14-523-005LIFE SAFETY CALCULATIONS SECOND FLOOR EXIT CALCULATIONS COMPT COMPARTMENT AREA (SF) OCCCUPAN T LOAD (PERSONS) EXIT CAPACITY PROVIDED (INCHES) TOTAL EXIT OCCPT. PROVIDED /REQ' D (PERSONS) SLEEPIN G (120 I SF /P) NOW SLEEPING (240 SF /P) OFFICE STAIR (.30) LEVEL (.20) 2A • FLORI • NFPA 14,043 - 59 4x/160 42/210 370/59 2B - •t,973 - 41 44/147 42/210 357/41 2C - 7,257 OD 30 - 42/210 210/30 2D - 17,092 F—D—H-1 71 - 84 /420 420/71 2E Fl 14,650 - 61 -- 48/240 240161 2F - 10,601 - 44 44/147 42/210 357/44 2G - 7,465 - 31 - 84/420 420/31 2H 11,417 49 — 84/420 420/48 21 6,090 - 25 48/160 -- 160/25 2J - 10,063 - 42 48/160 84/420 580/42 2K - 20,730 96 - 42/210 210/86 2L 9,111 - 39 48/160 46/230 390/38 SCALE: 1 /16" - 1' -0" NOTE: THIS LIFE SAFETY PLAN HAS BEEN PREPARED USING A$ REFERENCE THE LIFE SAFETY PLANS MADE BY BERMELLO AJAMIL 4 PARTNERS, INC. DATED: OCTOBER 22, 2010 AND PROVIDED BY SOUTH MIAMI HOSPITAL. MIGATEB cable WWTION TRAO"IG Wm TO THE EXTERIOR PROJECT AF AT 2ND lLO��lt SERVICE ELEVATOR APFROYE y WATER EXTEN,�;IcXq REQUIRED ICRA PRECAUTIONS FOR CLASS III DURING CONSTRUCTION PROJECT REMOVE OR ISOLATE HVAC SYSTEM IN AREA WHERE WORK IS BEING DONE TO PREVENT CONTAMINATION OF DUCT SYSTEM. COMPLETE ALL CRITICAL BARRIERS I.E, SHEETR❑CK, PLYWOOD, PLASTIC, TO SEAL AREA FROM NON WORK AREA OR IMPLEMENT CONTROL CUBE METHOD (CART WITH PLASTIC COVERING AND SEALED CONNECTI❑N TO WORK SITE WITH HEPA VACUUM FOR VACUUMING PRIOR TO EXIT) BEFORE CONSTRUCTION BEGINS. MAINTAIN NEGATIVE AIR PRESSURE WITHIN WORK SITE UTILIZING HEPA EQUIPPED AIR FILTRATION UNITS. CONTAIN CONSTRUCTION WASTE BEFORE TRANSPORT IN TIGHLY COVERED CONTAINERS BEFORE TRANSPORTING. COVER TRANSPORT RECEPTACLES OR CARTS. TAPE COVERING UNLESS SOLID LID. SEAL HOLES, PIPES, CONDUITS AND PUNCTURES APPROPRIATELY. UPON COMPLETION OF PROJECT DO NOT REMOVE BARRIERS FROM WORK AREA UNTIL COMPLETED PROJECT IS INSPECTED BY THE OWNER'S STAFF, VACUUM WORK AREA WITH HEPA FILTERED VACUUMS. WET MOP /WIPE EXPOSED SURFACES WITH APPROPRIATELY LAIiELED AND BHSF APPROVED HOSPITAL DISINFECTANT. CONTAIN CONSTRUCTION WASTE IN TIGHTLY COVERED CONTAINERS BEFORE TRANSPORTING. COVER TRANSPORT RECEPTACLES OR CARTS, TAPE COVERING UNLESS SOLID LID. REMOVE ISOLATION OF HVAC SYSTEM IN AREAS WHERE WORK IS BEING PERFORMED, REMOVE BARRIER MATERIALS CAREFULLY TO MINIMIZE SPREADING OF DIRT