14-375-001ouch .19 iamil Hospital k Affiliate of Baptist Health Systems of South Florida GENERAL NOTES I,- CONTRACTOR IS BEING PROVIDED WITH COMPLETE SETS OF DOCUMENTS. CONTRACTOR IS RESPONSIBLE FOR PROVIDING SUBCONTRACTORS WITH COMPLETE SETS OF DRAWINGS. INTENT IS FOR ALL SYSTEMS AND EQUIPMENT TO BE PROVIDED WITH UTILITY CONNECTIONS AS REQUIRED FOR OPERATION. EXAMPLE - IF A SINK IS SHOWN IN THE ARCHITECTURAL PLANS, THE PLUMBING PLANS DO NOT SHOW A WATER OR DRAWINGS CONNECTION THE ENGINEER WILL PROVIDE THE DESIGN DETAILS IN ACCORDANCE WITH THE DESIGN CRITERIA FOR THE REST OF THE INSTALLATIONS. CONTRACTOR IS RESPONSIBLE FOR PRO- VIDING THE CONNECTION AT NO ADDITIONAL COST TO THE OW- NER. 2.- CONTRACTOR IS RESPONSIBLE FOR VISITING THE SITE DURING THE BIDDING PERIOD AND VERIFY THAT THE CONDITIONS ARE AS DESCRIBED IN THE DOCUMENTS. DISCREPANCIES ARE TO BE NOTED IN WRITING, AND NOTIFY ARCHITECT / ENGINEERS. CONTRACTOR ACCEPTS CONDITIONS AS THEY ARE ON THE SITE, AND MUST PROVIDE SYSTEMS AND WORK AS DESCRIBED IN THE CONTRACT DOCUMENTS AT NO ADDITIONAL COST TO THE OWNER. 3.- DIMENSIONS PROVIDED ARE NOMINAL, NOT ACTUAL. THEY TAKE AS A BASIS EXISTING WALLS. IF DISCREPANCIES ARE FOUND, NOTIFY ARCHITECT IMMEDIATELY FOR COORDINATION. IF CON- TRACTOR PROCEEDS, HE DOES SO AT HIS OWN RISK AND IS RESPONSIBLE FOR ALL EXPENSES INCURRED, IF AT THE DISCRE TION OF THE OWNER OR THE ARCHITECT, THE WORK HAS TO BE RE -DONE, 4.- SHUTDOWN OF UTILITIES: IF A SHUTDOWN OR ANY TYPE OF INTER- FERENCE WITH EXISTING SYSTEMS IS ANTICIPATED, THE CONTRAC TOR MUST NOTIFY THE OWNER, 72 HOURS IN ADVANCEAND OBTA- IN APPROVAL IN WRITING PRIOR TO PROCEEDING. 5.- CONTRACTOR SHALL TAKE ALL NECESSARY PRECAUTIONS AND USE ALL APPROPRIATE CONSTRUCTION METHODS / TECHNIQUES TO PROTECT EXISTING UTILITIES AND OTHER PROPERTY NOT NOTED FOR REMOVAL, CONTRACTOR SHALL BE RESPONSIBLE FOR ANY DAMAGES INCURRED DURING CONSTRUCTION AND SHALL REPAIR ANY DAMAGES AT NO EXPENSE TO THE OWNER. 6.- IF THERE IS A DISCREPANCY BETWEEN THE DRAWINGS AND THE SPECIFICATIONS, THE CONTRACTOR IS TO OBTAIN CLARIFICATION DURING THE BIDDING PERIOD. IF THE DISCREPANCY COMES UP DURING THE CONSTRUCTION, IT IS ASSUMED THE CONTRACTOR BID THE MOST EXPENSIVE WAY AND WILL DO THE WORK AS PER THE DIRECTION OF THE OWNER /ARCHITECT AT NO ADDITIONAL COST TO THE OWNER. 7.- ABBREVIATIONS THROUGHOUT THE PLANS ARE THOSE IN COM- MON USE, ARCHITECT WILL DEFINE INTENT OF ANY IN QUESTION. 8.- THE CONTRACTOR SHALL PROVIDE ALL NECESSARY TEMPORARY BARRIERS, LIGHTING, COVERINGS, FIRE PREVENTION AND OTHER EQUIPMENT TO PROTECT THE SAFETY OF ALL PERSONS AND THE PROPERTY THROUGHOUT THE ENTIRE PERIOD OF THE CONSTRUC _ TION CONTRACT. 9.- THE CONTRACTOR SHALL VERIFY SIZES AND LOCATIONS OF ALL OPENINGS FOR MECHANICAL, ELECTRICAL AND PLUMBING EQUIPMENT WITH SUBCONTRACTORS, AS WELL AS SHOP DRAWINGS AS APPROVED BY ARCHITECT, BEFORE PROCEEDING WITH THE WORK. 10.