14-375-032System No. C -AJ -1226
F Rating — 3 Hr
T Rating — 0 Hr
L Rating At Ambient --- Less Than 1 CFM /5q Ft
L Rating At 400 F — 4 CFM /5q Ft
A
�~ A SECTION A -A
1. Floor or Wall Assembly — Min 4 -1/2 in. thick reinforced lightweight or normal weight (100 -150 pcf) concrete.
Wall may also be constructed of any UL Classified Concrete Blocks*. Max diam of opening is 32 in.
2. Metallic Sleeve — (Optional) Nom 32 in. diam (or smaller) Schedule 40 (or heavier) steel sleeve cast or
grouted into floor or wall assembly, flush with floor or wall surfaces or extending a max of 3 in. above floor or
beyond both surfaces of wall.
2A. Sheet Metal Sleeve — (Optional) Max 6 in. diam, min 26 ga galy steel provided with a 26 ga galy steel
square flange spot welded to the sleeve at approx mid - height, or flush with bottom of sleeve in floors, and sized
to be a min of 2 in. larger than the sleeve diam. The sleeve is to be cast in place and may extend a max of 4 in.
below the bottom of the deck and a max of 1 in. above the top surface of the concrete floor.
2B. Sheet Metal Sleeve — (Optional) - Max 12 in. diam, min 24 ga galy steel provided with a 24 ga galy steel
square flange spot welded to the sleeve at approx mid - height, or flush with bottom of sleeve in floors, and sized
to be a min of 2 in, larger than the sleeve diam. The sleeve is to be cast in place and may extend a max of 4 in.
below the bottom of the deck and a max of 1 in. above the top surface of the concrete floor.
3. Through - Penetrant — One metallic pipe, tube or conduit to be installed either concentrically or eccentrically
within the firestop system: The annular space between penetrant and periphery of opening shall be min 0 in.
(point contact) to max 1 -7 /E in. Penetrant may be installed with continuous point contact. Penetrant to be rigidly
supported on both sides of floor or wall assembly. The following types and sizes of metallic penetrants may be
used:
A. Steel Pipe — Nom 30 in. diam (or smaller) Schedule 10 (or heavier) steel pipe.
B. Iron Pipe — Nom 30 in. diam (or smaller) cast or ductile iron pipe.
i
C. Copper Pipe —Nom 6 in. diam (or smaller) Regular (or heavier) coppe r pipe.
D. Copper Tubing — Nom 6 in. diam (or smaller) Type L (or heavier) copper tubing.
E. Conduit — Nom 6 in. diam (or smaller) steel conduit.
F. Conduit Nom 4 in. diam (or smaller) steel electrical metallic tubing (EMT).
4. Firestop System — The firestop system shall consist of the following:
A. Packing Material — Min 4 in. thickness of min 4 pcf mineral wool batt insulation firmly packed into opening
as a permanent form. Packing material to be recessed from top surface of floor or sleeve or from both
surfaces of wall or sleeve as required to accommodate the required thickness of fill material.
B. Fill, Void or Cavity Material* — Sealant — Min 1/4 in. thickness of fill material applied within the annulus,
flush with top surface of floor or sleeve or with both surfaces of wall or sleeve. At the point or continuous
contact locations between penetrant and concrete or sleeve, a min 1/4 in. diam bead of fill material shall be
applied at the concrete or sleeve/ pipe penetrant interface on the top surface of floor and on both surfaces of
wall.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — FS -One Sealant
*Bearing the UL Classification Mark
�p,S51 Fj�,
Reproduced HILTI, Inc. Courtesy of V O
Underwriters Laboratories, Inc.
FIRESTOP SYSTEMS .tune 27, 2007 C m L us
System No. W -L -1054
F Ratings -1 and 2 Hr (See Items 1 and 3)
T Rating - 0 Hr
L Rating At Ambient - Less Than 1 CFM /Sq Ft
L Rating At 400 F - 4 CFMISq Ft
SECTION A -A
1. Wall Assembly -- The 1 or 2 hr fire -rated gypsum wallboard/stud wall assembly shall be Constructed of
the materials and in the manner specified in the individual U300 or U400 Series Wall and Partition Designs
in the UL Fire Resistance Directory.
