14-523-037I ALUMINUM
RMINAL
NO. A69OX=-
ALUMINUM HORIZ.
POINT BASE
NO. A165—
ALUMINUM
LOOP CUP
SIDE VEW
No. A28-28
STRANDS OF
14 GA. ALUMINUM
CONDUCTOR CABLE
-
TYPICAL.
07TYPICAL PARAPET WALL BASE DETAIL 04NO SCALE
NO SCALE
o cP)% TYPICAL THROUGH -ROOF DETAIL
NO SCALE
PIPE PENETRATION PIPE PENETRATION
FOR EXPOSED ARES I FOR EXPOSED AREA
INTERIOR WALL
CUT SMOOTH HOLE
PACK TIGHT W /FIRE SAFING
SCHEDULE 40 PIPE SLEEVE
CHROME PIPE COLLAR
PROVIDE 1* MINIMUM CLEARANCE
1' THICK 3M —FIRE STOP OR EQUAL
U.S. GYPSUM THERMA —FIBER
AROUND ALL PIPES (TYPICAL)
1' MINIMUM
U.L SYSTEM NO. W —L -1054
F RATING — 1 HOUR AND 2 HOUR
T RATING — 0 HOUR
FIRE PENETRATION DETAIL
NO SCALE
FRONT VIEW
•
Project *:413508.000 • • c • r r r • • •
yr 2121 Pont! de L!6`6'n3o�levar i
F Suite 350 ••••• W•••• •
:h Coral GablEs, FL 33134
phone: 305.5613.1632
INTEGRAL MOUNTING STRAP OF RECEPTACLE GROUNDED METAL 'w T fax: 305.5G9.1G93 , V Y • •
h�l•n•I GneulYn� in�imers • • • • 1
OUTLET BOX Austin . Dallas . Denver . Houston . Kansas City :`Miami ;
Nashville . Phoenix . Richmond . Washington -D.C. • E
GREEN HEX HEAD E300007658
GROUNDING SCREW
ro
r,
¢�Q O ROILING JUMPER
2 �1
og STANDARD RECEPTACLE GROUNDING DETAIL
NO souF
oPnONS
1.
TO GENERATOR ROOM GROUND ROD
2'
TO REMOTE ELECTRICAL ROOMS
GROUND BAR TYP.
3'
TO BUILDING STRCUT. STEEL &
CONCRETE ENCASED ELECTRODE
4'
TO GROUND RING & LIGHTNING
PROTECTION SYSTEM
5.
TO MAIN M /COMM. ROOM
GROUND BAR
6.
TO MAIN SERVICE EQUIPMENT
7.
TO DOMESTIC WATER SERVICE
L
TO CONCRETE ENCASED ELECTRODE
9.
TO BUILDING STRUCT, STEEL
TO UNIT SUBSTATION
10.
TRANSFORMER (S)
11.
CONDUIT NTH GROUNDING
WING EACH END TYP.
12
TO EXISTING MAIN ELECTRICAL ROOM
GROUND BAR.
TO REMOTE TELE COMM ROOMS
13.
GROUND BAR EACH TYP.
14.
TO EACH SERVICE ENTRANCE GROUND
BAR. NMSB MSN1 & MSN2
7200 VOLT INSULATOR FABRICATED FROM FLAME
RESISTANT FIBERGLASS — REINFORCED
THERMOSET POLYSTER MOLDING COMPOUND
(TYPICAL OF BOTH SIDES)
GREEK
ND�$"
A. NEW GROUND BARS IN DATACENTER SHALL BE BONDED TOGETHER VIA #3/0 AWG.
B. CONNECT ALL EXISTING INCOMING GROUNDING CONDUCTORS ORIGINATING FROM EXISTING
BRANCH IT ROOMS TO NEW GROUND BAR.
C. PROVIDE IDENTIFCATION TAGS WITH THE LOCATION THE GROUND CONDUCTORS ARE
TERMINATING.
0 THOMAS BETTS #'3100
SERIES COPPER CABLE
LUG
OR EQUAL
2'W 11/4' GAL STEEL
STANDOFF STRAP SECURE 2'Lx4'Tx1 /4'0 COPPER BAR 16 HOLES 2' O.C. EA. WAY
TO WALL (TIT.) DRILLED & TAPPED. COORDINATE EXACT LENGTH VATH
NUMBER OF CABLES CONNECTING.
O 0
0 J3/0 AWG
GROUND CONDUCTOR
o
0
0 11
13
#3 /0 AWG (IYP. B
GROUND CONDUCTOR
12
ALL EXPOSED NON— CURRENT CARRYING METAL
1 { PARTS WITHIN THE DATACENTER SHALL BE
BONDED TO THE EQUIPMENT GROUNDING
CONDUCTOR IN ACCORDANCE WITH NEC250 OR
SHALL BE INSULATED.
MAIN TELE /COMMUNICATIONS ROOM
a2NO GROUND BAR DETAIL
SCALD
SLAB OR
STRUCTURE
ABOVE
S -0' FOR 0-150V RAISED FLOOR TILE
NOMINAL PANEL MINIMUM 30" (DOES NOT
HAVE TO BE C017ERED FLOOR SUPPORT
4' -0` FOR 151 -600V ON EQUPM T)
NOMINAL PANEL WAl
i GNO TO BUILDING STEEL
CONNECTION/INSTA LATION AD /OR NEAREST GROUND BAR
BY ELECTRICAL'')
CONTRACTOR (TYMCAL) .
GROUND RAISED FLOOR AT EACH
PANEL PANEL 3/4" SEALTITE CORNER (TYPICAL)
�' -fi" MIN.
(MIN. 3' -0• LONG) BOIX •, ~• TO POWER RECEPTACLES IN
•?� ... FLOOR BOX (TYPICAL.)
FUNSHED
3/4' CONDUIT Mm TrrE FLEXIM.E 3 f 4 }
TO PANEL. SECURE TO CONDUIT (MIN. 3'-0 LGNG)
SUE VFW FRONT NEW SLAB, WITHIN 1B'
REQUIRED OFF JLNVCTION BOX.
CLEARANCE
PANELBOARD REQUIRED CLEAR
••• rr•
revwotwl
• . • Y
1 �{ V •
A
Z�
O
A In
<
<a 0
W
OO
w
x
w<
Z
w
�x
<�N
<0 Ile
y
...
CCS �
Ama
(Vill!
y
O �
3
+, 9
16, � ~
71
m<
W
Q
a
1"'
Iii
IJ
Ii
AHCA
STAGE III
12/13/13
mAVJ% CCRD
a�li CCIRD
DIA7L 12 -13 -13
SOMA AS 6HOWN
Q `1O'
v
ENGINEER `