14-375-036
ELECTRICAL SYMBOL LEGEND E] FIRE ALARM PULL STATION (48" A.F.F.) SEMI FLUSH MOUNTED, PROVIDE BREAKABLE GLASS COVER. 04 FIRE ALARM BELL WITH STROBE LIGHT (80 "A.F.F.) ADA 04 FIRE ALARM SPEAKER WITH STROBE LIGHT (80 "A.F.F.) ADA ss FIRE ALARM SPEAKER WITH STROBE LIGHT. CEILING MOUNTED pS FIRE ALARM MASS NOTIFICATION SPEAKER. CEILING MOUNTED FIRE ALARM STROBE LIGHT - 75 CANDELA MIN. - (80 " A.F.F.) OR 6" BELOW CEILING WHISHEVER IS LOWER, INSTALLATION SHALL COMPLY WITH A.D.A., FIRE ALARM STROBE LIGHT. CEILING MOUNTED sD 24V SMOKE DETECTOR (PHOTOELECTRIC TYPE). sD H SMOKE AND HEAT DETECTOR Q 24V FIXED TEMPERATURE 135' F THERMAL DETECTOR. DD 24V PHOTOELECTRIC DUCT DETECTOR. © FIRE ALARM TELEPHONE JACK DH FIRE ALARM DOOR HOLDER FS FIRE ALARM FLOW SWITCH TS FIRE ALARM TAMPER SWITCH FACP FIRE ALARM CONTROL PANEL POWER EQUIPMENT ® HIGH VOLTAGE DISTRIBUTION PANELBOARD 277/480V ® LOW VOLTAGE DISTRIBUTION PANELBOARD 120/208V HIGH VOLTAGE PANELBOARD 277/48OV. ® LOW VOLTAGE PANELBOARD 120 /208V. L❑ HD FUSIBLE DISCONNECT OR CIRCUIT BREAKER. NEMA 3R WHEN OUTDOORS. 3 0 3 =N0. OF POLES, 60 = SWITCH SIZE, 50 =FUSE, NF= NON - FUSED, " =FUSE SIZE AS REQUIRED BY LOAD. MOTOR STARTER W /CONTROL XMFR, HOA SELECTOR SW. AND RED PILOT LIGHT. NEMA SIZE BY MOTOR. PROVIDE NEMA 4 ENCLOSURE WHEN OUTDOORS COMBINATION MOTOR STARTER WITH DISCONNECT SWITCH OR CB. SAME Lu ENCLOSURE AND ACCESSORIES AS INDICATED ABOVE CONTACTOR. SAME ENCLOSURE AND ACCESSORIES AS STARTERS FAN 2� MOTOR "2" WHEN SHOWN INDICATES HORSEPOWER nT TRANSFORMER POWER DEVICES (ALL RECEPTACLES SHALL BE GROUNDING TYPE HOSPITAL GRADE TYPE) `� DUPLEX RECEPT - 20 AMP NEMA 5 -20R (18" A.F.F.) ej SINGLE RECEPT - 20 AMP NEMA 5 -20R (18" A.F.F.) DUPLEX RECEPT. MOUNTED ABOVE COUNTER - 20 AMP NEMA 5 -20R (44" A.F.F.) U.O.N. Q� POWER RECEPT. TWIST LOCK - 20 AMP NEMA 5 -20R (18" A.F.F.) QUAD - PLEX RECEPT - 20 AMP NEMA 5 -20R (18" A.F.F.) ® DUPLEX RECEPT FLUSH FLOOR MOUNTED - 20 AMP NEMA 5 -20R ® DUPLEX RECEPT FLUSH CEILING MOUNTED - 20 AMP NEMA 5 -20R SPECIAL PURPOSE RECEPT (18" A.F.F.) A, B, C A - 250V, 30A, 4W B - 250V, 50A, 4W. C - 25OV, 50A, 5W. O JUNCTION BOX a WALL MOUNTED JUNCTION BOX FLOOR MOUNTED JUNCTION BOX UNDER RAISED FLOOR FOR CONNECTION TO WIREMOLD PLUG STRIP MOUNTED AT RACKS AND FURNITURE BY A HARDWIRE FLEXIBLE CONNECTION BY ELECTRICAL CONTRACTOR. PE PULL BOX BRANCH CIRCUIT OR FEEDER WIRING IN CONDUIT. NO TICKS INDICATES 2# 12 CONDUCTORS & 1# 12 GROUND IN 3/4" CONDUIT. TICK MARKS WHEN SHOWN, INDICATES NUMBER OF #12 CONDUCTORS IF OTHER THAN THREE, (1) INDICATES GROUND. CONDUIT LARGER THAN 3/4" & CONDUCTOR LARGER THAN #12 SHALL BE AS INDICATED. HOME RUN TO PANEL "A " = PANEL DESIGNATION, 1,3,5 = CIRCUIT NUMBERS. U.O.N. MINIMUM SIZE OF 3/4 "C AND MAXIMUM OF THREE CIRCUITS PER �A-13,5 HOMERUN. (DEDICATED NEUTRAL FOR EACH HOT WIRES MUST BE PROVIDED) FLEXIBLE CONDUIT CONDUIT RUN CONCEALED IN CEILING OR WALLS -U /G- CONDUIT RUN UNDERGROUND OR IN SLAB --- - - - --- CONDUIT RUN EXPOSED [ CAPPED CONDUIT - -�-I- - + -- SYSTEM AND /OR EQUIPMENT GROUNDING CONDUCTOR ,�C ---- GROUNDING ELECTRODE AND CONDUCTOR SYSTEM CONDUIT SEAL CABLE TRAY DATA, COMMUNICATIONS AND SECURITY V TELEPHONE & DATA OUTLET (4 "x 4 "x 2 1/2" OUTLET BOX) (18" A.F.F.) ® TELEPHONE & DATA OUTLET FLUSH FLOOR MOUNTED 0 DATA OUTLET (4 "x 4 "x 2 1/2" OUTLET BOX) (18" A.F.F.) m TELEPHONE OUTLET FLUSH FLOOR MOUNTED . TELEPHONE OUTLET (4 "x 4 "x 2 1/2" OUTLET BOX)(18" A.F.F.) Vw WALL MOUNTED TELEPHONE OUTLET (60 "A.F.F.) © CLOCK (8' -0" AFF) D TERMINAL CABINET - TYPE INDICATED TELEPHONE TERMINAL BACK BOARD Q CLOSE CIRCUIT TV MONITORS CCr� CCTV CAMERA 0 RADIO REMOTE sR PAGER SPEAKER FB PHYSIOLOGICAL MONITOR OUTLET FEJ ROOM RESERVATION SYSTEM. POWERED OVER ETHERNET. is w INTERCOM STATION (WALL MTD) -3GANG BOX @ 4' -0" C p INTERCOM (DOOR STATION) SAME AS WALL MTD c INTERCOM @ 4 " -0" A.F.F. cT CATV STATIONS @ 2' -6" A.F.F. (U.N.O.) F0 WALL MOUNTED TV OUTLET. 