- ALL ITEMS USED IN CONSTRUCTION, BUT NOT SPECIFICALLY MENTIONED HEREIN, SHALL CONFORM TO ALL LOCAL CODES AND STATE ORDINANCES AS TO APPLICATION AND USE. II.- PROVIDE ELECTRIC INSULATION BETWEEN ALL DISSIMILAR METAL AND ALSO BETWEEN CEMENT AND METAL 12.- THE CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING ALL PERMITS TO COMPLETE THE PROJECT. 13.- CONTRACTOR TO REVIEW ALL EXISTING BUILDING SYSTEMS AS TO THEIR COMPLIANCE WITH ALL LOCAL AGENCY REQUIREMENTS AND BRING ANY NON - CONFORMING ITEMS TO ARCHITECT'S AND ENGINEER'S ATTENTION. 14.- GENERAL CONTRACTOR IS TO PROTECT EXISTING ADJACENT AREAS TO WHERE WORK IS TO BE PERFORMED. ANY EXISTING MILLWORK, EQUIPMENT DAMAGED DUE TO WORK PERFORMED SHALL BE REPAIRED/ REPLACED TO MATCH EXISTING (TYPICAL UNLESS OTHERWISE NOTED). 15.- DRAWINGS ARE SCHEMATIC SHOWING RELATIVE LOCATIONS AND CONNECTIONS AND SHALL NOT BE SCALED AT ANY TIME. 16.- ALL WOOD BLOCKING WITHIN BUILDING STRUCTURE, SHALL BE FIRE - RETARDANT TREATED AS PER SPECIFICATIONS. I7,- GENERAL CONTRACTOR SHALL INSPECT ALL EXISTING RATED WALLS / PARTITIONS WITHIN SCOPE OF WORK AREA. CONTRACTOR SHALL UPGRADE EXISTING PARTITIONS AS REQUIRED TO MAINTAIN THE INTEGRITY OF THE DESIGNATED RATING, I8.- ELEVATION AND LEVELS: A. ALL NUMERICAL ELEVATIONS ARE TO TOP OF CONCRETE SLAB. UNLESS NOTED OTHERWISE, I /8• TYPE X G.W.B. ON METAL 19- ALL INTERIOR GYPSUM WALL BOARD S 5 STUDS OR FURRING CHANNELS UNLESS NOTED OTHERWISE, SIZES AS DIMENSIONED ON FLOOR PLANS. SEE NOTES 9 FOR LOCATION OF WATER RESISTANT G.W.B. 20,- PROVIDE WATER RESISTANT TYPE X G.W.B. IN ALL TOILETS. AND JANITOR'S CLOSETS. 21,- BEFORE PATCHING ANY FIRE - RATED C.M.U. PARTITION, FILL ANY EXPOSED CELLS SOLID WITH GROUT. 22,- PROVIDE FINISH WALL UNDER AND BEHIND ALL EQUIPMENT AND CASEWORK. 23: LOCATION AND SIZE OF CEILING AND WALL ACCESS PANELS SHALL BE DETE12MINED BY THE POSITION OF VALVES AND OTHER MECHANICAL AND ELECTRICAL ITEMS WHICH REQUIRE ACCESS. THE CONTRACTOR SHALL COORDINATE WITH ALL TRADES. THE ARCHITECT SHALL REVIEW AND APPROVE ALL FINAL LOCATIONS OF ACCESS PANELS PRIOR TO INSTALLATION, 24.- THERE SHALL BE NO BACK - TO BACK ELECTRICAL TELEPHONE OR OTHER OUTLETS. 25.- ALL VERTICAL PIPING AND COLUMNS, EXPOSED IN ROOMS SHALL BE FURRED WITH METAL STUDS AND DRY WALL AND FINISHED TO MATCH ADJACENT WALLS, UNLESS NOTED OTHERWISE, EXCEPTIONS: A. ELECTRIC CLOSETS C, MECHANICAL ROOMS B. TELEPHONE CLOSETS D. STAIRS 26.- WHERE HVAC OR OTHER MECHANICAL, ELECTRICAL AND PLUMBING ITEMS PENETRATE PARTITIONS, STUDS SHALL BE BRACED AND FRAMED TO STRUCTURE AS REQUIRED TO PROVIDE ADEQUATE SUPPORTS. ALL PENETRATIONS THROUGH RATED WALLS SHALL BE SEALED TO PROVIDE FIRE, SMOKE AND / OR ACOUSTICAL ISOLATION OF SPACES WITH APPROPRIATE FIRE S.T.0 MATERIAL. 27.