14-1075-001
GENERAL NOTES SEA 1.- FM -200 CONTROL PANEL IS TO BE TIED INTO THE BLDG. FIRE ALARM SYSTEM (BY OTHERS). 2.- CLIPPING OF CEILING TILES (BY OTHERS). 1st ALARM 3.- ALL DOORS AND ROOMS TO BE SEALED (BY OTHERS). 4.- ALL VENTILATION INTO AND OUT OF THE PROTECTED SPACES MUST BE SHUT DOWN PRIOR TO THE FM -200 DISCHARGE. 5.- ANY DUCT WORK PENETRATING THE ENVELOPE OF THE ROOM MUST HAVE A CLASS 1 LOW LEAKAGE MOTORIZED DAMPERS INSTALLED AND WIRED TO OUR PANEL (BY OTHERS). 6.- ALL DOORS TO THE PROTECTED SPACES SHALL BE KEPT CLOSED, OR BE PROVIDED WITH AUTOMATIC CLOSERS TO OPERATE PRIOR TO FM -200 DISCHARGE. IT SHALL BE THE RESPONSIBILITY OF THE OWNER OR BUILDER TO MAKE THE ROOM TIGHT TO PREVENT FM -200 LOSS. 2nd ALARM 7.- THIS SYSTEM WILL NOT BE TIED TO THE EPO SWITCH. 8: TWO EXISTING SPRINKLER HEADS WILL BE REMOVED FROM THE ROOM. MECHANICAL NOT-PQ DISCHARGE UENCE OF OPERATION 1. -ALL CONTAINER AND PIPING INSTALLATIONS MUST CONFORM TO NFPA 2001, CURRENT EDITION. 2.- PIPING MUST BE BLACK IRON STEEL PER ASTM A -53 OR A -106, WITH AN INTERNAL PRESSURE RATING OF AT LEAST 620 PSIA. 3.- ALL PIPE FITTINGS TO COMPLY WITH WITH STRENGTH REQUIREMENTS IN NFPA 2001. ALL PIPE REDUCTIONS ARE TO BE MADE MANUAL RELEASE USING CONCENTRIC REDUCERS ONLY. 4.- CUT - GROOVED FITTINGS AREA ACCEPTABLE IF THEY ARE RATED AT A MINIMUM OF 620 PSIA WORKING PRESSURE. LUBRICATE GASKET ON ALL CUT - GROOVED FITTINGS USING A NON - PETROLEUM BASED LUBRICANT. 5.- ALL PIPE AND FITTINGS SHALL BE REAMED, BLOWN CLEAR, AND SWABBED WITH A CLEANING SOLVENT TO REMOVE DIRT, RUST AND CUTTING OILS. 6.- ALL THREADED JOINTS MUST BE SEALED USING TEFLON TAPE OR A HEAVY DUTY SEALING PASTE WITH TEFLON. 7.- ALL PIPING MUST BE RIGIDLY SUPPORTED WITH PIPE HANGARS AND PIPE SUPPORT BRACKETS. PIPE HANGERS SHOULD BE SPACED AT A 15 FOOT MAXIMUM. RIGID PIPE SUPPORTS ARE REQUIRED TO SUPPORT THE LIVE LOAD OF THE PIPE SYSTEM ABORT DURING DISCHARGE. RIGID BRACING IS REQUIRED AT EACH DIRECTIONAL CHANGE FITTINGS, TEE, AND NOZZLE. ALL DROPS TO 1800 NOZZLE REQUIRE BACK - BRACING IN THE OPPOSITE DIRECTION OF DISCHARGE. 8.- SYSTEM FLOW CALCULATIONS ARE BASED ON THE PIPE BEING INSTALLED EXACTLY AS INDICATED ON SYSTEM PLANS. ANY PIPING CHANGE IN THE FIELD MUST BE APPROVED BY TRIANGLE FIRE, INC. DOOR FAN TEST TROUBLE 1.- THE DOOR FAN TECHNICIAN WILL SET UP THE DOOR PANEL AND BLOWER. 2.- THE BLOWER WILL BE CONNECTED TO THE CONTROLS. 3.- THE ROOM VOLUME, ROOM HEIGHT, AGENT TYPE AND AGENT QUANTITY WILL BE ENTERED INTO THE COMPUTER. 4.