14-1075R-001I/
GENERAL NOTES,
SMH Data Center — 2nd Floor Main Building
1: FM 200 CONTROL PANEL IS TO BE TIED INTO THE BLDG. FIRE ALARM SYSTEM (BY OTHERS).
7440 SW 62nd Avenue
2.- CLIPPING OF CEILING TILES (BY OTHERS).
1st ALARM
3.- ALL DOORS AND ROOMS TO BE SEALED (BY OTHERS).
4- ALL VENTILATION INTO AND OUT OF THE PROTECTED SPACES MUST BE SHUT DOWN PRIOR TO THE FM-200 DISCHARGE.
5.- ANY DUCT WORK PENETRATING THE ENVELOPE OF THE ROOM MUST HAVE A CLASS 1 LOW LEAKAGE MOTORIZED DAMPERS
DISCIPLINE MECHANICAL ENGINEER
INSTALLED AND WIRED TO OUR PANEL (BY OTHERS).
DRAWN Orlando Alfonso
6- ALL DOORS TO THE PROTECTED SPACES SHALL BE KEPT CLOSED, OR BE PROVIDED WITH AUTOMATIC CLOSERS TO
OPERATE PRIOR TO FM 200 DISCHARGE. IT SHALL BE THE RESPONSIBILITY OF THE OWNER OR BUILDER TO MAKE THE ROOM
TIGHT TO PREVENT FM -200 LOSS.
2nd ALARM
7.- THIS SYSTEM WILL NOT BE TIED TO THE EPO SWITCH.
8.- TWO EXISTING SPRINKLER HEADS WILL BE REMOVED FROM THE ROOM.
TELEPHONE 305) 262 -3944
MECHANICAL N011"YE's-
DISCHARGE
1 -ALL CONTAINER AND PIPING INSTALLATIONS MUST CONFORM TO NFPA 2001, CURRENT EDITION.
2.- PIPING MUST BE BLACK IRON STEEL PER ASTM A-53 OR X106, WITH AN INTERNAL PRESSURE RATING OF AT LEAST 620 PSIA.
3.- ALL PIPE FITTINGS TO COMPLY WITH WITH STRENGTH REQUIREMENTS IN NFPA 2001. ALL PIPE REDUCTIONS ARE TO BE MADE MANUAL RELEASE
USING CONCENTRIC REDUCERS ONLY,
4.- CUT- GROOVED FITTINGS AREA ACCEPTABLE IF THEY ARE RATED AT A MINIMUM OF 620 PSIA WORKING PRESSURE. LUBRICATE
GASKET ON ALL CUT - GROOVED FITTINGS USING A NON - PETROLEUM BASED LUBRICANT,
5.- ALL PIPE AND FITTINGS SHALL BE REAMED, BLOWN CLEAR, AND SWABBED WITH A CLEANING SOLVENT TO REMOVE DIRT, RUST
AND CUTTING OILS.
6.- ALL THREADED JOINTS MUST BE SEALED USING TEFLON TAPE OR A HEAVY DUTY SEALING PASTE WITH TEFLON.
7.- ALL PIPING MUST BE RIGIDLY SUPPORTED WITH PIPE HANGARS AND PIPE SUPPORT BRACKETS. PIPE HANGERS SHOULD BE
SPACED AT A 15 FOOT MAXIMUM. RIGID PIPE SUPPORTS ARE REQUIRED TO SUPPORT THE LIVE LOAD OF THE PIPE SYSTEM ABORT
DURING DISCHARGE. RIGID BRACING IS REQUIRED AT EACH DIRECTIONAL CHANGE FITTINGS, TEE, AND NOZZLE. ALL DROPS TO
180° NOZZLE REQUIRE BACK - BRACING IN THE OPPOSITE DIRECTION OF DISCHARGE.
8.- SYSTEM FLOW CALCULATIONS ARE BASED ON THE PIPE BEING INSTALLED EXACTLY AS INDICATED ON SYSTEM PLANS. ANY
PIPING CHANGE IN THE FIELD MUST BE APPROVED BY TRIANGLE FIRE, INC.
DOOR FAN TEST-
1.- THE DOOR FAN TECHNICIAN WILL SET UP THE DOOR PANEL AND BLOWER.
2- THE BLOWER WILL BE CONNECTED TO THE CONTROLS.
3.- THE ROOM VOLUME, ROOM HEIGHT, AGENT TYPE AND AGENT QUANTITY
WILL BE ENTERED INTO THE COMPUTER.
4- ALL A/C UNITS WILL BE SHUT -OFF AND DAMPER'S CLOSED.
5.- THE TECH WILL "PRESSURIZE" THE ROOM WITHIN THE PRESSURE RANGES
GIVEN BY THE COMPUTER AND THEN ENTER THE DATA INOT THE PROGRAM.
6. -THE TECH WILL "DEPRESSURIZE" THE ROOM WITHIN THE PRESSURE
RANGES GIVEN BY THE COMPUTER AND THEN ENTER THE DATA INTO THE
PROGRAM.
7.- THE COMPUTER PROGRAM WILL THEN CALCULATE THE DATA AND EITHER
PASS OR FAIL THE ROOM.