AND DEBRIS ASSOCIATED WITH CONSTRUCTION. FINAL CLEANING BY ENVIRONMENTAL SERVICES PRIOR TO OCCUPANCY, SYMBOL LEGEND rrr� ONE HOUR FIRE RATED PARTITION 1Fq 0 1FSI 0 1FS1 ONE HOUR FIRE RATED/ SMOKE PARTITION HOSPITALS AND TWO HOUR FIRE RATED PARTITION 2FS 11 0 2FS I I = TWO HOUR FIRE RATED/ SMOKE PARTITION 111=111M THREE HOUR FIRE RATED/ SMOKE PARTITION NNINNINMEN l FOUR HOUR RATED/ SMOKE PARTITION • FLORI • NFPA EXIT LIGHT (CENTER ON DOOR(S)) NOTE: SHADED AREA INDICATES LIGHTED FACE ---� EXIT LIGHT: DIRECTIONAL (CENTER ON DOOR(S) AS REQUIRED) NOTE: SHADED AREA INDICATES LIGHTED FACE FF FIRE EXTINGUISHER: SEE DETAIL 6/A6.42 F FIRE JACK FHC FIRE HOSE CABINET 0 MANUAL FIRE ALARM BOX (PULL STATION) o4 FIRE ALARM COMBINATION AUDIBLE / VISIBLE NOTIFICATION APPLIANCE Ell FIRE ALARM VISIBLE NOTIFICATION APPLIANCE FIRE ALARM AUDIBLE NOTIFICATION APPLIANCE OD SMOKE DETECTOR (CEILING MOUNTED) a FIRE ALARM SPEAKER (CEILING MOUNTED) FAAP FIRE ALARM ANNUNCIATOR PANEL MGAP MEDICAL GAS ALARM PANEL F—D—H-1 SMOKE DOOR MECHANICAL HOLD OPEN EXIT CAPACITY: INCHES / NUMBER OF OCCUPANT CAP. �H HEAT DETECTOR Fl FIRE LIGHT FIRE INDICATOR LIGHT CEILING MOUNTED r.r r.a rrr NEW ADDITION DEMARCATION — --- EXITING DISTANCE AREA OF EXISTING BUILDING NOT IN SCOPE OF WORK C 11,5G: S.F. COMPARTMENT NUMBER & AREA SQUARE FOOTAGE APPLICABLE CODES: •••• •.. ••• ••• • • Y i • • • Y • • w V • • U • u • • i • • • V V NS ONLY, FOR OD1FIC 'flo �'j oqumv. 'lDr'Mpp1F 1EAPANC1✓) (NN* E'T N SON" A • FLORIDA DING CODE (FBC) - 20 (WITH 2009 FBC ADDENDUMS) • AIA GUI LINES FOR DESIGN AN ONSTRUCTION OF HOSPITALS AND HEALT CARE FACILITIES - 6 EDITION • FLORI A ACCESSIBILITY C - FBC CHAPTER 11 • FLORI • NFPA A STATUT C CHAPTER 4 101 - HAPTER 18, NEW HEATH CAR OCCUPANCIES • NFP 70 - 00 s r� G / • NFP 253 - 2006 EDITION OCCUPANCY TYPE: • INSTITUTIONAL (FLORIDA BUILDING CODE 200 BUILDING CLASSIFICATION: • TYPE I -A FULLY SPRINKLERED (FBC 2007) • NFPA 220 - TYPE II (2 -2 -2) ON 308.3 GROUP 1--2) Revlalons: ��y ` 14- 113 -14' 2 4COM^1Ehl • • A•V V U • • 4 Y Q J• •WW1 • • •' • •y ca ••oe • z ma Q< dIC �a > 00 z LLA C4 ~ �.1.� Z w U <0 a v) CCS �pow y love � 0 �V 400� zi O a O "`" Qom." V z A o� LLN h � V <�A W oG < a AHCA STAGE M 12/13/13 DRAY Me RG. ONA3CED" LEN. DATES 12 -13 -13 SCAM AS oi11N �...,. v A" A',R.) `y7L V . �G FRED Sheet No. LS -1 or 1 OF 2 L JOB 9 201316 1