- ALL A/C UNITS WILL BE SHUT -OFF AND DAMPER'S CLOSED. 5.- THE TECH WILL "PRESSURIZE" THE ROOM WITHIN THE PRESSURE RANGES GIVEN BY THE COMPUTER AND THEN ENTER THE DATA INOT THE PROGRAM. 6.- THE TECH WILL "DEPRESSURIZE" THE ROOM WITHIN THE PRESSURE RANGES GIVEN BY THE COMPUTER AND THEN ENTER THE DATA INTO THE PROGRAM. 7.- THE COMPUTER PROGRAM WILL THEN CALCULATE THE DATA AND EITHER PASS OR FAIL THE ROOM. - WHEN ANY DETECTOR IN THE COMPUTER ROOM AREA GOES INTO ALARM, IT SHALL ACTIVATE THE FOLLOWING: - BELLS WILL SOUND THE FIRST ALARM TONE. - ALARM CONTACTS SHALL NOTIFY BUILDING FIRE ALARM. - AIR HANDLER UNITS SHALL SHUT DOWN. - FIRE SMOKE DAMPERS SHALL FULLY CLOSE. - WHEN ANY DETECTOR IN THE COMPUTER ROOM AREA GOES INTO ALARM THE FOLLOWING WILL ACTIVATE: - HORN/STROBES SHALL SOUND THE SECOND ALARM TONE. THIS WILL ALSO BEGIN THE 30-SECOND DISCHARGE COUNTDOWN. - WHEN THE 30- SECOND TIME DELAY HAS EXPIRED THE SYSTEM WILL ACTIVATE THE FOLLOWING: - THE CLEAN AGENT CYLINDERS WILL DISCHARGE. -THIS DISCHARGE STROBE WILL ACTIVATE. - HORN/STROBES WILL ACTIVATE. -WHEN THE MANUAL RELEASE STATION IS ACTIVATED THE FOLLOWING SHALL OPERATE: - ALARM CONTACTS WILL ACTIVATE THE BUILDING FIRE ALARM. - THE CLEAN AGENT CYLINDERS WILL DISCHARGE. - THE HORN/STROBES WILL SOUND. - THIS DISCHARGE STROBE WILL ACTIVATE. - AIR HANDLER UNITS SHALL SHUT DOWN. - FIRE SMOKE DAMPERS SHALL FULLY CLOSE. - WHEN AN ABORT STATION IS ACTIVATED THE FOLLOWING SHALL OCCUR: -THE 30- SECOND DELAY (WHICH IS ACTIVATED BY (2) ALARMS IN THE ZONE) SHALL BE INTERRUPTED. THE TIME WILL RESET BACK TO ITS ORIGINAL VALUE OF 30 SECONDS AND HOLD THERE UNTIL THE ABORT BUTTON IS RELEASED, AT WHICH TIME THE SYSTEM RESUMES ITS COUNTDOWN TO DISCHARGE. THE ACTIVATION OF A MANUAL RELEASE STATION WILL OVERRIDE THE ABORT FUNCTION (EVEN IF THE ABORT IS ACTIVE), WHICH WILL RESULT IN IMMEDIATE DISCHARGE OF THE GAS. - A TROUBLE SIGNAL WILL BE ANNUNCIATED VISUALLY AND AUDIBLY AT THE CONTROL PANEL TO INDICATE A COMPROMISE PRESSURE TEST THE PIPING SHALL BE PNEUMATICALLY TESTED IN A CLOSED CIRCUIT FOR A PERIOS OF 10MIN. c@ 40psig (276 kPa). AT THE END OF 10MIN., THE PRESSURE DROP SHALL NOT EXCEED 20% OF THE TEST PRESSURE. PUFF TEST A FLOW TEST USING NITROGEN OR AN INERT GAS CHALL BE PERFOMED ON THE PIPING NETWORK TO VERIFY THAT FLOW IS CONTINUOUS AND THAT THE PIPING AND NOZZLE ARE UNOBSTRUCTED. TANK 'A' TANK 'B' SCALE: 1/4" =1' O O WARNI NG THIS AREA IS PROTECTED BY A FM -200 EXTINGUISHING SYSTEM. DO NOT ENTER WITHOUT AUTHORIZATION DURING OR AFTER DISCHARGE O O FM -200 WARNING SIGN