14-862-004GENERAL ELECTRICAL NOTES
1. ALL WORK SHALL CONFORM WITH ALL LOCAL, STATE, FEDERAL ORDINANCES, FLORIDA BUILDING
CODE 2010 AND ADDENDUMS, NEC 2008, GOVERNING THE INSTALLATION OF THE ELECTRICAL
SYSTEM. IF WORK AS LAID OUT, INDICATED OR SPECIFIED IS CONTRARY TO OR CONFLICTS WITH
LOCAL ORDINANCES, BUILDING CODES AND REGULATIONS,THE CONTRACTOR SHALL REPORT IN
WRITING TO THE ARCHITECT /ENGINEER BEFORE SUBMITTING A BID. THE ARCHITECT /ENGINEER WILL
THEN ISSUE INSTRUCTIONS AS HOW TO PROCEED.
2. THE DRAWING ARE TO BE CONSIDERED DIAGRAMMATIC, NOT NECESSARILY SHOWING IN DETAIL OR TO
SCALE ALL OF THE MINOR ITEMS. UNLESS SHOWING IN DETAIL OR TO SCALE ALL OF THE MINOR
ITEMS. UNLESS SPECIFIC DIMENSIONS ARE SHOWN, THE STRUCTURAL, ARCHITECTURAL AND SITE
CONDITIONS SHALL GOVERN THE EXACT LOCATIONS. CONTRACTOR SHALL FOLLOW DRAWINGS IN
LAYING OUT WORK, CHECK DRAWINGS OF ALL TRADES TO VERIFY SPACES IN WHICH WORK WILL BE
INSTALLED AND MAINTAIN MAXIMUM HEAD ROOM, OR SPACE CONDITIONS AT ALL POINTS. WHERE
HEADROOM, OR SPACE CONDITIONS APPEAR INADEQUATE, ARCHITECT /ENGINEER SHALL BE NOTIFIED
BEFORE PROCEEDING WITH INSTALLATION. THIS CONTRACTOR SHALL, WITHOUT EXTRA CHARGE, MAKE
FIELD MODIFICATION IN LAYOUT AS NEEDED TO PREVENT CONFLICT WITH WORK OF VARIOUS TRADES
OR FOR PROPER EXECUTION OF THE WORK.
3. INSTALL MATERIALS AND EQUIPMENT IN A NEAT AND FIRST CLASS WORKMANLIKE MANNER. THE
OWNER RESERVES THE RIGHT TO DIRECT REMOVAL AND REPLACEMENT OF ITEMS WHICH, IN HIS
OPINION, DO NOT PRESENT A NEAT AND WORKMANLIKE APPEARANCE. REMOVAL AND REPLACEMENT
IS TO BE DONE IMMEDIATELY WHEN DIRECTED BY THE OWNER IN WRITING, AT THE SOLE EXPENSE OF
CONTRACTOR.
4. START OF WORK BY CONTRACTOR SHALL BE CONSIDERED AS ACCEPTANCE BY HIM OF ALL CLAIMS
OR QUESTIONS AS TO SUITABILITY OF THE WORK OF OTHER TRADES OR OTHER CONTRACTORS TO
RECEIVE HIS WORK. THIS CONTRACTOR SHALL REMOVE AND REPLACE, AT HIS EXPENSE, ALL
ELECTRICAL WORK WHICH MAY HAVE TO BE REMOVED BECAUSE OF INTERFERENCE WITH OTHER
TRADES.
5. THIS CONTRACTOR SHALL OBTAIN AND PAY ALL INSURANCE, FEES, PERMITS ASSOCIATION DUES,
ROYALTIES, AND TAXES OF WHATEVER NATURE SHALL APPLY TO THIS WORK. HE SHALL ALSO PAY
ALL INSPECTION FEES AS MAY BE REQUIRED BY LAW OR ORDINANCE AND SHALL KEEP THE OWNER
HARMLESS FROM ANY DAMAGE AND EXPENSE ARISING FROM ANY VIOLATION OF THE LAWS, RULES
OR ORDINANCES.
