14-236-010TYP2 EXISTING
SERVICE. 30,4w
VOLTA Gf� 277/480
MOUNTING: SURFACE
LOCATION- ELECTRICALROOM
ELECTRICAL NOTES:
PANEL CRH5
BUS RATING 225A
MAINS: ML)D
POLES:42
FEEDER- EXISTING
NEUTRAL- EXISTING
CKT�
SERVES
TRIP
POLE
WIRE
CON
DUIT
VA
CKI
SERVES
TRIP
POLE
WIRE
CON
DUIT
VA
A
B
C
CODES.
-A
B
C
I
MST. ITS.
20'1
2.
-
1,700
1 IN 010 IrAyAll
2
MST. PANT- 'CRI-5
30,13
CONTRACTOR SHALL MEET All REQUIREMENTS SET FORTH BY
5,367
CONTRACTOR.
3
OUST. ITS.
20`I
-
29,
1,300
3.
4
(THERMAL-MAGNETIC). TWO AND THREE POLE CIRCUIT BREA-
FOR PROTECTION AGAINST PUBLIC LIABILITY AND PROPERTY
KERS SHALL BE COMMON TRIP. TIE HANDLES ARE NOT PERMI-
5,367
DAMAGE FOR THE DURATION OF THE WORK.
5
MST. LTS.
20'1
THE CONTRACTOR SHALL GUARANTEE ALL MATERIALS AND
-
ALL ELECTRICAL EQUIPMENT SHALL BE RAINTIGHT (NEMA 3R)
2,2
1 6
WHERE EXPOSED TO THE WEATHER. ALL FLEX CONDUITS CO-
LESS THAN (1) YEAR FROM DATE OF FINAL ACCEPTANCE.
NNECTED TO SUCH EQUIPMENT SHALL BE LIQUIDTIGHT.
5.
IT SHALL NOT BE THE INTENT OF THESE PLANS AND SPECIFI-
5367
7
EX[ST[NENV. LTS.
20/1
117
1/2
1 2,8301
CONTRACTOR SHALL FURNISH AND INSTALL ANY ADDITIONAL
11
8
1EXIST. PANEL'�
30V3
CLASSIFIED AREAS, U.O.N.
4-9ml
ELECTRICAL SYSTEM AND PROVIDE ALL REQUIREMENTS FOR
--iq
LOAD CALCULATION
CONNECTED LOAD=- 38,530 VA
25%UGHT LOAD = 2,008 VA
TOTAL LOAD = 40,538 VA 49 Amps
4,800
TYPE: EXISTING BUS RA TING: 225A
SERVICE: 30,4w MAINS: MLO
VOLTA CM 277/480 PANEL NH5 POLES: 42
MOUNTING: SURFACE FEEDER: EXISTING
LOCATION: IIECIRICALROOM NEUTRAL- EXISTING
ELECTRICAL NOTES:
1.
��
27.
®
THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE(NEC),
TED OR REQUIRED, WITH OVERLOAD RELAYS OR FUSES-IN EACH
®
AND THE LATEST EDITION OF THE FLORIDA BUILDING CODE
0-- Em
®
®
®�
CODES.
28.
FURNISH AND INSTALL DISCONNECT SWITCHES AND WIRING FOR
2.
ALL WORK SHALL BE PERFORMED BY A LICENSED ELECTRICAL
1 IN 010 IrAyAll
CONTRACTOR IN A FIRST CLASS WORKMANLIKE MANNER . SAID
THE HVAC CONTRACTOR AND INSTALLED BY THE ELECTRICAL
CONTRACTOR SHALL MEET All REQUIREMENTS SET FORTH BY
CONTRACTOR.
ANY LOCAL ORDINANCE AND GOVERNING AUTHORITIES.
29,
I.T. ROOM REC.
3.
THE CONTRACTOR SHALL PROVIDE ALL REQUIRED INSURANCE
(THERMAL-MAGNETIC). TWO AND THREE POLE CIRCUIT BREA-
FOR PROTECTION AGAINST PUBLIC LIABILITY AND PROPERTY
KERS SHALL BE COMMON TRIP. TIE HANDLES ARE NOT PERMI-
DAMAGE FOR THE DURATION OF THE WORK.
TTED.
4.
THE CONTRACTOR SHALL GUARANTEE ALL MATERIALS AND
30.
ALL ELECTRICAL EQUIPMENT SHALL BE RAINTIGHT (NEMA 3R)
WORKMANSHIP FREE FROM DEFECTS FOR A PERIOD OF NOT
WHERE EXPOSED TO THE WEATHER. ALL FLEX CONDUITS CO-
LESS THAN (1) YEAR FROM DATE OF FINAL ACCEPTANCE.
NNECTED TO SUCH EQUIPMENT SHALL BE LIQUIDTIGHT.
5.
IT SHALL NOT BE THE INTENT OF THESE PLANS AND SPECIFI-
31.
OUTLET BOXES SHALL BE PRESSED STEEL IN DRY LOCATIONS,
CATIONS TO SHOW EVERY MINOR DETAIL OF CONSTRUCTION.
CAST ALLOY WITH THREADED HUBS IN WET OR DAMP LOCA--
CONTRACTOR SHALL FURNISH AND INSTALL ANY ADDITIONAL
TIONS, AND SPECIAL ENCLOSURES".AS: REQUIRED FOR OTHER
CONDUIT, BOXES AND WIRING NECESSARY FOR A COMPLETE
CLASSIFIED AREAS, U.O.N.
ELECTRICAL SYSTEM AND PROVIDE ALL REQUIREMENTS FOR
A
EQUIPMENT TO BE PLACED IN PROPER WORKING ORDER.
32.
PROVIDE ALL FIXTURES WITH LAMPS, VERIFY TYPE WITH MANU-
FACTURER.
6.
THE CONTRACTOR SHALL BE RESPONSIBLE FOR REPAIRING TO
ORIGINAL CONDITIONS ANY AND ALL DAMAGES TO BUILDING
33.
ALL OPENINGS FOR LIGHT FIXTURES IN CEILINGS SHALL BE
SURFACES, EQUIPMENT, ETC. CAUSED DURING THE PERFOR-
PROTECTED IN A MANNER (PER ALL GOVERNING CODES) THAT
MANCE OF WORK.
WILL PROVIDE THE SAME RATING AS THE COILING. THIS APPLIES
TO ALL FIRE RATED CEILINGS.
7.
CORRECTION OF ANY DEFECTS SHALL BE COMPLETED WITHOUT
ADDITIONAL CHARGE OR DELAYS AND SHALL INCLUDE REPLACE-
34.
ELECTRICAL CONTRACTOR SHALL VERIFY THE CEILING FINISHES
MENT OR REPAIR OF ANY OTHER PHASE OF THE INSTALLATION
AND SUSPENSION SYSTEMS FOR SELECTION OF PROPER TRIMS
WHICH MAY HAVE BEEN DAMAGED THEREBY.
MORMONISM
AND SUPPORT ARRANGEMENTS FOR LIGHTING FIXTURES.
8.
THE CONTRACTOR SHALL VISIT THE JOB SITE AND VERIFY ALL
35.
ALL LIGHTING SWITCHES AND/OR DIMMERS SHALL BE GANGED
EXISTING CONDITIONS, AND SHALL THOROUGHLY REVIEW ALL
TOGETHER WHERE SHOWN TOGETHER.
DRAWINGS, SPECIFICATIONS AND POSSIBLE ADDENDA PRIOR TO
36.
