14-62-011FAN S C H E D U L E
DESIGNATION
SF -1 -1
- - -- 4
ROOF
MANUFACTURER
LOREN COOK
- _ a
,
1560
WEIGHT(LBS.)
50
250
= -- -_ - - -_
MODEL NUMBER
GN -184
210ACE6
-
TYPE
CENTRIFUGAL
IN -LINE FAN
DOWNBLAST CENTRIFUGAL
ROOF MOUNTED
3400
AREA SERVED
TOMOTHERAPY
E UIPM N
TOMOTHERAPY,
ACCELERATOR ROOM 2 AND
� 15.5
N.O.A.
NIA
13- 0708.12
( 30% EFFICIENCY MERV 7
C.F.M.
200
5750
5
E.S.P. (INCHES OF WATER)
0.65
0.55
SONES
4.8
21
R.P.M.
1500
971
H.P.
184 WATTS
1 1/2
VOLT - PH - HZ
120/1/60
t
DRIVE
DIRECT
BELT
BACKDRAFT DAMPER
-
YES
REMARKS
1,2,4,5
1,3,6
INTERLOCK
EXISTING PACKAGED
COOLING UNIT
EXISTING PACKAGED
COOLING UNIT
REMARKS:
1. TOGGLE SWITCH, NEMA 1, MOUNTED AND WIRED.
2. INSULATION 1" THICK: FAN HOUSING, MOTOR COVER.
3. PROVIDE ROOF CURB.
4. SPRING HANGING ISOLATORS AND BRACKETS.
5. PROVIDE SOLID STATE SPEED CONTROL.
6. THIS PRODUCT SHALL BE MIAMI -0ADE COUNTY APPROVED OR SUBMIT CALCULATIONS
MANUFACTURED BY TITUS.
OPTIONAL STEP DOWN TRANSFORMER 120V/24VAC
SED 1007
ENCLOSED SCROLL
0-200 GAUGE PRESS, RELIEF
0 -200 PSI
AC -1
(GA016701AV) 165 PSI
PRESSURE PRESSURE
RELIEF TRANSDUCER
w
(INTERNAL) (INTERNAL)
w
Q U
OL
AIR DISTRIBUTION SCHEDULE
1/2" B.V.
DESIGNATION A B C
FIELD SUPPLIED
MANUFACTURER TITUS TITUS TITU S
PIPING
MODEL NO. AND / OR �C-� 50 T3SQ -2
CATALOG NO. ALL ALUM. ALL ALUM.
2' X 2' 2' X 2' 2' X 2'
FRAME TYPE
LAY -IN LAY -IN LAY -IN
FIXED LOUVERED EGG CRATE VAV DIFFUSER
DEVICE TYPE
VANES 1/2 x 112 x 1/2
FUNCTION SUPPLY R /A, EXH OR TRANS. SUPPLY
NECK SIZE 18 x 18 LOUVERED FACE SEE DRAWINGS 18 x 18 LOUVERED FACE
NECK SIZE ON DRAWING NECK SIZE ON DRAWING
PATTERN SEE DRAWINGS SEE DRAWINGS SEE DRAWINGS
OPPOSED BLADE DAMPERS YES YES YES
NOTES:
3/4" FNPT
1. ALTERNATE MANUFACTURERS OF EQUAL QUALITY MAYBE SUBMITTED FOR APPROVAL.
AIR OUTLET
PRE - FILTER
TO AIR
2. ALL AIR DEVICES SHALL BE ALL ALUMINUM CONSTRUCTION AND FULLY GASKETED.
(ST178116AV)
REGULATOR
REFRIGERATED
GABINET
3. UNLESS OTHERWISE NOTED, FINISH OF ALL AIR DEVICES SHALL BE BAKED OFF WHffE.
I" DRAIN TO ` AIR DRAYER
1/2' B.V. (ACo100035>
4. MOUNTING BORDERS TO BE CONSISTENT WITH ACTUAL CEILING TYPE- COORDINATE WITH ARCHITECTURAL REFLECTED CEILING PLANS.
EXISTING 1' 1/2' B.V.
CONDENSATE DRAIN
VAV DIFFUSERS PROVIDE MASTER COMMUNICATION MODULE TITUS MCM AND CONTROLLER/THERMOSTAT
PIPE. REFER TO
FLOOR PLAN. FIXED AIR GAP
L&PROVIDE
MODEL 3950 BY
DRAIN PUMP �� JAY R.
BECKETT MODEL
CB151UL.
ELECTRICAL
SERVICE 115 V /
60HZ.
FAN S C H E D U L E
DESIGNATION
SF -1 -1
EF -2
ROOF
MANUFACTURER
LOREN COOK
LOREN COOK
1560
WEIGHT(LBS.)
50
250
= -- -_ - - -_
MODEL NUMBER
GN -184
210ACE6
-
TYPE
CENTRIFUGAL
IN -LINE FAN
DOWNBLAST CENTRIFUGAL
ROOF MOUNTED
3400
AREA SERVED
TOMOTHERAPY
E UIPM N
TOMOTHERAPY,
ACCELERATOR ROOM 2 AND
� 15.5
N.O.A.
NIA
13- 0708.12
( 30% EFFICIENCY MERV 7
C.F.M.