6. ALL WIRE COPPER, IN RACEWAY, UNLESS OTHERWISE SPECIFIED ON DRAWINGS.
7. PROVIDE MEANS "FURNISH AND INSTALL".
8. COORDINATE WORK WITH WORK OF OTHER TRADES TO AVOID ALL CONFLICTS.
9. PROVIDE A COMPLETE OPERATIONAL SYSTEM, EVERYTHING CONNECTED, READY FOR USE.
10. PROVIDE ALL WIRING DEVICES. AVOID 1/2 SIZE BREAKERS UNLESS APPROVED BY ENGINEER.
11. PRIOR TO CIRCUITING HOMERUNS, CONTRACTOR SHALL FIELD VERIFY EXISTING LOADS, SPARES,
SPACES, AVAILABILITY, AND WIRE ACOORDINGLY. IDENTIFY CLEARLY ON A TYPE WRITTEN PANEL
SCHEDULE ALL CIRCUITS TO CORRESPOND WITH EXISTING, AND NEW CONDITIONS. ATTACH INSIDE
THE PERTAINING PANEL DOOR.
12. RACEWAYS: ALL UNDERGROUND RACEWAYS TO BE PVC, INSIDE CONCRETE SLAB EMT WITH
APPROVED SET SCREW FITTING, INSIDE PARTITION EMT, AND, ENT WHERE ALLOWED. FOR FLOOR
PENETRATION USE ONLY EMT.
13. SHOP DRAWINGS: THIS CONTRACTOR SHALL FURNISH THE ENGINEER WITH SHOP DRAWINGS OF
EQUIPMENT PRIOR TO PURCHASE FOR APPROVAL.
14. TESTING: THE CONTRACTOR SHALL TEST ALL WORK AND EQUIPMENT AS DIRECTED BY THE ARCHITECT
AND BY AUTHORITIES HAVING JURISDICTION,FURNISHING ALL EQUIPMENT AND NECESSARY PERSONNEL
AND ELECTRIC POWER. THE ENTIRE INSTALLATION SHALL BE TESTED FOR SHORTS, GROUNDS AND
OPEN CIRCUITS, AND ALL DEFECTS SHALL BE DEMONSTRATED TO BE IN PROPER WORKING AND
OPERATING CONDITION TO THE COMPLETE SATISFACTION OF THE ENGINEER.
15. GUARANTEES: ONE YEAR AFTER THE DATE OF ACCEPTANCE BY OWNER.
16. AT COMPLETION OF PROJECT THE ELECTRICAL CONTRACTOR SHALL GIVE THE OWNER AN AS -BUILT
SET OF DRAWINGS SHOWING THE EXACT ELECTRICAL INSTALLATION. ALL EQUIPMENT AND MATERIALS
SHALL BE GUARANTEED FOR.
17. BEFORE BIDDING THE JOB THE ELECTRICAL CONTRACTOR SHALL VISIT THE SITE AND BECOME
FAMILIAR WITH ALL EXISTING CONDITIONS.
18. ALL EXISTING ELECTRICAL DEVICES AND EQUIPMENT AND THEIR ASSOCIATED WIRING INSIDE THE
REMOVED WALLS SHALL BE DISCONNECTED AND REMOVED.
19. CONTRACTOR SHALL COLOR CODE THE FEEDER, AND BRANCH WIRING AS FOLLOWS: 120/24OV:
BLACK, RED, BLUE, AND WHITE.
20. CONTRACTOR SHALL FIRE -STOP AND SEAL ALL PATHWAYS THROUGH FLOORS, WALLS, AND OTHER
RELATED PENETRATIONS IN ACCORDANCE WITH FBC.
1191
lire]
c
c
Ln
STUB -UP
O
REPLACED SUB -BASE DOUBLE TANK TO BE
RECONNECTED TO EXISTING GENERATOR SET. ALL
PIPING AND ELECTRICAL CONNECTIONS FOR
CONTROLLER AND ALARM TO BE RECONNECTED.