0 SECURITY PUSH BUTTON Eb SECURITY DOOR BELL CHIME KP SECURITY SYSTEM KEYPAD RR SECURITY SYSTEM CARD READER SECURITY SYSTEM UHF CARD READER ©D SECURITY SYSTEM MOTION DETECTOR DS SECURITY SYSTEM DOOR STRIKE (c SECURITY SYSTEM DOOR CONTACT ML SECURITY SYSTEM MAGNETIC LOCK PS POWER SUPPLY =EF0 EMERGENCY OFF BUTTON 48 "A.F.F. EH PUSH PLATE (48" A.F.F.) NURSE CALL NCMS NURSE CALL MASTER STATION FJ$ NURSE CALL STAFF STATION 48" AFF �/q NURSE CALL DUTY STATION 48" AFF 10 NURSE CALL TOILET EMERGENCY STATION 48" AFF T NURSE CALL CODE BLUE STATION 48" AFF FB T 91�1 NURSE CALL DOME LIGHT, CEILING MOUNTED PROJECT SPECIFICATION 1. SITE INVESTIGATION: PRIOR TO BIDDING THE CONTRACTOR SHALL VISIT THE JOBSITE AND BECOME ACQUAINTED WITH ALL OF THE EXISTING CONDITIONS WHICH WILL AFFECT HIS WORK. FAILURE TO DO SO WILL NOT BE ACCEPTED AS A REASON FOR REQUESTING EXTRA PAY WHERE THE EXISTING CONDITION RESULTS IN EXTRA MATERIAL OR LABOR. THE CONTRACTOR SHALL SUBMIT IN HIS BID AN AMOUNT THAT WOULD BE SET ASIDE FOR UNIDENTIFIED ITEMS. 2. THE CONTRACTOR SHALL FURNISH ALL LABOR, MATERIALS AND EQUIPMENT NECESSARY FOR THE COMPLETE INSTALLATION OF THE ELECTRICAL SYSTEMS, ALL IN ACCORDANCE WITH THESE CONSTRUCTION DOCUMENTS. ALL WORK PERFORMED UNDER THIS CONTRACT SHALL COMPLY WITH THE FLORIDA BUILDING CODE 2010 REVISIONS AND ALL THE STANDARDS OF CONSTRUCTION ESTABLISHED BY THE HOLY CROSS HOSPITAL INCLUDING, BUT NOT LIMITED TO THE FOLLOWING PUBLICATIONS: A) CHAPTER 59A -3 FLORIDA ADMINISTRATIVE CODE 2002, B) NFPA 70 -2008, NFPA 72 -2002, NFPA 99 -2005, NFPA 110 -2005, NFPA 101 -2006, AND C) AIA 2006 AND D) OSHA. 3. MINIMUM STANDARDS: THE MATERIAL, EQUIPMENT, INSTALLATIONS, AND WORKMANSHIP FURNISHED UNDER THIS SECTION SHALL CONFORM AT LEAST TO THE REQUIREMENTS OF THE REGULATING AGENCIES AS LISTED IN ITEM (2) ABOVE. ALL MATERIALS AND EQUIPMENT USED SHALL BE LISTED OR BEAR THE U.L. APPROVAL FOR THEIR INTENDED USE, 4. RESPONSIBILITIES: CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING A COMPLETE INSTALLATION OF THE RACEWAY SYSTEM, EQUIPMENT AND WIRING IN ACCORDANCE WITH THE CONTRACT DOCUMENTS. 5. GUARANTEE: THE CONTRACTOR /SUB - CONTRACTOR SHALL FURNISH A WRITTEN GUARANTEE THAT ALL WORK EXECUTED UNDER THIS CONTRACT SHALL BE FREE FROM DEFECTS OF WORKMANSHIP AND MATERIALS FOR A PERIOD OF ONE YEAR FROM THE DATE OF FINAL ACCEPTANCE AND THAT HE WILL AT HIS OWN EXPENSE, REPAIR OR REPLACE ALL WORK WHICH BECOMES DEFECTIVE DURING THE TIME OF THE GUARANTEE. 6. ALL EQUIPMENT, SYSTEM AND SYSTEM COMPONENTS SHALL BE FROM THE SAME MANUFACTURER AND SHALL BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS AND SPECIFICATIONS. 7. RACEWAYS AND FITTINGS: CONDUIT RUNS SHALL BE CONCEALED IN CEILING SPACES, AND WALL PARTITIONS; NO RACEWAY SHALL BE EXPOSED IN INTERIOR SPACES SUCH AS RESIDENT ROOMS. CONCEALED CONDUITS MAY BE EMT. THE MINIMUM CONDUIT SIZE IS TO BE 3/4" FOR HOME RUN. ALL CONDUITS AND RACEWAYS SHALL BE METAL. 8. CONDUCTOR: ALL CONDUCTOR WIRE AND CABLE SHALL CONSIST OF 98 % CONDUCTIVITY COPPER. ALL CABLES SHALL BE SINGLE CONDUCTOR, 600 VOLT, THERMOPLASTIC INSULATION. SUITABLE FOR CONTINUOUS OPERATION AT 75 DEGREES C. CONDUCTOR TEMPERATURE IN BOTH WET AND DRY LOCATIONS. THESE CABLES SHALL BE N.E.C. INSULATION CLASSIFICATION TYPE THWN/THHN. MINIMUM SIZE SHALL BE #12. ALL CONDUCTOR INSTALLATION SHALL BE COLOR CODED MAINTAINING THE INTEGRITY OF THE EXISTING INSTALLATION. COLORED INSULATION SHALL BE USED FOR AWG SIZES #10 AND SMALLER AND APPROVED COLOR TAPES SHALL BE USED FOR AWG SIZES #8 AND LARGER ALL POWER AND CONTROL CIRCUITS SHALL CARRY EQUIPMENT GROUNDING CONDUCTOR SIZED PER NEC 250 -95. 