIS E. NAPA, A.LA Fl. AR0008063
PROJECT NUMBER: 201304
(INTERIOR ALTERATION)
MARCH 28, 2014
INDEX
ARCHITECTURAL
OF DRAWINGS
A -0 COVER AND GENERAL INFORMATION.
A -1 PARTIAL THIRD FLOOR DEMOLITION PLAN, LEGEND AND NOTES.
A -2 PARTIAL THIRD FLOOR PLAN AND EQUIPMENT PLAN,
LEGEND AND NOTES.
A -3 PARTIAL THIRD FLOOR REFLECTED CEILING PLAN,
LEGEND AND NOTES.
A -3A INTERIOR ELEVATIONS.
A -4 PARTITION TYPES, DOOR AND FINISH SCHEDULES,
NOTES AND DETAILS.
A -5 CABINET AND MISCELLANEOUS DETAILS.
A -6 PENETRATION AND FIRE RATED DETAILS.
A -7 PENETRATION AND FIRE RATED DETAILS.
A -8 PENETRATION AND FIRE RATED DETAILS.
MECHANICAL
MO.00 SYMBOLS LEGEND AND GENERAL NOTES.
M3.00 THIRD FLOOR DEMOLITION PLAN.
M3.01 THIRD FLOOR PLAN.
M6.00 SCHEDULES.
M7.00 DETAILS.
PLUMBING
PO.00 SYMBOL LEGEND AND GENERAL NOTES.
P3.00 THIRD FLOOR PLAN, SANITARY WASTE.
P3.01 THIRD FLOOR PLAN, DOMESTIC WATER.
BUILDING INFORMATION
ORIGINAL BUILDING DESCRIPTION
BUILDING JURISDICTION: SOUTH MIAMI, MIAMI DADE COUNTY
PRIMARY USE CLASS BUSINESS
NUMBER OF STORIES : 6 (EXISTING BUILDING)
NEW PROJECT DESCRIPTION
PROJECT AREA: THIRD FLOOR: 3,760 S.F.
SPRINKLED: FULLY SPRINKLERED
APPLICABLE CODES
FLORIDA BUILDING CODE 2010 EDITION.
FLORIDA FIRE PREVENTION CODE 2010 EDITION.
NFPA 101 LIFE SAFETY CODE, 2009 EDITION.
FIRE, PROTECTION
FPO.00 SYMBOL, LEGEND AND GENERAL NOTES.
FP3.01 THIRD FLOOR PLAN FIRE PROTECTION.
FP7.00 DETAILS FIRE PROTECTION.
ELECTRICAL
EO.00 SYMBOL LEGEND AND GENERAL
E3,00 DEMOLITION THIRD FLOOR PLAN
E3.01 DEMOLITION THIRD FLOOR PLAN
E3.02 NEW WORK THIRD FLOOR PLAN
E3.03 NEW WORK THIRD FLOOR PLAN
E6.00 PANELBOARD SCHEDULES.
NOTES.
- LIGHTING.
- POWER & SYSTEMS.
- LIGHTING.
- POWER & SYSTEMS.
REVISIONS
Pull'm 01 0-1 ML
AlWHITEGTURAL AMIREVI,4TION& WOFKWx L)WONWN
4 AND
L ANGLE
AT
C CENTERING
O DIAMETER
" POUND OR NUMBER
A
LAVATORY
A/C
AIR CONDITIONING
ACI
AMERICAN CONCRETE INSTITUTE
ACP
A6bE5TOS CEMENT PIPE
ACSC
ASPHALTIC CONCRETE :SURFACE COURSE
ACU
AIR CONDITIONING UNIT
ACT
ACOUSTICAL CEILING TILE
AD
AREA DRAIN
ADJ
ADJUSTABLE
A/E
ARCHITECT/ENGINEER
AF
ACCESS FLOORING
AFF
ABOVE FINISHED FLOOR
AGGR
AGGREGATE
AHU
AIR HANDLING UNIT
ALT
ALTERNATE
AL
ALUMINUM
ANN
ANNUNCIATOR
ANSI
AMERICAN NATIONAL STANDARDS INSTITUTE
ANT
ANTENNA
AP
ACCE55 PANEL