CONTRACTOR TO VERIFY EXISTING CONDITIONS
�
BEFORE COMMENCING WORK.
O
SPARE
2 "NPT
II 1
-- �.
1-- --------------- 1 - -1 - -- -- -- ----- E-- L------- - - - - -- --------
- '--- I---- U - - -1 -�
_------------ ____ --- ___-------------------------------------------------- _ -----
6.909
I `
ii S P MECH FUEL �1
GAUCE
II \`
I II
1i FUEL SUPPLY Q0
HIGH FUEL AND RETURN SPARE
LEVEL
SENSOR 2 "NPT V 1 ,
'i LOW FUEL S
li LEVEL S P I
I' SENSOR34.246
35.021 ='
II
=--------------------------------- .
42.61 00 co
U-) (,D - -;- - - - 11C
- - -- _ - - -- -- _ - - - -- _---- - - - - -- _------- - - -- -- -- I
- J �---- - ====
- �
zi-
Up LEAK
N ('� DETECTOR
M SWITCH WITH
ff-) n ALARM KIT
SV
I I
I I
I I
I I
DESIGN CRITERIA
1 500 GALLON BASE TANK FOR A CAT 3306 GENERATOR SET
ADVANCED MANUFACTURING & POWER SYSTEMS, INC. TO PROVIDE:
500- GALLON UL -142, FUEL BASE TANK:
• 1 /a" MILD STEEL CONSTRUCTION
• RUPTURE BASIN
• MECHANICAL FUEL LEVEL GAUGE (VISIBLE AT FILL POINT)
• 2" FUEL FILL CAP WITH FDEP SPILL CONTAINMENT AND OVERFILL PREVENTION DEVICE
• NORMAL AND EMERGENCY VENTS PER UL -142
• HIGH AND LOW LEVEL FUEL ALARM SWITCHES WIRED TO GENERATOR CONTROL PANEL.
• LEAK DETECTION SWITCH WIRED TO GENERATOR CONTROL PANEL.
• SUPPLY AND RETURN CONNECTIONS
• CABLE STUB UP OPENING LOCATED AT REAR OF TANK
• GENERATOR MOUNTING PADS
• 2 LIFTING POINTS PER SIDE (4 TOTAL) FOR LIFTING GENERATOR SET, ENCLOSURE AND TANK (EMPTY)
• EXTERIOR TO BE PAINTED GLOSS BLACK
SYSTEM INTEGRATION:
• UNLOAD PANTROPIC POWER SUPPLIED GENERATOR SET AND COMPONENTS FROM TRUCKS.
• INSTALL GENERATOR TO FUEL TANK BASE AND PLUMB FUEL TANK TO GENERATOR SET ENGINE.
• LOAD UNIT ONTO PANTROPIC POWER PROVIDED TRUCKS FOR SHIPMENT.
PANTROPIC POWER TO PROVIDE:
• CAT 3306 PACKAGED GENERATOR SET WITH FACTORY INSTALLED RADIATOR AND ALL SPECIFIED OPTIONS.
