14-1187-0101 DEMOLITION PLAN "
E -1 id
GENERAL ELECTRICAL NOTES
1. ALL WORK SHALL BE IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE,
THE FLORIDA BUILDING CODE AND ANY OTHER APPLICABLE CODES AND STANDARDS.
2.a) THE DRAWINGS ARE DIAGRAMMATIC AND DO NOT SHOW ALL OFFSETS, BENDS AND
BOXES REQUIRED TO MAKE A COMPLETE NEAT INSTALLATION IN ACCORDANCE
WITH N.E.C.
2.b) WHEN CONFLICTS ARISE IN LOCATING ELECTRICAL EQUIPMENT, DISCONNECTS,
PANELBOARDS ETC. DUE TO FIELD CONDITION OR IMPROPER FIELD COORDINATION,
CONTRACTOR SHALL BRING IT TO THE A /E's ATTENTION AND AT NO EXTRA COST
RELOCATE, AND OR EXTEND WITHIN A REASONABLE DISTANCE SUCH ITEM WHICH
IS IN CONFLICT. THE CONTRACTOR IS RESPONSIBLE FOR COORDINATING LOCATION
OF ALL COMPONENT PRIOR TO ROUGH -IN WITH ALL TRADES- NO EXTRAS WILL BE
ALLOWED FOR FAILURE TO DO SO.
3. THE CONTRACTOR IS RESPONSIBLE FOR EVALUATING FIELD CONDITIONS BY
VISITING THE SITE PRIOR TO COMMENCING /BIDDING WORK.
4. THE CONTRACTOR SHALL SATISFACTORILY REPAIR /REPLACE EQUIPMENT
DAMAGED AS A RESULT OF HIS WORK.
5. WIRE SIZE SHALL BE MIN. #14 THHN /THWN UNLESS OTHERWISE NOTED ON PLANS.
CONDUCTORS #6 AND LARGER SHALL BE THWN.
6. ALL CONDUCTORS SHALL BE COPPER, UNLESS OTHERWISE NOTED.
7. ALL CONDUCTORS SHALL BE RUN IN CONDUIT (METALLIC TYPE). IF PVC SCHEDULE
40 IS USED, AN EQUIPMENT GROUNDING CONDUCTOR SIZED IN ACCORDANCE WITH
N.E.C. ARTICLE 250 SHALL BE RUN WITH THE PHASE CONDUCTORS.
8. ALL MATERIALS SHALL BE U. L. APPROVED.
9. ALL EMPTY CONDUITS TO BE PROVIDED WITH NYLON PULL STRINGS.
10. FUSES SHALL BE DUAL ELEMENT, TIME DELAY TYPE UNLESS OTHERWISE NOTED.
11. RISERS ARE DIAGRAMMATIC ONLY. THEY DO NOT SHOW EVERY BEND REQUIRED
FOR THE INSTALLATION.
12. THIS DRAWING IS A GUIDE FOR THE INSTALLATION OF ELECTRICAL SERVICE. THE
ELECTRICAL CONTRACTOR IS RESPONSIBLE TO PROVIDE A FUNCTIONING SYSTEM.
13. ALL CABLES SHALL BE RUN WITHOUT SPLICES EXCEPT OTHERWISE INDICATED.
14. ALL PULL AND JUNCTION BOXES SHALL BE ACCESSIBLE AT ALL TIMES.
15. EXACT POINT AND METHODS OF CONNECTION SHALL BE DETERMINED IN FIELD.
16. ALL WORK SHALL BE DONE IN A NEAT AND WORKMANLIKE MANNER.
17. ALL RACEWAY ROUTED, INSULATED CONDUCTORS SYSTEM SHALL BE COLOR
CODED AS FOLLOWS:
120/208V SYSTEM
PHASE 'A' BLACK
PHASE 'B' RED
NEUTRAL WHITE
GROUND GREEN
18. ALL ROUGH -IN DIMENSIONS ARE TO CENTER LINE OF DEVICE UNLESS OTHERWISE
NOTED.
19. ALL PULL BOXES, HAND HOLES AND MANHOLES TO HAVE COVER PLATE BOLTED
TO FRAME AND BONDED TO THE EQUIPMENT GROUND SYSTEM.
20. ELECTRICAL CONTRACTOR SHALL COORDINATE ALL ITS WORK WITH OTHER
TRADES AND VERIFY EXISTING UTILITIES ROUTING PRIOR TO COMMENCEMENT OF
WORK TO AVOID ANY CONFLICT.