2. Through- Penetrants -- One metallic pipe, conduit or tubing to be installed either concentrically or
eccentrically within the firestop system. The annular space shall be min 0 in. to max 2 -114 in. Pipe may
be installed with continuous point contact. Pipe, conduit or tubing may be installed at an angle not greater
than 45 degrees from perpendicular. Pipe, conduit or tubing to be rigidly supported on both sides of wall
assembly. The following types and sizes of metallic pipes, conduits or tubing may be used:
A. Steel Pipe -- Nom 30 in diam (or smaller) Schedule 10 (or heavier) steel pipe.
B. Iron Pipe -- Nom 30 in. diam (or smaller) cast or ductile iron pipe.
C. Conduit -- Nom 4 in diam (or smaller) steel electrical metallic tubing or 6 in. diam steel conduit.
D. Copper Tu bin g -- Nom 6 in. diam ( or smalle r ) T yp e L ( a
r heavier ) co pp er tubing.
E. Copper Pipe -- Nom 6 in. diam (or smaller) regular (or heavier) copper pipe.
3. Fill, Void or Cavity Material* -- Sealant -- Min 5/8 in. thickness of fill material applied within the
cations between pipe and
annulus, flush with both surfaces of wall. At the point or continuous contact to p p
wall, a min 112 in. diam bead of fill material shall be applied at the pipe wall interface on both surfaces
of wall .
HILTI CONSTRUCTION CHEMICALS, DIV OF
HILTI INC -- FS -One Sealant
*Bearing 'n the UL Classification Mark
o Reproduced by HILTI, Inc. Courtesy of
Underwriters Laboratories, Inc.
FIRESTOP SYSTEMS December 4, 2002
S I Fj�a
V
C m � US
System No. C -AJ -5091
F Rating — 2 Hr
T Ratings — 0 and 1 Hr (See Items 2 and 4)
L Rating At Ambient — 4 CFM /Sq Ft
L Rating At 400 F — Less Than 1 CFM /Sq Ft
1. Floor or Wall Assembly — Min 4 -1/2 in. (114 mm) thick reinforced lightweight or normal weight (100 -150 pcf or
1600 -2400 kg /m3) concrete. Wall may also be constructed of any UL Classified Concrete Blocks *. Max diam of
opening is 29 in. (737 mm).
See Concrete Blocks (CAZT) category in the Fire Resistance directory for names of manufacturers.
2. Metallic Sleeve — (Optional) — Nom 30 in. (762 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe
sleeve cast or grouted into floor or wall assembly, flush with floor or wall surfaces or extending a max of 3 in.
(76 mm) above floor or beyond both surfaces of wall. If the steel sleeve extends beyond the top surface of the
floor or both surfaces of the wall, the T Rating of the firestop system is 0 hr.
2A. Sheet Metal Sleeve — (Optional) - Max 6 in. (152 mm) diam, min 26 ga galy steel provided with a 26 ga galy
steel square flange spot welded to the sleeve at approximately mid- height, or flush with bottom of sleeve in
floors, and sized to be a min of 2 in. (51 mm) larger than the sleeve diam. The sleeve is to be cast in place flush
with bottom surface of floor and may extend a max of 1 in. (25 mm) above the top surface of the floor.
2B. Sheet Metal Sleeve — (Optional) - Max 12 in. (305 mm) diam, min 24 ga galy steel provided with a 24 ga
gals steel square flange spot welded to the sleeve at approximately mid- height, or flush with bottom of sleeve
in floors, and sized to be a min of 2 in. (51 mm) larger than the sleeve diam. The sleeve is to be cast in place
flush with bottom surface of floor and may extend a max of 1 in. (25 mm) above the top surface of the floor.
3. Through Penetrants — One metallic pipe or tubing to be installed either concentrically or eccentrically within
the firestop system. Pipe or tubing to be rigidly supported on both sides of floor or wall assembly. The following
types and sizes of metallic pipes or tubing may be used:
A. Steel Pipe — Nom 12 in. (305 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe.
B. Iron Pipe — Nom 12 in. (305 mm) diam (or smaller) cast or ductile iron pipe.
C. Copper Pipe — Nom 6 in. (152 mm) diam (or smaller) Regular (or heavier) copper pipe.
D. Copper Tubing — Nom 6 in. (152 mm) diam (or smaller) Type L (or heavier) copper tubing.
' ri I heavy density min 3 5
pcf or 56
k /m3 lass fiber
1 mm thick hollow c Ilntl ca kg /ml) 9
4. Pipe Covering —Min 112 in. (13 mm) to max 2 in. (5 ) y y Y ( p
units jacketed on the outside with an all- service jacket. Longitudinal joints sealed with metal fasteners or factory- applied, self- sealing lap
tape. Transverse joints secured with metal fasteners or with butt tape supplied with the product. The annular space between the
insulated pipe and the edge of the periphery of the opening shall be min 1/2 in. (13 mm) to max 12 in. (305 mm). When thickness of pipe
covering is less than 2 in. (51 mm), the T Rating for the firestop system is 0 hr.