0
FUEL FILL
19
-MAIN VENT
26
33
T PRIMARY
AND
SECONDARY
EMERGENCY
43 VENT
52
O
Ln
Z&
1111111111M�_
TANK FITTING LEGEND
F - FUEL FILL [ 179MCI 2" ] - 2" NPT
G - MECH. FUEL GAUGE - 1 1/2" NPT
D - LEAK DETECTOR [ MADISON M -7000 EQ#682 ] - 1" NPT
S - FUEL SUPPLY - 1" NPT
R - FUEL RETURN - 1" NPT
DS - DAYTANK FUEL SUPPLY - 1" NPT
DR - DAYTANK FUEL RETURN - 1" NPT
V - MAIN VENT - 2" NPT
SV - SECONDARY EMERGENCY VENT - 6" NPT
PV - PRIMARY EMERGENCY VENT - 4" NPT
H - HIGH FUEL LEVEL SENSOR [ MADISON M -7000 EQ#682 ] - 1" NPT
L - LOW FUEL LEVEL SENSOR [ MADISON M -7000 ] - 1" NPT
SP - SPARE - 2 "NPT
PS - FUEL POLISHING SUPPLY - 1" NPT
PR - FUEL POLISHING RETURN - 1" NPT
SS - 4 -20ma ULTRASONIC SENSOR - 2 "NPT
DTCS - DAYTANK CONTROL SWITCHES
AMPS UL -142 DOUBLE WALL TANK & SPILL CONTAINMENT - [EQ#5331
*NOTE: TANK FITTING SIZES SHOWN ON PLAN ARE OPENING SIZES
COMPONENT CAD DRAWING #(S) 132 -4889
("fill I / 1- 'tNI-rAINIAArAIT IAIITI.I
DRAWINGS FOR APPROVAL
APPROVED AS DRAWN ❑
REVISE AS NOTED ❑
SIGNATURE: DATE:
NAME (PLEASE PRINT):
TITLE:
NOTE- ALL DIMENSIONS ARE IN INCHES
REVISIONS
REV DESCRIPTON
DOUBLE WALL SUB BASE FUEL TANK DETAILS
Fuel Tank Features and Options
11 10 9 8 7 6 5 4 3 2
EXISTING
GENERATOR
1. Inner tank leak alarm kit 7. Lockable /sealed fill cap with riser (standard)
2. Emergency pressure relief vent outer tank (standard) 8. Mechanical fuel gauge (standard)
3. Emergency pressure relief vent inner tank (standard) 9. Low fuel level switch for controller alarm
4. Fuel supply line (compatible with Decision - Maker -3+ and Decision - Maker -550)
5. Normal vent with riser and mushroom cap (standard) 10. Day tank kit
6. Fuel return line 11. 1/2 in. NPT for leak detection switch
Figure 1 Double -Wall Subbase Fuel Tanks (Secondary Containment)
G M 16904 -1
DATE I BY
_n E_(2 _ III
^ L J � I
c
ADVANCED MANUFACTURING & POWER SYSTEMS INC.
1965 BENNETT DRIVE. DELAND, F1_ 32724
PHONE: 386.622.5565 FAX: 386.622.9669
CODE INFORMATION j
CODE VERSION N/A - TANK ONLY
MANUFACTURER ADVANCED MANUFACTURING
& POWER SYSTEMS INC
AGENCY N/A - TANK ONLY
CONSTRUCTION TYPE N/A - TANK ONLY
FIRE PROTECTION N/A - TANK ONLY
FIRE SUPPRESSION SYSTEM I N/A - TANK ONLY
OCCUPANCY
11
ALLOWABLE # OF STORIES
N/A - TANK ONLY
i ii 1
N/A - TANK ONLY
EXPOSURE
N/A - TANK ONLY
MAX. FLOOR LOAD
F-
N/A - TANK ONLY
ROOF LIVE LOAD
I I
11 it
"R" RATING OF FLOOR, WALL AND ROOF
II
MODULES PER BUILDING
N/A
I II
M'
LIFTI
IG
POINTS
ESTIMATED SHIPPING / WEIGHT INFORMATION
ILL
150 "1 x 52 5 "w x 41"h
SHIPPING DIMENSIONS
1r -- - -�1
I I I I
; II
��
II
- Ibs
TANK / BASE FRAME WEIGHT
I I III
IL
(x2
E
SIDE)
TOTAL SHIPPING WEIGHT:
'c
3,300 Ibs
Z
I,L
1
0 E
w
II
w
I-
1 III
U
w
IL
o
z
O
v
II
1
LLI
U
I II
1
U
CU
(°° E Q
W
0
Q
V,
I I
I I
1111
u
T. Baldwin P.E.
II
II
Florida
F-
1 II,
I 11 1
OF 1
n-
IL
U
1_ LLJ
O
I I
I I
11
11 11
11
11
II
a
I 11 ,
I 11,
I I
I I
11
„II
L Q
p
0-
I II,
I 111
7)
1 I
„II
„II
II
I I
p
I II,
I 11,
I I
1111
„II
11
II
I 111
I I
„II
I °1
I
II
II
II
I II
------------ - - - - --
1 1
--
------------------------- - - - - --
-
--
-
------------------------- - - - - --
------------------------ - - - - --
--
-I-
- --
- --
I I
-- - --
II
31 11
120 - UL142 TANK
1 G (1
Z&
1111111111M�_
TANK FITTING LEGEND
F - FUEL FILL [ 179MCI 2" ] - 2" NPT
G - MECH. FUEL GAUGE - 1 1/2" NPT
D - LEAK DETECTOR [ MADISON M -7000 EQ#682 ] - 1" NPT
S - FUEL SUPPLY - 1" NPT
R - FUEL RETURN - 1" NPT
DS - DAYTANK FUEL SUPPLY - 1" NPT
DR - DAYTANK FUEL RETURN - 1" NPT
V - MAIN VENT - 2" NPT
SV - SECONDARY EMERGENCY VENT - 6" NPT
PV - PRIMARY EMERGENCY VENT - 4" NPT
H - HIGH FUEL LEVEL SENSOR [ MADISON M -7000 EQ#682 ] - 1" NPT
L - LOW FUEL LEVEL SENSOR [ MADISON M -7000 ] - 1" NPT
SP - SPARE - 2 "NPT
PS - FUEL POLISHING SUPPLY - 1" NPT
PR - FUEL POLISHING RETURN - 1" NPT
SS - 4 -20ma ULTRASONIC SENSOR - 2 "NPT
DTCS - DAYTANK CONTROL SWITCHES
AMPS UL -142 DOUBLE WALL TANK & SPILL CONTAINMENT - [EQ#5331
*NOTE: TANK FITTING SIZES SHOWN ON PLAN ARE OPENING SIZES
COMPONENT CAD DRAWING #(S) 132 -4889
("fill I / 1- 'tNI-rAINIAArAIT IAIITI.I
DRAWINGS FOR APPROVAL
APPROVED AS DRAWN ❑
REVISE AS NOTED ❑
SIGNATURE: DATE:
NAME (PLEASE PRINT):
TITLE:
NOTE- ALL DIMENSIONS ARE IN INCHES
REVISIONS
REV DESCRIPTON
DOUBLE WALL SUB BASE FUEL TANK DETAILS
Fuel Tank Features and Options
11 10 9 8 7 6 5 4 3 2
EXISTING
GENERATOR
1. Inner tank leak alarm kit 7. Lockable /sealed fill cap with riser (standard)
2. Emergency pressure relief vent outer tank (standard) 8. Mechanical fuel gauge (standard)
3. Emergency pressure relief vent inner tank (standard) 9. Low fuel level switch for controller alarm
4. Fuel supply line (compatible with Decision - Maker -3+ and Decision - Maker -550)
5. Normal vent with riser and mushroom cap (standard) 10. Day tank kit
6. Fuel return line 11. 1/2 in. NPT for leak detection switch
Figure 1 Double -Wall Subbase Fuel Tanks (Secondary Containment)
G M 16904 -1
DATE I BY
_n E_(2 _ III
^ L J � I
c
ADVANCED MANUFACTURING & POWER SYSTEMS INC.
