MEP Engineer of Record
Randall A. Nelson, P. E.
14817 West 95th Street
Lenexa, Kansas 66215
Phone 913 322 5150
RTU SEQUENCE & CONTROLS
1) DESCRIPTION: INCLUSIVE OF UNIT CONTROL ARE ALL
ROOFTOP PACKAGE UNITS AND SPLIT SYSTEMS THAT
PROVIDE "PACKAGED" COOLING AND HEATING WITHIN THE
STORE, WITH NO MORE THAN TWO STAGES OF COOLING
AND TWO STAGES OF HEATING PER UNIT. ECONOMIZER
OVERRIDE CONTROL IS PROVIDED VIA EMS CONTROLS SO
AS TO PROVIDE CAPABILITY OF DEMAND CONTROLLED
VENTILATION.
2) SCHEDULES: BECAUSE THERE ARE DIFFERENT
CONFIGURATIONS FOR ALL STORES, THE FOLLOWING IS A
GUIDELINE FOR HOW THE SCHEDULE FOR THE RTU'S WILL
BE CONFIGURED. THE MAJORITY OF THE UNITS WILL
UTILIZE A PROGRAM CALLED "OPTIMAL START /STOP" THAT
TURNS THE UNITS ON AND OFF EFFICIENTLY SO THAT THE
UNITS ARE AT SETPOINT BY THE TIME THE STORE IS OPEN
FOR BUSINESS.
3) SETPOINTS: A FIXED ZONE TEMPERATURE SETPOINT WILL
BE UTILIZED FOR ALL RTU'S. BELOW ARE THE DEFINED
SETPOINTS FOR ALL STORES.
A. OCCUPIED: COOLING - 75'F, HEATING - 70'F,
RETAIL AREA)
B. OCCUPIED: COOLING - 75'F, HEATING - 70'F,
HUMIDITY - 60% (GROOMING AREA)
C. UNOCCUPIED: CONSIDERATION HAS BEEN GIVEN TO
THE ENVIRONMENTAL CONDITIONS REQUIRED FOR
ANIMAL WELFARE. THESE ARE PETCO SETBACK
SETTINGS FOR THE STORES:
SETBACK: COOLING - 78'F, HEATING - 65'F
(RETAIL AREA)
SETBACK: COOLING - 78'F, HEATING - 62'F
(GROOMING AREA)
SETBACK: HEATING - 58'F (VESTIBULE AND
PRE -SALES AREA)
4) DAMPER & FAN CONTROL
A. DURING UNOCCUPIED PERIODS, THE OUTSIDE
DAMPERS SHALL BE CLOSED AND THE FAN SHALL
RUN ONLY UPON A CALL FOR HEATING OR COOLING.
4" WIDE SHEET
METAL STRAP -
SECURE WIRE TO
STRUCTURE ABOVE
45'
RIGID ROUND
ELBOW
ROUND NECK
DIFFUSER OR
GRILLE
KEYNOTES (SYMBOLS 0,0 ETC.)
1. 12" ROUND DUCT UP TO EF ON ROOF.
2. GRILLE WITH HINGED FRAME FOR INTEGRAL,
WASHABLE FILTER.
3. PROVIDE WALL MOUNTED FILTERED RETURN GRILLE
SIZED AS SHOWN. INSTALL GRILLE AS HIGH AS
POSSIBLE IN WALL.
4. COORDINATE WITH ALL OTHER TRADES PRIOR TO
INSTALLATION OF THIS DUCTWORK. ALL DUCTWORK
SHALL BE INSTALLED AS HIGH AS POSSIBLE IN THE
SPACE BETWEEN JOISTS WHERE POSSIBLE.
5. SUPPLY AIR DUCT TEMPERATURE SENSOR (RTS -UVC)
SUPPLIED AND FACTORY INSTALLED AND WIRED BY
ROOFTOP UNIT MANUFACTURER.
6. TEMPERATURE CONTROLLER JUNCTION BOX AT 60"
AFF AND HUMIDITY SENSOR JUNCTION BOX AT 54"
AFF.
7. PROVIDE 22/2 SHIELDED CABLE IN ACCORDANCE
WITH EMS1.1 NOTES, IN A DAISY CHAIN STYLE, FROM
THE OPUS LOCATION TO EACH ROOF TOP UNIT'S
CONTROL SECTION FINISHING AT THE GROOMING UNIT.