See Pipe Equipment Covering — Materials — (BRGU) category in the Building Materials Directory for names of manufacturers.
Any pipe covering material meeting the above specifications and bearing the UL Classification Marking with a Flame Spread Index
of 25 or less and a Smoke Developed Index of 50 or less may be used.
4A. Pipe Covering — (Not Shown) — As an alternate to Item 4, max 2 in. (51 mm) thick cylindrical calcium silicate (min 14 pcf or 224
kg /m') units sized to the outside diam of the pipe or tube may be used. Pipe insulation secured with stainless steel bands or min 1 i
AWG stainless steel wire spaced max 12 in. (305 mm) OC. The annular space shall be min 1/2 in. (13 mm) to max 12 in. (305 mm).
5. Firestop System — The firestop system shall consist of the following:
A. Packing Material — Min 4 in. (102 mm) thickness of min 4 pcf (64 kg /m3) mineral wool batt insulation firmly packed into opening as
a permanent form. Packing material to be recessed from top surface of floor or from both surfaces of wall as required to
accommodate the required thickness of fill material.
B. Fill, Void or Cavity Material* — Sealant — Min 1/2 in. (13 mm) thickness of fill material applied within the annulus, flush with top
surface of floor or with both surfaces of wall,
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — FS -One Sealant
*Bearing the UL Classification Mark
U`Tss /F /gyp
• Reproduced by HILTI, Inc. Courtesy of C U` us
Underwriters Laboratories, Inc. Classified by
FIRESTOP SYSTEMS July 1a, 2011 Underwriters Laboratories, Inc.
to UL 1479 and CAN /ULC -S115
f?ROJ.'Nt' 2494 • • 924
LOUIS J!' AGUIERE &' ASSO IATES P.A.
C=0NiULT14G_' ENGINEERS
9150 SOUTH !ADELA'ND BLVD. SUITE 900
MIAMI, FLORIDA 33156
TLL,ED� ONF: (305),Z70- M0 L �...
FAx: -••• (305�t70 -J144 • w
www.l iaallo'com-� •
System No. W -L -5029
ANSI/UL1479 (ASTM E814)
CAN /ULC S115
F Ratings —1, 2 and 3 Hr (See Items 1, 3 and 4)
F Ratings —1, 2 and 3 Hr (See Items 1, 3 and 4)
T Ratings — 0, 112, 1 and 1 -114 Hr (See Item 3)
FT Ratings — 0, 1/2, 1 and 1 -1/4 Hr (See Item 3)
L Rating At Ambient -4 CFM /Sq Ft
FH Ratings —1, 2 and 3 Hr (See Items 1, 2 and 4)
rL Rating At 400 F — Less Than 1 CFM /Sq Ft
FTH Ratings — 0, 112, 1 and 1 -1/4 Hr (See Item 3)
L Rating At Ambient — 4 CFM /Sq Ft
L Rating At 400 F — Less Than 1 CFM /Sq Ft
L'.a
SECTION A -A
1. Wall Assembly — The 1, 2 or 3 hr fire -rated gypsum board /stud wall assembly shall be constructed of the
materials and in the manner specified in the individual U300, U400, V400 or W400 Series Wall and Partition
Designs in the UL Fire Resistance Directory and shall include the following construction features:
A. Studs — Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of
nom 2 by 4 in. (51 by 102 mm) lumber spaced 16 in. (406 mm) OC. Steel studs to be min 2 -1/2 in. (64 mm)
wide for 1 and 2 hr F and FH rating and 3 -1/2 in. (89 mm) wide for 3 hr F and FH rating and spaced max 24
in. (610 mm) OC.
B. Gypsum Board* — Min 5/8 in. (16 mm) thick with square or tapered edges. The gypsum board type,
thickness, number of layers, fastener type and sheet orientation ation shall be as specified ecified in the individual Wall
and Partition Design. Max diam of opening is 18-5/8 in. (473 mm).
The hourly F and FH Ratings of the firestop system are equal to the hourly fire rating of the wall assembly in
which it is installed.