1965 BENNETT DRIVE. DELAND, F1_ 32724
PHONE: 386.622.5565 FAX: 386.622.9669
CODE INFORMATION j
CODE VERSION N/A - TANK ONLY
MANUFACTURER ADVANCED MANUFACTURING
& POWER SYSTEMS INC
AGENCY N/A - TANK ONLY
CONSTRUCTION TYPE N/A - TANK ONLY
FIRE PROTECTION N/A - TANK ONLY
FIRE SUPPRESSION SYSTEM I N/A - TANK ONLY
OCCUPANCY
N/A - TANK ONLY
ALLOWABLE # OF STORIES
N/A - TANK ONLY
BASIC WIND SPEED
N/A - TANK ONLY
EXPOSURE
N/A - TANK ONLY
ENCLOSURE
Reviewed By:
N/A - TANK ONLY
INTERNAL PRESSURE COEFFICIENT
N/A - TANK ONLY
IMPORTANCE FACTOR
Date:
N/A - TANK ONLY
MAX. FLOOR LOAD
F-
N/A - TANK ONLY
ROOF LIVE LOAD
<
N/A - TANK ONLY
"R" RATING OF FLOOR, WALL AND ROOF
N/A - TANK ONLY
MODULES PER BUILDING
N/A
N/A - TANK ONLY
SQUARE FOOTAGE
N/A - TANK ONLY
ESTIMATED SHIPPING / WEIGHT INFORMATION
ILL
150 "1 x 52 5 "w x 41"h
SHIPPING DIMENSIONS
20140035
1
GENSET WEIGHT
- Ibs
TANK / BASE FRAME WEIGHT
Z
3,300 Ibs
ENCLOSURE & ACCESSORIES WEIGHT
_ Ibs
TOTAL SHIPPING WEIGHT:
'c
3,300 Ibs
Z
s
0 E
w
Q�
CL
w
I-
z z
U
w
IL
o
z
O
L1�
co
> O C N
LLI
U
Z M .
C:)
U
CU
(°° E Q
W
0
Q
V,
U
U)
T. Baldwin P.E.
Florida
F-
O a-
OF 1
n-
IL
U
1_ LLJ
O
Cn
a
o Q
LL
L Q
0-
as U-)
7)
DOUBLE WALL SUBBASE FUEL OPTIONS:
1. FUEL IN BASIN OPTIONS/LEAK DETECTION:
FUEL IN BASIN SWITCH, FLORIDA DEPT. OF
ENVIRONMENTAL PROTECTION (FDEP) FILE N'. EQ -014
APPROVED
2. FUEL FILL AND SPILL OPTIONS:
26.5L(7 GALLON) SPILL CONTAINMENT WITH 95% SHUTOFF,
FLORIDA DEPT. OF ENVIRONMENTAL PROTECTION (FDEP)
FILE N'. EQ- 226/EQ257 APPROVED
3. FUEL SUPPLY OPTIONS:
BALL VALVE (INSTALLED ON FUEL SUPPLY LINE).
4. HIGH FUEL LEVEL SWITCH/OVERFILL-
HIGH FUEL LEVEL SWITCH FOR OVERFILL PREVENTION,
FLORIDA DEPT. OF ENVIRONMENTAL PROTECTION (FDEP)
FILE N'. EQ -682 APPROVED.
5. NORMAL VENT OPTIONS:
3.7M (12FT) ABOVE GRADE (WITH SPILL CONTAINMENT).
VENT TO BE STEEL SCH 40.
6. TANK MARKING OPTIONS:
DECAL TANK NUMBER AND SAFE FUEL FILL HEIGHT,
NFPA 704 IDENTIFICATION
CONTRACTOR MAY USE EQUIVALENT OPTIONS, FDEP
APPROVED TO COMPLY WITH STATE OF FLORIDA
REQUIREMENTS
ALL EQUIPMENT SHALL BE FDEP APPROVED
SUB -BASE TANK EQ #533, UL 142
Al
SEAL:
Reviewed By:
(0 : E
DRAWN:
SC
MTB /CD
Date:
G3
S
"U)
T1_ r
c,) 4 6)
F-
3/25/14
<
Scale:
L0 •Q
O
0
N/A
Z_
Number:
QProject
U
ILL
LU
W
20140035
LU
oZj
Z_
a
Z
E-2
c-
Q
V
'c
Ne
Z
s
0 E
w
Q�
CL
Q
I-
{V
GT-
LL1
IL
C14 .Q
IN--
�
O
L1�
co
> O C N
U
Z M .