- SEE INTERIOR ELEVATIONS FOR FINISHES AND FINISH DETAILS FOR INTERIOR SPACES, SEE ARCHITECTURAL REFLECTED CEILING PLANS FOR ACOUSTICAL TILE FINISH. 28,- SEE ARCHITECTURAL REFLECTED CEILING PLANS FOR LOCATION OF CEILING MOUNTED MECHANICAL, ELECTRICAL FIXTURES. 29,- STAGGER JOINTS VERTICALLY AND HORIZONTALLY IN ALL G.W.B. PARTITIONS EA. SIDE OF PARTITION, JOINTS STAGGERED MINIMUM 2' -0". UNLESS OTHERWISE NOTED. 30, CONTRACTOR SHALL CONFIRM THAT ALL EXISTING EXPOSED STEEL COMPLIES WITH N.F.P.A FIRE PROTECTION REQUIRE- MENTS. CONTRACTOR SHALL PROVIDE ALL NECESSARY INSULA- TION /FIRE PROTECTIVE COATINGS. 31. CONTRACTOR TO SUBMIT ALL SHOP DRAWINGS TO ARCHITECT AND THE BUILDING DEPARTMENT FOR APPROVAL, (ELEVATOR, TRUSSES, WINDOWS, ETC.) 32. CONTRACTOR REQUIRED TO PULL SEPARATE DEMOLITION PERMIT. SMH /MAB SOUTH MIAM 6200 S.W. 72nd STREET TEL: (786) 596 -8386 ORTHO OFFICE -SUITE 602 I HOSPITAL - MEDICAL ARTS BUILDING EB0000924 LOUIS J. AGUIRRE & ASSOCIATES P.A. CONSULTING ENGINEERS 2600 DOUGLAS RD. SUITE 605 CORAL GABLES, FLORIDA 33134 TELEPHONE: (305) 444 -1679 FAX: (305) 448 -1405 E -MAIL ADDRESS: GRALMAIL@LJAAPA.COM CITY MAP 1� !671 r + r,( m i O ml ��...�. LS -1 PARTIAL 6th FLOOR LIFE SAFETY PLAN. pts1, t� n Cx{ y ttt 959 SYMBOLS /LEGEND AND GENERAL NOTES - PLUMBING. �eerrown -" . � FaUi�t7inr61eaU 95, Naomi Havana s41 � Dirwntawn py�' C� � �n va ♦t It � tdar�rai' Ia1anA 5wteiwn;rr Carel C,1 AND NOTES. P5.00 ISOMETRIC PLAN- DRAINAGE - PLUM=ING. 1a171t (States Park . ? wesiViAm4' k P5.01 t'rcktti A -3 PARTIAL 6th FLOOR EQUIPMENT ?LAN, LEGEND Wcst.hr. Gtr +r P7.00 Coral way A -4 PARTIAL 6th FLOOR REFLECTED CEILING PLAN, Urliver &icy Coral Cnsnadia DETAILS - PLUMBING. A -5 PARTIAL BUILDING SECTIONS AND DETAILS. i 7I F'ttrk (E?,) ) Terrace GCtrcourse ft ,!` ' lice Nli4inwright Vrrq+nia Ke FIRE PROTECTION A -7 R Park A -8 (KID •w.0 FPO.00 A -9 TYPICAL TOILET ROOM ENLARGED PLAN, LEGEND AND DETAILS. PROTECTION. A -10 ROOM FINISH SCHEDULE, NOTES AND DETAILS. Heights FLOOR PLAN -FIRE PROTECTION. A -11 DOOR SCHEDULE, NOTES AND DETAILS. FP7.00 DETAILS -FIRE PROTECTION. Coral Gables fle-A Lek PARTITION TYPES, NOTES AND DETAILS. A -13 Pirk %tCnVilr Coconut y • I frovr1a) A -15 Sunset ttei hts ,+ i t III gat 5oY .yy ri 9 M sr ELECTRICAL A -16 PENETRATION AND FIRE RATING DETAILS. - 0 PENETRATION AND FIRE RATING DETAILS. aEr� atrL SNt« MECHANICAL Key E0.01 LIGHTING FIXTURE SCHEDULE AND LIGETING CONTROL r" Siscayne DETAILS - ELECTRICAL. Snapper ". �� °' mom s',w "m x, E3.00 DEMOLITION PLAN - ELECTRICAL. M3.00 Creek Park E3.01 FLOOR PLAN - LIGHTING- ELECTRICAL. M3.01 ROOF PLAN -HVAC. E3.02 FLOOR PLAN- PO1rER- ELECTRICAL. M6.00 SCHEDULES -HVAC. f :uch rtfY7rop +Ci PROnCT, iA/CAMN Cllt dux: r Gn; 9 DETAILS- -HVAC. Kendall Botanic cardeil ENLARGED ELECTRICAL ROOM AND POWER RISER DIAGRAM - M7.01 /'tAr;A;a 5•�7tr i i « a, Pinecrest ELECTRICAL. E5.01 RISER DIAGRAM- ELECTRICAL. E6.00 PANEL SCHEDULES - ELECTRICAL. Du �+ Ltlkes' s AREA MAP x k ti ..