9. THE NATURE OF THIS TYPE OF CONSTRUCTION POSES SPECIAL PROBLEMS FOR THE DESIGN ENGINEERS AS WELL AS THE CONTRACTOR. EVERY EFFORT HAS BEEN MADE BY THE ENGINEERS TO SHOW AND VERIFY WHERE POSSIBLE. THE LOCATION OF THE EXISTING ELECTRICAL SYSTEMS. THE MAJOR PORTION OF THE ELECTRICAL SYSTEMS ARE AS SHOWN ON THE DRAWINGS. HOWEVER MINOR DEVIATIONS MAY BECOME EVIDENT AS THE JOB PROGRESSES. NO ADVANTAGE IS TO BE TAKEN BY THE CONTRACTOR BECAUSE THESE MINOR DIFFERENCES. 10. ALL FLOORS, WALLS, AND ROOF PENETRATIONS SHALL BE PROPERLY SEALED -OFF. IF FIRE RATED, AN APPROVED FIRE RETARDANT SEALANT SHALL BE USED. 11. THESE DRAWINGS ARE A GUIDE FOR THE INSTALLATION OF THE RACEWAY SYSTEM AND EQUIPMENT. THEY ARE INTENDED TO SHOW THE GENERAL ARRANGEMENT, DESIGN AND EXTENT OF THE WORK AND PARTLY DIAGRAMMATIC. THE CONTRACTOR IS RESPONSIBLE TO PROVIDE A COMPLETE AND FUNCTIONAL INSTALLATION. 12, ANY DEVIATIONS FROM THESE DRAWINGS AND SPECIFICATIONS MUST BE AUTHORIZED IN WRITING FROM THE ENGINEERS OFFICE. THE CONTRACTOR SHOULD BE HELD LIABLE FOR ANY DEVIATIONS WITHOUT SUCH AUTHORIZATION. SYSTEMS 13, ANY WORK NOT SHOWN OR SPECIFICALLY MENTIONED ON THESE PLANS AND /OR SPECIFICATIONS BUT CONSIDERED NECESSARY FOR COMPLETION OF THE WORK IN THE PROPER MANNER SHALL BE PROVIDED BY THE CONTRACTOR WITHOUT ADDITIONAL CHARGE. 14. CONTRACTOR SHALL VERIFY SPACE CONDITIONS AND DIMENSIONS AT JOB SITE PRIOR TO FABRICATION AND INSTALLATION OF MATERIALS AND EQUIPMENT. ELECTRICAL CONTRACTOR TO COORDINATE HIS WORK WITH THE ARCHITECT BEFORE ROUGH INSTALLATION OF ALL OUTLETS, (LIGHTS, RECEPTACLES, SWITCHES, PULL BOXES, ETC.) FOR EXACT LOCATION. 15. ALL ELECTRICAL EQUIPMENT SUCH AS PANELS, PULL /J- BOXES, FEEDERS, BREAKERS, ETC, SHALL BE PROPERLY IDENTIFIED WITH A PERMANENT LABEL AFFIXED TO THE EQUIPMENT. IDENTIFY BREAKERS IN PANELS BY MEANS OF A TYPED, PLASTIC COVERED DIRECTORY. CONTRACTOR SHALL PROVIDE UPDATED PANEL DIRECTORIES. 16. ALL SERVICE INTERRUPTIONS AND ALL REMOVAL AND DISPOSAL WORK SHALL BE SCHEDULED AND COORDINATED WITH THE AUTHORIZED REPRESENTATIVE OF THE OWNER. 17. CONTRACTOR SHALL SECURE AND PAY FOR ALL PERMITS, FEES, TAXES, INSPECTIONS, TESTS AND OTHER ITEMS AS REQUIRED FOR THE WORK AS OUTLINED IN THE PLANS. PROVIDE ALL THE REQUIRED INSURANCE FOR PROTECTION AGAINST PUBLIC LIABILITY AND PROPERTY DAMAGE FOR THE DURATION OF THE WORK. 18. UPON COMPLETION OF THE INSTALLATION, CONTRACTOR SHALL CONDUCT A COMPLETE EQUIPOTENTIAL TEST AS DEFINED IN N.F.P.A. -99 (2009). SUBMIT THE RESULTS OF THE TEST TO THE OWNER AND THE A /E. THE CONTRACTOR SHALL HAVE A TEST EQUIPMENT AVAILABLE FOR SPOT CHECKING AT FINAL CONSTRUCTION SURVEY. 19. CONTRACTOR SHALL MAINTAIN A COMPLETE SET OF PRINTS FOR INDICATING ALL CHANGES AS THE CONSTRUCTION PROGRESSES. AT THE COMPLETION OF THE WORK, THE CONTRACTOR SHALL DELIVER A SET OF "AS- BUILT" DRAWINGS TO THE OWNER IN REPRODUCIBLE MATERIAL. CONTRACTOR SHALL STAMP "AS- BUILT" ON THE PLANS, (EACH SHEET), AND PRINT, DATE AND SIGN IN INK. 20. CONVENIENCE RECEPTACLE LIGHTING SWITCHES AND WIRING DEVICES SHALL BE ENGRAVED INDICATING PANEL AND CIRCUIT NUMBERS. 21. SEPARATE PERMIT APPLICATION ARE REQUIRED FOR FIRE ALARM. BURGLAR ALARM, TELEPHONE, TV, CCTV, COMPUTER WIRING AND ANY OTHER LOW VOLTAGE SYSTEM. COPY OF CONTRACT MUST BE SUBMITTED WITH EACH APPLICATION. 22. FIRE ALARM SHOP DRAWING AND PERMIT SHALL BE PROVIDED BY THE CONTRACTOR CONDUIT AND BOXES COLOR CODE CHART ORANGE - CRITICAL BRANCH YELLOW - LIFE SAFETY BRANCH GREEN - EQUIPMENT BRANCH RED - FIRE ALARM NOTE: WIRING AND GROUNDING IN ALL PATIENT CARE AREAS SHALL BE INSTALLED IN COMPLIANCE WITH NEC ARTICLE 517.13 SYSTEMS COORDINATION SCHEDULE FIRE ALARM TELEPHONE /DATA NURSE CALL BUILDING AUTOMATION SYSTEMS / CONTROLS ACCESS CONTROL SECURITY CAMERAS P.A. SYSTEM EQUIPMENT NOTE: WIRING 1. SYMBOLS IN DASHED LINE INDICATE EXISTING ABBREVIATIONSISUFFIXES DEVICES. NOTES 2. ALL SYMBOLS MAY NOT BE USED IN THIS PROJECT. A.F.F. ABOVE FINISHED