APL
ACCE55 PLENUM
APROX
APPROXIMATE
ARCH
ARCHITECTURAL
A55
ASBESTOS
ASPH
ASPHALT
A5TM
AMERICAN 50CIETY OF TESTING 4 MATERIALS
15
NAME PLATE
RAT
BATTERY
BD
BOARD
BITUM
BITUMINOUS
BLDG
BUILDING
BLKG
BLOCKING
BM
BEAM
BOT
BOTTOM
C
OPPOSITE
GAB
CABINET
CB
CATCH BASIN
GEM
CEMENT
CER
CERAMIC
CFM
CUBIC FEET PER MINUTE
CCs
COMER GUARD
CHP
CRICKET HIGH POINT
CI
CAST IRON
GIG
CAST IRON COVER
GIP
CAST IRON PIPE
CJ
CONTROL JOINT
CLG
CEILING
CLGD
CELNG DIFFUSER
CLKG
CAULKING
CLO
CLOSET
CLP
CRICKET LOW POINT
CLR
CLOSER
CMP
CORRUGATED METAL PIPE
CMU
CONCRETE MASONRY UNIT
CNTR
COUNTER
CO
CLEAN OUT
COL
COLUMN
COMM
COMMUNICATION
CONC
CONCRETE
CONN
CONNECTION
CONSTS
CON87RUCTICN
CONT
CONTINUOUS
CPT
CARPET TILE
CT
CERAMIC TILE
GTR
CENTER
CT5K
COUNTERSUNK
5
STUCCO
DBL
DOUBLE
DEG
DEGREE
DEPT
DEPARTMENT
DE51G
DESIGNATION
DET
DETAIL
DF
DRINKING FOUNTAIN
DG
DOOR GRILLE
DIA
DIAMETER
DAG
DIAGRAM
DIM
DIMENSION
DSR
DISPENSER
DN
DOWN
DO
DOOR OPENING
DSP
DRY STANDPIPE
D5
DOWN SPOUT
P1166
DRAWINGS
DWR
DRAWER
E
SPEAKERS
EA
EACH
EC
EPDXY COATING
EHD
ELECTRIC HAND DRYER
EL
ELEVATION
EJ
EXPANSION JOINT
ELEC
ELECTRICAL
ELEV
ELEVATOR
EMER
EMERGENCY
ENCL
ENCLOSURE
ENGR
ENGINEER
EPNL
ELECTRICAL PANEL
FQ
EQUAL
EQPT
EQUIPMENT
EST
ESTIMATE
ET
EXPAN5ION TANK
EWC
ELECTRIC WATER COOLER
EXH
EXHAUST
EXBT
EXISTING
FXT
EXTERIOR
THK
THICK
FA
FIRFE ALARM
FABL
FIRE ALARM BELL
FD
FLOOR DRAIN
FG
FIBERGLASS
FCO
FLOOR CLEANOUT
FD
FIRE DAMPER
FDC
FIRE DEPARTMENT CONNECTOR
FDR
FIRE DOOR
FDN
FOUNDATIONS
FDV
FIRE DEPARTMENT VALVE
FEC
FIRE EXTINGUISHER CABINET
FEX
FIRE EXTINGUISHER
FF
FINISH FLOOR
FH
FIRE HYDRANT
FIN
FIN15H
FL
FLOOR
FM
FACTORY MANUAL
FLASH
FLASHING
FLG
FLANGE
FLOUR
FLUORESCENT
FOC
FACE OF CONCRETE
FOF
FACE OF FINISH
FOM
FACE OF MASONRY
F05
FACE OF STUD
FPRF
FIREPROOF
FPM
FEET PER MINUTE
FRD
FRENCH DRAIN
F5
FULL SIZE
FT
FOOT OR FEET
FTG
FOOTING
FT -LB
FOOT POUNDS
FURR
FURRING
FUT
FUTURE
a
WOOD
GA
GAUGE
GAL
GALLON
GALV
GALVANIZED
GB
GRADE BEAM
GEN
GENERATOR
GL
GLASS
GND
GROUND
GI-5
GLASS BLOCK
GR
GRILLE
GRID
GRADE
GWB
GYPSUM WALL BOARD
GYP
GYPSUM
H
HB HOSE BIB
HC HANDICAPPED
HDWD HARDWOOD
HDWE HARDWARE
HGT HEIGHT
HM HOLLOW METAL
HORIZ HORIZONTAL
HP HIGH POINT
HR HOUR
HTR HEATER
HVAC HEATING, VENTILATION, AND AIR CONDITIONING
HYD HYDRANT
I