+. y,.,t'tiw * , µ6r,.. :.1 a Y"...�" ,+ ,�.: a N, a ..p iW',Y ,����AW�� +�.::,,R..1'� T, •' � ";.. 1� '+n� ''iiw'"'k«' :' µ. ` _El .. As s. �'Wry' '; , I{i r Sri )'wry %.� �•'"'""r.�r�r� t � � � � �m� � � y, �`� 7`r�?,lr�,p9��`y��a,.. .r�' � ., Gwi, "•'it: Ukr" €,t r� 1 u -xV . A v` ,s' { . ' ie, .rj r t ',icy Fri III ,;r "./, , ,.:... -t,y 4k 9 j�W , r x y�+,..,,is,a,, ! tri..`- LF•.�, L...,.. .7; ,.0 s° s�f s , i II^, n " �j► SOUTH MIAMI, FLORIDA 33143 Fax: (786) 596 -2901 Q % 0 O a r c h 1 t e c t s FLORIDA LICENSE OAA0002689 2100 ?ONCE DE LEON BLVD. SWTE 1170, CORAL GABLES, FL 33134 TeL• (305)265 -7177 Fam (305)262 -*435 LUIS I- MAYA, A.LA FI. AROOO8W3 PROJECT NUMBER: 201335 (INTERIOR WORK ONLY) MARCH 12, 2014 INDEX OF DRAWINGS BUILDING INFORMATION ORIGINAL BUILDING DESCRIPTION BUILDING JURISDICTION: SOUTH MIAMI, MIAMI DADE COUNTY PRIMARY USE CLASS : BUSINESS NUMBER OF STORIES : 6 FLOOR EXISTING BUILDING NEW PROJECT DESCRIPTION PROJECT AREA: SIXTH FLOOR: 3,500 S.F. SPRINKLED: FULLY SPRINKLERED ,APPLICABLE CODES FLORIDA BUILDING CODE 2010 EDITION. FLORIDA FIRE PREVENTION CODE 2010 EDI'T'ION. NFPA 101 LIFE SAFETY CODE, 2009 EDITION. REVISIONS •Y•• ••• • • V•iGG a -i Y • • Y• U u Y G • - Y• V V V Y • Y Y Y • U • • • V • YE -•• ABBREV1.,4T*1'r_01*;S V . W V Y Y • • • •WY ••Y Y AF1r, -IITEC WF"L ABRMYIAT!": Ct �G`f ICII Yi�i? .IJING+6 I AND U • W • W Y L ANGLE ••••Y • •Y••• G ��• • wove • w AT L LENGTH C CENTERING LAM LAMINATE O DIAMETER LAV LAVATORY • POUND OR NUMBER LEIS POUNDS L55/4R POUNDS PER HOUR LD LINEAR DIFFUSER A/C AIR CONDITIONING LP LOW POINT ACI AMERICAN CONCRETE INSTITUTE LT LIGHT ACP ASBESTOS CEMENT PIPE M ACSC ASPHALTIC CONCRETE SURFACE COURSE ACU AIR CONDITIONING UNIT MATL MATERIAL ACT ACOUSTICAL CEILING TILE MAX MAXIMUM AD AREA DRAIN MC MEDICINE CABINET ADJ ADJUSTABLE MECH MECHANICAL A/E ARCHITECT/ENGINEER MEMB MEMBRANE AF ACCESS FLOORING MFR MANUFACTURER AFF ABOVE FINISHED FLOOR MIN MINIMUM AGGR AGGREGATE MISC MISCELANEOUS AHU AIR HANDLING UNIT Mo MASONRY OPENING ALT ALTERNATE MTD MOUNTED AL ALUMINUM MTL METAL ANN ANNUNCIATOR ANSI AMERICAN NATIONAL STANDARDS INSTITUTE MUL MULLION ANT ANTENNA MULT MULTIPLE AP ACCESS PANEL N APL ACCESS PLENUM APROX APPROXIMATE ARCH ARCHITECTURAL N NORTH ASB ASBESTOS NEC NATIONAL ELECTRIC CODE ASpH ASPHALT NIC NOT IN CONTRACT A5TM AMERICAN SOCIETY OF TESTING t MATERIALS R NUMBER ROM NOMINAL is NPL NAME PLATE BAT BATTERY NTS NOT TO SCALE BD BOARD 0 BITUM BITUMINOUS BLDG BUILDING BLKG BLOCKING OA OVERALL BM BEAM 055 OBSCURE BOT BOTTOM OC ON CENTER OD OUTSIDE DIAMETER DIM) 0 OFS OVERFLOW SCUPPER CAB CABINET OPP OPPOSITE CB CATCH BASIN CEM CEMENT 10 CER CERAMIC CFM CUBIC FEET PER MINUTE PC