14-862-004GENERAL ELECTRICAL NOTES 1. ALL WORK SHALL CONFORM WITH ALL LOCAL, STATE, FEDERAL ORDINANCES, FLORIDA BUILDING CODE 2010 AND ADDENDUMS, NEC 2008, GOVERNING THE INSTALLATION OF THE ELECTRICAL SYSTEM. IF WORK AS LAID OUT, INDICATED OR SPECIFIED IS CONTRARY TO OR CONFLICTS WITH LOCAL ORDINANCES, BUILDING CODES AND REGULATIONS,THE CONTRACTOR SHALL REPORT IN WRITING TO THE ARCHITECT /ENGINEER BEFORE SUBMITTING A BID. THE ARCHITECT /ENGINEER WILL THEN ISSUE INSTRUCTIONS AS HOW TO PROCEED. 2. THE DRAWING ARE TO BE CONSIDERED DIAGRAMMATIC, NOT NECESSARILY SHOWING IN DETAIL OR TO SCALE ALL OF THE MINOR ITEMS. UNLESS SHOWING IN DETAIL OR TO SCALE ALL OF THE MINOR ITEMS. UNLESS SPECIFIC DIMENSIONS ARE SHOWN, THE STRUCTURAL, ARCHITECTURAL AND SITE CONDITIONS SHALL GOVERN THE EXACT LOCATIONS. CONTRACTOR SHALL FOLLOW DRAWINGS IN LAYING OUT WORK, CHECK DRAWINGS OF ALL TRADES TO VERIFY SPACES IN WHICH WORK WILL BE INSTALLED AND MAINTAIN MAXIMUM HEAD ROOM, OR SPACE CONDITIONS AT ALL POINTS. WHERE HEADROOM, OR SPACE CONDITIONS APPEAR INADEQUATE, ARCHITECT /ENGINEER SHALL BE NOTIFIED BEFORE PROCEEDING WITH INSTALLATION. THIS CONTRACTOR SHALL, WITHOUT EXTRA CHARGE, MAKE FIELD MODIFICATION IN LAYOUT AS NEEDED TO PREVENT CONFLICT WITH WORK OF VARIOUS TRADES OR FOR PROPER EXECUTION OF THE WORK. 3. INSTALL MATERIALS AND EQUIPMENT IN A NEAT AND FIRST CLASS WORKMANLIKE MANNER. THE OWNER RESERVES THE RIGHT TO DIRECT REMOVAL AND REPLACEMENT OF ITEMS WHICH, IN HIS OPINION, DO NOT PRESENT A NEAT AND WORKMANLIKE APPEARANCE. REMOVAL AND REPLACEMENT IS TO BE DONE IMMEDIATELY WHEN DIRECTED BY THE OWNER IN WRITING, AT THE SOLE EXPENSE OF CONTRACTOR. 4. START OF WORK BY CONTRACTOR SHALL BE CONSIDERED AS ACCEPTANCE BY HIM OF ALL CLAIMS OR QUESTIONS AS TO SUITABILITY OF THE WORK OF OTHER TRADES OR OTHER CONTRACTORS TO RECEIVE HIS WORK. THIS CONTRACTOR SHALL REMOVE AND REPLACE, AT HIS EXPENSE, ALL ELECTRICAL WORK WHICH MAY HAVE TO BE REMOVED BECAUSE OF INTERFERENCE WITH OTHER TRADES. 5. THIS CONTRACTOR SHALL OBTAIN AND PAY ALL INSURANCE, FEES, PERMITS ASSOCIATION DUES, ROYALTIES, AND TAXES OF WHATEVER NATURE SHALL APPLY TO THIS WORK. HE SHALL ALSO PAY ALL INSPECTION FEES AS MAY BE REQUIRED BY LAW OR ORDINANCE AND SHALL KEEP THE OWNER HARMLESS FROM ANY DAMAGE AND EXPENSE ARISING FROM ANY VIOLATION OF THE LAWS, RULES OR ORDINANCES. 6. ALL WIRE COPPER, IN RACEWAY, UNLESS OTHERWISE SPECIFIED ON DRAWINGS. 7. PROVIDE MEANS "FURNISH AND INSTALL". 8. COORDINATE WORK WITH WORK OF OTHER TRADES TO AVOID ALL CONFLICTS. 9. PROVIDE A COMPLETE OPERATIONAL SYSTEM, EVERYTHING CONNECTED, READY FOR USE. 10. PROVIDE ALL WIRING DEVICES. AVOID 1/2 SIZE BREAKERS UNLESS APPROVED BY ENGINEER. 