14-17R-014Z 0 w 0 w o- z 0 L 0 x It c� Z 0 cc CL 0 0 M a- O O u7 •.r in M., e r MEP Engineer of Record Randall A. Nelson, P. E. 14817 West 95th Street Lenexa, Kansas 66215 Phone 913 322 5150 RTU SEQUENCE & CONTROLS 1) DESCRIPTION: INCLUSIVE OF UNIT CONTROL ARE ALL ROOFTOP PACKAGE UNITS AND SPLIT SYSTEMS THAT PROVIDE "PACKAGED" COOLING AND HEATING WITHIN THE STORE, WITH NO MORE THAN TWO STAGES OF COOLING AND TWO STAGES OF HEATING PER UNIT. ECONOMIZER OVERRIDE CONTROL IS PROVIDED VIA EMS CONTROLS SO AS TO PROVIDE CAPABILITY OF DEMAND CONTROLLED VENTILATION. 2) SCHEDULES: BECAUSE THERE ARE DIFFERENT CONFIGURATIONS FOR ALL STORES, THE FOLLOWING IS A GUIDELINE FOR HOW THE SCHEDULE FOR THE RTU'S WILL BE CONFIGURED. THE MAJORITY OF THE UNITS WILL UTILIZE A PROGRAM CALLED "OPTIMAL START /STOP" THAT TURNS THE UNITS ON AND OFF EFFICIENTLY SO THAT THE UNITS ARE AT SETPOINT BY THE TIME THE STORE IS OPEN FOR BUSINESS. 3) SETPOINTS: A FIXED ZONE TEMPERATURE SETPOINT WILL BE UTILIZED FOR ALL RTU'S. BELOW ARE THE DEFINED SETPOINTS FOR ALL STORES. A. OCCUPIED: COOLING - 75'F, HEATING - 70'F, RETAIL AREA) B. OCCUPIED: COOLING - 75'F, HEATING - 70'F, HUMIDITY - 60% (GROOMING AREA) C. UNOCCUPIED: CONSIDERATION HAS BEEN GIVEN TO THE ENVIRONMENTAL CONDITIONS REQUIRED FOR ANIMAL WELFARE. THESE ARE PETCO SETBACK SETTINGS FOR THE STORES: SETBACK: COOLING - 78'F, HEATING - 65'F (RETAIL AREA) SETBACK: COOLING - 78'F, HEATING - 62'F (GROOMING AREA) SETBACK: HEATING - 58'F (VESTIBULE AND PRE -SALES AREA) 4) DAMPER & FAN CONTROL A. DURING UNOCCUPIED PERIODS, THE OUTSIDE DAMPERS SHALL BE CLOSED AND THE FAN SHALL RUN ONLY UPON A CALL FOR HEATING OR COOLING. 4" WIDE SHEET METAL STRAP - SECURE WIRE TO STRUCTURE ABOVE 45' RIGID ROUND ELBOW ROUND NECK DIFFUSER OR GRILLE KEYNOTES (SYMBOLS 0,0 ETC.) 1. 12" ROUND DUCT UP TO EF ON ROOF. 2. GRILLE WITH HINGED FRAME FOR INTEGRAL, WASHABLE FILTER. 3. PROVIDE WALL MOUNTED FILTERED RETURN GRILLE SIZED AS SHOWN. INSTALL GRILLE AS HIGH AS POSSIBLE IN WALL. 4. COORDINATE WITH ALL OTHER TRADES PRIOR TO INSTALLATION OF THIS DUCTWORK. ALL DUCTWORK SHALL BE INSTALLED AS HIGH AS POSSIBLE IN THE SPACE BETWEEN JOISTS WHERE POSSIBLE. 5. SUPPLY AIR DUCT TEMPERATURE SENSOR (RTS -UVC) SUPPLIED AND FACTORY INSTALLED AND WIRED BY ROOFTOP UNIT MANUFACTURER. 