FLOOR A.F.G. ABOVE FINISHED GRADE AWG AMERICAN WIRE GAUGE BD. BOARD C. CONDUIT CAB. CABINET C.B. CIRCUIT BREAKER CKT. CIRCUIT CCTV CLOSED CIRCUIT TELEVISION CO -THW COPPER WIRE WITH THERMOPLASTIC, HEAT RESISTANT, DIV 16 MOISTURE RESISTANT CHARACTERISTICS E.A. EMPTY CONDUIT E.W.C. ELECTRIC WATER COOLER E EXISTING TO REMAIN ER EXISTING TO BE RELOCATED OR REMOVED EMT ELECTRICAL METALLIC TUBING F.A. FIRE ALARM G.F.I. GROUND FAULT INTERRUPTER GND. GROUND HID HIGH INTENSIVE DISCHARGE HPS HIGH PRESSURE SODIUM I.G. ISOLATED GROUND LT. LIGHT LTG. LIGHTING MCB MAIN CIRCUIT BREAKER MLO MAIN LUGS ONLY MT. MOUNT MTG. HT. MOUNTING HEIGHT N.E.C. NATIONAL ELECTRICAL CODE N.I.C. NOT IN CONTRACT NL NIGHT LIGHT NFPA NATIONAL FIRE PROTECTION ASSOCIATION NEMA NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION. LFMC LIQUID TIGHT FLEXIBLE METAL CONDUIT P.A. PUBLIC ADDRESS PNL. PANEL PTZ PAN - TILT -ZOOM CAMERA RECEPT. RECEPTACLE RMC RIGID METAL CONDUIT S.D.B.C. SOFT DRAWN BARE COPPER SW. SWITCH TVSS TRANSIENT VOLTAGE SURGE SUPPRESSION PANEL U.O.N. UNLESS OTHERWISE NOTED V.P. VAPOR PROOF VOC VOLATILE ORGANIC COMPOUND WAP WIRELESS ACCESS POINT W.G. WIRE GUARD. W.P. WEATHER PROOF (NEMA 3R ENCLOSURE) X.P. EXPLOSION PROOF (CLASS TO MEET N.E.C.) LIGHTING FIXTURES O LIGHTING FIXTURE IDENTIFICATION. SEE SCHEDULE Q HID OR FLUORESCENT DOWN LIGHT Q ACCENT TYPE LIGHT FIXTURE a HID OR FLUORESCENT WALL MOUNTED LIGHT FIXTURE O-J= RECESSED / LAY -IN MOUNTED FLUORESCENT LIGHT FIXTURE SURFACE OR PENDANT MOUNTED FLUORESCENT LIGHT FIXTURE WALL MOUNTED FLUORESCENT LIGHT FIXTURE I--e{ SURFACE OR PENDANT MOUNTED FLUORESCENT STRIP HID DOWN LIGHT CIRCUIT & EQUIPPED WITH RESTRIKE SYSTEM HID WALL MOUNTED LIGHT FIXTURE LIGHT CIRCUIT RECESSED /FLUORESCENT LIGHT FIXTURE ON EMERGENCY WITH BATTERY PACK. SURFACE MOUNTED FLUORESCENT LIGHT FIXTURE ON EMERGENCY WITH ® BATTERY PACK. RECESSED / LAY -IN MOUNTED FLUORESCENT LIGHT FIXTURE ON EMERGENCY LIFE SAFETY CIRCUIT. RECESSED MOUNTED /FLUORESCENT LIGHT FIXTURE ON EMERGENCY WITH BATTERY PACK. e EXIT LIGHT WALL MOUNTED EXIT LIGHT SHADED QUADRANT INDICATES NUMBER OF FACES. .- ARROWS AS SHOWN OR REQUIRED. UNIT EQUIPMENT BATTERY BACKUP EMERGENCY LIGHT COMBINATION EXIT / EMERGENCY LIGHT WITH BATTERY BACKUP. LANDSCAPE LIGHT FIXTURE o-❑ POLE MOUNTED SINGLE SITE LIGHTING FIXTURE [}o-Q POLE MOUNTED DOUBLE SITE LIGHTING FIXTURE C) CEILING MOUNTED OCCUPANCY SENSOR. INCLUDE POWER PACK AS REQUIRED. PP OCCUPANCY SENSOR POWER PACK. ® LTG. TRANSFER RELAY. S SINGLE POLE SWITCH - 20 AMP (48" A.F.F.) S3 THREE WAY SWITCH - 20 AMP (48" A.F.F.) S4 FOUR WAY SWITCH - 20 AMP (48" A.F.F.) SD DIMMER SWITCH 2000 WATTS 48" A.F.F.) S� FAN SPEED CONTROL (48" A.F.F.) SK KEY OPERATED SWITCH - 20 AMP (48" A.F.F.) SR SINGLE POLE SWITCH WITH PILOT LIGHT - 20 AMP(48" A.F.F.) Sm MOTOR RATED SWITCH (ONE, TWO OR THRI'E POLE AS REQUIRED) ST TIME CONTROL SWITCH SOS OCCUPANCY SENSOR SINGLE POLE SWITCH - 20 AMP. (42" AFF). Sos2 OCCUPANCY SENSOR 2 RELAY DUAL TECH SWITCH - 20 AMP. (42" AFF). SoR OVERRIDE SWITCH - 20 AMP. (42" AFF). FIRE ALARM DEVICES E] FIRE ALARM PULL STATION (48" A.F.F.) SEMI FLUSH MOUNTED, PROVIDE BREAKABLE GLASS COVER. 04 FIRE ALARM BELL WITH STROBE LIGHT (80 "A.F.F.) ADA 04 FIRE ALARM SPEAKER WITH STROBE LIGHT (80 "A.F.F.) ADA ss FIRE ALARM SPEAKER WITH STROBE LIGHT. CEILING MOUNTED pS FIRE ALARM MASS NOTIFICATION SPEAKER. CEILING MOUNTED FIRE ALARM STROBE LIGHT - 75 CANDELA MIN. - (80 " A.F.F.) OR 6" BELOW CEILING WHISHEVER IS LOWER, INSTALLATION SHALL COMPLY WITH A.D.A., FIRE ALARM STROBE LIGHT. CEILING MOUNTED sD 24V SMOKE DETECTOR (PHOTOELECTRIC TYPE). sD H SMOKE AND HEAT DETECTOR Q 24V FIXED TEMPERATURE 135' F THERMAL DETECTOR. DD 24V PHOTOELECTRIC DUCT DETECTOR. © FIRE ALARM TELEPHONE JACK DH FIRE ALARM DOOR HOLDER FS FIRE ALARM FLOW SWITCH TS FIRE ALARM TAMPER SWITCH FACP FIRE ALARM CONTROL PANEL POWER EQUIPMENT ® HIGH VOLTAGE DISTRIBUTION PANELBOARD 277/480V ® LOW VOLTAGE DISTRIBUTION PANELBOARD 120/208V HIGH VOLTAGE PANELBOARD 277/48OV. ® LOW VOLTAGE PANELBOARD 120 /208V. L❑ HD FUSIBLE DISCONNECT OR CIRCUIT BREAKER. NEMA 3R WHEN OUTDOORS. 