11. PRIOR TO CIRCUITING HOMERUNS, CONTRACTOR SHALL FIELD VERIFY EXISTING LOADS, SPARES, SPACES, AVAILABILITY, AND WIRE ACOORDINGLY. IDENTIFY CLEARLY ON A TYPE WRITTEN PANEL SCHEDULE ALL CIRCUITS TO CORRESPOND WITH EXISTING, AND NEW CONDITIONS. ATTACH INSIDE THE PERTAINING PANEL DOOR. 12. RACEWAYS: ALL UNDERGROUND RACEWAYS TO BE PVC, INSIDE CONCRETE SLAB EMT WITH APPROVED SET SCREW FITTING, INSIDE PARTITION EMT, AND, ENT WHERE ALLOWED. FOR FLOOR PENETRATION USE ONLY EMT. 13. SHOP DRAWINGS: THIS CONTRACTOR SHALL FURNISH THE ENGINEER WITH SHOP DRAWINGS OF EQUIPMENT PRIOR TO PURCHASE FOR APPROVAL. 14. TESTING: THE CONTRACTOR SHALL TEST ALL WORK AND EQUIPMENT AS DIRECTED BY THE ARCHITECT AND BY AUTHORITIES HAVING JURISDICTION,FURNISHING ALL EQUIPMENT AND NECESSARY PERSONNEL AND ELECTRIC POWER. THE ENTIRE INSTALLATION SHALL BE TESTED FOR SHORTS, GROUNDS AND OPEN CIRCUITS, AND ALL DEFECTS SHALL BE DEMONSTRATED TO BE IN PROPER WORKING AND OPERATING CONDITION TO THE COMPLETE SATISFACTION OF THE ENGINEER. 15. GUARANTEES: ONE YEAR AFTER THE DATE OF ACCEPTANCE BY OWNER. 16. AT COMPLETION OF PROJECT THE ELECTRICAL CONTRACTOR SHALL GIVE THE OWNER AN AS -BUILT SET OF DRAWINGS SHOWING THE EXACT ELECTRICAL INSTALLATION. ALL EQUIPMENT AND MATERIALS SHALL BE GUARANTEED FOR. 17. BEFORE BIDDING THE JOB THE ELECTRICAL CONTRACTOR SHALL VISIT THE SITE AND BECOME FAMILIAR WITH ALL EXISTING CONDITIONS. 18. ALL EXISTING ELECTRICAL DEVICES AND EQUIPMENT AND THEIR ASSOCIATED WIRING INSIDE THE REMOVED WALLS SHALL BE DISCONNECTED AND REMOVED. 19. CONTRACTOR SHALL COLOR CODE THE FEEDER, AND BRANCH WIRING AS FOLLOWS: 120/24OV: BLACK, RED, BLUE, AND WHITE. 20. CONTRACTOR SHALL FIRE -STOP AND SEAL ALL PATHWAYS THROUGH FLOORS, WALLS, AND OTHER RELATED PENETRATIONS IN ACCORDANCE WITH FBC. 1191 lire] c c Ln STUB -UP O REPLACED SUB -BASE DOUBLE TANK TO BE RECONNECTED TO EXISTING GENERATOR SET. ALL PIPING AND ELECTRICAL CONNECTIONS FOR CONTROLLER AND ALARM TO BE RECONNECTED. CONTRACTOR TO VERIFY EXISTING CONDITIONS � BEFORE COMMENCING WORK. O SPARE 2 "NPT II 1 -- �. 1-- --------------- 1 - -1 - -- -- -- ----- E-- L------- - - - - -- -------- - '--- I---- U - - -1 -� _------------ ____ --- ___-------------------------------------------------- _ ----- 6.909 I ` ii S P MECH FUEL �1 GAUCE II \` I II 1i FUEL SUPPLY Q0 HIGH FUEL AND RETURN SPARE LEVEL SENSOR 2 "NPT V 1 , 'i LOW FUEL S li LEVEL S P I I' SENSOR34.246 35.021 =' II =--------------------------------- . 