ALL CONNECTIONS TO GROUND RODS SHALL BE MADE WITH UL
BIDDING ON HIS WORK. NO EXTRAS TO HIS CONTRACT WILL BE
APPROVED WELDED CONNECTIONS, UNLESS NOTED OTHERWISE.
EU®a��00
ALLOWED FOR FAILURE TO COMPLY WITH THIS REQUIREMENT.
THE CONTRACTOR SHALL FORM A GROUNDING ELECTRODE SYS-
9.
THE CONTRACTOR SHALL NOT SCALE THE ELECTRICAL DWGS.
m 1
*401101111M, 171M
REFER TO ARCHITECTURAL PLANS AND ELEVATIONS FOR EXACT
37.
ALL ELECTRICAL EQUIPMENT SHALL BE INSTALLED IN ACCESIBLE
19 1 N VA, 1 111 a 0.402 1 [G
LOAD CALCULATION
CONNECTED LOAD- 9,550 VA
25% LIGHT LOAD = 2,388 VA
TOTAL LOAD = 11,938 VA 14 Amps
11 MSTING BUS RATING: 225A
VICE: 30,4u, MAINS: MLO
.TAGS: 120/208 PANEL CRL5B
MOUNTING: FLUSH FEEDER. FXISTING
LCCAT1ON: SHOWNONPLANS NEUTRAL EXISTING
ELECTRICAL NOTES:
1.
THE ENTIRE INSTALLATION SHALL BE IN ACCORDANCE WITH
27.
RH a,
THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE(NEC),
TED OR REQUIRED, WITH OVERLOAD RELAYS OR FUSES-IN EACH
AND THE LATEST EDITION OF THE FLORIDA BUILDING CODE
HOT LEG.
AND ANY OTHER APPLICABLE FEDERAL, STATE AND LOCAL
CODES.
28.
FURNISH AND INSTALL DISCONNECT SWITCHES AND WIRING FOR
2.
ALL WORK SHALL BE PERFORMED BY A LICENSED ELECTRICAL
1 IN 010 IrAyAll
CONTRACTOR IN A FIRST CLASS WORKMANLIKE MANNER . SAID
THE HVAC CONTRACTOR AND INSTALLED BY THE ELECTRICAL
CONTRACTOR SHALL MEET All REQUIREMENTS SET FORTH BY
CONTRACTOR.
ANY LOCAL ORDINANCE AND GOVERNING AUTHORITIES.
29,
I.T. ROOM REC.
3.
THE CONTRACTOR SHALL PROVIDE ALL REQUIRED INSURANCE
(THERMAL-MAGNETIC). TWO AND THREE POLE CIRCUIT BREA-
FOR PROTECTION AGAINST PUBLIC LIABILITY AND PROPERTY
KERS SHALL BE COMMON TRIP. TIE HANDLES ARE NOT PERMI-
DAMAGE FOR THE DURATION OF THE WORK.
TTED.
4.
THE CONTRACTOR SHALL GUARANTEE ALL MATERIALS AND
30.
ALL ELECTRICAL EQUIPMENT SHALL BE RAINTIGHT (NEMA 3R)
WORKMANSHIP FREE FROM DEFECTS FOR A PERIOD OF NOT
WHERE EXPOSED TO THE WEATHER. ALL FLEX CONDUITS CO-
LESS THAN (1) YEAR FROM DATE OF FINAL ACCEPTANCE.
NNECTED TO SUCH EQUIPMENT SHALL BE LIQUIDTIGHT.
5.
IT SHALL NOT BE THE INTENT OF THESE PLANS AND SPECIFI-
31.
OUTLET BOXES SHALL BE PRESSED STEEL IN DRY LOCATIONS,
CATIONS TO SHOW EVERY MINOR DETAIL OF CONSTRUCTION.
CAST ALLOY WITH THREADED HUBS IN WET OR DAMP LOCA--
CONTRACTOR SHALL FURNISH AND INSTALL ANY ADDITIONAL
TIONS, AND SPECIAL ENCLOSURES".AS: REQUIRED FOR OTHER
CONDUIT, BOXES AND WIRING NECESSARY FOR A COMPLETE
CLASSIFIED AREAS, U.O.N.
ELECTRICAL SYSTEM AND PROVIDE ALL REQUIREMENTS FOR
A
EQUIPMENT TO BE PLACED IN PROPER WORKING ORDER.
32.
PROVIDE ALL FIXTURES WITH LAMPS, VERIFY TYPE WITH MANU-
FACTURER.
6.
THE CONTRACTOR SHALL BE RESPONSIBLE FOR REPAIRING TO
ORIGINAL CONDITIONS ANY AND ALL DAMAGES TO BUILDING
33.
ALL OPENINGS FOR LIGHT FIXTURES IN CEILINGS SHALL BE
SURFACES, EQUIPMENT, ETC. CAUSED DURING THE PERFOR-
PROTECTED IN A MANNER (PER ALL GOVERNING CODES) THAT
MANCE OF WORK.
WILL PROVIDE THE SAME RATING AS THE COILING. THIS APPLIES
TO ALL FIRE RATED CEILINGS.
7.
CORRECTION OF ANY DEFECTS SHALL BE COMPLETED WITHOUT
ADDITIONAL CHARGE OR DELAYS AND SHALL INCLUDE REPLACE-
34.
ELECTRICAL CONTRACTOR SHALL VERIFY THE CEILING FINISHES
MENT OR REPAIR OF ANY OTHER PHASE OF THE INSTALLATION
AND SUSPENSION SYSTEMS FOR SELECTION OF PROPER TRIMS
WHICH MAY HAVE BEEN DAMAGED THEREBY.
MORMONISM
AND SUPPORT ARRANGEMENTS FOR LIGHTING FIXTURES.
8.
THE CONTRACTOR SHALL VISIT THE JOB SITE AND VERIFY ALL
35.
ALL LIGHTING SWITCHES AND/OR DIMMERS SHALL BE GANGED
EXISTING CONDITIONS, AND SHALL THOROUGHLY REVIEW ALL
TOGETHER WHERE SHOWN TOGETHER.
DRAWINGS, SPECIFICATIONS AND POSSIBLE ADDENDA PRIOR TO
36.
ALL CONNECTIONS TO GROUND RODS SHALL BE MADE WITH UL
BIDDING ON HIS WORK. NO EXTRAS TO HIS CONTRACT WILL BE
APPROVED WELDED CONNECTIONS, UNLESS NOTED OTHERWISE.
EU®a��00
ALLOWED FOR FAILURE TO COMPLY WITH THIS REQUIREMENT.
THE CONTRACTOR SHALL FORM A GROUNDING ELECTRODE SYS-
9.
THE CONTRACTOR SHALL NOT SCALE THE ELECTRICAL DWGS.
m 1
*401101111M, 171M
REFER TO ARCHITECTURAL PLANS AND ELEVATIONS FOR EXACT
37.
ALL ELECTRICAL EQUIPMENT SHALL BE INSTALLED IN ACCESIBLE
LOCATIONS OF ALL EQUIPMENT UNLESS NOTED OTHERWISE.
rox M r.. �-
10.
CONTRACTOR SHALL COORDINATE HIS WORK WITH THE GENERAL
38.
THE ELECTRICAL INSTALLATION SHALL MEET ALL STANDARD RE-
CONTRACTOR SO THAT INTERFERENCE WITH OTHER TRADES BE
�M
AVOIDED.
39.
