14-825-001i a. BASIC FIRE PROTECTION REQUIREMENTS SECTION 15010 PART 1 - GENERAL 1.01 SECTION INCLUDES A. ilasic Fire Protection requirements specifically applicable to Division 15 Sections. 1.02 REFERENCES A. FM: Factory Mutual B. IRI: Industrial Risk Insurers C. MSS: Manufacturer's Standardization Society of the Valve and Fitting Industry. D. NEMA: National Electrical Manufacturers' Association. E. NFPA: National Fire_ Protection Association. F. UL: Underwriters' Laboratories, Inc. 1.03 SUBMITTALS A. Include Products as specified in the individual sections of Division 15. G. Submit shop drawing and product data grouped to includo complete submittals of related systems, products, and accessories in a single submittal for approval by Engineer prior to purchasing and installation. C. Brochures: Submit manufacturer's product data and brochures including: 1. Complete descriptions, 2. Illustrations. 3. Rating data, accessories, dimensional data, and applicable options and features marked for the specific items scheduled on drawings and specified here in. 4. The third time review of any submittal by the architect /engineer will incur a back charge to the contractor at a C rate of $150.00 per hour, minimum one hour charge. 1.04 REGULATORY REQUIREMENTS A. NFPA 13: Sprinkler System Installation (2007), B. NFPA 14: Standpipe and Hose Systems (2007). C. Florida Building Codes - 2010. D, NFPA g9: Healthcare Facilities. (2005) E. NFPA 101: Life Safety Code. (2009) F. FGI Guidelines for Dosign and Construction of Healthcare Facilities - 2010 Edition. G. Special regulations, supplement, and amendments of the State and /or local authorities having jurisdiction. H. Comply with the applicable edition date of each regulation as adopted by the authorities having jurisdiction. 1.05 PR03ECT /SITE CONDITIONS A. Fire protection layouts Indicated on drawings are diagrammat €cal and intended to show relative positions and arrangement of equipment, ductwork and piping. Coordinate fire protection work with other trades and measurements obtained at the job site, as applicabbe, prior to installation. Generally, install work in locations shown on Drawings, using as necessary, rises, drops, offsets and transitions to fit in the available space unless prevented by Project conditions. B. If prevented by project conditions, prepare drawings showing proposed rearrangement of Work, including changes to Work specified in oth er sections. Obtain permission of owner, architect a nd engineer before proceeding. C. Cause as little interference or interruption of existing utilities and services as possible, Schedule work which will cause interference or interruption in advance with Owner, authorities having jurisdiction, and all affected trades. D. Determine sizes and verify locations of existing utilities on or near site, E. Keep roads clear of materials and debris. F. Visit site and be informed of conditions under which Work must be performed. 