42.61 00 co U-) (,D - -;- - - - 11C - - -- _ - - -- -- _ - - - -- _---- - - - - -- _------- - - -- -- -- I - J �---- - ==== - � zi- Up LEAK N ('� DETECTOR M SWITCH WITH ff-) n ALARM KIT SV I I I I I I I I DESIGN CRITERIA 1 500 GALLON BASE TANK FOR A CAT 3306 GENERATOR SET ADVANCED MANUFACTURING & POWER SYSTEMS, INC. TO PROVIDE: 500- GALLON UL -142, FUEL BASE TANK: • 1 /a" MILD STEEL CONSTRUCTION • RUPTURE BASIN • MECHANICAL FUEL LEVEL GAUGE (VISIBLE AT FILL POINT) • 2" FUEL FILL CAP WITH FDEP SPILL CONTAINMENT AND OVERFILL PREVENTION DEVICE • NORMAL AND EMERGENCY VENTS PER UL -142 • HIGH AND LOW LEVEL FUEL ALARM SWITCHES WIRED TO GENERATOR CONTROL PANEL. • LEAK DETECTION SWITCH WIRED TO GENERATOR CONTROL PANEL. • SUPPLY AND RETURN CONNECTIONS • CABLE STUB UP OPENING LOCATED AT REAR OF TANK • GENERATOR MOUNTING PADS • 2 LIFTING POINTS PER SIDE (4 TOTAL) FOR LIFTING GENERATOR SET, ENCLOSURE AND TANK (EMPTY) • EXTERIOR TO BE PAINTED GLOSS BLACK SYSTEM INTEGRATION: • UNLOAD PANTROPIC POWER SUPPLIED GENERATOR SET AND COMPONENTS FROM TRUCKS. • INSTALL GENERATOR TO FUEL TANK BASE AND PLUMB FUEL TANK TO GENERATOR SET ENGINE. • LOAD UNIT ONTO PANTROPIC POWER PROVIDED TRUCKS FOR SHIPMENT. PANTROPIC POWER TO PROVIDE: • CAT 3306 PACKAGED GENERATOR SET WITH FACTORY INSTALLED RADIATOR AND ALL SPECIFIED OPTIONS. 0 FUEL FILL 19 -MAIN VENT 26 33 T PRIMARY AND SECONDARY EMERGENCY 43 VENT 52 O Ln Z& 1111111111M�_ TANK FITTING LEGEND F - FUEL FILL [ 179MCI 2" ] - 2" NPT G - MECH. FUEL GAUGE - 1 1/2" NPT D - LEAK DETECTOR [ MADISON M -7000 EQ#682 ] - 1" NPT S - FUEL SUPPLY - 1" NPT R - FUEL RETURN - 1" NPT DS - DAYTANK FUEL SUPPLY - 1" NPT DR - DAYTANK FUEL RETURN - 1" NPT V - MAIN VENT - 2" NPT SV - SECONDARY EMERGENCY VENT - 6" NPT PV - PRIMARY EMERGENCY VENT - 4" NPT H - HIGH FUEL LEVEL SENSOR [ MADISON M -7000 EQ#682 ] - 1" NPT L - LOW FUEL LEVEL SENSOR [ MADISON M -7000 ] - 1" NPT SP - SPARE - 2 "NPT PS - FUEL POLISHING SUPPLY - 1" NPT PR - FUEL POLISHING RETURN - 1" NPT SS - 4 -20ma ULTRASONIC SENSOR - 2 "NPT DTCS - DAYTANK CONTROL SWITCHES AMPS UL -142 DOUBLE WALL TANK & SPILL CONTAINMENT - [EQ#5331 *NOTE: TANK FITTING SIZES SHOWN ON PLAN ARE OPENING SIZES COMPONENT CAD DRAWING #(S) 132 -4889 ("fill I / 1- 'tNI-rAINIAArAIT IAIITI.I DRAWINGS FOR APPROVAL APPROVED AS DRAWN ❑ REVISE AS NOTED ❑ SIGNATURE: DATE: NAME (PLEASE PRINT): TITLE: NOTE- ALL DIMENSIONS ARE IN INCHES REVISIONS REV DESCRIPTON DOUBLE WALL SUB BASE FUEL TANK DETAILS Fuel Tank Features and Options 11 10 9 8 7 6 5 4 3 2 EXISTING GENERATOR 1. Inner tank leak alarm kit 7. Lockable /sealed fill cap with riser (standard) 2. Emergency pressure relief vent outer tank (standard) 8. Mechanical fuel gauge (standard) 3. Emergency pressure relief vent inner tank (standard) 9. Low fuel level switch for controller alarm 4. Fuel supply line (compatible with Decision - Maker -3+ and Decision - Maker -550) 5. Normal vent with riser and mushroom cap (standard) 10. Day tank kit 6. Fuel return line 11. 