LIGHTING FIXTURES DESCRIBED HEREIN ARE INTENDED TO INDI-
11.
IT SHALL BE THE RESPONSIBILITY OF THE ELECTRICAL CON-
CATE THE GENERAL FIXTURE TYPE, WHICH SHALL BE SUBSTAN-
TRACTOR TO PROVIDE ALL LABOR, MATERIALS AND NECESSARY
TIALLY AS SPECIFIED. IT IS NOT THE INTENT OF THIS SPECIFI-
SUPERVISION TO ACCOMPLISH THE WORK AS SHOWN AND/OR
CATIONS TO REQUIRE THE PRODUCT OF ANY PARTICULAR MA --
NOTED ON THE PLANS.
NUFACTUREIR WHOSE PRODUCT IS SPECIFIED.
12.
IT SHALL BE THE RESPONSIBILITY OF THE ELECTRICAL CON-
40.
CONNECT ALL EMERGENCY AND EXIT LIGHTS TO INDICATED CIR-
TRACTOR FOR THE ADVANCE ORDERING OF LONG LEAD ITEMS,
•�10
"S
AS TO NOT INTERFERE WITH THE WORK OF OTHER TRADES
RESULTING IN ANY DOWN OR LAC TIME. THE CONTRACTOR
41.
PROPER PLASTER RINGS SHALL BE USED WITH OUTLET BOXES.
SHALL NOT ORDER ANY ITEMS UNTIL APPROVED SHOP DWGS.
PLASTER RINGS SHALL BE A MAXIMUM OF 1/8" -FROM THE -
ARE RETURNED TO HIM.
FINISHED SURFACE OF THE DRYWALL AFTER THE `DRYWALL IS
INSTALLED. PROPER COORDINATION BETWEEN THE ELECTRICAL
13.
CONTRACTOR SHALL COORDINATE SERVICES WITH THE RESPEC-
CONTRACTOR AND THE GENERAL CONTRACTOR FOR"RING INSTA-'
TIVE UTILITY COMPANIES.
LILATION IS REQUIRED. ALL OUTLET BOXES SHALL BE SECURELY,
14.
CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFICATION OF
FASTENED. ANY AND ALL IMPROPERLY INSTALLED-` PLASTER RING
CEILING CONSTRUCTION BEFORE ORDERING OR INSTALLING ANY
OR OUTLET BOXES SHALL BE REMOVED AND A NEW RING OR
LIGHT FIXTURES.
1 MY 11110 1.4
15.
ALL CONDUCTORS SHALL BE STRANDED COPPER, TYPE THHN/
THWN, EXCEPT WHERE OTHERWISE REQUIRED BY U.L OR ANY
42.
APPROVAL SHALL BE OBTAINED FROM AN STRUCT. ENGINEER
CODE. MINIMUM WIRE SIZE SHALL BE 12 AWG, EXCLUDING
PRIOR TO CUTTING OR DRILLING ANY STRUCTURAL SUPPORT
CONTROL WIRING.
MEMBER.
16.
ALL CONDUCTORS SHALL BE IN CONDUITS. CONDUITS SHALL
43.
INSTALL POWER AND CONTROL WIRING AND REQUIRED CONTROL
BE GALVANIZED RIGID STEEL (GRC) EXCEPT THAT:
COMPONENTS FOR A/C SYSTEMS AS SHOWN/NOTED ON THESE
(A) PVC CONDUITS MAY BE USED UNDERGROUND PROVIDED
DRAWINGS AND PER OTHER APPLICABLE DRAWINGS/INSTRUCTIONS.
ELBOWS AND RISERS ARE GRC; (B) ELECTRICAL METALLIC
SEE AIR CONDITIONING DRAWING:,
TUBING (EMT) MAY BE USED IN OR ON WALLS OR CEILINGS
44.
ALL MATERIAL REMOVED SHALL, BE "DISPOSED OF AS DIRECTED
WHERE NOT SUBJECT TO MECHANICAL DAMAGE, DAMP OR CO-
RROSIVE CONDITIONS; (C) LIQUIDTIGHT FLEXIBLE CONDUIT
BY OWNER.
WHERE REQUIRED; (D) FLEXIBLE METALLIC CONDUIT WHERE
45.
EMPTY CONDUITS TO BE PROVIDED WITH NYLON PULL STRINGS.
REQUIRED IN DRY LOCACATIONS ONLY. ALL CONDUITS IN HA-
ZARDOUS AREAS (PER NEC) SHALL MEET THE REQUIREMENTS
46.
CONTRACTOR IS RESPONSIBLE FOR PROVIDING ALL WIRING, BKR,
OF NEC CHAPTER 5.
AND FUSE; SIZES IN ACCORDANCE WITH A/C EQUIPMENT NAMEPLATE
17.
APPLY TWO COATS OF BITUMASTIC (KOPPERS 60) TO ALL ME-
IF DIFFERENT FROM THAT SPECIFIED ON DWGS, AS WELL AS ANY
TALLIC CONDUITS IN SLABS OR UNDERGROUND. EMT IS NOT
FEEDER CHANGES BEING AFFECTED BY THIS CHANGE. CONTRACTOR
PERMITTED IN SLABS. ALUMINUM CONDUITS ARE NOT PERMI-
SHALL MAKE ABOVE MENTIONED CHANGES AT NO EXTRA COST.
TIED ANYWHERE.
47.
CONTRACTOR, SHALL COORDINATE ALL HIS WORK WITH OTHER
18.
FLEXIBLE CONDUIT SHALL BE USED FOR CONNECTIONS TO VI-
1 IN IN 3 R
BRATING EQUIPMENT AND RECESSED LIGHT FIXTURES, WHERE
AND RACEWAYS AS SHOWN ON THE A/C DRAWINGS AND/OR
PERMITTED BY CODE.
SPECIFICATIONS. AIR CONDITIONING DRAWINGS REFER TO
MANUFACTURERS WIRING DIAGRAMS, THE CONTRACTOR SHALL VERIFY
19.
FOR UNDERGROUND ELECTRICAL CONDUITS, PROVIDE PULL BO-
WITH SAID MANUFACTURER ALL REQUIREMENTS AND INCLUDE ALL
XES SUCH THAT NO SINGLE CONDUCE RUN HAS BENDS IN EX-
RELATED WORK IN HIS CONTRACT.
CESS OF 360 DEGREES, OR 180 DEGREES FOR TELEPHONE.
01
PULL BOXES SHALL BE SUITABLE AND APPROVED FOR THE IN-
48.
ALL LUMINARIES SHALL BE PROPERLY SUPPORTED IN ACCORDAN-
TENDED USE AND WITH IRON COVERS. WARNING TAPES WHICH
LOAD CALCULAT[ON
CONNECTED LOA D�- 14,400 VA
ALL BREAKERS TO HAVE 10,000 AIC TOTAL LOAD 14,400 NTA 40 Amps
!TYPE- EMSTING BUS RATINQ 225A
�SERVICF- 30,4w MAINS: MLO
VOLTAGE- 12G208 PANEL NLB5B POLES: 42
MOUNTING: FLUSH (SBC-TIONT-1) FEEDER- EXISTING
LOCATION. SHOWN • PLANS NEUTRAL EMSTING
ELECTRICAL NOTES:
1.
THE ENTIRE INSTALLATION SHALL BE IN ACCORDANCE WITH
27.