1,06 FEES AND PERMITS 'r A. Obtain and pay for all necessary permits and inspection fees required to perform Division 15 work. 1.07 COMPLETE-NESS OF WORK A. The Contract Documents depict mechanical, fire protection, and plumbing systems which are intended to be complete and functioning systems. All products, materials, and labor necessary to render a fully functional system to fulfill the design intent shown on the documents shall be provided by the Contractor. ITS. Catalog numbers referenced throughout the Division IS Drawings and Specifications are intended to convey a general understanding of the type and quality of the product required. Where written descriptions differ from information conveyed by a catalog number, the written description shall govern. No extra shall be allowed because a catalog number is found to be incomplete or obsolete. 1.013 PRODUCT SUBSTITUTIONS A. All substitution requests shall be submitted 10 business days prior to bid opening. 1.09 RECORD DRAWINGS A. Provide record drawings that illustrate the work of Division 15 as finally constructed. Final record drawings shall be prepaid by the contractor in AutoCad or MicroStation format. All field revisions to the contract documents shall be clouded and identified. Deliver the bond sets of final record drawings to the architect/engineer for review. 1. Record drawings shall be up to date for review by architect /engineer prior to each request for pay application. 2. Record drawings prepared by the contractor in AutoCad or MicroStation format shall become part of the case out documents. 15. Record drawings shall reflect all changes made to the Contract Documents, whether generated by addenda, RFI's - request for information, change orders, or field conditions. Maintain a daily record of these changes and keep current set of drawings showing these changes. Changes shall include isometric riser diagram changes. C. Deliver record drawings to archtect/engineer within 30 days of Substantial Completion. MATERIALS AND METHODS SECTION 15050 BASIC MATERIALS AND METHODS rART 1 - GENERAL 1.01 RELATED WORK A. Cutting and Patching. 5. Division 16: Electrical 1.02 OWNER FURNISHED INFORMATION A.To the extent the Owner has performed and made available as Owner Furnished Information an Infection Control Risk Assessment (ICRA), the Contractor shall execute all requirements of the Contract Documents In accordance with the ICRA, and shall perform and provide all labor, materials and supervision to execute the specific infection control measures identified therein. B.The Contract Documents do not necessarily depict all the work required by the ICRA, nor are the Contract Documents responsible for the information contained in the ICRA. The Contractor shall request, and obtain if available, the Owner's ICRA documentation, become familiar with its requirements and perform all work accordingly. 1.03 CUTTING AND PATCHING A.Repair or replace damage caused by cutting or installation of work specified in Division 1.5. B.Perform repairs with materials which match existing and install In accordance with the appropriate section of these specifications. 