MEP Engineer of Record
Randall A. Nelson, P. E.
14817 West 95th Street
Lenexa, Kansas 66215
Phone 913 322 5150
NOTES FOR THIS DRAWING
1. INSTALL WATER PIPING AS HIGH AS POSSIBLE TOWARD ROOF STRUCTURE.
2. INSTALL 4" SOIL AND WASTE PIPING AT- 1 /8 "--FALL-PER ro61.- INSTALL OTHER SOIL AND WASTE
PIPING AT 1/4" FALL PER FOOT. SLOPE TOWARD POINTS OF CONNECTION. FIELD VERIFY
FINISHED FLOOR ELEVATION AND INVERT ELEVATION OF EXISTING SOIL /SEWER PIPE FOR POINTS
OF CONNECTION. ,.. a .• n n
3. ALL CONNECTIONS TO SAN ITAR -Y( - 4TERALS -SHALL-BE MACIE -USING WYE OR DOUBLE —WYE
FITTINGS, NO TEE FITTINGS PERMITTED.
4. PLANS DO NOT SHOW ALL VALVES. PROVIDE ISOLATION VALVES AT ALL FIXTURES AND VALVES
FOR EACH WATER PIPE SUPPLYING A FIXTURE GROUP (E.G. TOILET ROOM, GROOMING AREA,
ETC.) FOR EASE OF SERVICE AND MAINTENANCE. PROVIDE ISOLATION VALVE ON AQUARIUM
GROUP, AND AT EACH SIDE OF VENDOR— SUPPLIED EQUIPMENT. DO NOT LOCATE ISOLATION
VALVES ABOVE HARD CEILINGS.
5. CONTRACTOR IS RESPONSIBLE TO HAVE FULLY INVESTIGATED THE ENTIRE EXISTING SANITARY
SEWER SYSTEM. DEVIATIONS FROM PROPOSED DESIGN DUE TO FAILURE TO INVESTIGATE
EXISTING SANITARY SYSTEM WILL BE AT NO EXTRA COST TO THE OWNER.
6. WATER PIPING IN OUTSIDE WALLS SHALL BE INSTALLED WITHIN BUILDING INSULATION ENVELOPE.
CHECK FOR ALL BREACHES PRIOR TO INSTALLATION OF FINISHED WALL.
7. ALL NEW WATER PIPING TO BE INSULATED AS PER SPECIFICATIONS.
FIRE SPRINKLER SPECIFICATIONS
1. AT THE DISCRETION OF THE CONTRACTOR AND WITH THE APPROVAL OF THE PETCO PM, LOCAL
AUTHORITY HAVING JURISDICTION AND IN ACCORDANCE WITH ALL LOCAL, STATE AND NFPA
CODES ALL OR PARTS OF THE EXISTING SYSTEM(S) MAY BE REUSED AND MODIFIED. IN AREAS
CONTAINING A CEILING, THE SPRINKLER HEADS AND MAINS SHALL BE RELOCATED AS REQUIRED
TO COORDINATE WITH THE NEW DIFFUSER AND LIGHTING LAYOUT, AND WITH THE NEW CEILING
HEIGHT(S). THIS MAY INCLUDE BUT NOT BE LIMITED TO THE MODIFICATION OR RELOCATION OF;
BRANCH OR MAIN SPRINKLER PIPING AND SPRINKLER HEADS. THE FINAL SPRINKLER HEAD
LAYOUT WILL BE BASED UPON THE FINAL FIXTURE PLAN LAYOUT. SEE ARCHITECTURAL DRAWINGS
FOR FINAL LAYOUT.
2. MATCH EXISTING SPRINKLER HEAD TYPE AND MATERIAL FOR MODIFIED AREAS.
KEYNOTES (SYMBOLS 0,0 ETC.)
1. THE FLOOR IN THIS ROOM IS SLOPED. REFER TO ARCHITECTURAL PLANS AND COORDINATE WITH
GENERAL CONTRACTOR PRIOR TO INSTALLATION OF FLOOR DRAIN IN THIS AREA.
2. 3" WASTE HEADER INSTALLED TO BOTTOM OF CAGES FOR CAGE DRAINAGE. COORDINATE WITH
PET CAGE VENDOR FOR EXACT MOUNTING HEIGHTS, REQUIREMENTS AND LOCATIONS. INSTALL
WASTES HEADER AS HIGH AS POSSIBLE TO BOTTOM OF CAGE STRUCTURE WITH PROPER SLOPE
TO AVOID INTERFERENCE WITH FLOOR CLEANUP OPERATIONS. INSTALL CLEANOUT PLUG AT END
OF DRAINAGE HEADER.
3. CONNECT 3" WASTE TO CAGE OUTLET WITH 3" SHORT SWEEP, PROVIDE ADAPTER COUPLING AS
REQUIRED.
4. INSTALL 3" CLEANOUT FLUSH WITH FACE OF PET CAGE FOR MAINTENANCE AND CLEANING.
CLEANOUT OUT CONNECTION TO WASTE HEADER SHALL BE MADE WITH LONG SWEEP ELBOW.
5. TERMINATE 3" WASTE HEADER OVER FLOOD RIM OF FLUSHING FLOOR DRAIN WITH AIR GAP PER
CODE.