RH a,
THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE(NEC),
TED OR REQUIRED, WITH OVERLOAD RELAYS OR FUSES-IN EACH
AND THE LATEST EDITION OF THE FLORIDA BUILDING CODE
HOT LEG.
AND ANY OTHER APPLICABLE FEDERAL, STATE AND LOCAL
CODES.
28.
FURNISH AND INSTALL DISCONNECT SWITCHES AND WIRING FOR
2.
ALL WORK SHALL BE PERFORMED BY A LICENSED ELECTRICAL
1 IN 010 IrAyAll
CONTRACTOR IN A FIRST CLASS WORKMANLIKE MANNER . SAID
THE HVAC CONTRACTOR AND INSTALLED BY THE ELECTRICAL
CONTRACTOR SHALL MEET All REQUIREMENTS SET FORTH BY
CONTRACTOR.
ANY LOCAL ORDINANCE AND GOVERNING AUTHORITIES.
29,
ALL CIRCUIT BREAKERS SHALL BE OF THE INVERSE 11ME TYPE
3.
THE CONTRACTOR SHALL PROVIDE ALL REQUIRED INSURANCE
(THERMAL-MAGNETIC). TWO AND THREE POLE CIRCUIT BREA-
FOR PROTECTION AGAINST PUBLIC LIABILITY AND PROPERTY
KERS SHALL BE COMMON TRIP. TIE HANDLES ARE NOT PERMI-
DAMAGE FOR THE DURATION OF THE WORK.
TTED.
4.
THE CONTRACTOR SHALL GUARANTEE ALL MATERIALS AND
30.
ALL ELECTRICAL EQUIPMENT SHALL BE RAINTIGHT (NEMA 3R)
WORKMANSHIP FREE FROM DEFECTS FOR A PERIOD OF NOT
WHERE EXPOSED TO THE WEATHER. ALL FLEX CONDUITS CO-
LESS THAN (1) YEAR FROM DATE OF FINAL ACCEPTANCE.
NNECTED TO SUCH EQUIPMENT SHALL BE LIQUIDTIGHT.
5.
IT SHALL NOT BE THE INTENT OF THESE PLANS AND SPECIFI-
31.
OUTLET BOXES SHALL BE PRESSED STEEL IN DRY LOCATIONS,
CATIONS TO SHOW EVERY MINOR DETAIL OF CONSTRUCTION.
CAST ALLOY WITH THREADED HUBS IN WET OR DAMP LOCA--
CONTRACTOR SHALL FURNISH AND INSTALL ANY ADDITIONAL
TIONS, AND SPECIAL ENCLOSURES".AS: REQUIRED FOR OTHER
CONDUIT, BOXES AND WIRING NECESSARY FOR A COMPLETE
CLASSIFIED AREAS, U.O.N.
ELECTRICAL SYSTEM AND PROVIDE ALL REQUIREMENTS FOR
A
EQUIPMENT TO BE PLACED IN PROPER WORKING ORDER.
32.
PROVIDE ALL FIXTURES WITH LAMPS, VERIFY TYPE WITH MANU-
FACTURER.
6.
THE CONTRACTOR SHALL BE RESPONSIBLE FOR REPAIRING TO
ORIGINAL CONDITIONS ANY AND ALL DAMAGES TO BUILDING
33.
ALL OPENINGS FOR LIGHT FIXTURES IN CEILINGS SHALL BE
SURFACES, EQUIPMENT, ETC. CAUSED DURING THE PERFOR-
PROTECTED IN A MANNER (PER ALL GOVERNING CODES) THAT
MANCE OF WORK.
WILL PROVIDE THE SAME RATING AS THE COILING. THIS APPLIES
TO ALL FIRE RATED CEILINGS.
7.
CORRECTION OF ANY DEFECTS SHALL BE COMPLETED WITHOUT
ADDITIONAL CHARGE OR DELAYS AND SHALL INCLUDE REPLACE-
34.
ELECTRICAL CONTRACTOR SHALL VERIFY THE CEILING FINISHES
MENT OR REPAIR OF ANY OTHER PHASE OF THE INSTALLATION
AND SUSPENSION SYSTEMS FOR SELECTION OF PROPER TRIMS
WHICH MAY HAVE BEEN DAMAGED THEREBY.
MORMONISM
AND SUPPORT ARRANGEMENTS FOR LIGHTING FIXTURES.
8.
THE CONTRACTOR SHALL VISIT THE JOB SITE AND VERIFY ALL
35.
ALL LIGHTING SWITCHES AND/OR DIMMERS SHALL BE GANGED
EXISTING CONDITIONS, AND SHALL THOROUGHLY REVIEW ALL
TOGETHER WHERE SHOWN TOGETHER.
DRAWINGS, SPECIFICATIONS AND POSSIBLE ADDENDA PRIOR TO
36.
ALL CONNECTIONS TO GROUND RODS SHALL BE MADE WITH UL
BIDDING ON HIS WORK. NO EXTRAS TO HIS CONTRACT WILL BE
APPROVED WELDED CONNECTIONS, UNLESS NOTED OTHERWISE.
EU®a��00
ALLOWED FOR FAILURE TO COMPLY WITH THIS REQUIREMENT.
THE CONTRACTOR SHALL FORM A GROUNDING ELECTRODE SYS-
9.
THE CONTRACTOR SHALL NOT SCALE THE ELECTRICAL DWGS.
m 1
*401101111M, 171M
REFER TO ARCHITECTURAL PLANS AND ELEVATIONS FOR EXACT
37.
ALL ELECTRICAL EQUIPMENT SHALL BE INSTALLED IN ACCESIBLE
LOCATIONS OF ALL EQUIPMENT UNLESS NOTED OTHERWISE.
rox M r.. �-
10.
CONTRACTOR SHALL COORDINATE HIS WORK WITH THE GENERAL
38.
THE ELECTRICAL INSTALLATION SHALL MEET ALL STANDARD RE-
CONTRACTOR SO THAT INTERFERENCE WITH OTHER TRADES BE
�M
AVOIDED.
39.
LIGHTING FIXTURES DESCRIBED HEREIN ARE INTENDED TO INDI-
11.
IT SHALL BE THE RESPONSIBILITY OF THE ELECTRICAL CON-
CATE THE GENERAL FIXTURE TYPE, WHICH SHALL BE SUBSTAN-
TRACTOR TO PROVIDE ALL LABOR, MATERIALS AND NECESSARY
TIALLY AS SPECIFIED. IT IS NOT THE INTENT OF THIS SPECIFI-
SUPERVISION TO ACCOMPLISH THE WORK AS SHOWN AND/OR
CATIONS TO REQUIRE THE PRODUCT OF ANY PARTICULAR MA --
NOTED ON THE PLANS.
NUFACTUREIR WHOSE PRODUCT IS SPECIFIED.
12.
IT SHALL BE THE RESPONSIBILITY OF THE ELECTRICAL CON-
40.
CONNECT ALL EMERGENCY AND EXIT LIGHTS TO INDICATED CIR-
TRACTOR FOR THE ADVANCE ORDERING OF LONG LEAD ITEMS,
•�10
"S
AS TO NOT INTERFERE WITH THE WORK OF OTHER TRADES
RESULTING IN ANY DOWN OR LAC TIME. THE CONTRACTOR
41.
PROPER PLASTER RINGS SHALL BE USED WITH OUTLET BOXES.
SHALL NOT ORDER ANY ITEMS UNTIL APPROVED SHOP DWGS.
PLASTER RINGS SHALL BE A MAXIMUM OF 1/8" -FROM THE -
ARE RETURNED TO HIM.