1.04 DELIVERY, STORAGE, AND PROTECTION A.insofaras possible, deliver items in manufacturer's original unopened packaging. Where deliver in original packaging Is not practical, provide cover and shielding for all items with protective materials to keep them from being damaged. Use care in loading, transporting, unloading, and storing to keep items from being damaged. e.Store items in a dean, dry place, and protect from damage„ Fire protection piping and equipment may not be staged or stored outdoors unless intended for outdoor use. C.Keep dirt and debris out of pipes. Provide temporary dips or plugs on all piping systems and caps. Caps and covers shall be installed during transit and job site storage. Storge of material shall be indoors. Materials that must be stored outdoor exposed to the elements shall be elevated above grade and covered with heavy mil visqueen. Material found stored outdoors not covered or sitting in stan ding water shall be removed from the jobsite and replace with new material at the contractor expense. D.Repair, restore, and replace damaged items. e.Cover ill equipment and material during work of finished trades with heavy mil visqueen. F.AII materials and equipment stored off site shall be Stored in a insured and bonded location. Materials and equipment shall not be stored outdoors. 1.05 CLEANING FIRE PROTECTION SYSTEMS A- General Cleanup: I Upon complet ion of contract and progressively as work proceeds, clean rip dirt, debris, oil materials, etc., and remove frorn site:, keeping premises in neat and clean condition to satisfaction of the owner, architect/engineer . See Division 1. of specifications for further requirements, 2.Seepage, discoloration or other damage to parts of the building, its finish, or furnishings due to Contractor's failure to property clean piping systems or duct systems shall be repaired without cost to the Owner. B.Factory Finishes: 1 -Clean all materials to like new condition, Touch up bare places, scratches and other minor damage to finishes. Use only factory supplied paint of matching color and formula. If finishes are badly damaged or if there are many damaged, scratched or barn, places, refinish the entire Item. 1 -06 TESTING FIRE PROTECTION SYSTEMS A.Correct and retest work found defective when tested. B.Make repairs to piping systems with new materials. Peening, doping, or caulking of joints or holes will not be acceptable. C.Fire Protection system piping: Hydrostatically test piping at 204 psi pre ;sure for a period *f two hours without evidence of leaking and as per NFPA. 1.07 INFECTION CONTROL REQUIREMENTS A.Coordinate with the Owner the exact requirements for the infection control measures to be executed and performed during the course of this Project. IS-Prior to execution, present to the Owner for approval a written execution plan for each infection control measure. C- Coordinate infection control measures as needed with all other trades and disclpli'nes. D.Provide documentation of infection control measures to the Owner, as required and specified in the ICRA. FIDE PROTECTION LEGEND SYMBOL DESCRIPTION SYMBOL DESCRIPTION - F -- FiRE LINE OR MAIN -Iiiiiiiiiiiiir FIRE DEPARTMENT VALVE CAISINET -A/S --- AUTOMATIC SPRINKLER MAIN FP -1, ETC FIXTURE INDENTIFIC_ATIQN D DRAIN LINE F.SP. CONNECTION TO EXISTING -� PIPE TURNED UP ! FIRE EXTINGUISHER ZP PIPE TURNED DOWN T.S. FLOW SWITCH - ° °- - SALL VALVE 3 CAP ON LINE -+-44 CHECK VALVE ELECTRICAL HYDRAULIC CALCULATION PIPE NODE 1 -100 -- l �f--- UNION IN PIPE © HYDRAULIC CALCULATION SPRINKLER NODE A#'S, "S, CVS --- --1•4- -•- SECTIONAL CONTROL VALVE --+4-*,- FIRE HYDRANT {KITH VALVE J--- ---X FEMOVE EXISTING HEAD AND PLUG FITTING w O.S - &Y. GATE OR BUTTERFLY VALVE W/TAMPER SWITCH. REMOVE EXISTING HEAD & EXTEND 1" PRANCH LINE TO NEW HEAD LOCATION �--� FIRE DEPARTMENT CONNECTION PiPING TO BE REMOVED -�t-� CHECK VALVE r - a SPRINKLER HEAD BELOW DUCT WORK CONTROL VALVE AND CHECK VALVE WITH FLOW AND TAMPER SWITCHES • • W NATIONAL FM.E PROTECTION REFEREN:.E DRAB INCS CONTRACT RESPONSIBILITIES VKW rTERI NFP /aT1if_'R, -, LJACFPGAC D PIPITG ELECTMCAL. WRING DETECTKN .uxTUlG CENTER Of TILE FIRE PROTECTION SECTION 15300 SPRINKLER NOTES PART1 - GENERAL _..- ...�.__.,........�....- :....,. w .._ ____.- ._. -...- .. _.._..- . . - _...._ ._. - ._. - _.- ..___.._...,...... _...... ...... - -.. ____- ._ -_.. _._..._____.. __ °-- -._.___,....--- -- -... _4 1.01 WORK INCLUDED 1, ALL F!RF PROTECTION :aN �Ti.M S,11ALI. BE .If1 COMPLIANCE tt�nTFi THE t C "'AL FIRE � CODES AN I r:.,ND w. S PER NFPA 13 2037 EDITt0t I REOUtRE.ME" i a S. A. Provide materials and labor required to completely execute the sprinkler and fire protection work fihr this "SPRINKLER SYSTEM SHALL BE INSTALLED 130 A STATE CERTIFIED FIRE project, as indicated on the drawings and as herein specified. PROTECTION CONTRACTOR. ; B. Scope of work: 1. Interior pipe and fittings. 3- EXISTING SERVICES INDICATED ON THESE DRAWINGS WERE DERIVED 2. Testing and flushing. FROM EXISTING DRAWINGS AND LIMITED FIELD OBSERVATIONS. THESE DR"iINGS MAY NOT BE ALL INCLUSIVE OF SERVICES THAT EXIST IN THE 1.02 RELATED WORK PROJECT AREA. CONTRACTOR SHALL VERIFY SERVICES, LOCATION, TYPE 4 AND S12E PRIOR TO ANY CONSTRUCTION. ANY DEVIATIONS IMPACTING WORK A. Section 15010: General Requirements SHOWN ON THESE DOCUMENTS SHALL BE REPORTED TO THE ARCHITECT FOR COORDINATION PRIOR TO CONSTRUCTION. i ` a B. Section 15050: Basic Materials and Methods 4. CONTRACTOR IS RESPONSIBLE FOR RELOCATING ALL EXISTING FIRE MAINS AND 1.03 INSTALLER QUALIFICATIONS SPRINKLER PIPING TO FACILITATE THE INSTALLATION OF NEW ELECTRICAL, MECHANICAL, PLUMBING AND STRUCTURAL SYSTEMS. A, Comply with local and state licensure requirements for installation of fire protection systems. 5, PRESSURE TEST PINING AT 200 PSIG FOR A MINIMUM OF TWO HOURS_ iF LEAKS, 1.04 SYSTEM DESIGN ARE FOUND THEN CONTRACTOR SHALL FIX LEAKS AND TEST AGAIN. i 1,05 QUAUTY ASSURANCE 6. SEAL PENETRATIONS OF FIRE RATED WALLS, ROOF AND FLOORS IN ACCORDANCE WITH U.L. FIRE RESISTANCE INDEX FOR THROUGH PENETRATION FIRE STOP A. Underwriters Laboratories (U.L) listed and Factory Mutual (P.M.) approved material. SYSTEMS. COORDINATE REQUIREMENTS WITH PLANS AND SPECIFICATIONS. i 1.06 SUBMITTALS AND SHOP DRAWINGS ALL PENETRATIONS OR OPENINGS FROM REMOVED C. include the following manufacturer's product data with submittal: PIPES THROUGH EXISTING BUILDING 1. Pipe and fittings. WALLS AND FLOORS SHALL BE SLEEVED AND /OR PATCHED TO MATCH ORIGINAL. PART 2 - PRODUCTS 2,01 PIPE AND FITTINGS 3, CONTRACTOR SHALL BE RESPONSIBLE FOR ANY DAMAGE TO EXISTING PIPING OR EQUIPMENT DUE TO NEW CONSTRUCTION AND HE SHALL RESTORE EXISTING A. interior Pipe and Fittings: WORK TO ITS ORIGINAL CONDITION AT NO COST TO THE 1. Schedule 10 ASTM -135, electric - resistance welded steel pipe suitable for roll grooving for p iping 3" and larger. OWNER. Provide ABF coating on pipe. Piping shall be rated for 300 psi. I 3. Schedule 5 piping shall not be approved or permitted. 