LEAVE 6' AT THE OPUS LOCATION. LEAVE 3' IN
EACH ROOFTOP UNIT CONTROL SECTION AND LABEL
WIRES WITH UNIT NUMBER THEY ARE RUN TO.
THESE WIRES ARE TO BE RUN FROM THE CEILING
SPACE TO THE ROOFTOP UNIT IN THEIR OWN
RACEWAY. DO NOT RUN LOW VOLTAGE WIRES INSIDE
THE POWER CONDUIT.
8. PROVIDE 2"X4"X2"D JUNCTION BOX WITH SINGLE
GANG PLASTER RING BELOW THE ADOPTION CENTER
ROOFTOP UNIT TEMPERATURE SENSOR JUNCTION BOX
FOR HUMIDITY SENSOR. 22/2 CABLE FROM THIS
LOCATION TO OPUS.
ACOUSTICAL FLEX DUCT
6' -0" MAXIMUM LENGTH
VOLUME DAMPER
CEILING PRE -FAB SPIRAL
ROUND DUCT ----
DiFFUSER CONNECTION DETAIL
REF.:
W/4 (MINIMUM OF 4 ")
TAPERED
TAP -IN FITTI—
M OR
MANUAL VOLUME
DAMPER
BRANCH DUCT -SEE
FLOOR PLANS FOR
SIZE AND ROUTING
CONICAL SHAPED
SPIN -IN TYPE FITTING.
MODULAR METAL
FLEX SM -22
PLENUM OR 7LOW-LOSS DUCT HEIGHT MINUS 2"
RECTANGULAR TO ROUND
USE THIS FITTING FITTING
WHERE SPIN IN
FITTING IS ATTACH WITH SHEET METAL BRANCH DUCT -SEE
LARGER THAN SCREWS AND SEAL WITH MEDIUM FLOOR PLANS FOR
DUCT OR PLENUM PRESSURE DUCT SEALER SIZE AND ROUTING
Adoption Center (Exhaust ERV)
NOTES FOR THIS DRAWING
1. SEE STRUCTURAL DRAWINGS FOR EXACT PLACEMENT
OF ROOFTOP HVAC UNITS, EXHAUST FANS, SUPPLY
AIR AND RETURN AIR OPENINGS AND LOCATIONS
THROUGH ROOF. CAREFULLY LOCATE ROOFTOP
UNITS SUCH THAT CONCENTRIC DIFFUSERS FALLS IN
A STRUCTURAL BAY.
2. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN
FOR EXACT PLACEMENT OF CEILING DIFFUSERS AND
GRILLES.
3. UNLESS OTHERWISE NOTED, ALL DUCTWORK IS
RECTANGULAR SHEET METAL. EXPOSED SUPPLY
AND RETURN DUCTWORK SHALL BE INTERNALLY
LINED, WHILE ALL CONCEALED SUPPLY DUCTWORK
SHALL BE WRAPPED. REFER TO PROJECT MANUAL
FOR DETAILS. THE CONTRACTOR, AT HIS
DISCRETION, MAY USE ROUND DUCTWORK WITH
PROPERLY INSTALLED EXTERNAL DUCT WRAP
INSULATION IN CONCEALED AREAS, AND MAY USE
ROUND OR SPIRAL, (INTERNALLY LINED WHERE
APPLICABLE) DUCTWORK IN EXPOSED AREAS.
4. IN EXPOSED AREAS, ROOF OPENINGS FOR HVAC
EQUIPMENT SHALL BE LIMITED, WHERE POSSIBLE AND
PRACTICAL, TO ACCOMMODATE THE DUCT OPENINGS
AND NO MORE, THE INTENT BEING TO MAINTAIN A
NEAT AND AESTHETICALLY PLEASING FINISHED
PRODUCT WITH AS MUCH OF THE ROOF ITSELF
INTACT AS POSSIBLE.
System Checksums
By acertus
5. _- S eE AR 'HITEC"14RAL =DR�WINGS WITH RESPECT TO
"Pr 0\401N0- - WASHABL -C- CEILING TILES, FOR PROJECTS
THAT WILL REQUIRE A DROPPED CEILING ON THE
SALES FLOOR, ADJACENT TO THE DIFFUSERS FOR A
_b'STAr46E'OF -44 FT. R.V IUS FROM DISCHARGE OF
TiE DIFF=USER_'S EDGE- ry
6. MAINTAIN MINIMUM 10' -0" BETWEEN OUTSIDE AIR
INTAKES AND ANY EXHAUST OUTLET OR PLUMBING
VENT.