FINISHED SURFACE OF THE DRYWALL AFTER THE `DRYWALL IS
INSTALLED. PROPER COORDINATION BETWEEN THE ELECTRICAL
13.
CONTRACTOR SHALL COORDINATE SERVICES WITH THE RESPEC-
CONTRACTOR AND THE GENERAL CONTRACTOR FOR"RING INSTA-'
TIVE UTILITY COMPANIES.
LILATION IS REQUIRED. ALL OUTLET BOXES SHALL BE SECURELY,
14.
CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFICATION OF
FASTENED. ANY AND ALL IMPROPERLY INSTALLED-` PLASTER RING
CEILING CONSTRUCTION BEFORE ORDERING OR INSTALLING ANY
OR OUTLET BOXES SHALL BE REMOVED AND A NEW RING OR
LIGHT FIXTURES.
1 MY 11110 1.4
15.
ALL CONDUCTORS SHALL BE STRANDED COPPER, TYPE THHN/
THWN, EXCEPT WHERE OTHERWISE REQUIRED BY U.L OR ANY
42.
APPROVAL SHALL BE OBTAINED FROM AN STRUCT. ENGINEER
CODE. MINIMUM WIRE SIZE SHALL BE 12 AWG, EXCLUDING
PRIOR TO CUTTING OR DRILLING ANY STRUCTURAL SUPPORT
CONTROL WIRING.
MEMBER.
16.
ALL CONDUCTORS SHALL BE IN CONDUITS. CONDUITS SHALL
43.
INSTALL POWER AND CONTROL WIRING AND REQUIRED CONTROL
BE GALVANIZED RIGID STEEL (GRC) EXCEPT THAT:
COMPONENTS FOR A/C SYSTEMS AS SHOWN/NOTED ON THESE
(A) PVC CONDUITS MAY BE USED UNDERGROUND PROVIDED
DRAWINGS AND PER OTHER APPLICABLE DRAWINGS/INSTRUCTIONS.
ELBOWS AND RISERS ARE GRC; (B) ELECTRICAL METALLIC
SEE AIR CONDITIONING DRAWING:,
TUBING (EMT) MAY BE USED IN OR ON WALLS OR CEILINGS
44.
ALL MATERIAL REMOVED SHALL, BE "DISPOSED OF AS DIRECTED
WHERE NOT SUBJECT TO MECHANICAL DAMAGE, DAMP OR CO-
RROSIVE CONDITIONS; (C) LIQUIDTIGHT FLEXIBLE CONDUIT
BY OWNER.
WHERE REQUIRED; (D) FLEXIBLE METALLIC CONDUIT WHERE
45.
EMPTY CONDUITS TO BE PROVIDED WITH NYLON PULL STRINGS.
REQUIRED IN DRY LOCACATIONS ONLY. ALL CONDUITS IN HA-
ZARDOUS AREAS (PER NEC) SHALL MEET THE REQUIREMENTS
46.
CONTRACTOR IS RESPONSIBLE FOR PROVIDING ALL WIRING, BKR,
OF NEC CHAPTER 5.
AND FUSE; SIZES IN ACCORDANCE WITH A/C EQUIPMENT NAMEPLATE
17.
APPLY TWO COATS OF BITUMASTIC (KOPPERS 60) TO ALL ME-
IF DIFFERENT FROM THAT SPECIFIED ON DWGS, AS WELL AS ANY
TALLIC CONDUITS IN SLABS OR UNDERGROUND. EMT IS NOT
FEEDER CHANGES BEING AFFECTED BY THIS CHANGE. CONTRACTOR
PERMITTED IN SLABS. ALUMINUM CONDUITS ARE NOT PERMI-
SHALL MAKE ABOVE MENTIONED CHANGES AT NO EXTRA COST.
TIED ANYWHERE.
47.
CONTRACTOR, SHALL COORDINATE ALL HIS WORK WITH OTHER
18.
FLEXIBLE CONDUIT SHALL BE USED FOR CONNECTIONS TO VI-
1 IN IN 3 R
BRATING EQUIPMENT AND RECESSED LIGHT FIXTURES, WHERE
AND RACEWAYS AS SHOWN ON THE A/C DRAWINGS AND/OR
PERMITTED BY CODE.
SPECIFICATIONS. AIR CONDITIONING DRAWINGS REFER TO
MANUFACTURERS WIRING DIAGRAMS, THE CONTRACTOR SHALL VERIFY
19.
FOR UNDERGROUND ELECTRICAL CONDUITS, PROVIDE PULL BO-
WITH SAID MANUFACTURER ALL REQUIREMENTS AND INCLUDE ALL
XES SUCH THAT NO SINGLE CONDUCE RUN HAS BENDS IN EX-
RELATED WORK IN HIS CONTRACT.
CESS OF 360 DEGREES, OR 180 DEGREES FOR TELEPHONE.
01
PULL BOXES SHALL BE SUITABLE AND APPROVED FOR THE IN-
48.
ALL LUMINARIES SHALL BE PROPERLY SUPPORTED IN ACCORDAN-
TENDED USE AND WITH IRON COVERS. WARNING TAPES WHICH
KERS TO HAVE 10,000 AIC
WAD CALCULATION
CONNECTED LOAD= 25,500 VA
TOTAL LOAD (SECT.-1 +SECL-2) = 30,120 VA 84 Amps
'ITYPE- EM STING BUS RATING: 225A
3(D,4w MAINS: MLO
VOLTAGE- 120/208 PANEL NLB5B POLES: 42
MOUNTING: FLUSH (SEMON-2) FEEDER-- EXISTING
LOCATION. SHOWN ON PLANS NEUTRA L EXISTING
ELECTRICAL NOTES:
1.
THE ENTIRE INSTALLATION SHALL BE IN ACCORDANCE WITH
27.
RH a,
THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE(NEC),
TED OR REQUIRED, WITH OVERLOAD RELAYS OR FUSES-IN EACH
AND THE LATEST EDITION OF THE FLORIDA BUILDING CODE
HOT LEG.
AND ANY OTHER APPLICABLE FEDERAL, STATE AND LOCAL
CODES.
28.
FURNISH AND INSTALL DISCONNECT SWITCHES AND WIRING FOR
2.
ALL WORK SHALL BE PERFORMED BY A LICENSED ELECTRICAL
TE RECOMMENDATIONS. CONTROLS ARE TO BE SUPPLIED BY
CONTRACTOR IN A FIRST CLASS WORKMANLIKE MANNER . SAID
THE HVAC CONTRACTOR AND INSTALLED BY THE ELECTRICAL
CONTRACTOR SHALL MEET All REQUIREMENTS SET FORTH BY
CONTRACTOR.
ANY LOCAL ORDINANCE AND GOVERNING AUTHORITIES.
29,
ALL CIRCUIT BREAKERS SHALL BE OF THE INVERSE 11ME TYPE
3.
THE CONTRACTOR SHALL PROVIDE ALL REQUIRED INSURANCE
(THERMAL-MAGNETIC). TWO AND THREE POLE CIRCUIT BREA-
FOR PROTECTION AGAINST PUBLIC LIABILITY AND PROPERTY
KERS SHALL BE COMMON TRIP. TIE HANDLES ARE NOT PERMI-
DAMAGE FOR THE DURATION OF THE WORK.
TTED.
4.
THE CONTRACTOR SHALL GUARANTEE ALL MATERIALS AND
30.