PRECAST CONCRETE CG CORNER GUARD PJ PIPE JOINT CHP CRICKET HIGH POINT PL PLASTIC CI CAST IRON P LAM PLASTIC LAMINATE CIC CAST IRON COVER PLAS PLASTER GIP CAST IRON PIPE PLYWD PLYWOOD CJ CONTROL JOINT PNT PAINT CLG CEILING PT POINT OR PATIENT CL-60 CEILING DIFFUSER PTO PAPER TOWEL 015PENCER CLKG CAULKING PTN PARTITION CLO CLOSET PTR PAPER TOWEL RECEPTACLE CLP CRICKET LOW POINT CLR CLOSER CMP CORRUGATED METAL PIPE Q CMU CONCRETE MA5ONRY UNIT CNTR COUNTER Q QUARTER CO T T QUARRY TILE O CLEAN OUT COL COLUMN COMM COMMUNICATION CONC CONCRETE R CONN CONNECTION CONSTS CONSTRUCTION R REAR CONT CONTINUOUS RA RETURN AIR CPT CARPET TILE RAD RADIUS CT CERAMIC TILE RB REINFORCED BEAM GTR CENTER RCPT RECEPTION CTSK COUNTERSUNK RD ROOF DRAIN REP REFERENCE REINP REINFORCED REQ REQUIRED DBL DOUBLE RESL RESILIENT DEG DEGREE RGTR REGISTER DEPT DEPARTMENT R" ROOM DESIG DESIGNATION RO ROUGH OPENING DET DETAIL RWL RAIN WATER LEADER DF DRINKING FOUNTAIN DG DOOR GRILLE PIA DIAMI°_TER d DIAG DIAGRAM DIM DIMENSION S STUCCO 0I5R DISPENSER 5C SCREED CONCRETE DN DOWN SCHED SCHEDULE DO DOOR OPENING SEC SECOND D5P DRY STANDPIPE 50 SMOKE DETECTOR D5 DOWN SPOUT DWGS DRAWINGS SECT SECTION N DWR DRAWER 5F SUPPLY FA 5G SPANDREL GLASS 5GR SYNTHETIC GRADE F SHR SHOWER SHT SHEET EA EACH SIG SIGNAL EC EPDXY COATING 5M SMILAR EHD ELECTRIC HAND DRYER SK SINK EL ELEVATION SM SHEET METAL EJ EXPAN51ON JOINT SMK SMOKE ELEC ELECTRICAL SND SOUND ELEv ELEVATOR SPEC SPECIFICATION EMER EMERGENCY SPKR SPEAKERS ENCL ENCLOSURE SQ SQUARE ENGR ENGINEER SQFT SQUARE FEET EPNL ELECTRICAL PANEL 55T 5TAINLE56 5TEEL EQ EQUAL ST STREET EQPT EQUIPMENT STC SOUND TRANSMISSION COEFFICIENT EST ESTIMATE STD STANDARD ET EXPANSION TANK 5T -D STOW DRAIN EWC ELECTRIC WATER COOLER 5TL STEEL EXH EXHAUST STRL STRUCTURAL I- XST EXISTING SUSP SUSPENDED EXT EXTERIOR SYM SYMMETRICAL 5YS 5Y5TEM ? T FA FIRE ALARM FABL FIRE ALARM BELL T TOILET FD FLOOR DRAIN TB TIE BEAM FG FIBERGLASS TC TIE COLUMN FCO FLOOR CLEANOUT TEL TELEPHONE FD FIRE PAMPER y S i �' 44, `TEMP TEMPERATURE FDC FIRE FDR FIRE DOOR TMENT CONNECTOR i v THK THI TONGUE AND GROVE FDN FOUNDATIONS TOC TOP OF CUW FDV FIRE DEPARTMENT VALVE TOPP TOP OF PARAPET PEG FIRE EXTINGUISHER CABINET M.. Y. `, ^� TOS TOP OF SLAB FEX FIRE EXTINGUISHER TP TOP OF PAVEMENT FF FINISH FLOOR TRD TREAD PH FRE HYDRANT T5 TUBULAR STEEL FIN FINISH T5TAT THERMOSTAT FL FLOOR TV TELEVISION FM FACTORY MANUAL " °'' TW TOP OP WALL FLASH FLASHING 11 TYP TYPICAL FLG FLANGE FLOUR FLUORESCENT -.: V FOC FACE OF CONCRETE FOF FACE OF FINISH US UNDERCUT FOM FACE OF MASONRY UL UNDERWRITER'S LABORATORIES Fos FACE OF STUD UNF UNFINISHED FPRF FIREPROOF LION UNLE55 OTHERWISE NOTED FPM FEET PER MINUTE UOS UNLE55 OTHER SPECIFIED UTI UTILI FRO FRENCH DRAIN TY F5 FULL SIZE UTIL UTILITY FT FOOT OR FEET y FTG FOOTING AV PT -LB FOOT POUNDS �� 41 