DETAIL N.T.S. O O CAUTION WHEN LIGHT IS FLASHING AGENT HAS DISCHARGED o O OUTSIDE STROBE SIGN DETAIL N.T.S. O O WARNING WHEN ALARM SOUNDS VACATE AT ONCE EXTINGUISHING AGENT IS BEING RELEASED O O INSIDE HORNISTROBES SIGN DETAIL N.T.S. 0 0 FM -200 PULL STATION 0 0 0 0 FM -200 ABORT STATION 0 0 HORN /STROBE LEGEND 75- 000082 -002 8 BELL GEMINI II SUPPRESSION CONTROL P/N 75- 000031 -001 Main Building FSCP _PANEL P/N 84- 322001 --06' - 75- 000005 -022 O PHOTOELECTRIC DETECTOR TANK A 35u La.- -AGENT TANK P/N 71- 570000 -001 Oj IONIZATION DETECTOR Uzp MODEL CPD 7054 P/N 70- 540000 -001 TANK B 40 LB. AGENT TANK PHOTOELECTRIC DETECTOR (Subfloor) MODEL PSD 7157 P/N 90- 100040 -001 P/N 71- 570000 -001 QI IONIZATION DETECTOR (Subfloor) KIDDE PENDANT NOZZLE ® ELECTRIC CONTROL HEAD KIDDE P/N 486500 -01 ABORT STATION y4 KIDDE MODEL 878752 MANUAL PULL STATION 4 6 11 9 7 14 '. (D 0 0 MI�M1 X SUBFLO R y'K DETECT R �•w ROE M NOZZLE \ (TYP.) -t00 S UB �n ate r� 'r. r N� ROOM NO LE �YJ .�J r 1 a I + .' 8 15 � w v ��; 3 - RO 9 M NOZZLE z. r SUB LOOR NO ZLE SCALE: 1/4" =1' O O WARNI NG THIS AREA IS PROTECTED BY A FM -200 EXTINGUISHING SYSTEM. DO NOT ENTER WITHOUT AUTHORIZATION DURING OR AFTER DISCHARGE O O FM -200 WARNING SIGN DETAIL N.T.S. O O CAUTION WHEN LIGHT IS FLASHING AGENT HAS DISCHARGED o O OUTSIDE STROBE SIGN DETAIL N.T.S. O O WARNING WHEN ALARM SOUNDS VACATE AT ONCE EXTINGUISHING AGENT IS BEING RELEASED O O INSIDE HORNISTROBES SIGN DETAIL N.T.S. 0 0 FM -200 PULL STATION 0 0 0 0 FM -200 ABORT STATION 0 0 KIDDE PENDANT NOZZLE © MODEL 3300 NO SCALE P/N 90- 19402X -XXX P/N 84- 330001 -001 FM -200 PULL SIGN DETAIL FM -200 ABORT SIGN DETAIL N.T.S. N.T.S. * *SIGN PLATES ARE LOCATED NEAR DEVICE ** vA1 vc nI m_ET 58.36" 53.10" PLAN VIEW CYUNDER VALVE NAME PLATE 16.00" DIA. KIDDE FM -200 TANK 350 LB. AGENT TANK w/ 282 LBS OF AGENT NO SCALE �--- 19.50 " -� 7. 5" 15.50" .437" I r- • -�I �" 350 LBS. CYLINDER MOUNTING STRAP NO SCALE P/N 281868 CIL APPPRED By 0, 5 PITY f IRE Di CEILING HEIGHT SUBFLOOR 1 ELEVATION THE FOLLOWING LIFE SAFETY FEATURES M BE PROVIDED AT TIME OF OCCUPANCY: i WAT'- 4. l ENGINEERS NAME MICHAEL C. GUERRERO DISCIPLINE MECHANICAL ENGINEER (305) 262 -3944 # 15235 TELEPHONE LIC. FL ADDRESS 8230 CORAL WAY MIAMI, FL 33155 ENGINEERS DATED SEAL © KEY MAINTENANCE BYPASS SWITCH KIDDE P/N 76- 600000 -200 HORN /STROBE LEGEND 75- 000082 -002 8 BELL GEMINI II SUPPRESSION CONTROL P/N 75- 000031 -001 Main Building FSCP _PANEL P/N 84- 322001 --06' - 75- 000005 -022 O PHOTOELECTRIC DETECTOR TANK A 35u La.