ALL ELECTRICAL EQUIPMENT SHALL BE RAINTIGHT (NEMA 3R)
WORKMANSHIP FREE FROM DEFECTS FOR A PERIOD OF NOT
WHERE EXPOSED TO THE WEATHER. ALL FLEX CONDUITS CO-
LESS THAN (1) YEAR FROM DATE OF FINAL ACCEPTANCE.
NNECTED TO SUCH EQUIPMENT SHALL BE LIQUIDTIGHT.
5.
IT SHALL NOT BE THE INTENT OF THESE PLANS AND SPECIFI-
31.
OUTLET BOXES SHALL BE PRESSED STEEL IN DRY LOCATIONS,
CATIONS TO SHOW EVERY MINOR DETAIL OF CONSTRUCTION.
CAST ALLOY WITH THREADED HUBS IN WET OR DAMP LOCA--
CONTRACTOR SHALL FURNISH AND INSTALL ANY ADDITIONAL
TIONS, AND SPECIAL ENCLOSURES".AS: REQUIRED FOR OTHER
CONDUIT, BOXES AND WIRING NECESSARY FOR A COMPLETE
CLASSIFIED AREAS, U.O.N.
ELECTRICAL SYSTEM AND PROVIDE ALL REQUIREMENTS FOR
A
EQUIPMENT TO BE PLACED IN PROPER WORKING ORDER.
32.
PROVIDE ALL FIXTURES WITH LAMPS, VERIFY TYPE WITH MANU-
FACTURER.
6.
THE CONTRACTOR SHALL BE RESPONSIBLE FOR REPAIRING TO
ORIGINAL CONDITIONS ANY AND ALL DAMAGES TO BUILDING
33.
ALL OPENINGS FOR LIGHT FIXTURES IN CEILINGS SHALL BE
SURFACES, EQUIPMENT, ETC. CAUSED DURING THE PERFOR-
PROTECTED IN A MANNER (PER ALL GOVERNING CODES) THAT
MANCE OF WORK.
WILL PROVIDE THE SAME RATING AS THE COILING. THIS APPLIES
TO ALL FIRE RATED CEILINGS.
7.
CORRECTION OF ANY DEFECTS SHALL BE COMPLETED WITHOUT
ADDITIONAL CHARGE OR DELAYS AND SHALL INCLUDE REPLACE-
34.
ELECTRICAL CONTRACTOR SHALL VERIFY THE CEILING FINISHES
MENT OR REPAIR OF ANY OTHER PHASE OF THE INSTALLATION
AND SUSPENSION SYSTEMS FOR SELECTION OF PROPER TRIMS
WHICH MAY HAVE BEEN DAMAGED THEREBY.
AND SUPPORT ARRANGEMENTS FOR LIGHTING FIXTURES.
8.
THE CONTRACTOR SHALL VISIT THE JOB SITE AND VERIFY ALL
35.
ALL LIGHTING SWITCHES AND/OR DIMMERS SHALL BE GANGED
EXISTING CONDITIONS, AND SHALL THOROUGHLY REVIEW ALL
TOGETHER WHERE SHOWN TOGETHER.
DRAWINGS, SPECIFICATIONS AND POSSIBLE ADDENDA PRIOR TO
36.
ALL CONNECTIONS TO GROUND RODS SHALL BE MADE WITH UL
BIDDING ON HIS WORK. NO EXTRAS TO HIS CONTRACT WILL BE
FAN M N 1.1 1.4 Will 1.4 a " 061 *9 rim:1111 [111101,1741%
LOAD CALCUTAT]ON
CONNECTED LOAD= 4,620 VA
TOTAL LOAD = 4,620 VA 13 Amps
NOTE:
ALL PANELS ARE EXISTING. CIRCUIT NUMBERS SHOWN ARE TO DETERMINE THE
NUMBER OF REQUIRED Ib AND NOT ACTUAL CIRCUR NUMBERS FOUND IN
THE FIELD. CONTRACTOR MAY CHANGE SHOWN CIRCUIT NUMBERS TO COORDINATE
WITH FIELD CONDITIONS. IT IS ASSUMED THAT SOME CIRCUITS WILL BECOME
AVAILABLE AFTER DEMOLITION OF SPACE, WHICH CAN BE REUSED FOR THIS
TENANT. VERIFY THIS AND ADVISE ENGINEER IF THIS IS NOT THE CASE.
N
111 Jl�ll 1.
desi g n
2930 Northeast 2nd Court
Miami, FL 33137
305.545.4964
AA0003130 ID0003964
ti
♦
♦
ti
L0
0
L0 0
5
CL
Cf)
0
CO
cf)
Cl) Cc
13
CY) 0 Oily
U- >
C
E
CF
0
coC,
0 0
0 1
e4
W I
M
r
ELECTRICAL NOTES:
1.
THE ENTIRE INSTALLATION SHALL BE IN ACCORDANCE WITH
27.
MOTORS STARTERS SHALL BE MANUAL OR MAGNETIC-AS INDICA-
THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE(NEC),
TED OR REQUIRED, WITH OVERLOAD RELAYS OR FUSES-IN EACH
AND THE LATEST EDITION OF THE FLORIDA BUILDING CODE
HOT LEG.
AND ANY OTHER APPLICABLE FEDERAL, STATE AND LOCAL
CODES.
28.
FURNISH AND INSTALL DISCONNECT SWITCHES AND WIRING FOR
2.
ALL WORK SHALL BE PERFORMED BY A LICENSED ELECTRICAL
TE RECOMMENDATIONS. CONTROLS ARE TO BE SUPPLIED BY
CONTRACTOR IN A FIRST CLASS WORKMANLIKE MANNER . SAID
THE HVAC CONTRACTOR AND INSTALLED BY THE ELECTRICAL
CONTRACTOR SHALL MEET All REQUIREMENTS SET FORTH BY
CONTRACTOR.
ANY LOCAL ORDINANCE AND GOVERNING AUTHORITIES.
29,
ALL CIRCUIT BREAKERS SHALL BE OF THE INVERSE 11ME TYPE
3.
THE CONTRACTOR SHALL PROVIDE ALL REQUIRED INSURANCE
(THERMAL-MAGNETIC). TWO AND THREE POLE CIRCUIT BREA-
FOR PROTECTION AGAINST PUBLIC LIABILITY AND PROPERTY
KERS SHALL BE COMMON TRIP. TIE HANDLES ARE NOT PERMI-
DAMAGE FOR THE DURATION OF THE WORK.
TTED.
4.
THE CONTRACTOR SHALL GUARANTEE ALL MATERIALS AND
30.
ALL ELECTRICAL EQUIPMENT SHALL BE RAINTIGHT (NEMA 3R)
WORKMANSHIP FREE FROM DEFECTS FOR A PERIOD OF NOT
WHERE EXPOSED TO THE WEATHER. ALL FLEX CONDUITS CO-
LESS THAN (1) YEAR FROM DATE OF FINAL ACCEPTANCE.
NNECTED TO SUCH EQUIPMENT SHALL BE LIQUIDTIGHT.
5.
IT SHALL NOT BE THE INTENT OF THESE PLANS AND SPECIFI-
31.
OUTLET BOXES SHALL BE PRESSED STEEL IN DRY LOCATIONS,
CATIONS TO SHOW EVERY MINOR DETAIL OF CONSTRUCTION.