6. DRAIN GRATE SHALL BE LEFT IN THE HALF OPEN POSITION RESTING ON THE PET CAGE INDIRECT
WASTE LINE FOR VISUAL INSPECTION THAT DRAIN IS CLEAN AND CLEAR AFTER FLUSHING.
7. 4" SANITARY WASTE EXITING THE ADOPTION CENTER AREA SHALL BE CONNECTED INTO THE
EXISTING SANITARY WASTE MAIN OF THE SAME SIZE OR LARGER. FIELD VERIFY EXACT LOCATION,
DEPTH, SIZE AND DIRECTION OF FLOW OF EXISTING MAIN BEFORE WORK BEGINS.
8. 1/2- FLEXIBLE BRAIDED STEEL HOSE SHALL BE INSTALLED BELOW PET CAGES FOR MANUAL
FLUSHING OF 3" WASTE HEADER. BRAIDED HOSE SHALL BE HARD CONNECTED TO 3" WASTE
HEADER WHERE INDICATED. THE BRAIDED HOSE SHALL BE MINIMUM OF 5'— 0" LONG FOR
MOVING OF PET CAGES FOR MAINTENANCE AND CLEANING.
9. INSTALL NEW ADOPTION CENTER COLD WATER LINE WITH SHUT —OFF VALVE INTO EXISTING WATER
SYSTEM OF SAME PIPE SIZE OR LARGER AND WHERE NEW ADOPTION CENTER OPERATIONS DOES
NOT CONFLICT WITH EXISTING WATER OPERATIONS.
10. INSTALL NEW ADOPTION CENTER HOT WATER LINE WITH SHUT —OFF VALVE AT EXISTING WATER
HEATER SERVICING EXISTING PET GROOMING OPERATIONS. NEW ADOPTION CENTER HOT WATER
PIPING SHALL NOT CONFLICT WITH EXISTING GROOMING AREA OPERATIONS. VERIFY THAT EXISTING
WATER HEATER IS LARGE ENOUGH FOR NEW TOTAL HOT WATER DEMAND BEFORE BID. IF
EXISTING HEATER IS FOUND TO BE UNDERSIZE, CONTRACTOR SHALL NOTIFY PETCO PROJECT
MANAGER AND ARCHITECT AS SOON AS POSSIBLE FOR ISSUE TO BE RESOLVED NOT TO DELAY
CONSTRUCTION SCHEDULE.
11. PROVIDE 1/2" COLD WATER PIPING INSTALLED ON EXTERIOR FACE OF WALL FOR MANUAL
FLUSHING OF 3" PET CAGE WASTE HEADER. INSTALL A 1/2" WATTS 9D DUAL CHECK VALVE
WITH INTERMEDIATE ATMOSPHERIC VENT AS SOON AS PIPE EXISTS THE WALL. INSTALL 1/4
TURN BALL VALVE FOR MANUAL FLUSHING OF WASTE HEADER. SECURE PIPING TO FACE OF
WALL APPROXIMATELY 24 "AFF. SLOPE PIPING AS REQUIRED TO DRAIN. WHERE INDICATED ON
PLAN, TURN PIPING DOWN AND CONNECT TO 1/2" FLEXIBLE STEEL HOSE ROUTED BELOW PET
CAGE.
12. INSTALL NEW 3 "VTR FOR ADOPTION CENTER AREA. COORDINATE FINAL LOCATION WITH
DIMENSIONS OF EXISTING OPENINGS AND EQUIPMENT TO MAINTAIN A MINIMUM OF 10' FROM ALL
FRESH AIR INTAKES.
13. PROVIDE VACUUM BREAKERS AT HOT AND COLD WATER PIPING SERVING WASHING MACHIN7BOX.
14. STACKED WASHER AND DRYER BY PETCO.
15. MOUNT SOLIDS INTERCEPTOR ON FLOOR ACCORDING TO MANUFACTURER'S INSTRUCTIONS.
LARGE SCALE WATER PLAN
04
DISTRIBUTION:
LARGE SCALE SANITARY PLAN
02
KEY PLAN
01
REF.:
REF.:
1/4" =1' -0"
.
REF.:
NO SCALE
yb
e
E b�
kB 5
r pMpp0 yy u ++pp 4h
� � qka gF V pq.�g. { C F 4 l
4 �. e��p, �A f 4 6 ie. 9wd A R ?x G x egvx
[i'1
PETCO ANIMAL MIAMI DADE ADOPTION CENTER
SUPPLIES STORES, INC. 6200 SOUTH DIXIE HWY
654 RICtLAND FULLS IX 82 SOUTH MIAMI, FL 33143
SAN ANTONIO, TEXAS 7 78245
i
DISTRIBUTIOR
DATE;
DISTRIBUTION:
DATE:
DISTRIBUTION:
DATE
DISTRIBUTION:
DATE:
96 %SUBMISSION
12 -04-13
100% PERMIT SUBMISSION
12 -11 -13
BUILDING DEPT COMMENTS
01 -27 -14
FACERTLIS
ADDENDUM #1
01 -31 -14
ADDENDUM #2
02 -26-14
BJT
DRAWNG TITLE:
LARGE
SCALE
PLANS
P2.1
4