7. REFER TO SHEET E2.5 FOR CONTROL DEVICES.
8. ALL DUCTWORK IN AREAS WITH SUSPENDED CEILINGS
SHALL BE CONCEALED ABOVE CEILING.
9. CONTRACTOR MAY AT HIS DISCRETION, USE ROUND
DUCT OF EQUIVALENT SIZE IN LIEU OF RECTANGULAR
IN CONCEALED AREAS. DUCT SHALL BE INSULATED
AS SPECIFIED.
10. NO SENSOR WIRING SHALL BE INSTALLED
UNSUPPORTED BY TIE - WRAPS, OR CONDUIT.
11. ALL SENSOR WIRING INSTALLED EXPOSED BELOW THE
BOTTOM OF THE CHORD OF BAR JOIST SHALL BE
INSTALLED IN EMT CONDUIT OR SHALL BE
CONCEALED BEHIND WALLS OR CEILINGS OR
INSTALLED THROUGH HOLLOW MULLIONS.
12. E.C. TO VERIFY LOCAL .REQUIREMENTS FOR LOW
VOLTAGE SYSTEMS WIRING AND PROVIDE CONDUIT(S)
WHERE REQUIRED.
Single Zone
COOLING COIL PEAK
05
CLG SPACE PEAK
HEATING COIL PEAK
03
TEMPERATURES
Peaked at Time:
Motor. 8117
01
Mohr.
Sum of
Mo)Hr.
Heating Design
REF.:
NO SCALE
Cooling
Heating
Outside Air:
OADBNVBMR: 90177/122
OADB:
Peaks
OADB:
47
SADB
57.5
72.8
RaPlenum
75.0
70.0
Space
Plenum
Net
Percent:
Space
Percent :
Space Peak
Coll Peak Percent
Return
76.1
70.0
Sens.+
Lat.
Sens. + Lat
Total
Of Total,
Sensible
Of Total
Space Sens
Tot Sens of Total
Ret/0A
77.4
59.5
Btu/h
Bluth
Btu/h
(%) ;
Btu/h
( %) ;
Btu/h
Btu/h ( %)
Fn MtrTD
0.1
0.0
Envelope loads
; Envelope Loads
Fn SIdTO
0.1
0.0
Skylite Solar
0
0
0
0
0
0 ; Skylite Solar
0
0 0.00
Fn Frick
0.4
0.0
Skylite Cond
0
0
0
0
0
0 Skylite Cond
0
0 0.00
Roof Cond 3,734 0 3,734 4: 3,038 5: RoofCond -1,161 -1,161 2.63
Glass Solar
0
0
0
0°
0
0: Glass Solar
0
0 0.00
AIRFLOWS
Glass/Door Con d
0
0
0
0;
0
0: Glass /DoorCond
0
0 0.00
Coaling
Heating
Wall Cond
10,708
0
10,708
12:
13.312
23: Wall Cond
-5,609
-5,609 1232
Partitlon/Door
0
0
0;
0
0; Partition /Door
0
0 0.00
Diffuser
2,988
2,988
Floor
0
0
0:
0
0: Floor
0
0 0.00
Terminal
2,988
2,988
Adjacent Floor
0
0
0
0:
0
0: Adjacent Floor
0
0 0
Main Fan
2,988
2,988
Infiltration
0
0
0;
0
0• Infiltration
0
0 0.00
Sec Fan
0
0
Sub Total = =>
14,442
0
14,442
16;
16,350
28 ; Sub Total = =>
-6,770
-6,770 15.35
Nam Vent
1,363
1,363
AHU Vent
1,363
1,363
Internal Loads
: Internal Loads
infil
0
0
Lights
8,377
2,067
10,444
11
8,377
14 • Lights
0
0 0.00
MinStop/Rh
0
0
People
6,813
0
6,813
7:
3,785
6: People
0
0 0.00
Return
1,626
1,626
Misc
29,365
0
29,365
32:
29,365
50: Misc
0
0 0.00
Exhaust
0
0
Sub Total = =>
44,555
2,067
46,622
51 :
41,527
71 : Sub Total = =>
0
0 0.00
Rm Exh
1,363
1,363
Auxiliary
0
0
Ceiling Load
0
0
0
0:
0
0: Ceiling Load
0
0 0.00
Leakage Dwn
0
0
Ventilation Load
0
0
28,157
31 :
0
0: Ventilation Load
0
- 34,947 79.23
Leakage Ups
0
0
AdJ Air Trans Heat
0
0
0:
0
0 AdJAirTransHeat
0
0 0
Dehumid. Ov Sizing
0
0:
: Ov /Undr Sizing
-2,391
-2,391 542
Ov/UndrSlzing
546
546
1:
546
1 ; Exhaust Heat
0 0.00
ENGINEERING CKS
Exhaust Heat
0
0
0
OA Preheat DIM
0 0.00
Sup. Fan Heat
1,771
2;
: RA Preheat Diff.