CAST ALLOY WITH THREADED HUBS IN WET OR DAMP LOCA--
CONTRACTOR SHALL FURNISH AND INSTALL ANY ADDITIONAL
TIONS, AND SPECIAL ENCLOSURES".AS: REQUIRED FOR OTHER
CONDUIT, BOXES AND WIRING NECESSARY FOR A COMPLETE
CLASSIFIED AREAS, U.O.N.
ELECTRICAL SYSTEM AND PROVIDE ALL REQUIREMENTS FOR
A
EQUIPMENT TO BE PLACED IN PROPER WORKING ORDER.
32.
PROVIDE ALL FIXTURES WITH LAMPS, VERIFY TYPE WITH MANU-
FACTURER.
6.
THE CONTRACTOR SHALL BE RESPONSIBLE FOR REPAIRING TO
ORIGINAL CONDITIONS ANY AND ALL DAMAGES TO BUILDING
33.
ALL OPENINGS FOR LIGHT FIXTURES IN CEILINGS SHALL BE
SURFACES, EQUIPMENT, ETC. CAUSED DURING THE PERFOR-
PROTECTED IN A MANNER (PER ALL GOVERNING CODES) THAT
MANCE OF WORK.
WILL PROVIDE THE SAME RATING AS THE COILING. THIS APPLIES
TO ALL FIRE RATED CEILINGS.
7.
CORRECTION OF ANY DEFECTS SHALL BE COMPLETED WITHOUT
ADDITIONAL CHARGE OR DELAYS AND SHALL INCLUDE REPLACE-
34.
ELECTRICAL CONTRACTOR SHALL VERIFY THE CEILING FINISHES
MENT OR REPAIR OF ANY OTHER PHASE OF THE INSTALLATION
AND SUSPENSION SYSTEMS FOR SELECTION OF PROPER TRIMS
WHICH MAY HAVE BEEN DAMAGED THEREBY.
AND SUPPORT ARRANGEMENTS FOR LIGHTING FIXTURES.
8.
THE CONTRACTOR SHALL VISIT THE JOB SITE AND VERIFY ALL
35.
ALL LIGHTING SWITCHES AND/OR DIMMERS SHALL BE GANGED
EXISTING CONDITIONS, AND SHALL THOROUGHLY REVIEW ALL
TOGETHER WHERE SHOWN TOGETHER.
DRAWINGS, SPECIFICATIONS AND POSSIBLE ADDENDA PRIOR TO
36.
ALL CONNECTIONS TO GROUND RODS SHALL BE MADE WITH UL
BIDDING ON HIS WORK. NO EXTRAS TO HIS CONTRACT WILL BE
APPROVED WELDED CONNECTIONS, UNLESS NOTED OTHERWISE.
ALLOWED FOR FAILURE TO COMPLY WITH THIS REQUIREMENT.
THE CONTRACTOR SHALL FORM A GROUNDING ELECTRODE SYS-
9.
THE CONTRACTOR SHALL NOT SCALE THE ELECTRICAL DWGS.
TEM AS PER NEC ARTICLE 250.
REFER TO ARCHITECTURAL PLANS AND ELEVATIONS FOR EXACT
37.
ALL ELECTRICAL EQUIPMENT SHALL BE INSTALLED IN ACCESIBLE
LOCATIONS OF ALL EQUIPMENT UNLESS NOTED OTHERWISE.
AREAS ONLY.
10.
CONTRACTOR SHALL COORDINATE HIS WORK WITH THE GENERAL
38.
THE ELECTRICAL INSTALLATION SHALL MEET ALL STANDARD RE-
CONTRACTOR SO THAT INTERFERENCE WITH OTHER TRADES BE
QUIREMENTS OF POWER AND TELEPHONE COMPANIES.
AVOIDED.
39.
LIGHTING FIXTURES DESCRIBED HEREIN ARE INTENDED TO INDI-
11.
IT SHALL BE THE RESPONSIBILITY OF THE ELECTRICAL CON-
CATE THE GENERAL FIXTURE TYPE, WHICH SHALL BE SUBSTAN-
TRACTOR TO PROVIDE ALL LABOR, MATERIALS AND NECESSARY
TIALLY AS SPECIFIED. IT IS NOT THE INTENT OF THIS SPECIFI-
SUPERVISION TO ACCOMPLISH THE WORK AS SHOWN AND/OR
CATIONS TO REQUIRE THE PRODUCT OF ANY PARTICULAR MA --
NOTED ON THE PLANS.
NUFACTUREIR WHOSE PRODUCT IS SPECIFIED.
12.
IT SHALL BE THE RESPONSIBILITY OF THE ELECTRICAL CON-
40.
CONNECT ALL EMERGENCY AND EXIT LIGHTS TO INDICATED CIR-
TRACTOR FOR THE ADVANCE ORDERING OF LONG LEAD ITEMS,
CUITS AHEAD OF ANY SWITCH.
AS TO NOT INTERFERE WITH THE WORK OF OTHER TRADES
RESULTING IN ANY DOWN OR LAC TIME. THE CONTRACTOR
41.
PROPER PLASTER RINGS SHALL BE USED WITH OUTLET BOXES.
SHALL NOT ORDER ANY ITEMS UNTIL APPROVED SHOP DWGS.
PLASTER RINGS SHALL BE A MAXIMUM OF 1/8" -FROM THE -
ARE RETURNED TO HIM.
FINISHED SURFACE OF THE DRYWALL AFTER THE `DRYWALL IS
INSTALLED. PROPER COORDINATION BETWEEN THE ELECTRICAL
13.
CONTRACTOR SHALL COORDINATE SERVICES WITH THE RESPEC-
CONTRACTOR AND THE GENERAL CONTRACTOR FOR"RING INSTA-'
TIVE UTILITY COMPANIES.
LILATION IS REQUIRED. ALL OUTLET BOXES SHALL BE SECURELY,
14.
CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFICATION OF
FASTENED. ANY AND ALL IMPROPERLY INSTALLED-` PLASTER RING
CEILING CONSTRUCTION BEFORE ORDERING OR INSTALLING ANY
OR OUTLET BOXES SHALL BE REMOVED AND A NEW RING OR
LIGHT FIXTURES.
OUTLET INSTALLED AT THE CONTRACTOR'S EXPENSE.
15.
ALL CONDUCTORS SHALL BE STRANDED COPPER, TYPE THHN/
THWN, EXCEPT WHERE OTHERWISE REQUIRED BY U.L OR ANY
42.
APPROVAL SHALL BE OBTAINED FROM AN STRUCT. ENGINEER
CODE. MINIMUM WIRE SIZE SHALL BE 12 AWG, EXCLUDING
PRIOR TO CUTTING OR DRILLING ANY STRUCTURAL SUPPORT
CONTROL WIRING.
MEMBER.
16.
ALL CONDUCTORS SHALL BE IN CONDUITS. CONDUITS SHALL
43.
INSTALL POWER AND CONTROL WIRING AND REQUIRED CONTROL
BE GALVANIZED RIGID STEEL (GRC) EXCEPT THAT:
COMPONENTS FOR A/C SYSTEMS AS SHOWN/NOTED ON THESE
(A) PVC CONDUITS MAY BE USED UNDERGROUND PROVIDED
DRAWINGS AND PER OTHER APPLICABLE DRAWINGS/INSTRUCTIONS.
ELBOWS AND RISERS ARE GRC; (B) ELECTRICAL METALLIC
SEE AIR CONDITIONING DRAWING:,
TUBING (EMT) MAY BE USED IN OR ON WALLS OR CEILINGS
44.