11 ii 111 19
-WHEN ANY DETECTOR IN THE COMPUTER ROOM AREA GOES INTO ALARM, IT SHALL
ACTIVATE THE FOLLOWING:
- BELLS WILL SOUND THE FIRST ALARM TONE.
- ALARM CONTACTS SHALL NOTIFY BUILDING FIRE ALARM.
- AIR HANDLER UNITS SHALL SHUT DOWN.
- FIRE SMOKE DAMPERS SHALL FULLY CLOSE.
- WHEN ANY DETECTOR IN THE COMPUTER ROOM AREA GOES INTO ALARM THE FOLLOWING WILL ACTIVATE:
- HORN/STROBES SHALL SOUND THE SECOND ALARM TONE.
THIS WILL ALSO BEGIN THE 3D-SECOND DISCHARGE COUNTDOWN.
- WHEN THE 30- SECOND TIME DELAY HAS EXPIRED THE SYSTEM WILL ACTIVATE THE FOLLOWING:
-THE CLEAN AGENT CYLINDERS WILL DISCHARGE.
-THIS DISCHARGE STROBE WILL ACTIVATE.
- HORN/STROBES WILL ACTIVATE.
- WHEN THE MANUAL RELEASE STATION IS ACTIVATED THE FOLLOWING SHALL OPERATE:
-ALARM CONTACTS WILL ACTIVATE THE BUILDING FIRE ALARM.
- THE CLEAN AGENT CYLINDERS WILL DISCHARGE.
- THE HORN/STROBES WILL SOUND.
- THIS DISCHARGE STROBE WILL ACTIVATE.
- AIR HANDLER UNITS SHALL SHUT DOWN.
- FIRE SMOKE DAMPERS SHALL FULLY CLOSE.
- WHEN AN ABORT STATION IS ACTIVATED THE FOLLOWING SHALL OCCUR:
- THE 30- SECOND DELAY (WHICH IS ACTIVATED BY (2) ALARMS IN THE ZONE) SHALL BE INTERRUPTED.
THE TIME WILL RESET BACK TO ITS ORIGINAL VALUE OF 30 SECONDS AND HOLD THERE UNTIL THE
ABORT BUTTON IS RELEASED, AT WHICH TIME THE SYSTEM RESUMES ITS COUNTDOWN TO DISCHARGE.
THE ACTIVATION OF A MANUAL RELEASE STATION WILL OVERRIDE THE ABORT FUNCTION (EVEN IF THE
ABORT IS ACTIVE), WHICH WILL RESULT IN IMMEDIATE DISCHARGE OF THE GAS.
- A TROUBLE SIGNAL WILL BE ANNUNCIATED VISUALLY AND AUDIBLY AT THE CONTROL PANEL TO INDICATE A
COMPROMISE
PrR..jESSURE TEST
THE PIPING SHALL BE PNEUMATICALLY TESTED IN A CLOSED CIRCUIT FOR A PERIOS OF 10MIN. @ 40ps1g (276 kPa).
AT THE END OF 10MIN., THE PRESSURE DROP SHALL NOT EXCEED 20% OF THE TEST PRESSURE.
PU- FF TEST
A FLOW TEST USING NITROGEN OR AN INERT GAS CHALL BE PERFOMED ON
THE PIPING NETWORK TO VERIFY THAT FLOW IS CONTINUOUS AND THAT THE
PIPING AND NOZZLE ARE UNOBSTRUCTED.
0 0
WARNING
THIS AREA IS PROTECTED BY A
FM -200 EXTINGUISHING
SYSTEM. DO NOT ENTER WITHOUT
AUTHORIZATION DURING OR
AFTER DISCHARGE
0 0
FM -200 WARNING SIGN DETAIL
N.T.S.
0 0
CAUTION
WHEN LIGHT IS
FLASHING AGENT
HAS DISCHARGED
0 0
[fill r_ -•: r
o a
WARNING
WHEN ALARM SOUNDS
VACATE AT ONCE
EXTINGUISHING AGENT
IS BEING RELEASED
0 0
INSIDE HORN /STROBES SIGN DETAIL
N.T.S.
0 0
FM -200
PULL
STATION
0 0
o a
FM -200
ABORT
STATION
;0 Q
KID DE i' •
NO SCALE P/N .0 ..0
FM -200 PULL SIGN DETAIL FM -200 ABORT SIGN DETAIL
N.T.S. N.T.S.
* *SIGN PLATES ARE LOCATED NEAR DEVICE"
VALVE 0Un-ET
PLAN VIEW
CYLINDER VALVE
10'
SUBFLOOR 1/
PLAN VIEW
CYUNDER VALVE
SMH Data Center — 2nd Floor Main Building
7440 SW 62nd Avenue
South Miami, FL 33145
ENGINEERS
NAME MICHAEL C. GUERRERO
DISCIPLINE MECHANICAL ENGINEER
scALE AS SHOWN
DRAWN Orlando Alfonso
TELEPHONE 305) 262 -3944
UC. FL 15235
4
r ' "' ' '
DATE July 10, 2014
REVISED 10/1/2014
ADDRESS 8230 CORAL WAY
KIDDE FM 200 FIRE SUPRESSION
SHEET
MIAMI, FL 33155
`; . , `
SYSTEM W /ONE 350LB. AND ONE
1
ENGIN oA D SEAL
40LB. AGENT TANK.
OF 3 SHEETS