3 0 3 =N0. OF POLES, 60 = SWITCH SIZE, 50 =FUSE, NF= NON - FUSED, " =FUSE SIZE AS REQUIRED BY LOAD. MOTOR STARTER W /CONTROL XMFR, HOA SELECTOR SW. AND RED PILOT LIGHT. NEMA SIZE BY MOTOR. PROVIDE NEMA 4 ENCLOSURE WHEN OUTDOORS COMBINATION MOTOR STARTER WITH DISCONNECT SWITCH OR CB. SAME Lu ENCLOSURE AND ACCESSORIES AS INDICATED ABOVE CONTACTOR. SAME ENCLOSURE AND ACCESSORIES AS STARTERS FAN 2� MOTOR "2" WHEN SHOWN INDICATES HORSEPOWER nT TRANSFORMER POWER DEVICES (ALL RECEPTACLES SHALL BE GROUNDING TYPE HOSPITAL GRADE TYPE) `� DUPLEX RECEPT - 20 AMP NEMA 5 -20R (18" A.F.F.) ej SINGLE RECEPT - 20 AMP NEMA 5 -20R (18" A.F.F.) DUPLEX RECEPT. MOUNTED ABOVE COUNTER - 20 AMP NEMA 5 -20R (44" A.F.F.) U.O.N. Q� POWER RECEPT. TWIST LOCK - 20 AMP NEMA 5 -20R (18" A.F.F.) QUAD - PLEX RECEPT - 20 AMP NEMA 5 -20R (18" A.F.F.) ® DUPLEX RECEPT FLUSH FLOOR MOUNTED - 20 AMP NEMA 5 -20R ® DUPLEX RECEPT FLUSH CEILING MOUNTED - 20 AMP NEMA 5 -20R SPECIAL PURPOSE RECEPT (18" A.F.F.) A, B, C A - 250V, 30A, 4W B - 250V, 50A, 4W. C - 25OV, 50A, 5W. O JUNCTION BOX a WALL MOUNTED JUNCTION BOX FLOOR MOUNTED JUNCTION BOX UNDER RAISED FLOOR FOR CONNECTION TO WIREMOLD PLUG STRIP MOUNTED AT RACKS AND FURNITURE BY A HARDWIRE FLEXIBLE CONNECTION BY ELECTRICAL CONTRACTOR. PE PULL BOX BRANCH CIRCUIT OR FEEDER WIRING IN CONDUIT. NO TICKS INDICATES 2# 12 CONDUCTORS & 1# 12 GROUND IN 3/4" CONDUIT. TICK MARKS WHEN SHOWN, INDICATES NUMBER OF #12 CONDUCTORS IF OTHER THAN THREE, (1) INDICATES GROUND. CONDUIT LARGER THAN 3/4" & CONDUCTOR LARGER THAN #12 SHALL BE AS INDICATED. HOME RUN TO PANEL "A " = PANEL DESIGNATION, 1,3,5 = CIRCUIT NUMBERS. U.O.N. MINIMUM SIZE OF 3/4 "C AND MAXIMUM OF THREE CIRCUITS PER �A-13,5 HOMERUN. (DEDICATED NEUTRAL FOR EACH HOT WIRES MUST BE PROVIDED) FLEXIBLE CONDUIT CONDUIT RUN CONCEALED IN CEILING OR WALLS -U /G- CONDUIT RUN UNDERGROUND OR IN SLAB --- - - - --- CONDUIT RUN EXPOSED [ CAPPED CONDUIT - -�-I- - + -- SYSTEM AND /OR EQUIPMENT GROUNDING CONDUCTOR ,�C ---- GROUNDING ELECTRODE AND CONDUCTOR SYSTEM CONDUIT SEAL CABLE TRAY DATA, COMMUNICATIONS AND SECURITY V TELEPHONE & DATA OUTLET (4 "x 4 "x 2 1/2" OUTLET BOX) (18" A.F.F.) ® TELEPHONE & DATA OUTLET FLUSH FLOOR MOUNTED 0 DATA OUTLET (4 "x 4 "x 2 1/2" OUTLET BOX) (18" A.F.F.) m TELEPHONE OUTLET FLUSH FLOOR MOUNTED . TELEPHONE OUTLET (4 "x 4 "x 2 1/2" OUTLET BOX)(18" A.F.F.) Vw WALL MOUNTED TELEPHONE OUTLET (60 "A.F.F.) © CLOCK (8' -0" AFF) D TERMINAL CABINET - TYPE INDICATED TELEPHONE TERMINAL BACK BOARD Q CLOSE CIRCUIT TV MONITORS CCr� CCTV CAMERA 0 RADIO REMOTE sR PAGER SPEAKER FB PHYSIOLOGICAL MONITOR OUTLET FEJ ROOM RESERVATION SYSTEM. POWERED OVER ETHERNET. is w INTERCOM STATION (WALL MTD) -3GANG BOX @ 4' -0" C p INTERCOM (DOOR STATION) SAME AS WALL MTD c INTERCOM @ 4 " -0" A.F.F. cT CATV STATIONS @ 2' -6" A.F.F. (U.N.O.) F0 WALL MOUNTED TV OUTLET. 0 SECURITY PUSH BUTTON Eb SECURITY DOOR BELL CHIME KP SECURITY SYSTEM KEYPAD RR SECURITY SYSTEM CARD READER SECURITY SYSTEM UHF CARD READER ©D SECURITY SYSTEM MOTION DETECTOR DS SECURITY SYSTEM DOOR STRIKE (c SECURITY SYSTEM DOOR CONTACT ML SECURITY SYSTEM MAGNETIC LOCK PS POWER SUPPLY =EF0 EMERGENCY OFF BUTTON 48 "A.F.F. EH PUSH PLATE (48" A.F.F.) NURSE CALL NCMS NURSE CALL MASTER STATION FJ$ NURSE CALL STAFF STATION 48" AFF �/q NURSE CALL DUTY STATION 48" AFF 10 NURSE CALL TOILET EMERGENCY STATION 48" AFF T NURSE CALL CODE BLUE STATION 48" AFF FB T 91�1 NURSE CALL DOME LIGHT, CEILING MOUNTED PROJECT SPECIFICATION 1. SITE INVESTIGATION: PRIOR TO BIDDING THE CONTRACTOR SHALL VISIT THE JOBSITE AND BECOME ACQUAINTED WITH ALL OF THE EXISTING CONDITIONS WHICH WILL AFFECT HIS WORK. FAILURE TO DO SO WILL NOT BE ACCEPTED AS A REASON FOR REQUESTING EXTRA PAY WHERE THE EXISTING CONDITION RESULTS IN EXTRA MATERIAL OR LABOR. THE CONTRACTOR SHALL SUBMIT IN HIS BID AN AMOUNT THAT WOULD BE SET ASIDE FOR UNIDENTIFIED ITEMS. 