14-523-006LIFE SAFETY CALCULATIONS _._.._.. _ ....... .. .... ...._, m.... ----------- .._ ...__._ .._ .__ _.__. _..__..._____... __..._._ ._.._.,_.. SECOND FLOOR EXIT CALCULATIONS COMPT COMPARTMENT AREA (SF) OCCCUPAN T LOAD (PERSONS) EXIT CAPACITY PROVIDED (INCHES) TOTAL EXIT OCCPT. PROVIDED /REQ' D (PERSONS) SLEEPIN G (120 SF /P) NON- SLEEPING (240 SF /P) OFFICE STAIR (.30) LEVEL (.20) 2A - 14,043 59 48/160 42/210 370/59 2B - 1,873 _ 41 44/147 42/210 357141 2C - 7,257 - 30 - 42/210 21 0130 2D - 17,082 - 71 - 84/420 420/71 2E - 14,6850 - 61 -- 48/240 240/61 2F - 10,601 - 44 44/147 42/210 357/44 2G 7,465 - 31 -- 84/420 420/31 2H - 11,417 48 - 84/420 420/48 21 - 6,090 25 48/160 - 160/25 2J 10,063 - 42 48/160 84/420 580/42 2K - 20,730 - 86 - 42/210 210/86 2L 9,111 - 38 48/160 46/230 390/38 t=) A t= -r I A I C, = r' /1N 11—1 =1 /1 /) t= I I = = C, A = = -r -,r- t= I A 'Is, NOTE: THIS LIFE SAFETY PLAN HAS BEEN PREPARED USING AS REFERENCE THE LIFE SAFETY PLANS MADE BY BERMELLO AJAMIL 4 PARTNERS, INC_ DATED: OCTOBER 22, 2010 AND PROVIDED BY SOUTH MIAMI HOSPITAL. 111111MINIIIIIIIIII I WIWI] IIJ V ® CORR ONE HOUR FIRE RATED PARTITION 1Fq W IFq M 1FSl IIIIIII JJOLTEMANAGER OFFI 2 OFFICE MDICATE6 C 0TRUCTION TRAwIC V40M TO THE EXTERIOR �EXTERI•RT PROJECT AREA AT 210 FLOOR SERVICE ELEVATOR REQUIRED ICRA PRECAUTIONS FOR CLASS III • DURING C❑NSTRUCTI ❑N PROJECT 1, REMOVE OR IS ❑LATE HVAC SYSTEM IN AREA WHERE WORK IS FLING DONE TO PREVENT CONTAMINATION OF DUCT SYSTEM. 8, COMPLETE ALL CRITICAL BARRIERS LE, SHEETROCK, PLYWOOD, PLASTIC, TO SEAL AREA FROM NON WORK AREA OR IMPLEMENT CONTROL CURL METHOD (CART WITH PLASTIC COVERING AND SEALED CONNECTION TO WORK SITE WITH HEPA VACUUM FOR VACUUMING PRI ❑R TO EXIT) BEFORE CONSTRUCTION BEGINS, 3. MAINTAIN NEGATIVE AIR PRESSURE WITHIN WORK SITE UTILIZING HEPA EQUIPPED AIR FILTRATION UNITS, 4, CONTAIN CONSTRUCTION WASTE BEFORE TRANSPORT IN TIGHLY COVERED CONTAINERS BEFORE TRANSPORTING 5, COVER TRANSPURT RECEPTACLES OR CARTS. TAPE COVERING UNLESS SOLID LID, 6, SEAL HOLES, PIPES, CONDUITS AND PUNCTURES APPROPRIATELY, • UP ❑N C❑MPLETI ❑N OF PROJECT 1, DO NOT REMOVE BARRIERS FROM WORK AREA UNTIL COMPLETED PROJECT IS INSPECTED BY THE OWNER'S STAFF, 2. VACUUM WORK AREA WITH H PA FILTERED VACUUMS, 3. WET M ❑P /WIPE EXPOSED SURFACES WITH APPROPRIATELY LABELED AND BHSF APPROVED HOSPITAL DISINFECTANT, 4. CONTAIN CONSTRUCTION WASTE IN TIGHTLY COVERED CONTAINERS BEFORE TRANSPORTING. 