C:)
z
CU
(°° E Q
W
0
V,
V)
Matthew
T. Baldwin P.E.
Florida
License #64608
Sheet: S-1
OF 1
J
r
DOUBLE WALL SUBBASE FUEL OPTIONS:
1. FUEL IN BASIN OPTIONS/LEAK DETECTION:
FUEL IN BASIN SWITCH, FLORIDA DEPT. OF
ENVIRONMENTAL PROTECTION (FDEP) FILE N'. EQ -014
APPROVED
2. FUEL FILL AND SPILL OPTIONS:
26.5L(7 GALLON) SPILL CONTAINMENT WITH 95% SHUTOFF,
FLORIDA DEPT. OF ENVIRONMENTAL PROTECTION (FDEP)
FILE N'. EQ- 226/EQ257 APPROVED
3. FUEL SUPPLY OPTIONS:
BALL VALVE (INSTALLED ON FUEL SUPPLY LINE).
4. HIGH FUEL LEVEL SWITCH/OVERFILL-
HIGH FUEL LEVEL SWITCH FOR OVERFILL PREVENTION,
FLORIDA DEPT. OF ENVIRONMENTAL PROTECTION (FDEP)
FILE N'. EQ -682 APPROVED.
5. NORMAL VENT OPTIONS:
3.7M (12FT) ABOVE GRADE (WITH SPILL CONTAINMENT).
VENT TO BE STEEL SCH 40.
6. TANK MARKING OPTIONS:
DECAL TANK NUMBER AND SAFE FUEL FILL HEIGHT,
NFPA 704 IDENTIFICATION
CONTRACTOR MAY USE EQUIVALENT OPTIONS, FDEP
APPROVED TO COMPLY WITH STATE OF FLORIDA
REQUIREMENTS
ALL EQUIPMENT SHALL BE FDEP APPROVED
SUB -BASE TANK EQ #533, UL 142
Al
SEAL:
r
PABLO J. VITERI ;
PE# 59535 '
09 -23 -13
(0 : E
DRAWN:
SC
(0 CD
U
0
G3
S
"U)
T1_ r
c,) 4 6)
Z
J 00 N LL
<
LU
L0 •Q
r�
V
0
E2 C:)
` M
Z_
co
CG
U
ILL
LU
W
(J)
O
LU
oZj
Z_
a
Z
E-2
c-
`'
V
'c
Ne
Z
s
0 E
w
Q�
CL
LO U
I-
{V
GT-
T-
IL
C14 .Q
O
�
O
co
> O C N
j
Z M .
C:)
O♦^>♦
CU
(°° E Q
W
�
r
PABLO J. VITERI ;
PE# 59535 '
CUENT:
BAPTIST HEALTH
SOUTH FLORIDA.
PROJECT LOCATION:
6200 SW 73 STREET,
SOUTH MIAMI, FL 33176
ISSUE
PERMIT
GT10�; m DERM COMM
p vY,
DATE
9 -23 -13
04/09/14
DATE:
09 -23 -13
W
DRAWN:
SC
CHECKED:
V
F-
SHEET T17LE:
J
<
Z
NOTES.
Q
co
a.
W
N r
3
(J)
O
Uo
Q
W
T
Z
Z
E-2
c-
`'
O
-
Ne
0.
Q
Q�
CL
I-
O
�
ZU
W
IL
O
�
O
j
a:
O♦^>♦
W
�
V,
_
LL
v,
a
CUENT:
BAPTIST HEALTH
SOUTH FLORIDA.
PROJECT LOCATION:
6200 SW 73 STREET,
SOUTH MIAMI, FL 33176
ISSUE
PERMIT
GT10�; m DERM COMM
p vY,
DATE
9 -23 -13
04/09/14
DATE:
09 -23 -13
DRAWN:
SC
CHECKED:
PV
SHEET T17LE:
DETAILS AND
-
NOTES.
SHEET:
3
E-2
,