2. THE CONTRACTOR SHALL FURNISH ALL LABOR, MATERIALS AND EQUIPMENT NECESSARY FOR THE COMPLETE INSTALLATION OF THE ELECTRICAL SYSTEMS, ALL IN ACCORDANCE WITH THESE CONSTRUCTION DOCUMENTS. ALL WORK PERFORMED UNDER THIS CONTRACT SHALL COMPLY WITH THE FLORIDA BUILDING CODE 2010 REVISIONS AND ALL THE STANDARDS OF CONSTRUCTION ESTABLISHED BY THE HOLY CROSS HOSPITAL INCLUDING, BUT NOT LIMITED TO THE FOLLOWING PUBLICATIONS: A) CHAPTER 59A -3 FLORIDA ADMINISTRATIVE CODE 2002, B) NFPA 70 -2008, NFPA 72 -2002, NFPA 99 -2005, NFPA 110 -2005, NFPA 101 -2006, AND C) AIA 2006 AND D) OSHA. 3. MINIMUM STANDARDS: THE MATERIAL, EQUIPMENT, INSTALLATIONS, AND WORKMANSHIP FURNISHED UNDER THIS SECTION SHALL CONFORM AT LEAST TO THE REQUIREMENTS OF THE REGULATING AGENCIES AS LISTED IN ITEM (2) ABOVE. ALL MATERIALS AND EQUIPMENT USED SHALL BE LISTED OR BEAR THE U.L. APPROVAL FOR THEIR INTENDED USE, 4. RESPONSIBILITIES: CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING A COMPLETE INSTALLATION OF THE RACEWAY SYSTEM, EQUIPMENT AND WIRING IN ACCORDANCE WITH THE CONTRACT DOCUMENTS. 5. GUARANTEE: THE CONTRACTOR /SUB - CONTRACTOR SHALL FURNISH A WRITTEN GUARANTEE THAT ALL WORK EXECUTED UNDER THIS CONTRACT SHALL BE FREE FROM DEFECTS OF WORKMANSHIP AND MATERIALS FOR A PERIOD OF ONE YEAR FROM THE DATE OF FINAL ACCEPTANCE AND THAT HE WILL AT HIS OWN EXPENSE, REPAIR OR REPLACE ALL WORK WHICH BECOMES DEFECTIVE DURING THE TIME OF THE GUARANTEE. 6. ALL EQUIPMENT, SYSTEM AND SYSTEM COMPONENTS SHALL BE FROM THE SAME MANUFACTURER AND SHALL BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS AND SPECIFICATIONS. 7. RACEWAYS AND FITTINGS: CONDUIT RUNS SHALL BE CONCEALED IN CEILING SPACES, AND WALL PARTITIONS; NO RACEWAY SHALL BE EXPOSED IN INTERIOR SPACES SUCH AS RESIDENT ROOMS. CONCEALED CONDUITS MAY BE EMT. THE MINIMUM CONDUIT SIZE IS TO BE 3/4" FOR HOME RUN. ALL CONDUITS AND RACEWAYS SHALL BE METAL. 8. CONDUCTOR: ALL CONDUCTOR WIRE AND CABLE SHALL CONSIST OF 98 % CONDUCTIVITY COPPER. ALL CABLES SHALL BE SINGLE CONDUCTOR, 600 VOLT, THERMOPLASTIC INSULATION. SUITABLE FOR CONTINUOUS OPERATION AT 75 DEGREES C. CONDUCTOR TEMPERATURE IN BOTH WET AND DRY LOCATIONS. THESE CABLES SHALL BE N.E.C. INSULATION CLASSIFICATION TYPE THWN/THHN. MINIMUM SIZE SHALL BE #12. ALL CONDUCTOR INSTALLATION SHALL BE COLOR CODED MAINTAINING THE INTEGRITY OF THE EXISTING INSTALLATION. COLORED INSULATION SHALL BE USED FOR AWG SIZES #10 AND SMALLER AND APPROVED COLOR TAPES SHALL BE USED FOR AWG SIZES #8 AND LARGER ALL POWER AND CONTROL CIRCUITS SHALL CARRY EQUIPMENT GROUNDING CONDUCTOR SIZED PER NEC 250 -95. 9. THE NATURE OF THIS TYPE OF CONSTRUCTION POSES SPECIAL PROBLEMS FOR THE DESIGN ENGINEERS AS WELL AS THE CONTRACTOR. EVERY EFFORT HAS BEEN MADE BY THE ENGINEERS TO SHOW AND VERIFY WHERE POSSIBLE. THE LOCATION OF THE EXISTING ELECTRICAL SYSTEMS. THE MAJOR PORTION OF THE ELECTRICAL SYSTEMS ARE AS SHOWN ON THE DRAWINGS. HOWEVER MINOR DEVIATIONS MAY BECOME EVIDENT AS THE JOB PROGRESSES. NO ADVANTAGE IS TO BE TAKEN BY THE CONTRACTOR BECAUSE THESE MINOR DIFFERENCES. 10. ALL FLOORS, WALLS, AND ROOF PENETRATIONS SHALL BE PROPERLY SEALED -OFF. IF FIRE RATED, AN APPROVED FIRE RETARDANT SEALANT SHALL BE USED. 11. THESE DRAWINGS ARE A GUIDE FOR THE INSTALLATION OF THE RACEWAY SYSTEM AND EQUIPMENT. THEY ARE INTENDED TO SHOW THE GENERAL ARRANGEMENT, DESIGN AND EXTENT OF THE WORK AND PARTLY DIAGRAMMATIC. THE CONTRACTOR IS RESPONSIBLE TO PROVIDE A COMPLETE AND FUNCTIONAL INSTALLATION. 