5, COVER TRANSPORT RECEPTACLES OR CARTS, TAPE COVERING UNLESS S ❑LID LID. 6, REMOVE ISOLATION OF HVAC SYSTEM IN AREAS WHERE WORK IS BEING PERFORMED, 7. REMOVE BARRIER MATERIALS CAREFULLY TO MINIMIZE SPREADING OF DIRT AND DEBRIS ASSOCIATED WITH CONSTRUCTION. S. FINAL CLEANING BY ENVIRONMENTAL SERVICES PRIOR TO OCCUPANCY, ECHO WORKRM. SYMBOL LEGEND i � I � I m ONE HOUR FIRE RATED PARTITION 1Fq W IFq M 1FSl IIIIIII ONE HOUR FIRE RATED/ SMOKE PARTITION i i ■ TWO HOUR FIRE RATED PARTITION 2FS I 10 2FS I I TWO HOUR FIRE RATED/ SMOKE PARTITION THREE HOUR FIRE RATED/ SMOKE PARTITION A MEMENEEN FOUR HOUR RATED/ SMOKE PARTITION EXIT LIGHT (CENTER ON DOOR(S)) NOTE: SHADED AREA INDICATES LIGHTED FACE EXIT LIGHT: DIRECTIONAL (CENTER ON DOOR(S) AS REQUIRED) NOTE: SHADED AREA INDICATES LIGHTED FACE FE FIRE EXTINGUISHER: SEE DETAIL 6/A6.42 FIRE JACK FHC FIRE HOSE CABINET MANUAL FIRE ALARM BOX (PULL STATION) FIRE ALARM COMBINATION AUDIBLE / VISIBLE NOTIFICATION APPLIANCE FIRE ALARM VISIBLE NOTIFICATION APPLIANCE FIRE ALARM AUDIBLE NOTIFICATION APPLIANCE DO SMOKE DETECTOR (CEILING MOUNTED) FIRE ALARM SPEAKER (CEILING MOUNTED) FAAP FIRE ALARM ANNUNCIATOR PANEL MGAR MEDICAL GAS ALARM PANEL �H SMOKE DOOR MECHANICAL HOLD OPEN 36" 180 EXIT CAPACITY: INCHES / NUMBER OF OCCUPANT CAP. O HEAT DETECTOR FL FIRE LIGHT FIRE INDICATOR LIGHT CEILING MOUNTED rr wwiw NEW ADDITION DEMARCATION —— — EXITING DISTANCE - y AREA OF EXISTING BUILDING NOT IN SCOPE OF WORK C 11,sc8 S.F. COMPARTMENT NUMBER & AREA SQUARE FOOTAGE •Wa• W•• ••• • • ♦ • • ••• • u u • f • W a • • a • r•Y• 4, a • •Ii• • 0.000 • S APPLICABLE CODES: " • FLORIDA BUILDING CODE (FBC) - 2007 (WITH 2009 FBC ADDENDWS) • AIA GUIDELINES FOR DESIGN AND CONSTRUCTION OF HOSPITALS AND HEALTH CARE FACILITIES - 2006 EDITION lfi • FLORIDA ACCESSIBILITY CODE - FBC CHAPTER 11 • TES - F • NFPA 101 - 20 6 CHAPTER 18, NEW HEALTH CARE OCCUPA IES t600k • NFPA 220 - EDITIO f7� • NFPA 253 - 2006 EDITION OCCUPANCY TYPE: • INSTITUTIONAL (FLORIDA BUILDING CODE 2007 - SECTION 308.3 GROUP 1 -2) BUILDING CLASSIFICATION: • TYPE 1 -A FULLY SPRINKLERED (FBC 2007) • NFPA 220 - TYPE II (2 -2 -2) . //� \y� •rar• / 3 i • Y• • • W • W W r • f • Y • 041 4 "a z� w cG oG < w H� w� ux ow 1 w t� .m, � ...w 0 M ' o y ♦A� +f #a O � � V 16.q. O � � cG O < z A O w w V) < V Z '� Carl r ' AHCA `tTAGE M 12/13/13 DRA1M R.G. CHFXX M. LEN. DATE 12 -13 -13 SCALE; AS SHOUJN SF,AI.�`' i err ;m Sheet NO. LS -1 OF 1 OF 2