2. Through Penetrants — One metallic pipe or tubing to be installed within the firestop system. Pipe or tubing to
be rigidly supported on both sides of wall assembly. The following types and sizes of metallic pipes or tubing
may be used:
A. Steel Pipe — Nom 12 in. (305 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe.
B. Iron Pipe — Nom 12 in. (305 mm) diam (or smaller) cast or ductile iron pipe.
C. Copper Tubing — Nom 6 in. (152 mm) diam (or smaller) Type L (or heavier) copper tubing. When the
hourly F or FH Rating of the firestop system is 3 hr, the nom diam of copper tube shall not exceed 4 in. (102
mm).
D. Copper Pipe — Nom 6 in. (152 mm) diam (or smaller) Regular (or heavier) copper pipe. When the hourly F
or FH Rating of the firestop system is 3 hr, the nom diam of copper pipe shall not exceed 4 in. (102 mm).
3. Pipe Covering* — Nom 1, 1 -1/2 or 2 in. (25, 38 or 51 mm) thick hollow cylindrical heavy density (min 3.5 pcf or
56 kg /m3) glass fiber units jacketed on the outside with an all service jacket. Longitudinal joints sealed with
metal fasteners or factory- applied self- sealing lap tape. Transverse joints secured with metal fasteners or with
butt tape supplied with the product. For 1 and 2 hr F and FH Ratings, the annular space between insulated
penetrant and periphery of opening shall be min 0 in. (point contact) to max 1 -7 /E in. (4E mm). For 3 hr F and
FH Ratings, the annular space shall be min 0 in. (point contact) to max 1 -1/4 in. (32 mm).
See Pipe and Equipment Covering — Materials (BRGU) category in the Building Material Directory for the
names of manufacturers. Any pipe covering material meeting the above specifications and bearing the UL
Classification Marking with a Flame Spread Index of 25 or less and a Smoke Developed Index of 50 or less
may be used.
The hourly T, FT, FTH Ratings of the firestop system are 1/2 hr for 1 hr rated walls and 1 hr for 2 hr rated walls.
For 3 hr rated walls, the hourly T, FT and FTH Ratings when steel and iron pipes are used are 1 hr. For 3 hr
rated walls, the hourly T, FT and FTH Ratings when copper penetrants are used are 1 -1/4 hr for 2 in. (51 mm)
thick pipe covering and 0 hr for pipe covering thickness less than 2 in. (51 mm).
3A. Pipe Covering* — (Not Shown) — As an alternate to Item 3, max 2 in. (51 mm) thick cylindrical calcium
silicate (min 14 pcf) units sized to the outside diam of the pipe or tube may be used. Pipe insulation secured
with stainless steel bands or min 1E AWG stainless steel wire spaced max 12 in. (305 mm) OC. When the
alternate pipe covering is used, the T and FT Rating shall be as specified in item 3 above.
See Pipe and Equipment Covering — Materials (BRGU) category in the Building Materials Directory for names
Of manufacturers. Any pipe covering material meeting the above specifications and bearing the UL
Classification Marking with a Flame Spread Index of 25 or less and a Smoke Developed Index of 50 or less
may be used.
4. Fill, Void or Cavity Material* — Sealant — For 1 and 2 hr F and FH Rating, min 5/8 in. (16 mm) thickness of fill
material applied within the annulus, flush with both surfaces of wall. For 3 hr F and FH Rating, min 1 in. (25 mm)
thickness of fill material applied within the annulus, flush with both surfaces of wall. At the point contact location
between pipe covering and gypsum board, a min 1/2 in. (13 mm) diam bead of fill material shall be applied at
the pipe covering /gypsum board interface on both surfaces of wall.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC ---- FS -One Sealant
*Bearing the UL Classification Mark
E==E=
LJ Reproduced HILTI, Inc. Courtesy of
u LJ Underwriteto rs Laboratories, Inc.
FIRESTOP SYSTEMS May 30, 2012
�`o
c D us
Classified by
Underwriters Laboratories, Inc.
to UL 147a and CAN /ULC -5115
Revisions:
0
ZL
�O
lu l
H
c�
ti
LL-4
0
0
Ind
F
0
x
N
ag in
W
il�A
ti 0
—r
C�
-4 .. A 5
=Zr N
T^ F
O
d
OPEN
V
� V
Z
a
CONSTRUCTION
DOCUMENTS
DRAWN: JB
CHECKED: ES
DA'L'E: 03-12-14
SCALE: AS &HOtt1N
SEAL �, C 'V
4
�* r ..
•�AN.�`CAL�' ,n
El` , DO A::SLIAPaZ, P.E
L f1�[.S� x 64759
Sheet No.
P7.01
J015 # 201335
I
N
,