12, ANY DEVIATIONS FROM THESE DRAWINGS AND SPECIFICATIONS MUST BE AUTHORIZED IN WRITING FROM THE ENGINEERS OFFICE. THE CONTRACTOR SHOULD BE HELD LIABLE FOR ANY DEVIATIONS WITHOUT SUCH AUTHORIZATION. SYSTEMS 13, ANY WORK NOT SHOWN OR SPECIFICALLY MENTIONED ON THESE PLANS AND /OR SPECIFICATIONS BUT CONSIDERED NECESSARY FOR COMPLETION OF THE WORK IN THE PROPER MANNER SHALL BE PROVIDED BY THE CONTRACTOR WITHOUT ADDITIONAL CHARGE. 14. CONTRACTOR SHALL VERIFY SPACE CONDITIONS AND DIMENSIONS AT JOB SITE PRIOR TO FABRICATION AND INSTALLATION OF MATERIALS AND EQUIPMENT. ELECTRICAL CONTRACTOR TO COORDINATE HIS WORK WITH THE ARCHITECT BEFORE ROUGH INSTALLATION OF ALL OUTLETS, (LIGHTS, RECEPTACLES, SWITCHES, PULL BOXES, ETC.) FOR EXACT LOCATION. 15. ALL ELECTRICAL EQUIPMENT SUCH AS PANELS, PULL /J- BOXES, FEEDERS, BREAKERS, ETC, SHALL BE PROPERLY IDENTIFIED WITH A PERMANENT LABEL AFFIXED TO THE EQUIPMENT. IDENTIFY BREAKERS IN PANELS BY MEANS OF A TYPED, PLASTIC COVERED DIRECTORY. CONTRACTOR SHALL PROVIDE UPDATED PANEL DIRECTORIES. 16. ALL SERVICE INTERRUPTIONS AND ALL REMOVAL AND DISPOSAL WORK SHALL BE SCHEDULED AND COORDINATED WITH THE AUTHORIZED REPRESENTATIVE OF THE OWNER. 17. CONTRACTOR SHALL SECURE AND PAY FOR ALL PERMITS, FEES, TAXES, INSPECTIONS, TESTS AND OTHER ITEMS AS REQUIRED FOR THE WORK AS OUTLINED IN THE PLANS. PROVIDE ALL THE REQUIRED INSURANCE FOR PROTECTION AGAINST PUBLIC LIABILITY AND PROPERTY DAMAGE FOR THE DURATION OF THE WORK. 18. UPON COMPLETION OF THE INSTALLATION, CONTRACTOR SHALL CONDUCT A COMPLETE EQUIPOTENTIAL TEST AS DEFINED IN N.F.P.A. -99 (2009). SUBMIT THE RESULTS OF THE TEST TO THE OWNER AND THE A /E. THE CONTRACTOR SHALL HAVE A TEST EQUIPMENT AVAILABLE FOR SPOT CHECKING AT FINAL CONSTRUCTION SURVEY. 19. CONTRACTOR SHALL MAINTAIN A COMPLETE SET OF PRINTS FOR INDICATING ALL CHANGES AS THE CONSTRUCTION PROGRESSES. AT THE COMPLETION OF THE WORK, THE CONTRACTOR SHALL DELIVER A SET OF "AS- BUILT" DRAWINGS TO THE OWNER IN REPRODUCIBLE MATERIAL. CONTRACTOR SHALL STAMP "AS- BUILT" ON THE PLANS, (EACH SHEET), AND PRINT, DATE AND SIGN IN INK. 20. CONVENIENCE RECEPTACLE LIGHTING SWITCHES AND WIRING DEVICES SHALL BE ENGRAVED INDICATING PANEL AND CIRCUIT NUMBERS. 21. SEPARATE PERMIT APPLICATION ARE REQUIRED FOR FIRE ALARM. BURGLAR ALARM, TELEPHONE, TV, CCTV, COMPUTER WIRING AND ANY OTHER LOW VOLTAGE SYSTEM. COPY OF CONTRACT MUST BE SUBMITTED WITH EACH APPLICATION. 22. FIRE ALARM SHOP DRAWING AND PERMIT SHALL BE PROVIDED BY THE CONTRACTOR CONDUIT AND BOXES COLOR CODE CHART ORANGE - CRITICAL BRANCH YELLOW - LIFE SAFETY BRANCH GREEN - EQUIPMENT BRANCH RED - FIRE ALARM NOTE: WIRING AND GROUNDING IN ALL PATIENT CARE AREAS SHALL BE INSTALLED IN COMPLIANCE WITH NEC ARTICLE 517.13 SYSTEMS COORDINATION SCHEDULE FIRE ALARM TELEPHONE /DATA NURSE CALL BUILDING AUTOMATION SYSTEMS / CONTROLS ACCESS CONTROL SECURITY CAMERAS P.A. SYSTEM EQUIPMENT EQUIPMENT WIRING WIRING EXTENT OF NOTES FURNISHED INSTALLED FURNISHED INSTALLED CONDUIT DIV 16 DIV 16 DIV 16 DIV 16 DIV 16 THROUGHOUT NOTE 1 VENDOR VENDOR VENDOR VENDOR NOTE5 NOTE DIV 16 DIV 16 DIV 16 DIV 16 NOTE 5 NOTE 3 DIV 15 DIV 15 DIV 15 DIV 15 NOTE 5 NOTE 4 DIV 16 DIV 16 DIV 16 DIV 16 NOTE 5 NOTE 2 VENDOR VENDOR VENDOR VENDOR NOTE NOTE2 DIV 16 DIV 16 DIV 16 DIV 16 NOTE 5 NOTE 2 NOTE 1: COORDINATE EXACT REQUIREMENTS WITH SIMPLEX GRINNEL NOTE 2: VENDOR CONTRACTED DIRECTLY BY OWNER. NOTE 3: COORDINATE EQUIPMENT & WIRING TYPE, SPECIFICATIONS AND WORK WITH DUKANE. NOTE 4: COORDINATE EXACT REQUIREMENTS WITH CONTROL CONTRACTOR, NOTE 5: STUB -UP TO ABOVE ACCESSIBLE CEILING SPACE IN CORRIDOR. TERMINATE WITH PLASTIC BUSHING. DIV 15 - DIVISION 15 CONTRACTOR DIV 16 - DIVISION 16 CONTRACTOR COORDINATION DRAWINGS 1. THE CONTRACTOR SHALL SUBMIT COORDINATION DRAWINGS TO ARCH. /ENG AND OWNER'S PROJECT MANAGER FOR APPROVAL PRIOR TO ANY FABRICATION AND INSTALLATION. 