4. Fittings: 9. VvARRANTY;GL.ARAN , r_f a. Mechanical couplings: Roll groove rigid type by Victaulic, or Grinnell U.L. listed for 300 psi. A- THE (: ONT"R CTOF-, . ,HALL_ t/ AF FY,CtIA,t A "1T E AND MA: NTAiN -T"HE STA,DI .ITY ►. Class 250 cast iron sprinkler fittings U.L. listed - strewed flanged. Of: WORK AND MA T i PlALS AND KEEr SANIE !N PERFECT REPAIR AND CONDITION c. All fittings shall be by the same manufacturer and shall be UL/FM approved. FOR THE PERIOD 0'F +' -:111 41 YEAR. B. All components in Fire Protection System shall be manufactured in the U.S. Components not manufactured in the B, DEFECTS OF ;,NY K;ND DUE TO FAULTY 1',,'0RK OR. r,AATERIALS, AP,; EA,R6N G U.S. shall not be acceptable. C)tJRItG THE ABC I. "'"NTICI,IEI7 I'CI'itD, Iii. /ST r,F tI*' "; "EFt'FLY RI= PAISE"3 BY TfiE CCNTRACTG" rI HIS 11AI FX E ,S SE TCTHE: ENTIRE SA. rSa AClIr N tF ii-t_ +; i 0VW,,EP AND E ?,JG NF ER, R, SUCI-4 RECCP45TR {C II>.:N Aiw-yD REPAIRS `HALL INCLUDE ? DAMAGE TO THE OR €''URN,St'UNG OF i HE BUILM'NG, RESULTINC` FROM TI--1E ORS GC "BAR DEFECT 0R x -ZEF'Aa R "T HE =RETO, 10, THE FIRE PROTECTION CONTRACTOR SHALL KEEP A SET OF MARKED UP DRAWINGS AS THE JOB PROGRESSES. NO MAJOR CHANGE SHALL BE MADE TO FIRE. PROTECTION DESIGN ENGINEERING UNLESS IT HAS BEEN COORDINATED, DRAWN AND SUBMITTED FOR APPROVAL. 11. FIRE PROTECTION SERVICES TO BE REMOVED SHALL BE CAPPED. 12. CONTINUITY OF SERVICE: INTERRUPTIONS OF EXISTING SERVICES ar k OR FACILITIES SHALL BE KEPT TO A MINIMUM AND THE ) tv t CONTRACTOR SHALL FURNISH ALL MATERIALS AND LABOR ' REQUIRED WHENEVER TEMPORARY CONNECTIONS ARE NECESSARY TO MAINTAIN CONTINUITY OF SERVICE. INTERRUPTIONS OF THE ,.'. r EXISTING SERVICES, THE INSTALLATION OF TEMPORARY FACILITIES, AND THE WORK OF MAKING FINAL CONNECTIONS TO NEW WORK SHALL BE DONE ONLY AT SUCH TIMES AS PERMITTED AND SCHEDULED BY THE OWNER_ ALL SUCH CONNECTIONS AND TIE -INS SHALL BE COORDINATED THROUGH THE OWNERS PROJECT MANAGER. T: 1_ THE DURATION OF EACH SHUTDOWN SHALL BE LIMITED TO NIGHTS AND /OR WEEKENDS WITH THE TIME FRAME FOR SHUTDOWNS AS SPECIFIED BY THE OWNER. THE CONTRACTOR SHALL NOTIFY THE OWNER IN WRITING FORTY -EIGHT (413 ) HOURS IN ADVANCE OF EACH REQUIRED INTERRUPTION OF EXISTING SERVICE. ANY AREA AFFECTED BY NHUTDOWN SHALL REQUIRE A 24 HOURt7 DAYS PER WEEK FiRE WATCH. 2. THE CONTRACTOR SHALL INCLUDE IN BID PRICE ALL PREMIUM TIME CHARGES FOR LABOR AND EQUIPMENT REQUIRED FOR ALL NIGHT AND WEEKEND OVERTIME WORK, AS NECESSARY, TO COMPLETE THE SCOPE OF THE CONTRACT. 13. CONTRACTOR SHALL COORDINATE WITH FIRE ALARM CONTRACTOR FOR THE REMOVAL OF FIRE ALARM DEVICES. 14. CONTRACTOR SHALL PATCH WALLS, FLOORS, ROOFING AND CEILINGS TO MATCH EXISITNG FINISHES FOR DEMOLITION OF FIRE PROTECTION SYSTEMS. 15, CONTRACTOR SHALL PROVIDE (2) COMPLETE SETS OF AS BUILT DRAWINGS ALONG i WITH ALL CLOSE OUT DOCUMENTS PRIOR TO PROJECT COMPLETION. d w!Y t,� ter. afi t x,a ,. ' i ",, M(,,'v+^- ywst1!F,, �i �4..