PURR FURRING VB VINYL BASE ti PUT FUTURE Q 5 VCT VINYL COMPOSITION TILE 0 lea VEST VERTICAL ' ��' VEST VESTIBULE �. VP VERIFY IN FIELD VOLU GA GAUGE 't 0 VOY VAPOR TIGHT GAL GALLON vTR VENT THRU ROOF GALV GALVANIZED GB GRADE BEAM W GEN GENERATORaW GL GLASS �'► ,4 L WR WIRE GND GROUND 4p Q ! W WINDOW GLI GRILLE BLOCK O 0 W/ WTH WC WATER CLOSET G((115 GYPSUM WAVY BOARD (► p� (t WCO WALL CLEANOUT GYP GYPSUM T LF WALL W FABRIC "Y W/o WITHOUT Lt ` WP WATER PROOF r'^'tV W5GT WAINSCOT H WT WEIGHT WUF WELDED WIRE FABRIC HB HOSE BIB WWM WELDED WIRE MESH HC HANDICAPPED HDWD HARDWOOD HDWE HARDWARE HGT HEIGHT HM HOLLOW METAL HORIZ HORIZONTAL HP HIGH POINT HR HOUR HTR HEATER HVAC HEATING, VENTILATION, AND AIR CONDITIONING HYD HYDRANT it) IN5IDE DIAMETER C DIAM) N INCHES INT INTERIOR { V JAN JANITOR r \ _ JB JUNCTION BOX `! 1 \ JCT JUNCTION \+s J5K JANITORS SINK JT JOINT KO KNOCK OUT CONSTRUCTION DOCUMENTS jI i A I f i } f " 0 ,x•, x' LIFE SAFETY PLUMBING LS -1 PARTIAL 6th FLOOR LIFE SAFETY PLAN. P0.00 SYMBOLS /LEGEND AND GENERAL NOTES - PLUMBING. P3.01 FLOOR PLAN - DRAINAGE- PLUMBING. ARCHITECTURAL P3.02 FLOOR PLAN - DOMESTIC WATER- PLUMBING. A -i PARTIAL 6th FLOOR DEMOLITION PLAN, LEGEND AND NOTES. P5.00 ISOMETRIC PLAN- DRAINAGE - PLUM=ING. A -2 PARTIAL 6th FLOOR PLAN, LEGEND, NOTES AND DETAILS. P5.01 ISOMETRIC PLAN - DOMESTIC WATER- PLUMBING. A -3 PARTIAL 6th FLOOR EQUIPMENT ?LAN, LEGEND AND NOTES. P7.00 DETAILS - PLUMBING. A -4 PARTIAL 6th FLOOR REFLECTED CEILING PLAN, LEGEND AND NOTES. P7.01 DETAILS - PLUMBING. A -5 PARTIAL BUILDING SECTIONS AND DETAILS. A -6 INTERIOR ELEVATIONS. FIRE PROTECTION A -7 INTERIOR ELEVATIONS. A -8 CABINET DETAILS AND NOTES. FPO.00 SYMBOLS /LEGEND AND GENERAL NOTES -FIRE A -9 TYPICAL TOILET ROOM ENLARGED PLAN, LEGEND AND DETAILS. PROTECTION. A -10 ROOM FINISH SCHEDULE, NOTES AND DETAILS. FP3.01 FLOOR PLAN -FIRE PROTECTION. A -11 DOOR SCHEDULE, NOTES AND DETAILS. FP7.00 DETAILS -FIRE PROTECTION. A -12 PARTITION TYPES, NOTES AND DETAILS. A -13 MISCELLANEOUS DETAILS. A -14 MISCELLANEOUS DETAILS. A -15 PENETRATION AND FIRE RATING DETAILS. ELECTRICAL A -16 PENETRATION AND FIRE RATING DETAILS. A -17 PENETRATION AND FIRE RATING DETAILS. E0.00 SYMBOL /LEGEND AND GENERAL NOTES- ELECTRICAL. MECHANICAL E0.01 LIGHTING FIXTURE SCHEDULE AND LIGETING CONTROL DETAILS - ELECTRICAL. M0.00 SYMBOLS /LEGEND AND GENERAL NOTES -HVAC. E3.00 DEMOLITION PLAN - ELECTRICAL. M3.00 FLOOR PLAN -HVAC. E3.01 FLOOR PLAN - LIGHTING- ELECTRICAL. M3.01 ROOF PLAN -HVAC. E3.02 FLOOR PLAN- PO1rER- ELECTRICAL. M6.00 SCHEDULES -HVAC. E3.03 FLOOR PLAN- SYSTEMS - ELECTRICAL. M7.00 DETAILS- -HVAC. E5.00 ENLARGED ELECTRICAL ROOM AND POWER RISER DIAGRAM - M7.01 DETAILS -HVAC. ELECTRICAL. E5.01 RISER DIAGRAM- ELECTRICAL. E6.00 PANEL SCHEDULES - ELECTRICAL. BUILDING INFORMATION ORIGINAL BUILDING DESCRIPTION