6. TEMPERATURE CONTROLLER JUNCTION BOX AT 60" AFF AND HUMIDITY SENSOR JUNCTION BOX AT 54" AFF. 7. PROVIDE 22/2 SHIELDED CABLE IN ACCORDANCE WITH EMS1.1 NOTES, IN A DAISY CHAIN STYLE, FROM THE OPUS LOCATION TO EACH ROOF TOP UNIT'S CONTROL SECTION FINISHING AT THE GROOMING UNIT. LEAVE 6' AT THE OPUS LOCATION. LEAVE 3' IN EACH ROOFTOP UNIT CONTROL SECTION AND LABEL WIRES WITH UNIT NUMBER THEY ARE RUN TO. THESE WIRES ARE TO BE RUN FROM THE CEILING SPACE TO THE ROOFTOP UNIT IN THEIR OWN RACEWAY. DO NOT RUN LOW VOLTAGE WIRES INSIDE THE POWER CONDUIT. 8. PROVIDE 2"X4"X2"D JUNCTION BOX WITH SINGLE GANG PLASTER RING BELOW THE ADOPTION CENTER ROOFTOP UNIT TEMPERATURE SENSOR JUNCTION BOX FOR HUMIDITY SENSOR. 22/2 CABLE FROM THIS LOCATION TO OPUS. ACOUSTICAL FLEX DUCT 6' -0" MAXIMUM LENGTH VOLUME DAMPER CEILING PRE -FAB SPIRAL ROUND DUCT ---- DiFFUSER CONNECTION DETAIL REF.: W/4 (MINIMUM OF 4 ") TAPERED TAP -IN FITTI— M OR MANUAL VOLUME DAMPER BRANCH DUCT -SEE FLOOR PLANS FOR SIZE AND ROUTING CONICAL SHAPED SPIN -IN TYPE FITTING. MODULAR METAL FLEX SM -22 PLENUM OR 7LOW-LOSS DUCT HEIGHT MINUS 2" RECTANGULAR TO ROUND USE THIS FITTING FITTING WHERE SPIN IN FITTING IS ATTACH WITH SHEET METAL BRANCH DUCT -SEE LARGER THAN SCREWS AND SEAL WITH MEDIUM FLOOR PLANS FOR DUCT OR PLENUM PRESSURE DUCT SEALER SIZE AND ROUTING Adoption Center (Exhaust ERV) NOTES FOR THIS DRAWING 1. SEE STRUCTURAL DRAWINGS FOR EXACT PLACEMENT OF ROOFTOP HVAC UNITS, EXHAUST FANS, SUPPLY AIR AND RETURN AIR OPENINGS AND LOCATIONS THROUGH ROOF. CAREFULLY LOCATE ROOFTOP UNITS SUCH THAT CONCENTRIC DIFFUSERS FALLS IN A STRUCTURAL BAY. 2. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN FOR EXACT PLACEMENT OF CEILING DIFFUSERS AND GRILLES. 3. UNLESS OTHERWISE NOTED, ALL DUCTWORK IS RECTANGULAR SHEET METAL. EXPOSED SUPPLY AND RETURN DUCTWORK SHALL BE INTERNALLY LINED, WHILE ALL CONCEALED SUPPLY DUCTWORK SHALL BE WRAPPED. REFER TO PROJECT MANUAL FOR DETAILS. THE CONTRACTOR, AT HIS DISCRETION, MAY USE ROUND DUCTWORK WITH PROPERLY INSTALLED EXTERNAL DUCT WRAP INSULATION IN CONCEALED AREAS, AND MAY USE ROUND OR SPIRAL, (INTERNALLY LINED WHERE APPLICABLE) DUCTWORK IN EXPOSED AREAS. 4. IN EXPOSED AREAS, ROOF OPENINGS FOR HVAC EQUIPMENT SHALL BE LIMITED, WHERE POSSIBLE AND PRACTICAL, TO ACCOMMODATE THE DUCT OPENINGS AND NO MORE, THE INTENT BEING TO MAINTAIN A NEAT AND AESTHETICALLY PLEASING FINISHED PRODUCT WITH AS MUCH OF THE ROOF ITSELF INTACT AS POSSIBLE. System Checksums By acertus 5. _- S eE AR 'HITEC"14RAL =DR�WINGS WITH RESPECT TO "Pr 0\401N0- - WASHABL -C- CEILING TILES, FOR PROJECTS THAT WILL REQUIRE A DROPPED CEILING ON THE SALES FLOOR, ADJACENT TO THE DIFFUSERS FOR A _b'STAr46E'OF -44 FT. R.V IUS FROM DISCHARGE OF TiE DIFF=USER_'S EDGE- ry 6. MAINTAIN MINIMUM 10' -0" BETWEEN OUTSIDE AIR INTAKES AND ANY EXHAUST OUTLET OR PLUMBING VENT. 7. REFER TO SHEET E2.5 FOR CONTROL DEVICES. 