200
5750
5
E.S.P. (INCHES OF WATER)
0.65
0.55
SONES
4.8
21
R.P.M.
1500
971
H.P.
184 WATTS
1 1/2
VOLT - PH - HZ
120/1/60
208/3/60
DRIVE
DIRECT
BELT
BACKDRAFT DAMPER
-
YES
REMARKS
1,2,4,5
1,3,6
INTERLOCK
EXISTING PACKAGED
COOLING UNIT
EXISTING PACKAGED
COOLING UNIT
REMARKS:
1. TOGGLE SWITCH, NEMA 1, MOUNTED AND WIRED.
2. INSULATION 1" THICK: FAN HOUSING, MOTOR COVER.
3. PROVIDE ROOF CURB.
4. SPRING HANGING ISOLATORS AND BRACKETS.
5. PROVIDE SOLID STATE SPEED CONTROL.
6. THIS PRODUCT SHALL BE MIAMI -0ADE COUNTY APPROVED OR SUBMIT CALCULATIONS
EXISTING RTU - LA(BEFORE DEMOLITION)
AREA SERVED
TOMOTHERAPY LINEAR ACCELERATOR # 2
LOCATION +
ROOF
AIR FLOW -CFM
1560
OUTSIDE AIR -CFM
1560
RETURN AIR -CFM
I -
PRE- FILTER 30% EFFICIENCY
FINAL FILTER � 90 - 95% EFFICIENCY
FAN MOTOR H.P. 3
EXISTING RTU - LA(AFTER DEMOLITION)
AREA SERVED
TOMOTHERAPY LINEAR ACCELERATOR # 2
LOCATION
ROOF
AIR FLOW -CFM
3400
OUTSIDE AIR -CFM
� 3400
HOT WATER FLOW (GPM)
� 15.5
CHILLED WATER FLOW (GPM)
46
PRE - FILTER
( 30% EFFICIENCY MERV 7
FINAL FILTER
90 - 95% EFFICIENC -MERV 14
FAN MOTOR H.P. (1)
5
(1) PROVIDE VARIABLE FREQUENCY DRIVE FOR BALANCE ONLY.
(2) RE- FURBISHED OR REPAIR EXISTING RTU -LA TO RESTORE THE ORIIGINAL CONDITION.
(3) UPDATED EXISTING CONTROLS AS REQUIRED.
(4) RE- BALANCE CHILLED WATER AND HOT WATER FLOW.
MANUFACTURED BY TITUS.
OPTIONAL STEP DOWN TRANSFORMER 120V/24VAC
EXISTING RTU - LA(BEFORE DEMOLITION)
AREA SERVED
TOMOTHERAPY LINEAR ACCELERATOR # 2
LOCATION +
ROOF
AIR FLOW -CFM
1560
OUTSIDE AIR -CFM
1560
RETURN AIR -CFM
I -
PRE- FILTER 30% EFFICIENCY
FINAL FILTER � 90 - 95% EFFICIENCY
FAN MOTOR H.P. 3
EXISTING RTU - LA(AFTER DEMOLITION)
AREA SERVED
TOMOTHERAPY LINEAR ACCELERATOR # 2
LOCATION
ROOF
AIR FLOW -CFM
3400
OUTSIDE AIR -CFM
� 3400
HOT WATER FLOW (GPM)
� 15.5
CHILLED WATER FLOW (GPM)
46
PRE - FILTER
( 30% EFFICIENCY MERV 7
FINAL FILTER
90 - 95% EFFICIENC -MERV 14
FAN MOTOR H.P. (1)
5
(1) PROVIDE VARIABLE FREQUENCY DRIVE FOR BALANCE ONLY.
(2) RE- FURBISHED OR REPAIR EXISTING RTU -LA TO RESTORE THE ORIIGINAL CONDITION.
(3) UPDATED EXISTING CONTROLS AS REQUIRED.
(4) RE- BALANCE CHILLED WATER AND HOT WATER FLOW.
ARCHITECT:
B27-F:MELLO AJAMIL &PARTNERS, INC.
Architecture Engineering Planning
Interior Design Landscape Architecture
2661 South Bayshore Drive 10th Floor
" "- Miami, Florida 33133
(305) 859 -2050 Fax (305) 860 -3700
L
LOUIS J. AGUIRRE &ASSOCIATES, P.A.
Consulting Engineers
9150 South Dadeland Blvd. •Suite 900
Miami •Florida 33156 E60000924
Telephone 305.670.0141
Facsimile 305.670.0144
www.ljyaoa.com
Project No.: 23075
EbUARDb • A. SDAREZ,' P.E.
' t li��NSE Z:.64759
CONSTRUCTION
DOCUMENTS
REVISIONS:
0 12/06/13 AHCA COMMENTS.
PROJECT NAME:
SMH -Tomo Equipment Replace
PROJECT ADDRESS:
7400 S.W. 62nd Ave.
South Miami, Florida 33143
KEY PLAN
COMM. NO. 40073.000
SCALE: AS SHOWN
DATE: 11-14-2013
DRAWN: AP
CHECKED: Ac
CADD FILE: H:INSTITUTIONAL
DRAWING TITLE:
DIAGRAMS AND
SCHEDULES
HVAC
SHEET NO.
M6.00