21. ALL CONDUCTOR SPLICES IN EXTERIOR JUNCTION /PULL BOXES - EXPOSED TO
THE WEATHER TO BE WEATHER SEALED BY USING AN APPROVED METHOD SUCH AS 3M
SCOTCHLOCK CONNECTOR EPDXY SEALING PACKS OR SIMILAR.
22. ALL DISCONNECT SWITCHES AND ELECTRICAL PANELS SHALL BE DURABLY AND
PERMANENTLY ENGRAVED TO WARN QUALIFIED PERSONS OF POTENTIAL ELECTRIC ARC
FLASH HAZARDS.
r - - - - SCOPE OF WORK -- - - - --�
ELECTRICAL SYMBOL LEGEND
USE THOSE THAT APPLY
$ 120/277 V., 20 AMP., SINGLE POLE LIGHT SWITCH.
$3 120/277 V., 20 AMP., THREE WAY SWITCH.
$OS OCCUPANCY SENSOR WITH WALL SWITCH, 'LEVITON',
120/277 002- ODS10 -1DW OR EQUAL
0 ELECTRICAL PANEL
DISCONNECT SWITCH. '3' INDICATES NUMBER OF POLES;
6001 "60" = FRAME SIZE AND 'F - DENOTES FUSE SIZE AS
3 F RECOMMENDED BY EQUIPMENT MANUFACTURER.
® 250V SPECIAL PURPOSE RECEPTACLE, TO MATCH EQUIPMENT PLUG
20 A, 120., V., DUPLEX RECEPTACLE, GROUNDING TYPE,
U.O.N. MOUNTED 18' A.F.F. OR AS DIRECTED BY ARCHITECT.
qp 20A, 120V Gn DUPLEX RECEPTACLE
(t1 20A, 120V SINGLE RECEPTACLE
20A, 120V QUADRUPLEX RECEPTACLE
❑J CEILING OR WALL MOUNTED JUNCTION BOX.
PHONE DATA OUTLET 0 +18' A.F.F.
(J. BO W/3/4' EMPTY CONDUIT TO CEILING SPACE). PROVIDE
PPULL STRING
® WALL OR CEILING MOUNTED EXIT LIGHT W /BATTERY. ARROWS, NUMBER OF
FACES AND MOUNTING AS REQUIRED TO INDICATE A CLEAN PART TO EXIT
WALL/CEILING MOUNT EMERGENCY /EXIT LIGHT COMBO UNIT
WITH BATTERY BACKUP.
QS SMOKE DETECTOR
® FIRE ALARM SPEAKER
SQL HORN /STROBE
ER EXISTING TO BE REMOVED
E EXISTING TO REMAIN
R RELOCATED
N NEW
EM EXISTING UGHT FIXTURE WITH BATTERY PACK
L.
r - - -- SCOPEOFWORK - - - - - -,
('3'
REFLECTED CEILING PLAN "
id id
NOTES:
1- U.O.N. EXISTING /RELOCATED LIGHT FIXTURES TO
REMAIN CONNECTED TO CORRESPONDING EXISTING
CIRCUITS AND SWITCHES.
2- PATIENT CARE AREA: EXAM ROOM 030A.
WIRING INSIDE PATIENT CARE AREA SHALL COMPLY
WITH NEC ARTICLE 517.13(A)(B).
j
l�j%%111111fl,�, .
U.I, -
w uj
•,� � S 1 r1 - • \ �
JS�0N
L_
id
O
Y ~,
insight
design
2930 Northeast 2nd Court
Miami, FL
33137
305.545.4964
AA0003130
ID0003964
0
:a
M
EVISIONS
,& I DATE /TYPE OF REVISI
SHEET TITLE:
ELECTRICAL
PLAN
N
N
rn
a
ALEJANDRO BONET
PROJECT NO: 1110 -11 loft
DRAWN BY: LNI
DATE: 05.12.2014
SCALE: AS NOTED
SHEET NO:
E -1
e
t
110
a
rir
�:.titif ,:Ga►
j
W
M
L
.0
M
Q
c
r'
M
a
0)
U
4
as
o
M
co
c
O
o
0
i
CD
CO
a,w
�
�
o
04
3:
Z
alai
a
0
:a
M
EVISIONS
,& I DATE /TYPE OF REVISI
SHEET TITLE:
ELECTRICAL
PLAN
N
N
rn
a
ALEJANDRO BONET
PROJECT NO: 1110 -11 loft
DRAWN BY: LNI
DATE: 05.12.2014
SCALE: AS NOTED
SHEET NO:
E -1