- -AGENT TANK P/N 71- 570000 -001 Oj IONIZATION DETECTOR P/N 90- 100350 -001 MODEL CPD 7054 P/N 70- 540000 -001 TANK B 40 LB. AGENT TANK PHOTOELECTRIC DETECTOR (Subfloor) MODEL PSD 7157 P/N 90- 100040 -001 P/N 71- 570000 -001 QI IONIZATION DETECTOR (Subfloor) KIDDE PENDANT NOZZLE ® ELECTRIC CONTROL HEAD KIDDE P/N 486500 -01 ABORT STATION KIDDE MODEL 878752 MANUAL PULL STATION KIDDE PENDANT NOZZLE © MODEL 3300 NO SCALE P/N 90- 19402X -XXX P/N 84- 330001 -001 FM -200 PULL SIGN DETAIL FM -200 ABORT SIGN DETAIL N.T.S. N.T.S. * *SIGN PLATES ARE LOCATED NEAR DEVICE ** vA1 vc nI m_ET 58.36" 53.10" PLAN VIEW CYUNDER VALVE NAME PLATE 16.00" DIA. KIDDE FM -200 TANK 350 LB. AGENT TANK w/ 282 LBS OF AGENT NO SCALE �--- 19.50 " -� 7. 5" 15.50" .437" I r- • -�I �" 350 LBS. CYLINDER MOUNTING STRAP NO SCALE P/N 281868 CIL APPPRED By 0, 5 PITY f IRE Di CEILING HEIGHT SUBFLOOR 1 ELEVATION THE FOLLOWING LIFE SAFETY FEATURES M BE PROVIDED AT TIME OF OCCUPANCY: i WAT'- 4. l ENGINEERS NAME MICHAEL C. GUERRERO DISCIPLINE MECHANICAL ENGINEER (305) 262 -3944 # 15235 TELEPHONE LIC. FL ADDRESS 8230 CORAL WAY MIAMI, FL 33155 ENGINEERS DATED SEAL © KEY MAINTENANCE BYPASS SWITCH KIDDE P/N 76- 600000 -200 SAFE1I MODEL CPD 7054 P/N 70- 540000 -001 PLAN VIEW CYLINDER VALVE 26.76" 22.8" CYUNDER NAME PLATE 9.00" DIA. KIDDE FM -200 TANK 40 LB. AGENT TANK w/ 35 LBS OF AGENT NO SCALE �+-- 11.69 " -� .5" 8.16" .437" �_ •_� �" T 40 LBS. CYLINDER MOUNTING STRAP NO SCALE P/N 283934 FILE NAME: SMH Data Center - 2nd Floor Main Buildin Triangle HORN /STROBE Inc. 75- 000082 -002 8 BELL 592 -5254 P/N 75- 000031 -001 Main Building STROBE Q 75- 000005 -022 O PHOTOELECTRIC DETECTOR MODEL PSD 7157 P/N 71- 570000 -001 Oj IONIZATION DETECTOR MODEL CPD 7054 P/N 70- 540000 -001 © PHOTOELECTRIC DETECTOR (Subfloor) MODEL PSD 7157 P/N 71- 570000 -001 QI IONIZATION DETECTOR (Subfloor) SAFE1I MODEL CPD 7054 P/N 70- 540000 -001 PLAN VIEW CYLINDER VALVE 26.76" 22.8" CYUNDER NAME PLATE 9.00" DIA. KIDDE FM -200 TANK 40 LB. AGENT TANK w/ 35 LBS OF AGENT NO SCALE �+-- 11.69 " -� .5" 8.16" .437" �_ •_� �" T 40 LBS. CYLINDER MOUNTING STRAP NO SCALE P/N 283934 FILE NAME: SMH Data Center - 2nd Floor Main Buildin Triangle Fire, Inc. ' 7720 N.W. 53rd Street, Miami, FL 33166 (305) 592-3011, Fax: (305) 592 -5254 SMH Data Center - 2nd Floor Main Building 7400 SW 62nd Avenue South Miami, FL 33145 SCALE AS SHOWN DRAWN Orlando Alfonso DATE July 10, 2014 REVISED KIDDE FM 200 FIRE SUPRESSION SHEET SYSTEM W /ONE 350LB. AND ONE 1 40LB. AGENT TANK. of 3 SHEETS