14-1222-002Is
N SCALE: 3/16" = 1' -0"
JOB TOTALS
TYPE OF SPRINKLERS
SYMB(5
TOTAL
SIN
FACTOR
TEMP
DESCRIPTION
FINISH
ESCUTCHEON
Q
2
TY3531
5.6
155'
TYCO MODEL 'RFII' QUICK RESPONSE CONCEALED PENDENT
WHITE
CONCEALED
1
TY3531
5.6
155'
TYCO MODEL 'RFII' QUICK RESPONSE CONCEALED PENDENT
WHITE
CONCEALED
12 -0
15
TY3531
5.6
155'
TYCO MODEL 'RFII' QUICK RESPONSE CONCEALED PENDENT
WHITE
CONCEALED
CONCRETE SLAB
CONCRETE SLAB
IWDER DRIVEN STUD
DROP IN ANCHOR
POWDER DRIVEN STUD & II ROCOUPLING
DROP IN ANCHORS do ALL THREAD ROD ALL THREAD ROD SIZES
ALL THREAD ROD SIZES
FOR 1" THRV 4" PIPE
FOR 1" THRU 4" PIPE 3/8" IS TO BE USED ALLHREAD ROD'
3/8" IS TO BE USED
FOR 6" do 8" PIPE HANGER RING
1/2" IS TO BE USED
— PIPE
HANGER DETAIL #1
+NOTE: PER NFPA 13, FIG. A.9.2.3.4.3(b)
ROD WILL SE INSTALLED TIGHT TO PIPE. N.T.S.
— HAf,ER RING
— PIE
HANGER DETAIL #2
NOTE: PER NFPA 13, FIG. A.9.2.3.4.3(b) N.T.S.
ROD WILL BE INSTALLED TIC HT TO PIPE.
Hanger Schedule
Nominal Pipe Size
°
1'.
1 YC
11�"
2"
21Z"
Steel pipe except
N/A
12 -0
12 -0
15 -0
15 -0
15 -0
threaded lightwall
Steel pipe
N/A
12 -0
12 -0
12 -0
12 -0
12 -0
threaded lightwall
Nominal Pipe Size
3"
3%"
4"
5"
6"
8"
Steel pipe except
15 -0
15 -0
15 -0
15 -0
15 -0
15 -0
threaded lightwall
Steel pipe
12 -0
N/A
N/A
N/A
N/A
N/A
threaded lightwall
1" ARMOVER
(LENGTH VARIES)
1' 90' ELL 1' 90' ELL
1" x 0-4 NIP:'CE: ^ -
I" CROP —
(LENGTH VANES)
BRANCHLINE OR MAIL
RED. COUPLING —
CONCEALED PENDENT
— CEILING
SPRINKLER DETAIL #1
+ ARMOVERS GREATER THAN 12'
IN LENGTH SIALL BE SUPPORTED
BY A HANGEF
1" V
ARMOER
(LENGTH VARIES)
I
1" 90' ELL —
1'ARMOVER
(LENTH VARIES) — 1" x 0-4 N
1- 90' ELL — — 1 " TEE
— 1" x 0-4 N
1" DROP —
(LENGTH VARIES)
r�
RED. COUPLING —' / EXISTING BRANCHLINE OR MAIN
N.T.S.
— CO:EALED PENDENT CONCEALED PENDENT —
s ARMOVERS GREATER THAN 12'
IN LENGTH SHALL BE SUPPORTED
BY A HANGER.
C J �
CEILING
SPRINKLER DETAIL #2
V10
k.
I
INSTALLAON NOTES:
1" 90' ELL
- 1" DROP
(LENGTH VARIES)
— RED. COUPLING
' '• • R6 COVPp N ��
1) FOR INTEFR / PRESSURE TEST INSPECTION PLEASE MAKE
SURE THAT CLING TILES ARE NOT INSTALLED TO ALLOW FOR
PROPER INSCTION OF HANGERS.
2) FOR FIRE RINKLER FINAL INSPECTION, PLEASE MAKE SURE
THAT ALL CENG TILES ARE INSTALLED TO ALLOW FOR PROPER
INSPECTION ' THE ESCUTCHEONS AND DEFLECTOR HEIGHT.
GENERAL NOTES:
1) DESIGN AND INSTALLATION PERFPA 13, 2007 EDITION AND THE CITY OF
SOUTH MIAMI FOR LIGHT HAZARD CUPANCY.
2) ALL MATERIALS TO BE U.L. LIS).
3) - - - - DENOTES EXISTING FIRE 'RINKLER PIPING TO REMAIN.
4) DENOTES NEW FIRE SPR,LER PIPING (ALLIED 'XL').
5) DENOTES HANGER (SEE NGER DETAIL).
6) DENOTES NEW MECHANIC TEE OR SNAP-0-LET.
7) O DENOTES RELOCATED FIFSPRINKLER HEAD LOCATIONS.
8) • DENOTES NEW FIRE SPRLER HEAD LOCATIONS.
9) DENOTES EXISTING FIRE RINKLER HEAD TO REMAIN.
10) O DENOTES EXISTING 1 " OIET TO SUPPLY SPRINKLERS.
1 1) ANY ARM -OVER THAT EXCEED]' -0" SHALL BE PROPERLY SUPPORTED
PER NFPA -13 WITH A LISTED HAIR ASSEMBLY.(SEE DETAIL)
12) SCOPE OF WORK PER THIS GT (FP -1):
• RELOCATE (2) EXISTING CO[AALED PENDENT FIRE SPRINKLERS.
• ADD (1) NEW CONCEALED FDENT FIRE SPRINKLERS.
N.T.S.
Phillips Fire Sprinklers, Inc.
'The Service You Deserve'
425 S.W. 148th Avenue
Davie, Florida 33325
- - info ®phillipsfire.com
4) 217 -0600
T-
Mx) 217 -0601