ID INSIDE DIAMETER ( DIAN )
N INCHES
INT INTERIOR
J
JAN JANITOR
JB JUNCTION BOX
JCT JUNCTION
J5K JANITORS SINK
JT JOINT
K►
KO KNOCK OUT
IL
LENGTH
LAM
LAMINATE
LAV
LAVATORY
LB5
POUNDS
LBS /HR
POUNDS PER HOUR
LP
LINEAR DIFFUSER
LP
LOW POINT
LT
LIGHT
PSI
MATL
MATERIAL
MAX
MAXIMUM
MC
MEDICINE CABINET
MECH
MECHANICAL
MEMB
MEMBRANE
MFR
MANUFACTURER
MIN
MINIMUM
M 5
MBCELANECUS
MO
MASONRY OPENING
MTD
MOUNTED
MTL
METAL
MUL
MULLION
MULT
MULTIPLE
N
N
NORTH
NEC
NATIONAL ELECTRIC CODE
NIC
NOT IN CONTRACT
NO
NUMBER
ROM
NOMINAL
NFL
NAME PLATE
NT5
NOT TO SCALE
O
OA
OVERALL
058
OBSCURE
OC
ON CENTER
OD
OUTSIDE DIAMETER DIM)
OFS
OVERFLOW SCUPPER
OPP
OPPOSITE
10
PC
PRECAST CONCRETE
Pi
PIPE JOINT
PL
PLASTIC
P LAM
PLASTIC LAMINATE
PLAS
PLASTER
PLYWD
PLYWOOD
PNT
PAINT
PT
POINT OR PATIENT
PTD
PAPER TOWEL DISPENCER
PTN
PARTITION
PTR
PAPER TOWEL RECEPTACLE
42
QRT
QUARTER
QT
QUARRY TILE
R
R
REAR
RA
RETURN AIR
RAP
RADIUS
RB
REINFORCED BEAM
RCPT
RECEPTION
RD
ROOF DRAIN
REF
REFERENCE
REINF
REINFORCED
REQ
REQUIRED
RE5L
RESILIENT
R9TR
REGISTER
RM
ROOM
RO
ROUGH OPENING
RWL
RAIN WATER LEADER
a
5
STUCCO
SC
SCREED CONCRETE
SCHED
SCHEDULE
5EC
SECOND
BD
SMOKE DETECTOR
SECT
SECTION
SF
SUPPLY FAN
SG
SPANDREL GLASS
5GR
SYNTHETIC GRADE
SHR
SHOWER
SHT
SHEET
SIG
SIGNAL
SIM
61MILAR
SI4
SINK
SM
SHEET METAL
SMK
SMOKE
SND
BOUND
SPEC
SPECIFICATION
SPKR
SPEAKERS
SQ
SQUARE
SQFT
SQUARE FEET
55T
STAINLESS STEEL
5T
STREET
5TC
SOUND TRANSMISSION COEFFICIENT
STD
STANDARD
ST -D
STORM DRAIN
BTL
STEEL
STRL
STRUCTURAL
5USP
SUSPENDED
SYM
SYMMETRICAL
SYS
SYSTEM
T
T
TOILET
TB
TIE BEAM
TC
TIE COLUMN
TEL
TELEPHONE
TEMP
TEMPERATURE
T4G
TONGUE AND GROVE
THK
THICK
TOC
TOP OF CURB
TOPP
TOP OF PARAPET
T05
TOP OF BLAB
TP
TOP OF PAVEMENT
TRD
TREAD
T5
TUBULAR STEEL
TSTAT
THERMOSTAT
TV
TELEVISION
TW
TOP OF WALL
TYP
TYPICAL
U
US
UNDERCUT
UL
UNDERWRITER'S LABORATORIES
UNF
UNFINISHED
UON
UNLESS OTHERWISE NOTED
U05
UNLESS OTHER SPECIFIED
UR
URINAL
UTIL
UTILITY
Y
VB
VINYL BASE
VCT
VINYL COMPOSITION TILE
VERT
VERTICAL
VEST
VESTIBULE
VF
VERIFY IN FIELD
VOL
VOLUME
VT
VAPOR TIGHT
VTR
VENT THRU ROOF
w
WR
WIRE
W
WINDOW
W/
WITH
WC
WATER CLOSET
WCO
WALL CLEANOUT
WD
WOOD
WF
WALL FABRIC
W/o
WITHOUT
WP
WATER PROOF
WSCT
WAINSCOT
WT
WEIGHT
WWF
WWM
WELDED WIRE FABRIC
WELDED WIRE MESH
PERMIT SET
05/12/14