+d INSPECTOR w TF fS APPROVAL WAS ISSUED BASED ON THE INFORi4IATiON PROVIDED BY THE FIRE PROTECTION CONTRACTOR. i ACCORDING TO THE GENERAL NOTE THE NEW COOLING TOWER IS CONSTRUCTED WITH NON I } COMBUSTIBLE MATERIAL. CHECK THE BASING AREA INSIDE THE COOLING TOWER IF THE FILLS SHEETS ARE MADE OF VINYL OR PLASTIC MATERIAL THIS y APPROVAL IS VOIDED AND NULL. FIRE E PROTECTION ABBREVIATIONS COORDINATION ACCEPTANCE TRADE- CONTRACTOR DATE SIGNATURE FIRE HOSE CABINET ARCHITECTLif �L�tAy F.E. MECHANICAL - - -- - - - -- - MEC14AP11CAL AUTOMATIC SPRINKLER PLU".tEiisVG FIRE HYDRANT F.SP. FIRE STANDPIPE R.P.B.P. ELECTRICAL RCV RISER CONTROL VALVE A.F.F. ABOVE FINISHED FLOOR T.S. TAMPER SWITCH F.S. CEILING F RV. GENFPAi CONTRACTOR N.O. NORMALLY OPEN? ELECTRICAL NATIONAL FM.E PROTECTION REFEREN:.E DRAB INCS CONTRACT RESPONSIBILITIES VKW rTERI NFP /aT1if_'R, -, LJACFPGAC D PIPITG ELECTMCAL. WRING DETECTKN .uxTUlG CENTER Of TILE FIRE PROTECTION SECTION 15300 SPRINKLER NOTES PART1 - GENERAL _..- ...�.__.,........�....- :....,. w .._ ____.- ._. -...- .. _.._..- . . - _...._ ._. - ._. - _.- ..___.._...,...... _...... ...... - -.. ____- ._ -_.. _._..._____.. __ °-- -._.___,....--- -- -... _4 1.01 WORK INCLUDED 1, ALL F!RF PROTECTION :aN �Ti.M S,11ALI. BE .If1 COMPLIANCE tt�nTFi THE t C "'AL FIRE � CODES AN I r:.,ND w. S PER NFPA 13 2037 EDITt0t I REOUtRE.ME" i a S. A. Provide materials and labor required to completely execute the sprinkler and fire protection work fihr this "SPRINKLER SYSTEM SHALL BE INSTALLED 130 A STATE CERTIFIED FIRE project, as indicated on the drawings and as herein specified. PROTECTION CONTRACTOR. ; B. Scope of work: 1. Interior pipe and fittings. 3- EXISTING SERVICES INDICATED ON THESE DRAWINGS WERE DERIVED 2. Testing and flushing. FROM EXISTING DRAWINGS AND LIMITED FIELD OBSERVATIONS. THESE DR"iINGS MAY NOT BE ALL INCLUSIVE OF SERVICES THAT EXIST IN THE 1.02 RELATED WORK PROJECT AREA. CONTRACTOR SHALL VERIFY SERVICES, LOCATION, TYPE 4 AND S12E PRIOR TO ANY CONSTRUCTION. ANY DEVIATIONS IMPACTING WORK A. Section 15010: General Requirements SHOWN ON THESE DOCUMENTS SHALL BE REPORTED TO THE ARCHITECT FOR COORDINATION PRIOR TO CONSTRUCTION. i ` a B. Section 15050: Basic Materials and Methods 4. CONTRACTOR IS RESPONSIBLE FOR RELOCATING ALL EXISTING FIRE MAINS AND 1.03 INSTALLER QUALIFICATIONS SPRINKLER PIPING TO FACILITATE THE INSTALLATION OF NEW ELECTRICAL, MECHANICAL, PLUMBING AND STRUCTURAL SYSTEMS. A, Comply with local and state licensure requirements for installation of fire protection systems. 5, PRESSURE TEST PINING AT 200 PSIG FOR A MINIMUM OF TWO HOURS_ iF LEAKS, 1.04 SYSTEM DESIGN ARE FOUND THEN CONTRACTOR SHALL FIX LEAKS AND TEST AGAIN. i 1,05 QUAUTY ASSURANCE 6. SEAL PENETRATIONS OF FIRE RATED WALLS, ROOF AND FLOORS IN ACCORDANCE WITH U.L. FIRE RESISTANCE INDEX FOR THROUGH PENETRATION FIRE STOP A. Underwriters Laboratories (U.L) listed and Factory Mutual (P.M.) approved material. SYSTEMS. COORDINATE REQUIREMENTS WITH PLANS AND SPECIFICATIONS. i 1.06 SUBMITTALS AND SHOP DRAWINGS ALL PENETRATIONS OR OPENINGS FROM REMOVED C. include the following manufacturer's product data with submittal: PIPES THROUGH EXISTING BUILDING 1. Pipe and fittings. WALLS AND FLOORS SHALL BE SLEEVED AND /OR PATCHED TO MATCH ORIGINAL. PART 2 - PRODUCTS 