1/2 in. NPT for leak detection switch Figure 1 Double -Wall Subbase Fuel Tanks (Secondary Containment) G M 16904 -1 DATE I BY _n E_(2 _ III ^ L J � I c ADVANCED MANUFACTURING & POWER SYSTEMS INC. 1965 BENNETT DRIVE. DELAND, F1_ 32724 PHONE: 386.622.5565 FAX: 386.622.9669 CODE INFORMATION j CODE VERSION N/A - TANK ONLY MANUFACTURER ADVANCED MANUFACTURING & POWER SYSTEMS INC AGENCY N/A - TANK ONLY CONSTRUCTION TYPE N/A - TANK ONLY FIRE PROTECTION N/A - TANK ONLY FIRE SUPPRESSION SYSTEM I N/A - TANK ONLY OCCUPANCY 11 ALLOWABLE # OF STORIES N/A - TANK ONLY i ii 1 N/A - TANK ONLY EXPOSURE N/A - TANK ONLY MAX. FLOOR LOAD F- N/A - TANK ONLY ROOF LIVE LOAD I I 11 it "R" RATING OF FLOOR, WALL AND ROOF II MODULES PER BUILDING N/A I II M' LIFTI IG POINTS ESTIMATED SHIPPING / WEIGHT INFORMATION ILL 150 "1 x 52 5 "w x 41"h SHIPPING DIMENSIONS 1r -- - -�1 I I I I ; II �� II - Ibs TANK / BASE FRAME WEIGHT I I III IL (x2 E SIDE) TOTAL SHIPPING WEIGHT: 'c 3,300 Ibs Z I,L 1 0 E w II w I- 1 III U w IL o z O v II 1 LLI U I II 1 U CU (°° E Q W 0 Q V, I I I I 1111 u T. Baldwin P.E. II II Florida F- 1 II, I 11 1 OF 1 n- IL U 1_ LLJ O I I I I 11 11 11 11 11 II a I 11 , I 11, I I I I 11 „II L Q p 0- I II, I 111 7) 1 I „II „II II I I p I II, I 11, I I 1111 „II 11 II I 111 I I „II I °1 I II II II I II ------------ - - - - -- 1 1 -- ------------------------- - - - - -- - -- - ------------------------- - - - - -- ------------------------ - - - - -- -- -I- - -- - -- I I -- - -- II 31 11 120 - UL142 TANK 1 G (1 Z& 1111111111M�_ TANK FITTING LEGEND F - FUEL FILL [ 179MCI 2" ] - 2" NPT G - MECH. FUEL GAUGE - 1 1/2" NPT D - LEAK DETECTOR [ MADISON M -7000 EQ#682 ] - 1" NPT S - FUEL SUPPLY - 1" NPT R - FUEL RETURN - 1" NPT DS - DAYTANK FUEL SUPPLY - 1" NPT DR - DAYTANK FUEL RETURN - 1" NPT V - MAIN VENT - 2" NPT SV - SECONDARY EMERGENCY VENT - 6" NPT PV - PRIMARY EMERGENCY VENT - 4" NPT H - HIGH FUEL LEVEL SENSOR [ MADISON M -7000 EQ#682 ] - 1" NPT L - LOW FUEL LEVEL SENSOR [ MADISON M -7000 ] - 1" NPT SP - SPARE - 2 "NPT PS - FUEL POLISHING SUPPLY - 1" NPT PR - FUEL POLISHING RETURN - 1" NPT SS - 4 -20ma ULTRASONIC SENSOR - 2 "NPT DTCS - DAYTANK CONTROL SWITCHES AMPS UL -142 DOUBLE WALL TANK & SPILL CONTAINMENT - [EQ#5331 *NOTE: TANK FITTING SIZES SHOWN ON PLAN ARE OPENING SIZES COMPONENT CAD DRAWING #(S) 132 -4889 ("fill I / 1- 'tNI-rAINIAArAIT IAIITI.I DRAWINGS FOR APPROVAL APPROVED AS DRAWN ❑ REVISE AS NOTED ❑ SIGNATURE: DATE: NAME (PLEASE PRINT): TITLE: NOTE- ALL DIMENSIONS ARE IN INCHES REVISIONS REV DESCRIPTON DOUBLE WALL SUB BASE FUEL TANK DETAILS Fuel Tank Features and Options 11 10 9 8 7 6 5 4 3 2 EXISTING GENERATOR 1. Inner tank leak alarm kit 7. Lockable /sealed fill cap with riser (standard) 2. Emergency pressure relief vent outer tank (standard) 8. Mechanical fuel gauge (standard) 3. Emergency pressure relief vent inner tank (standard) 9. Low fuel level switch for controller alarm 4. Fuel supply line (compatible with Decision - Maker -3+ and Decision - Maker -550) 5. Normal vent with riser and mushroom cap (standard) 10. Day tank kit 6. Fuel return line 11. 1/2 in. NPT for leak detection switch Figure 1 Double -Wall Subbase Fuel Tanks (Secondary Containment) G M 16904 -1 DATE I BY _n E_(2 _ III ^ L J � I c ADVANCED MANUFACTURING & POWER SYSTEMS INC. 1965 BENNETT DRIVE. DELAND, F1_ 32724 PHONE: 386.622.5565 FAX: 386.622.9669 CODE INFORMATION j CODE VERSION N/A - TANK ONLY MANUFACTURER ADVANCED MANUFACTURING & POWER SYSTEMS INC AGENCY N/A - TANK ONLY CONSTRUCTION TYPE N/A - TANK ONLY FIRE PROTECTION N/A - TANK ONLY FIRE SUPPRESSION SYSTEM I N/A - TANK ONLY OCCUPANCY N/A - TANK ONLY ALLOWABLE # OF STORIES N/A - TANK ONLY BASIC WIND SPEED N/A - TANK ONLY EXPOSURE N/A - TANK ONLY ENCLOSURE Reviewed By: N/A - TANK ONLY INTERNAL PRESSURE COEFFICIENT N/A - TANK ONLY IMPORTANCE FACTOR Date: N/A - TANK ONLY MAX. FLOOR LOAD F- N/A - TANK ONLY ROOF LIVE LOAD < N/A - TANK ONLY "R" RATING OF FLOOR, WALL AND ROOF N/A - TANK ONLY MODULES PER BUILDING N/A N/A - TANK ONLY SQUARE FOOTAGE N/A - TANK ONLY ESTIMATED SHIPPING / WEIGHT INFORMATION ILL 150 "1 x 52 5 "w x 41"h SHIPPING DIMENSIONS 20140035 1 GENSET WEIGHT - Ibs TANK / BASE FRAME WEIGHT Z 3,300 Ibs ENCLOSURE & ACCESSORIES WEIGHT _ Ibs TOTAL SHIPPING WEIGHT: 'c 3,300 Ibs Z s 0 E w Q� CL w I- z z U w IL o z O L1� co > O C N LLI U Z M . C:) U CU (°° E Q W 0 Q V, U U) T. Baldwin P.E. Florida F- O a- OF 1 n- IL U 1_ LLJ O Cn a o Q LL L Q 0- as U-) 7) DOUBLE WALL SUBBASE FUEL OPTIONS: 1. FUEL IN BASIN OPTIONS/LEAK DETECTION: FUEL IN BASIN SWITCH, FLORIDA DEPT. OF ENVIRONMENTAL PROTECTION (FDEP) FILE N'. EQ -014 APPROVED 2. FUEL FILL AND SPILL OPTIONS: 26.5L(7 GALLON) SPILL CONTAINMENT WITH 95% SHUTOFF, FLORIDA DEPT. OF ENVIRONMENTAL PROTECTION (FDEP) FILE N'. EQ- 226/EQ257 APPROVED 3. FUEL SUPPLY OPTIONS: BALL VALVE (INSTALLED ON FUEL SUPPLY LINE). 4. HIGH FUEL LEVEL SWITCH/OVERFILL- HIGH FUEL LEVEL SWITCH FOR OVERFILL PREVENTION, FLORIDA DEPT. OF ENVIRONMENTAL PROTECTION (FDEP) FILE N'. EQ -682 APPROVED. 