BUILDING JURISDICTION: SOUTH MIAMI, MIAMI DADE COUNTY PRIMARY USE CLASS : BUSINESS NUMBER OF STORIES : 6 FLOOR EXISTING BUILDING NEW PROJECT DESCRIPTION PROJECT AREA: SIXTH FLOOR: 3,500 S.F. SPRINKLED: FULLY SPRINKLERED ,APPLICABLE CODES FLORIDA BUILDING CODE 2010 EDITION. FLORIDA FIRE PREVENTION CODE 2010 EDI'T'ION. NFPA 101 LIFE SAFETY CODE, 2009 EDITION. REVISIONS •Y•• ••• • • V•iGG a -i Y • • Y• U u Y G • - Y• V V V Y • Y Y Y • U • • • V • YE -•• ABBREV1.,4T*1'r_01*;S V . W V Y Y • • • •WY ••Y Y AF1r, -IITEC WF"L ABRMYIAT!": Ct �G`f ICII Yi�i? .IJING+6 I AND U • W • W Y L ANGLE ••••Y • •Y••• G ��• • wove • w AT L LENGTH C CENTERING LAM LAMINATE O DIAMETER LAV LAVATORY • POUND OR NUMBER LEIS POUNDS L55/4R POUNDS PER HOUR LD LINEAR DIFFUSER A/C AIR CONDITIONING LP LOW POINT ACI AMERICAN CONCRETE INSTITUTE LT LIGHT ACP ASBESTOS CEMENT PIPE M ACSC ASPHALTIC CONCRETE SURFACE COURSE ACU AIR CONDITIONING UNIT MATL MATERIAL ACT ACOUSTICAL CEILING TILE MAX MAXIMUM AD AREA DRAIN MC MEDICINE CABINET ADJ ADJUSTABLE MECH MECHANICAL A/E ARCHITECT/ENGINEER MEMB MEMBRANE AF ACCESS FLOORING MFR MANUFACTURER AFF ABOVE FINISHED FLOOR MIN MINIMUM AGGR AGGREGATE MISC MISCELANEOUS AHU AIR HANDLING UNIT Mo MASONRY OPENING ALT ALTERNATE MTD MOUNTED AL ALUMINUM MTL METAL ANN ANNUNCIATOR ANSI AMERICAN NATIONAL STANDARDS INSTITUTE MUL MULLION ANT ANTENNA MULT MULTIPLE AP ACCESS PANEL N APL ACCESS PLENUM APROX APPROXIMATE ARCH ARCHITECTURAL N NORTH ASB ASBESTOS NEC NATIONAL ELECTRIC CODE ASpH ASPHALT NIC NOT IN CONTRACT A5TM AMERICAN SOCIETY OF TESTING t MATERIALS R NUMBER ROM NOMINAL is NPL NAME PLATE BAT BATTERY NTS NOT TO SCALE BD BOARD 0 BITUM BITUMINOUS BLDG BUILDING BLKG BLOCKING OA OVERALL BM BEAM 055 OBSCURE BOT BOTTOM OC ON CENTER OD OUTSIDE DIAMETER DIM) 0 OFS OVERFLOW SCUPPER CAB CABINET OPP OPPOSITE CB CATCH BASIN CEM CEMENT 10 CER CERAMIC CFM CUBIC FEET PER MINUTE PC PRECAST CONCRETE CG CORNER GUARD PJ PIPE JOINT CHP CRICKET HIGH POINT PL PLASTIC CI CAST IRON P LAM PLASTIC LAMINATE CIC CAST IRON COVER PLAS PLASTER GIP CAST IRON PIPE PLYWD PLYWOOD CJ CONTROL JOINT PNT PAINT CLG CEILING PT POINT OR PATIENT CL-60 CEILING DIFFUSER PTO PAPER TOWEL 015PENCER CLKG CAULKING PTN PARTITION CLO CLOSET PTR PAPER TOWEL RECEPTACLE CLP CRICKET LOW POINT CLR CLOSER CMP CORRUGATED METAL PIPE Q CMU CONCRETE MA5ONRY UNIT CNTR COUNTER Q QUARTER CO T T QUARRY TILE O CLEAN OUT COL COLUMN COMM COMMUNICATION CONC CONCRETE R CONN CONNECTION CONSTS CONSTRUCTION R REAR CONT CONTINUOUS RA RETURN AIR CPT CARPET TILE RAD RADIUS CT CERAMIC TILE RB REINFORCED BEAM GTR CENTER RCPT RECEPTION CTSK COUNTERSUNK RD ROOF DRAIN REP REFERENCE REINP REINFORCED REQ REQUIRED DBL DOUBLE RESL RESILIENT DEG DEGREE RGTR REGISTER DEPT DEPARTMENT R" ROOM DESIG DESIGNATION RO ROUGH OPENING DET DETAIL RWL RAIN WATER LEADER DF DRINKING