14-375-035System No. C -AJ -1226
F Rating — 3 Hr
T Rating — 0 Hr
L Rating At Ambient — Less Than 1 CFM /Sq Ft
L Rating At 400 F — 4 CFM /Sq Ft
A
A SECTION A -A
1. Floor or Wall Assembly -- Min 4 -1/2 in. thick reinforced lightweight or normal weight (100 -150 pcf) concrete.
Wall may also be constructed of any UL Classified Concrete Blocks *. Max diam of opening is 32 in.
2. Metallic Sleeve ---- (Optional) Nom 32 in. diam (or smaller) Schedule 40 (or heavier) steel sleeve cast or
grouted into floor or wall assembly, flush with floor or wall surfaces or extending a max of 3 in. above floor or
beyond both surfaces of wall.
2A. Sheet Metal Sleeve — (Optional) Max 6 in. diam, min 26 ga galy steel provided with a 26 ga galy steel
square flange spot welded to the sleeve at approx mid- height, or flush with bottom of sleeve in floors, and sized
to be a min of 2 in. larger than the sleeve diam. The sleeve is to be cast in place and may extend a max of 4 in.
below the bottom of the deck and a max of 1 in. above the top surface of the concrete floor.
2B. Sheet Metal Sleeve — (Optional) - Max 12 in. diam, min 24 ga galy steel provided with a 24 ga galy steel
square flange spot welded to the sleeve at approx mid - height, or flush with bottom of sleeve in floors, and sized
to be a min of 2 in. larger than the sleeve diam. The sleeve is to be cast in place and may extend a max of 4 in.
below the bottom of the deck and a max of 1 in, above the top surface of the concrete floor.
3. Through- Penetrant — One metallic pipe, tube or conduit to be installed either concentrically or eccentrically
within the firestop system. The annular space between penetrant and periphery of opening shall be min 0 in.
(point contact) to max 1 -7 /8 in. Penetrant may be installed with continuous paint contact. Penetrant to be rigidly
supported on both sides of floor or wall assembly. The following types and sizes of metallic penetrants may be
used:
A. Steel Pipe — Nom 30 in. diam (or smaller) Schedule 10 (or heavier) steel pipe.
B. Iron Pipe — Nom 30 in. diam (or smaller) cast or ductile iron pipe.
C. Copper Pipe -- Nom 6 in. diam (or smaller) Regular (or heavier) copper pipe.
D. Copper Tubing — Nom 6 in. diam (or smaller) Type L (or heavier) copper tubing.
E. Conduit — Nom 6 in. diam (or smaller) steel conduit.
F. Conduit -- Nom 4 in. diam (or smaller) steel electrical metallic tubing (EMT).
4. Firestop System — The firestop system shall consist of the following:
A. Packing Material — Min 4 in. thickness of min 4 pcf mineral wool batt insulation firmly packed into opening
as a permanent form. Packing material to be recessed from top surface of floor or sleeve or from both
surfaces of wall or sleeve as required to accommodate the required thickness of fill material.
B. Fill, Void or Cavity Material* — Sealant -- Min 1/4 in. thickness of fill material applied within the annulus,
flush with top surface of floor or sleeve or with both surfaces of wall or sleeve. At the point or continuous
contact locations between penetrant and concrete or sleeve, a min 1/4 in, diam bead of fill material shall be
applied at the concrete or sleeve/ pipe penetrant interface on the top surface of floor and on both surfaces of
wall.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — FS -One Sealant
*Bearing the UL Classification Mark
�PSS I Fj<
Reproduced HILTI, Inc. Courtesy of v Q
Underwriteto rs Laboratories, Inc.
FIRESTOR SYSTEMS ,tune 27, 2007 C m L us
NEW 1" 90 DEG
90 DEG PIPE ELBOW
ELBOW
NEW 1" 90 DEG
PIPE ELBOW
NEW 1"
TEE
DROP NEW 1" RISER —�_
NIPPLE NIPPLE ® EXISTING
BRANCH LINE
EXISTING DROP
1" TAP NIPPLE
1" X 1/2" REDUCER FOR 1/2" SPRINKLER
" X 3/4" REDUCER FOR 3/4" SPRINKLER
NEW CEILING
CEILING COVER CEILING COVER
PLATE PLATE
ARMOVER DETAIL 2 -HEAD RELOCATE
N.T.S.