5. NORMAL VENT OPTIONS: 3.7M (12FT) ABOVE GRADE (WITH SPILL CONTAINMENT). VENT TO BE STEEL SCH 40. 6. TANK MARKING OPTIONS: DECAL TANK NUMBER AND SAFE FUEL FILL HEIGHT, NFPA 704 IDENTIFICATION CONTRACTOR MAY USE EQUIVALENT OPTIONS, FDEP APPROVED TO COMPLY WITH STATE OF FLORIDA REQUIREMENTS ALL EQUIPMENT SHALL BE FDEP APPROVED SUB -BASE TANK EQ #533, UL 142 Al SEAL: Reviewed By: (0 : E DRAWN: SC MTB /CD Date: G3 S "U) T1_ r c,) 4 6) F- 3/25/14 < Scale: L0 •Q O 0 N/A Z_ Number: QProject U ILL LU W 20140035 LU oZj Z_ a Z E-2 c- Q V 'c Ne Z s 0 E w Q� CL Q I- {V GT- LL1 IL C14 .Q IN-- � O L1� co > O C N U Z M . C:) z CU (°° E Q W 0 V, V) Matthew T. Baldwin P.E. Florida License #64608 Sheet: S-1 OF 1 J r DOUBLE WALL SUBBASE FUEL OPTIONS: 1. FUEL IN BASIN OPTIONS/LEAK DETECTION: FUEL IN BASIN SWITCH, FLORIDA DEPT. OF ENVIRONMENTAL PROTECTION (FDEP) FILE N'. EQ -014 APPROVED 2. FUEL FILL AND SPILL OPTIONS: 26.5L(7 GALLON) SPILL CONTAINMENT WITH 95% SHUTOFF, FLORIDA DEPT. OF ENVIRONMENTAL PROTECTION (FDEP) FILE N'. EQ- 226/EQ257 APPROVED 3. FUEL SUPPLY OPTIONS: BALL VALVE (INSTALLED ON FUEL SUPPLY LINE). 4. HIGH FUEL LEVEL SWITCH/OVERFILL- HIGH FUEL LEVEL SWITCH FOR OVERFILL PREVENTION, FLORIDA DEPT. OF ENVIRONMENTAL PROTECTION (FDEP) FILE N'. EQ -682 APPROVED. 5. NORMAL VENT OPTIONS: 3.7M (12FT) ABOVE GRADE (WITH SPILL CONTAINMENT). VENT TO BE STEEL SCH 40. 6. TANK MARKING OPTIONS: DECAL TANK NUMBER AND SAFE FUEL FILL HEIGHT, NFPA 704 IDENTIFICATION CONTRACTOR MAY USE EQUIVALENT OPTIONS, FDEP APPROVED TO COMPLY WITH STATE OF FLORIDA REQUIREMENTS ALL EQUIPMENT SHALL BE FDEP APPROVED SUB -BASE TANK EQ #533, UL 142 Al SEAL: r PABLO J. VITERI ; PE# 59535 ' 09 -23 -13 (0 : E DRAWN: SC (0 CD U 0 G3 S "U) T1_ r c,) 4 6) Z J 00 N LL < LU L0 •Q r� V 0 E2 C:) ` M Z_ co CG U ILL LU W (J) O LU oZj Z_ a Z E-2 c- `' V 'c Ne Z s 0 E w Q� CL LO U I- {V GT- T- IL C14 .Q O � O co > O C N j Z M . C:) O♦^>♦ CU (°° E Q W � r PABLO J. VITERI ; PE# 59535 ' CUENT: BAPTIST HEALTH SOUTH FLORIDA. PROJECT LOCATION: 6200 SW 73 STREET, SOUTH MIAMI, FL 33176 ISSUE PERMIT GT10�; m DERM COMM p vY, DATE 9 -23 -13 04/09/14 DATE: 09 -23 -13 W DRAWN: SC CHECKED: V F- SHEET T17LE: J < Z NOTES. Q co a. W N r 3 (J) O Uo Q W T Z Z E-2 c- `' O - Ne 0. Q Q� CL I- O � ZU W IL O � O j a: O♦^>♦ W � V, _ LL v, a CUENT: BAPTIST HEALTH SOUTH FLORIDA. PROJECT LOCATION: 6200 SW 73 STREET, SOUTH MIAMI, FL 33176 ISSUE PERMIT GT10�; m DERM COMM p vY, DATE 9 -23 -13 04/09/14 DATE: 09 -23 -13 DRAWN: SC CHECKED: PV SHEET T17LE: DETAILS AND - NOTES. SHEET: 3 E-2 ,