0 0.00
Cooling
Heating
ReL Fan Heat
0
0
0:
: Additional Reheat
0 0.00
% OA
45.6
45.6
Duct Heat Pkup
0
0
0:
cfmlfe
1.97
1.97
Underflr Sup Ht Pkup
0
0:
: Underfir Sup Ht Pkup
0 0.00
cfmtton
391.74
Supply Air Leakage
0
0
0:
; Supply Air Leakage
0 0.00
fPlkon
198.48
Btu/hr-ft'
60.46
-28.60
Grand Total =>
59,543
2,067
91,538
100.00:
58,424
100.00 ` Grand Total =>
-9,160
- 44,108 100.00
No. People
15
COOLING COIL SELECTION
AREAS
HEATING COIL SELECTION
Total
Capacity
Sens Cap.
Coll Airflow
Enter DBNVBIHR
Leave DBIW BMR
Gross Total
Glass
Capacity Coif
Airflow
Ent Lvg
ton
MBh
MBh
cfm
'F 'F
gr/ib
°F °F grAb
ft= ( %)
MBh
cfm
°F 7
Main Clg 7.6
91.5
66.0
2,988
77.3 65.4
74.6
57.0 55.5 63.4
Floor
1,514
Main Htg
43.3
2,988 59.8 72.8
Aux Cig 0.0
0.0
0.0
0
0.0 0.0
0.0
0.0 OA 0,0
Part
0
Aux Htg
OA
0
0.0 0.0
Opt Vent 0.0
0.0
0.0
0
0.0 0.0
0.0
0.0 0.0 0.0
int Door
0
Preheat
0.0
0
0.0 0.0
ExFIr
0
Total 7.6
91.5
Roof
1,514
0 0
Humtdif
0.0
0
0.0 0.0
Wall
828
0 0
Opt Vent
0.0
0
0.0 0.0
Ext Door
0
0 0
Total
-43.3
Project Name: PETCO
DatasetName: PETCO HVAC LOAD.TRC
SECURE TO STRUCTURE ABOVE
AS RECOMMENDED BY SMACNA.
GALVANIZED IRON STRAP OR ALUMINUM
STRAP, TURN UNDER DUCT MINIMUM 1 ".
RIVET OR BOLT TO UNDERSIDE OF DUCT.
SHEET METAL SCREW, RIVET OR
BOLT TO BOTH SIDES OF DUCT.
WHERE APPLICABLE,
A) SUPPORT FROM UNISTRUT SPANNING
TOP CHORD OF BAR JOISTS.
B) USE DUCT STRAPS WITH BOLT
CLAMP TO SUPPORT ROUND DUCTWORK.
BRACING ANGLES SEE NOTES.
NU I AND WASHER AT END OF ROD.
TRACE@ 700 v6.2.10 calculated at 11:05 AM on 01123/2014
Alternative -1 System Checksums Report Page 1 of 1
HVAC LOAD CALCULATIONS 06
REF.: I NO SCALE
MECHANICAL PLAN
05
BRANCH DUCT TAKE -OFF DETAIL
03
DUCT HANGER DETAILS
02
KEY PLAN
01
REF.:
1/4" =1' -0"
REF.: 06/M2.1
NO SCALE
REF.:
NO SCALE
REF.:
NO SCALE
T
e
tl . 0 7
C
ae°
,
s�
1 DRAWING TITLE: 1
MECHANICAL
PLAN