System No. W -L -1054
F Ratings -1 and 2 Hr (See Items 1 and 3)
T Rating - 0 Hr
L Rating At Ambient - Less Than 1 CFMISq Ft
L Rating At 400 F - 4 CFMISq Ft
SECTION A -A
1. Wall Assembly - The 1 or 2 hr fire -rated gypsum wallboard /stud wall assembly shall be constructed of
the materials and in the manner specified in the individual U300 or U400 Series Wall and Partition Designs
in the UL Fire Resistance Directory.
2. Through - Penetrants -- One metallic pipe, conduit or tubing to be installed either concentrically or
eccentrically within the firestop system. The annular space shall be min 0 in. to max 2 -114 in. Pipe may
be installed with continuous point contact. Pipe, conduit or tubing may be installed at an angle not greater
than 45 degrees from perpendicular. Pipe, conduit or tubing to be rigidly supported on both sides of wall
assembly. The following types and sizes of metallic pipes, conduits or tubing may be used:
A. Steel Pipe -- Nom 30 in diam (or smaller) Schedule 10 (or heavier) steel pipe.
B. Iron Pipe -- Nom 30 in. diam (or smaller) cast or ductile iron pipe.
C. Conduit -- Nom 4 in diam (or smaller) steel electrical metallic tubing or 6 in. diam steel conduit.
D. Copper Tubing -- Nom 6 in. diam (or smaller) Type L (or heavier) copper tubing.
E. Copper Pipe -- Nom 6 in, diam (or smaller) regular (or heavier) copper pipe.
3. Fill, Void or Cavity Material* -- Sealant -- Min 5/8 in. thickness of fill material applied within the
annulus, flush with both surfaces of wall. At the point or continuous contact locations between pipe and
wall, a min 1/2 in. diam bead of fill material shall be applied at the pipe wall interface on both surfaces
of will .
HILTI CONSTRUCTION CHEMICALS, DIV OF
HILTI INC -- FS -One Sealant
*Bearing the UL Classification Mark
17-1 G 0��0° Reproduced HILTI, Inc. Courtesy of
Underwriters Laboratories, Inc.
FIRESTOP SYSTEMS December 4, 2002
90 uE(
ELBOV
BRANCH
LINE
S I Fj�O
C U` US
— Mrs
2 FOR 1/2" SPRINKLER
7 FOR 3/4" SPRINKLER
PLATE
TYPICAL RETURN -BEND DETAIL
N.T.S.
HANGERS
A
FLAT IRON HANGER
FASTENERS
A
SELF DRILLING ANCHOR
•ii• •rte i • ••rrw ••EI
PROJ. No. 2400: • • �r�h, 92 i
LOUIS J. AGUIRRG & ASSOC?AT .,
CONW.TING ENGftEEII
9150 SOUTH DADELAND BLVD. SUITE 900
MIAMI, FLORIDA 33156
TELEPHONE: (�05 j X570 -Wi *: `• z • • y V •
FAX: (Z'O V 070 -0144
• Fu •
WWW.Ij.copa.cor'I- ••��• • �•• • -�•ti
A
_J��r
TOP BEAM CLAMP
MAXIMUM
DISTANCE
BETWEEN
HANGERS
(FT -IN.)
NOMINAL PIPE
SIZE (IN.)
3/4 1 11/4
11/2 2 21/2
3 31/2 4
5 6 8
ROD SIZE
N/A 3/8" 3/3"
3/8" 3/8" 1/2"
1/2" 1/2" 5/8"
5/8" 3/4" 7/8"
DISTANCE BETWEEN
N/A 12 -0 12 -0
15 -0 15 -0 15 -0
15 -0 15 -0 15 -0
15 -0 15 -0 15 -0
HANGERS - STEEL PIPE
NOTE: TABLE 9.2.2.1 (NFPA 13 2007 EDITION)
UPPEI
SHELL
CEILING —
CEILING
PLATE
SPRINKLER`S
SPRINKLER,
AN
a
DETAIL FOR FLUSH CONCEALED SPRINKLER
N.T.S.
�I
Revisions:
0
0
0
117*4 p
[ o or,
� W
IW
w
Q
x �
� s
Q
con
QQ�
N v�
w
F
O
Gh <1i> .
O 1A
4
Q V
164
Z
0
r~
V) U
�w
�F
F- 0
w�
A�
w
CONSTRUCTION
DOCUMENTS
DRAWN: J15
CHECKED: II
DATE- 03-12-14
SCALE: ,48 SHOWN
SEAL.r
t
A JAI
°r
r •,
E[�'I AeD'0 A . StJAREZ" P E
fiC NSE Y-6 759
Sheet No.
FP7.00
JOB # 201335
;M
1 4 .