2,01 PIPE AND FITTINGS 3, CONTRACTOR SHALL BE RESPONSIBLE FOR ANY DAMAGE TO EXISTING PIPING OR EQUIPMENT DUE TO NEW CONSTRUCTION AND HE SHALL RESTORE EXISTING A. interior Pipe and Fittings: WORK TO ITS ORIGINAL CONDITION AT NO COST TO THE 1. Schedule 10 ASTM -135, electric - resistance welded steel pipe suitable for roll grooving for p iping 3" and larger. OWNER. Provide ABF coating on pipe. Piping shall be rated for 300 psi. I 3. Schedule 5 piping shall not be approved or permitted. 4. Fittings: 9. VvARRANTY;GL.ARAN , r_f a. Mechanical couplings: Roll groove rigid type by Victaulic, or Grinnell U.L. listed for 300 psi. A- THE (: ONT"R CTOF-, . ,HALL_ t/ AF FY,CtIA,t A "1T E AND MA: NTAiN -T"HE STA,DI .ITY ►. Class 250 cast iron sprinkler fittings U.L. listed - strewed flanged. Of: WORK AND MA T i PlALS AND KEEr SANIE !N PERFECT REPAIR AND CONDITION c. All fittings shall be by the same manufacturer and shall be UL/FM approved. FOR THE PERIOD 0'F +' -:111 41 YEAR. B. All components in Fire Protection System shall be manufactured in the U.S. Components not manufactured in the B, DEFECTS OF ;,NY K;ND DUE TO FAULTY 1',,'0RK OR. r,AATERIALS, AP,; EA,R6N G U.S. shall not be acceptable. C)tJRItG THE ABC I. "'"NTICI,IEI7 I'CI'itD, Iii. /ST r,F tI*' "; "EFt'FLY RI= PAISE"3 BY TfiE CCNTRACTG" rI HIS 11AI FX E ,S SE TCTHE: ENTIRE SA. rSa AClIr N tF ii-t_ +; i 0VW,,EP AND E ?,JG NF ER, R, SUCI-4 RECCP45TR {C II>.:N Aiw-yD REPAIRS `HALL INCLUDE ? DAMAGE TO THE OR €''URN,St'UNG OF i HE BUILM'NG, RESULTINC` FROM TI--1E ORS GC "BAR DEFECT 0R x -ZEF'Aa R "T HE =RETO, 10, THE FIRE PROTECTION CONTRACTOR SHALL KEEP A SET OF MARKED UP DRAWINGS AS THE JOB PROGRESSES. NO MAJOR CHANGE SHALL BE MADE TO FIRE. PROTECTION DESIGN ENGINEERING UNLESS IT HAS BEEN COORDINATED, DRAWN AND SUBMITTED FOR APPROVAL. 11. FIRE PROTECTION SERVICES TO BE REMOVED SHALL BE CAPPED. 12. CONTINUITY OF SERVICE: INTERRUPTIONS OF EXISTING SERVICES ar k OR FACILITIES SHALL BE KEPT TO A MINIMUM AND THE ) tv t CONTRACTOR SHALL FURNISH ALL MATERIALS AND LABOR ' REQUIRED WHENEVER TEMPORARY CONNECTIONS ARE NECESSARY TO MAINTAIN CONTINUITY OF SERVICE. INTERRUPTIONS OF THE ,.'. r EXISTING SERVICES, THE INSTALLATION OF TEMPORARY FACILITIES, AND THE WORK OF MAKING FINAL CONNECTIONS TO NEW WORK SHALL BE DONE ONLY AT SUCH TIMES AS PERMITTED AND SCHEDULED BY THE OWNER_ ALL SUCH CONNECTIONS AND TIE -INS SHALL BE COORDINATED THROUGH THE OWNERS PROJECT MANAGER. T: 1_ THE DURATION OF EACH SHUTDOWN SHALL BE LIMITED TO NIGHTS AND /OR WEEKENDS WITH THE TIME FRAME FOR SHUTDOWNS AS SPECIFIED BY THE OWNER. THE CONTRACTOR SHALL NOTIFY THE OWNER IN WRITING FORTY -EIGHT (413 ) HOURS IN ADVANCE OF EACH REQUIRED INTERRUPTION OF EXISTING SERVICE. ANY AREA AFFECTED BY NHUTDOWN SHALL REQUIRE A 24 HOURt7 DAYS PER WEEK FiRE WATCH. 2. THE CONTRACTOR SHALL INCLUDE IN BID PRICE ALL PREMIUM TIME CHARGES FOR LABOR AND EQUIPMENT REQUIRED FOR ALL NIGHT AND WEEKEND OVERTIME WORK, AS NECESSARY, TO COMPLETE THE SCOPE OF THE CONTRACT. 13. CONTRACTOR SHALL COORDINATE WITH FIRE ALARM CONTRACTOR FOR THE REMOVAL OF FIRE ALARM DEVICES. 14. CONTRACTOR SHALL PATCH WALLS, FLOORS, ROOFING AND CEILINGS TO MATCH EXISITNG FINISHES FOR DEMOLITION OF FIRE PROTECTION SYSTEMS. 