8. ALL DUCTWORK IN AREAS WITH SUSPENDED CEILINGS SHALL BE CONCEALED ABOVE CEILING. 9. CONTRACTOR MAY AT HIS DISCRETION, USE ROUND DUCT OF EQUIVALENT SIZE IN LIEU OF RECTANGULAR IN CONCEALED AREAS. DUCT SHALL BE INSULATED AS SPECIFIED. 10. NO SENSOR WIRING SHALL BE INSTALLED UNSUPPORTED BY TIE - WRAPS, OR CONDUIT. 11. ALL SENSOR WIRING INSTALLED EXPOSED BELOW THE BOTTOM OF THE CHORD OF BAR JOIST SHALL BE INSTALLED IN EMT CONDUIT OR SHALL BE CONCEALED BEHIND WALLS OR CEILINGS OR INSTALLED THROUGH HOLLOW MULLIONS. 12. E.C. TO VERIFY LOCAL .REQUIREMENTS FOR LOW VOLTAGE SYSTEMS WIRING AND PROVIDE CONDUIT(S) WHERE REQUIRED. Single Zone COOLING COIL PEAK 05 CLG SPACE PEAK HEATING COIL PEAK 03 TEMPERATURES Peaked at Time: Motor. 8117 01 Mohr. Sum of Mo)Hr. Heating Design REF.: NO SCALE Cooling Heating Outside Air: OADBNVBMR: 90177/122 OADB: Peaks OADB: 47 SADB 57.5 72.8 RaPlenum 75.0 70.0 Space Plenum Net Percent: Space Percent : Space Peak Coll Peak Percent Return 76.1 70.0 Sens.+ Lat. Sens. + Lat Total Of Total, Sensible Of Total Space Sens Tot Sens of Total Ret/0A 77.4 59.5 Btu/h Bluth Btu/h (%) ; Btu/h ( %) ; Btu/h Btu/h ( %) Fn MtrTD 0.1 0.0 Envelope loads ; Envelope Loads Fn SIdTO 0.1 0.0 Skylite Solar 0 0 0 0 0 0 ; Skylite Solar 0 0 0.00 Fn Frick 0.4 0.0 Skylite Cond 0 0 0 0 0 0 Skylite Cond 0 0 0.00 Roof Cond 3,734 0 3,734 4: 3,038 5: RoofCond -1,161 -1,161 2.63 Glass Solar 0 0 0 0° 0 0: Glass Solar 0 0 0.00 AIRFLOWS Glass/Door Con d 0 0 0 0; 0 0: Glass /DoorCond 0 0 0.00 Coaling Heating Wall Cond 10,708 0 10,708 12: 13.312 23: Wall Cond -5,609 -5,609 1232 Partitlon/Door 0 0 0; 0 0; Partition /Door 0 0 0.00 Diffuser 2,988 2,988 Floor 0 0 0: 0 0: Floor 0 0 0.00 Terminal 2,988 2,988 Adjacent Floor 0 0 0 0: 0 0: Adjacent Floor 0 0 0 Main Fan 2,988 2,988 Infiltration 0 0 0; 0 0• Infiltration 0 0 0.00 Sec Fan 0 0 Sub Total = => 14,442 0 14,442 16; 16,350 28 ; Sub Total = => -6,770 -6,770 15.35 Nam Vent 1,363 1,363 AHU Vent 1,363 1,363 Internal Loads : Internal Loads infil 0 0 Lights 8,377 2,067 10,444 11 8,377 14 • Lights 0 0 0.00 MinStop/Rh 0 0 People 6,813 0 6,813 7: 3,785 6: People 0 0 0.00 Return 1,626 1,626 Misc 29,365 0 