ALL MATERIAL REMOVED SHALL, BE "DISPOSED OF AS DIRECTED
WHERE NOT SUBJECT TO MECHANICAL DAMAGE, DAMP OR CO-
RROSIVE CONDITIONS; (C) LIQUIDTIGHT FLEXIBLE CONDUIT
BY OWNER.
WHERE REQUIRED; (D) FLEXIBLE METALLIC CONDUIT WHERE
45.
EMPTY CONDUITS TO BE PROVIDED WITH NYLON PULL STRINGS.
REQUIRED IN DRY LOCACATIONS ONLY. ALL CONDUITS IN HA-
ZARDOUS AREAS (PER NEC) SHALL MEET THE REQUIREMENTS
46.
CONTRACTOR IS RESPONSIBLE FOR PROVIDING ALL WIRING, BKR,
OF NEC CHAPTER 5.
AND FUSE; SIZES IN ACCORDANCE WITH A/C EQUIPMENT NAMEPLATE
17.
APPLY TWO COATS OF BITUMASTIC (KOPPERS 60) TO ALL ME-
IF DIFFERENT FROM THAT SPECIFIED ON DWGS, AS WELL AS ANY
TALLIC CONDUITS IN SLABS OR UNDERGROUND. EMT IS NOT
FEEDER CHANGES BEING AFFECTED BY THIS CHANGE. CONTRACTOR
PERMITTED IN SLABS. ALUMINUM CONDUITS ARE NOT PERMI-
SHALL MAKE ABOVE MENTIONED CHANGES AT NO EXTRA COST.
TIED ANYWHERE.
47.
CONTRACTOR, SHALL COORDINATE ALL HIS WORK WITH OTHER
18.
FLEXIBLE CONDUIT SHALL BE USED FOR CONNECTIONS TO VI-
TRADES IN OTHER TO FURNISH AND INSTALL ALL CONTROL WIRING
BRATING EQUIPMENT AND RECESSED LIGHT FIXTURES, WHERE
AND RACEWAYS AS SHOWN ON THE A/C DRAWINGS AND/OR
PERMITTED BY CODE.
SPECIFICATIONS. AIR CONDITIONING DRAWINGS REFER TO
MANUFACTURERS WIRING DIAGRAMS, THE CONTRACTOR SHALL VERIFY
19.
FOR UNDERGROUND ELECTRICAL CONDUITS, PROVIDE PULL BO-
WITH SAID MANUFACTURER ALL REQUIREMENTS AND INCLUDE ALL
XES SUCH THAT NO SINGLE CONDUCE RUN HAS BENDS IN EX-
RELATED WORK IN HIS CONTRACT.
CESS OF 360 DEGREES, OR 180 DEGREES FOR TELEPHONE.
PULL BOXES SHALL BE SUITABLE AND APPROVED FOR THE IN-
48.
ALL LUMINARIES SHALL BE PROPERLY SUPPORTED IN ACCORDAN-
TENDED USE AND WITH IRON COVERS. WARNING TAPES WHICH
CE WITH THE COILING SYSTEM MANUFACTURER RECOMMENDA-
"WARNING BURIED ELECTRIC" SHALL BE PLACED IN TRENCHES'
TIONS AND LOCAL CODE REQUIREMENTS.
ABOVE ELECTRIC CONDUITS. WHERE CONDUITS PASS UNDER
49
THIS DRAWING IS A GUIDE FOR THE ELECTRICAL INSTALLATION
PAVED AREAS, THEY SHALL BE GRC. WHERE UNDERGROUND
THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR PROVIDING A
CONDUITS ARE NOT EXPOSED TO MECHANICAL DAMAGE OR ARE
FUNCTIONING SYSTEM.
NOT UNDER PAVED AREAS, THEY SHALL BE SCHEDULE 40 PVC.
ELBOWS AND RISERS SHALL BE GRC.
50
ALL CABLES SHALL BE RUN WITHOUT SPLICES, U.O.N.
20.
ALL CONDUIT RUNS ARE SHOWN DIAGRAMMATICALLY. THE EXACT
51
ALL PULL AND J-BOXES SHALL BE ACCESSIBLE AT ALL TIMES.
ROUTING SHALL BE DETERMINED IN THE FIELD, UNLESS NOTED
OTHERWISE.
52 .
EXACT POINT/METHODS OF CONNECTION SHALL BE DETERMINED
21.
PROVIDE FIRE RETARDANT U.L. APPROVED SEALANT ON ALL PE-
IN THE FIELD.
NETRATIONS, WALLS AND STRUCTURAL SLABS. IT SHALL BE THE
53 .
ALL RACEWAY ROUTED INSULATED CONDUCTORS SYSTEM SHALL BE
RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR TO VERIFY
COLOR CODED AS FOLLOWS.
PRIOR TO SUBMITTING BID, THE LOCATIONS OF ALL SUCH FIRE
120/208 V SYSTEM:
RATED PARTITIONS, WALLS, AND STRUCTURAL SLABS.
PHASE 'A' BLACK
22,
UNLESS NOTED AS EXISTING, ALL EQUIPMENT, WIRING, DEVICES,
PHASE 'B' RED
ETC. SHALL BE NEW.
PHASE 'C' BLUE
23.
A PULL WIRE OR CORD SHALL BE INSTALLED IN ALL EMPTY
NEUTRAL WHITE (see note below)
CONDUITS.
GROUND GREEN
24.
ALL DISCONNECT SWITCHES SHALL BE SIZED BY NEC REQUIRE-
277/480 V SYSTEM
'A'
MENTS TO ACCOMODATE THE EQUIPMENT SERVED, INCLUDING
PHASE BROWN
'B'
REJECTION CLIPS AND FUSES. SWITCHES SHALL BE HIP RATED
PHASE PURPLE
FOR MAXIMUM HORSEPOWER.
PHASE 'C' YELLOW
NEUTRAL GRAY
25.
CONTRACTOR SHALL VERIFY CIRCUIT PROTECTIVE DEVICE RATING
GROUND GREEN
FOR EQUIPMENT PRIOR TO INSTALLATION.
Note: When mixing different voltage systems in the same raceway
26.
ALL FUSES SHALL BE CURRENT LIMITING, PER U.L RATED 600V
or enclosure use white insulation wire with a readily distinguishable
OR 250V AS REQUIRED, WITH:
color stripe running along its entire length.
a) NON TIME DELAY FUSES IN MAIN SWITCHES AND SWITCHES
FEEDING PANELS.
b) DUAL ELEMENT TIME DELAY FUSES FOR MOTORS AND HVAC
EQUIPMENT.
N
111 Jl�ll 1.
desi g n
2930 Northeast 2nd Court
Miami, FL 33137
305.545.4964
AA0003130 ID0003964
ti
♦
♦
ti
L0
0
L0 0
5
CL
Cf)
0
CO
cf)
Cl) Cc
13
CY) 0 Oily
U- >
C
E
CF
0
coC,
0 0
0 1
e4
W I
M
r
ALEJANDRO BONET
PROJECT NO: 1110 -05
DRAWN BY. LINI
DATE: 01.10.2014
Sckz' AS NOTED
SHEET NO:
E-2
cv
ko
rn
SHEEr"FITILE:
ELECTRICAL
NOTESAND
PANELS
ALEJANDRO BONET
PROJECT NO: 1110 -05
DRAWN BY. LINI
DATE: 01.10.2014
Sckz' AS NOTED
SHEET NO:
E-2
cv
ko
rn