15, CONTRACTOR SHALL PROVIDE (2) COMPLETE SETS OF AS BUILT DRAWINGS ALONG i WITH ALL CLOSE OUT DOCUMENTS PRIOR TO PROJECT COMPLETION. d w!Y t,� ter. afi t x,a ,. ' i ",, M(,,'v+^- ywst1!F,, �i �4..+d INSPECTOR w TF fS APPROVAL WAS ISSUED BASED ON THE INFORi4IATiON PROVIDED BY THE FIRE PROTECTION CONTRACTOR. i ACCORDING TO THE GENERAL NOTE THE NEW COOLING TOWER IS CONSTRUCTED WITH NON I } COMBUSTIBLE MATERIAL. CHECK THE BASING AREA INSIDE THE COOLING TOWER IF THE FILLS SHEETS ARE MADE OF VINYL OR PLASTIC MATERIAL THIS y APPROVAL IS VOIDED AND NULL. FIRE E PROTECTION ABBREVIATIONS F.H.C. FIRE HOSE CABINET O.S. & Y. OUTSIDE STEM AND YOKE F.E. FIRE EXTINGUISHER S.U. SECTIONAL CONTROL VALVE A/S AUTOMATIC SPRINKLER F.H. FIRE HYDRANT F.SP. FIRE STANDPIPE R.P.B.P. REDUCED PRESSURE BACKFLOW PREVENTER RCV RISER CONTROL VALVE A.F.F. ABOVE FINISHED FLOOR T.S. TAMPER SWITCH F.S. FLOW SNITCH F RV. FIRE DEPARTMENT VALVE N.O. NORMALLY OPEN? E.P. ELECTRICAL PANEL w!• • 0 a FIRE PROTECTION DRAWING INDEX I IMPORTANT IMPORTANT mw IN LOCAIJTFr_s Si,m -;ECT TO FrtFF ZING CONOMONS, 1177 IS THE OWNER'S RESPONSIRKI y TO PROVIDE ADEQUATE HEAT THROUGHOW bf-T PIPE SPRINKLER SYSTEMS AND IN ENCLOSURES FOlt DRY PIPE, DELUGE AND OTHER TYPES OF VALVE! S CONTROLLING WATT ? SUFFUES TO THE SPr?OWLER SYSTEM. THIS DRIL.Vw'NG AND TT'lE INFORMATION AN) DESIGN APPLICATION CONTANED H07F111l IS THE PROPERTY Or NATIONAL FIRE PROTECT''C?N. LLC AND is LOANED U"4 EXPRESS CONDITIONS THAT THE SAME BE RETUF?�D TO WTONAL. FIRE PROTECTION UPON REQUEST, ALL IN1,0PINIATION CONTAINED HEREIN SHALL RE TREATED AS PPOPRiETARY AND CONFIDENTIAL., NO REPRODUCTION OF THIS DRAWING SHALL IFF MADE Will IOU rTHE W'T3nTFN CON, ENT OF NATIONAL FIRE PROTECTION. 0 kiyd.-aul I. •yi Elov. e-a -1-] ] lev- tit on 2►-Y -Ti Of �> Ceiling I [ . Demotes -- - -Rise up - -_. a APPROVED BY FIRE PROTECTION DRAWING INDEX I NO. SHEET TITLE • t • FPOA1 FP1.01 FP1.02 FIRE PROTECTION LEGEND, SPECIFir;,ATIONS, NOTES& _ DRAWING INDEX FIRST FLOOR - DEMOLITION - FIRE PROTECTION SECOND FLOOR - DEMOLITION - FIRE PROTECTION J • • APPROVED BY _ REVISIONS M RGscription (?tt. I All . I- -A NATIONAL FIRE PROTECTION, LLC rxwFxr 3125 W. Commercial Bivd. Suite 200 SMH - Cooling Tower # 4 6200 SW 73 Street Fort Lauderdale, Florida 33301 Miarni, Florida 33143 Phone: (954) 739 -8107 Fax: (954) 739 -5471 CONTRACT'eiTO, Er,kr " w,.+NC. v ,W)MY.M& -o,,4+ wvro,,.natlfire.corn rrt;.M F; RW L7inAn�y ORAVomW I ""GW~ CA Tr OCAM,�T+. _. Cover Sheet CONTwicrr u3v _ti) crrr�nTr Tar FP - 1 <N ) LATFST FL"'N15K1M #1 1 f� • t • • ll U 4 • • • Wi•! w!• • 0 • ••W• 4 W • • • i W • W �'., w • W • • W !!4 W" 4.0 • v • Y Y y y, • Y Y rY• • •W• • i •!! •60lY •!l: i *!•• •iiY i • ` 0 w • • W � Y • Y W ! Y Y r0•• 0 040.0 • ••e 0 •900 0 _ REVISIONS M RGscription (?tt. I All . I- -A NATIONAL FIRE PROTECTION, LLC rxwFxr 3125 W. Commercial Bivd. Suite 200 SMH - Cooling Tower # 4 6200 SW 73 Street Fort Lauderdale, Florida 33301 Miarni, Florida 33143 Phone: (954) 739 -8107 Fax: (954) 739 -5471 CONTRACT'eiTO, Er,kr " w,.+NC. v ,W)MY.M& -o,,4+ wvro,,.natlfire.corn rrt;.M F; RW L7inAn�y ORAVomW I ""GW~ CA Tr OCAM,�T+. _. Cover Sheet CONTwicrr u3v _ti) crrr�nTr Tar FP - 1 <N ) LATFST FL"'N15K1M #1 1 f