29,365 32: 29,365 50: Misc 0 0 0.00 Exhaust 0 0 Sub Total = => 44,555 2,067 46,622 51 : 41,527 71 : Sub Total = => 0 0 0.00 Rm Exh 1,363 1,363 Auxiliary 0 0 Ceiling Load 0 0 0 0: 0 0: Ceiling Load 0 0 0.00 Leakage Dwn 0 0 Ventilation Load 0 0 28,157 31 : 0 0: Ventilation Load 0 - 34,947 79.23 Leakage Ups 0 0 AdJ Air Trans Heat 0 0 0: 0 0 AdJAirTransHeat 0 0 0 Dehumid. Ov Sizing 0 0: : Ov /Undr Sizing -2,391 -2,391 542 Ov/UndrSlzing 546 546 1: 546 1 ; Exhaust Heat 0 0.00 ENGINEERING CKS Exhaust Heat 0 0 0 OA Preheat DIM 0 0.00 Sup. Fan Heat 1,771 2; : RA Preheat Diff. 0 0.00 Cooling Heating ReL Fan Heat 0 0 0: : Additional Reheat 0 0.00 % OA 45.6 45.6 Duct Heat Pkup 0 0 0: cfmlfe 1.97 1.97 Underflr Sup Ht Pkup 0 0: : Underfir Sup Ht Pkup 0 0.00 cfmtton 391.74 Supply Air Leakage 0 0 0: ; Supply Air Leakage 0 0.00 fPlkon 198.48 Btu/hr-ft' 60.46 -28.60 Grand Total => 59,543 2,067 91,538 100.00: 58,424 100.00 ` Grand Total => -9,160 - 44,108 100.00 No. People 15 COOLING COIL SELECTION AREAS HEATING COIL SELECTION Total Capacity Sens Cap. Coll Airflow Enter DBNVBIHR Leave DBIW BMR Gross Total Glass Capacity Coif Airflow Ent Lvg ton MBh MBh cfm 'F 'F gr/ib °F °F grAb ft= ( %) MBh cfm °F 7 Main Clg 7.6 91.5 66.0 2,988 77.3 65.4 74.6 57.0 55.5 63.4 Floor 1,514 Main Htg 43.3 2,988 59.8 72.8 Aux Cig 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 OA 0,0 Part 0 Aux Htg OA 0 0.0 0.0 Opt Vent 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0 int Door 0 Preheat 0.0 0 0.0 0.0 ExFIr 0 Total 7.6 91.5 Roof 1,514 0 0 Humtdif 0.0 0 0.0 0.0 Wall 828 0 0 Opt Vent 0.0 0 0.0 0.0 Ext Door 0 0 0 Total -43.3 Project Name: PETCO DatasetName: PETCO HVAC LOAD.TRC SECURE TO STRUCTURE ABOVE AS RECOMMENDED BY SMACNA. GALVANIZED IRON STRAP OR ALUMINUM STRAP, TURN UNDER DUCT MINIMUM 1 ". RIVET OR BOLT TO UNDERSIDE OF DUCT. SHEET METAL SCREW, RIVET OR BOLT TO BOTH SIDES OF DUCT. WHERE APPLICABLE, A) SUPPORT FROM UNISTRUT SPANNING TOP CHORD OF BAR JOISTS. B) USE DUCT STRAPS WITH BOLT CLAMP TO SUPPORT ROUND DUCTWORK. BRACING ANGLES SEE NOTES. NU I AND WASHER AT END OF ROD. TRACE@ 700 v6.2.10 calculated at 11:05 AM on 01123/2014 Alternative -1 System Checksums Report Page 1 of 1 HVAC LOAD CALCULATIONS 06 REF.: I NO SCALE MECHANICAL PLAN 05 BRANCH DUCT TAKE -OFF DETAIL 03 DUCT HANGER DETAILS 02 KEY PLAN 01 REF.: 1/4" =1' -0" REF.: 06/M2.1 NO SCALE REF.: NO SCALE REF.: NO SCALE T e tl . 0 7 C ae° , s� 1 DRAWING TITLE: 1 MECHANICAL PLAN