2. CONTRACTOR SHALL COORDINATE THE LOCATION OF ALL NEW PIPING, DUCTWORK, CONDUITS, ECT. WITH ARCHITECTURAL, STRUCTURAL, MECHANICAL AND ELECTRICAL SYSTEMS OF THE BUILDING, VERIFY ALL SPACE CONDITIONS AND DIMENSIONS AT JOBSITE PRIOR TO FABRICATION AND INSTALLATION OF EQUIPMENT AND MATERIALS. ANY CONFLICTS SHALL BE REPORTED IMMEDIATELY TO THE ARCHITECT /ENGINEER PRIOR TO BEGINNING OF CONSTRUCTION. COORDINATION NOTE AS PART OF THIS CONTRACT, THE SUB - CONTRACTOR AND THE CONTRACTOR ARE RESPONSIBLE FOR COORDINATION AND VERIFICATION THAT ALL EQUIPMENT, SHOWN IN THE ARCHITECTURAL DRAWINGS PARTICULARLY, BUT NOT LIMITED TO THE ARCHITECTURAL EQUIPMENT PLAN, INCLUDE ALL SERVICE /UTILITY REQUIRED TO OPERATE THE EQUIPMENT SHOWN. ANY DISCREPANCIES ARE TO BE POINTED OUT DURING THE BIDDING PROCESS. DISCREPANCIES NOT POINTED OUT DURING THE BIDDING PROCESS WILL BE RESOLVED BY THE CONTRACTOR AS PER THE ARCHITECT DETAILS AT NO ADDITIONAL COST TO THE OWNER. WIRING DEVICE NOTE ALL NEW WIRING DEVICES AND ASSOCIATED DEVICE PLATES ON NORMAL POWER SHALL MATCH COLOR OF EXISTING NORMAL POWER WIRING DEVICES THROUGHOUT THE BUILDING. REFER TO SPECIFICATIONS FOR FURTHER REQUIREMENTS. 0000 000 • r rrr!• rrr -rrr c • • r 1 PROJ, No. 24004 r C 92` Gvr �r J r � „•... .. LOUIS J. AGUIRRU & ASSOCIATFS P.AV CONSULTINC EI'ICINCERS t v r y 9150 SOUTH DADEI'AND BLVD. ' _ SUllFl00 MIAMI, FLORIDA 33156 TELEPHONE: 0065)- X70- @7`4lr: 4rrGGrrry FAX: r • � www.Ijoapa.001Y { rr• W r rrVUr r 4r•r . �orrT F PPLICABLE CODES / STANDARDS PE OF THE WORK SHALL INCLUDE THE FURNISHING AND TION OF THE NECESSARY MATERIAL AND LABOR TO ACCOMPLISH THE WORK INDICATED BY THE DRAWINGS AND HEREIN SPECIFIED. ALL WORK BY CONTRACTOR SHALL CONFORM TO ALL APPLICABLE FEDERAL, STATE AND LOCAL BUILDING CODES AND STANDARDS INCLUDING BUT NOT LIMITED TO: 1. STATE OF FLORIDA 2. LIFE SAFETY CODE - NFPA 101 (2006) 3. UNDERWRITERS LABORATORIES, INC. PUBLICATIONS (UL) 4. NATIONAL FIRE PROTECTION ASSOCIATION. (NFPA) 5. AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI) 6. NATIONAL ELECTRICAL CODE - NFPA 70 (2008) 7. INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE) S. NATIONAL ELECTRICAL MANUFACTURER'S ASSOCIATION (NEMA) 9. INTERNATIONAL POWER CABLE ENGINEER'S ASSOCIATION (IPCEA) 10. NATIONAL ELECTRICAL SAFETY CODE 11. REQUIREMENTS OF LOCAL UTILITY COMPANY 12. NATIONAL FIRE PROTECTION ASSOCIATION 72 (2002) 13. NATIONAL FIRE PROTECTION ASSOCIATION 99 (2005) 14. THE STATE FIRE PREVENTION CODE, 4A60 (2001) 15. BUILDING CODE: FLORIDA BUILDING CODE (2010) 16. AIA GUIDELINES (2006) 17. NFPA 110 (2005) INFECTION CONTROL NOTE CONTRACTOR SHALL OBTAIN A COPY OF THE INFECTION CONTROL RISK ASSESMENT FOR THIS PROJECT. ALL WORK SHALL BE IN COMPLIANCE WITH THE REPORT. ALL WORK OUTSIDE THE SCOPE OF WORK AREA REQUIRED FOR THIS PROJECT, SHALL BE COORDINATED WITH OWNER AND BE IN COMPLIANCE WITH THE ICRA REPORT AND BE SUPERVISED BY THE OWNER'S REPRESENTATIVE. BID NOTE THE DRAWINGS DO NOT INDICATE EXISTING INSTALLATIONS OTHER THAN TO IDENTIFY MODIFICATIONS OR EXTENSIONS THERETO. VISIT THE SITE AND ASCERTAIN THE EXISTING CONDITIONS. REVIEW CONSTRUCTION DETAILS OF THE EXISTING PORTION OF THE BUILDING DURING THE SITE INSPECTION. INCLUDE ALL WORK REQUIRED TO REMOVE OR MODIFY PORTIONS OF THE EXISTING INSTALLATION IN ORDER TO ACCOMMODATE THE NEW WORK . FAILURE TO COMPLY WITH THIS WILL NOT BE CONSIDERED GROUNDS FOR ADDITIONAL PAYMENT IN CONNECTION WITH REMOVING OR MODIFYING ANY PART OF THE EXISTING INSTALLATION OR INSTALLING ANY NEW OR TEMPORARY WORK. Revisions: 0 N 9 O \O V '^ wa x Pte' n N W W LL. U O O� �..� N one O go < V) v r.. C� RS o 1n 1 Q1 u J 16o i Lg ■ A LLj Z0 W Z U V j ,a W 00 W W �V c/1 CONSTRUCTION DOCUMENTS fDKkAWNDRAWN: CHECKEI> AP PA DATE: 03-12-14 SCALE: AS SHOWN .l *ri t-�ECTRI�CAL: r Lc Uls pE` LICENSP 11642 Sheet No. E0.00 JOI3 f 201335 i