FOUNTAIN DG DOOR GRILLE PIA DIAMI°_TER d DIAG DIAGRAM DIM DIMENSION S STUCCO 0I5R DISPENSER 5C SCREED CONCRETE DN DOWN SCHED SCHEDULE DO DOOR OPENING SEC SECOND D5P DRY STANDPIPE 50 SMOKE DETECTOR D5 DOWN SPOUT DWGS DRAWINGS SECT SECTION N DWR DRAWER 5F SUPPLY FA 5G SPANDREL GLASS 5GR SYNTHETIC GRADE F SHR SHOWER SHT SHEET EA EACH SIG SIGNAL EC EPDXY COATING 5M SMILAR EHD ELECTRIC HAND DRYER SK SINK EL ELEVATION SM SHEET METAL EJ EXPAN51ON JOINT SMK SMOKE ELEC ELECTRICAL SND SOUND ELEv ELEVATOR SPEC SPECIFICATION EMER EMERGENCY SPKR SPEAKERS ENCL ENCLOSURE SQ SQUARE ENGR ENGINEER SQFT SQUARE FEET EPNL ELECTRICAL PANEL 55T 5TAINLE56 5TEEL EQ EQUAL ST STREET EQPT EQUIPMENT STC SOUND TRANSMISSION COEFFICIENT EST ESTIMATE STD STANDARD ET EXPANSION TANK 5T -D STOW DRAIN EWC ELECTRIC WATER COOLER 5TL STEEL EXH EXHAUST STRL STRUCTURAL I- XST EXISTING SUSP SUSPENDED EXT EXTERIOR SYM SYMMETRICAL 5YS 5Y5TEM ? T FA FIRE ALARM FABL FIRE ALARM BELL T TOILET FD FLOOR DRAIN TB TIE BEAM FG FIBERGLASS TC TIE COLUMN FCO FLOOR CLEANOUT TEL TELEPHONE FD FIRE PAMPER y S i �' 44, `TEMP TEMPERATURE FDC FIRE FDR FIRE DOOR TMENT CONNECTOR i v THK THI TONGUE AND GROVE FDN FOUNDATIONS TOC TOP OF CUW FDV FIRE DEPARTMENT VALVE TOPP TOP OF PARAPET PEG FIRE EXTINGUISHER CABINET M.. Y. `, ^� TOS TOP OF SLAB FEX FIRE EXTINGUISHER TP TOP OF PAVEMENT FF FINISH FLOOR TRD TREAD PH FRE HYDRANT T5 TUBULAR STEEL FIN FINISH T5TAT THERMOSTAT FL FLOOR TV TELEVISION FM FACTORY MANUAL " °'' TW TOP OP WALL FLASH FLASHING 11 TYP TYPICAL FLG FLANGE FLOUR FLUORESCENT -.: V FOC FACE OF CONCRETE FOF FACE OF FINISH US UNDERCUT FOM FACE OF MASONRY UL UNDERWRITER'S LABORATORIES Fos FACE OF STUD UNF UNFINISHED FPRF FIREPROOF LION UNLE55 OTHERWISE NOTED FPM FEET PER MINUTE UOS UNLE55 OTHER SPECIFIED UTI UTILI FRO FRENCH DRAIN TY F5 FULL SIZE UTIL UTILITY FT FOOT OR FEET y FTG FOOTING AV PT -LB FOOT POUNDS �� 41 PURR FURRING VB VINYL BASE ti PUT FUTURE Q 5 VCT VINYL COMPOSITION TILE 0 lea VEST VERTICAL ' ��' VEST VESTIBULE �. VP VERIFY IN FIELD VOLU GA GAUGE 't 0 VOY VAPOR TIGHT GAL GALLON vTR VENT THRU ROOF GALV GALVANIZED GB GRADE BEAM W GEN GENERATORaW GL GLASS �'► ,4 L WR WIRE GND GROUND 4p Q ! W WINDOW GLI GRILLE BLOCK O 0 W/ WTH WC WATER CLOSET G((115 GYPSUM WAVY BOARD (► p� (t WCO WALL CLEANOUT GYP GYPSUM T LF WALL W FABRIC "Y W/o WITHOUT Lt ` WP WATER PROOF r'^'tV W5GT WAINSCOT H WT WEIGHT WUF WELDED WIRE FABRIC HB HOSE BIB WWM WELDED WIRE MESH HC HANDICAPPED HDWD HARDWOOD HDWE HARDWARE HGT HEIGHT HM HOLLOW METAL HORIZ HORIZONTAL HP HIGH POINT HR HOUR HTR HEATER HVAC HEATING, VENTILATION, AND AIR CONDITIONING HYD HYDRANT it) IN5IDE DIAMETER C DIAM) N INCHES INT INTERIOR { V JAN JANITOR r \ _ JB JUNCTION BOX `! 1 \ JCT JUNCTION \+s J5K JANITORS SINK JT JOINT KO KNOCK OUT CONSTRUCTION DOCUMENTS jI i A I f i } f " 0 ,x•, x'