13-834R-025EXISTING PANEL: NH1B FED FROM: DP NORMAL LOCATION: ELEC RM WIRES: 4W + G NEUTRAL BUS: Yes MAIN BUS: 225A ENCLOSURE: NEMA 1 GROUND BUS: Yes MCB: N/A BUS TYPE: Copper ISOLATED GROUND BUS: No VOLTAGE: 480/277 MOUNTING: Surface 200% NEUTRAL: No AIC: 10,000A PANEL LUGS: Main Lugs Only FEED THROUGH LUGS: Yes CKT N0. DESCRIPTION TOTAL LOAD (VA) CIRCUIT BREAKER PHASE CIRCUIT BREAKER TOTAL LOAD (VA) DESCRIPTION CKT NO AMPS POLES AMPS =POLES 1 SPARE - 20 1 A 20 1 1000 CASHIERS 2 3 LIGHTS 1000 20 1 B 20 1 1000 LIGHITNG 4 5 LIGHTS 1000 20 1 C 20 1 1000 LIGHTING 6 7 OUTDOOR LIGHTS 900 20 1 A 20 1 900 INSTAN HOT 8 9 SPARE - 20 1 B 20 1 900 INSTAN HOT 10 11 OFFICE LIGHTS 1200 20 1 C 20 1 - SPARE 12 13 FAN 1500 30 3 A 20 1 1000 LIGHTING 14 15 - 1500 - - B 20 1 1000 LIGHITNG 16 17 - 1500 20 - C 20 1 - LIGHTING 18 19 FAN 1500 30 3 A 20 3 - SPARE 20 21 - - 1500 - - B - - - - 22 23 - 1500 - - C - 1 500 ENVIROMENTAL 24 25 SPARE - 20 1 A 30 3 - NEW CHAPEL RTU NOTE 1 26 27 SPARE - 20 1 B - - - - 28 29 SPARE - 20 1 C - - - - 30 31 PANEL N1_1 12000 60 3 A 20 3 4426 XMER FRON COMP 32 33 - 12000 - - B - - 4426 - 34 35 - 12000 - - C - - 4426 - 36 37 PANEL 1NLCF1 12000 60 3 A 45 3 9960 PANEL NL1B 38 39 - 12000 - - B - - 9960 - 40 41 - 12000 - - C - - 9960 - 42 NOTES: NOTE: REMOVE EXISTING 3P -70A CB INCLUDING WIRING AND REPLACE WITH A NEW 3P -30A CB WITH 3 #10, 1 #10G, 1#10N IN EXISTING CONDUIT RUN. 'NH1B' LOAD SUMMARY CKT NO. LTS RCPTS MTRS MISC TOTAL (KVA) TOTAL (AMPS) TOTAL CONNECTED LOAD 9.1 0.0 9,0 117.0 135.1 162.4 DEMAND FACTOR SEE DEMAND FACTOR TABLE TOTAL DEMAND LOAD 9.1 0.0 10.1 117.0 136.2 163.8 CONTINUOUS (DESIGN) FACTOR 1.25 1.00 1.00 1,00 1 B TOTAL DESIGN LOAD 11,4 0.0 10.1 117.0 138.5 166.5 EXISTING PANEL: LA FED FROM: MSBL3 CRITICAL LOCATION: ELEC RM WIRES: 4W + G NEUTRAL BUS: Yes MAIN BUS: 100A ENCLOSURE: NEMA 1 GROUND BUS: Yes MCB: N/A BUS TYPE: Copper ISOLATED GROUND BUS: No VOLTAGE: 208/120 MOUNTING: Recessed 200% NEUTRAL: No AIC: 10,000A PANEL LUGS: Main Lugs Only FEED THROUGH LUGS: Yes CKT NO. DESCRIPTION TOTAL LOAD (VA) CIRCUIT BREAKER PHASE CIRCUIT BREAKER TOTAL LOAD (VA) DESCRIPTION CKT NO AMPS POLES AMPS POLES 1 CONE. RM A _ 900 20 1 A 20 1 900 HALL 2 3 CONE RM A AND B 1200 20 1 B 20 1 900 RECEPTACLES 4 5 CONF RM A 850 20 1 C 20 1 900 RECEPTACLES 6 7 HALLWAY 500 20 1 A 20 1 200 DDC CONTROLLER NOTE i 8 9 RECEPTACLES 900 20 1 B 20 1 720 CUSTODIAL 10 11 RECEPTACLES 900 20 1 C 20 1 900 WAITING 12 13 LIGHTING 1000 20 1 A 20 1 200 CONTROLS 14 15 LIGHTING 1000 20 1 B 20 1 500 RH 16 17 LIGHTING 1000 20 1 C 20 1 900 LIGHTING 18 19 CONF B AND D 1000 20 1 A 20 1 450 BLOWERS 20 2.1 LIGHTING 900 20 1 B 20 1 450 BACK 22 23 LIGHTING 900 20 1 C 20 1 500 ENVIROMENTAL 24 25 LIGHTING 900 20 1 A 20 1 900 RECEPTACLES 26 27 LIGHTING 900 20 1 B 20 1 900 RECEPTACLES 28 29 LIGHTING 900 20 1 C 20 1 900 RECEPTACLES 30 NOTES: NOTE 1: PROVIDE A NEW 1P -20A CB WITH 2 #12, 1 #12G IN 3/4 "C. 'LA' LOAD SUMMARY CKT N0. LTS RCPTS MISC TOTAL (KVA) TOTAL (AMPS) TOTAL CONNECTED LOAD 12.9 8.8 2.3 24.0 66.5 DEMAND FACTOR SEE DEMAND FACTOR TABLE TOTAL DEMAND LOAD 119 8.8 2.3 24.0 1 66.5 CONTINUOUS (DESIGN) FACTOR 1.25 1.00 1.00 3 - TOTAL DESIGN LOAD 16.1 $.8 2.3 27.2 1 75.5 EXISTING PANEL: 1MNH1 FED FROM: MSBH4 NORMAL LOCATION: ELEC ROOM WIRES: 4W + G NEUTRAL BUS: Yes MAIN BUS: 225A ENCLOSURE: NEMA 1 GROUND BUS: Yes MCB: N/A BUS TYPE: Copper ISOLATED GROUND BUS: No VOLTAGE: 480/277 MOB_, AG: Surface 200% NEUTRAL: No AIC: 65,000A PANEL LUGS: Main Lugs Only FEED THROUGH LUGS: Yes CKT N0. DESCRIPTION TOTAL LOAD (VA) CIRCUIT BREAKER PHASE CIRCUIT BREAKER TOTAL LOAD (VA) DESCRIPTION CKT NO AMPS POLES AMPS POLES 1 COMPACTOR 3000 20 3 A 20 3 3000 COMPACTOR 2 3 - 3000 - - B - - 3000 143.3 4 5 - 3000 - - C - - 3000 - 6 7 TRASH COMPACTOR 3000 20 1 3 A 20 3 3000 SURGE ARRESTER 8 9 - 3000 - - B - - 3000 - 10 11 - 3000 - - C - - 3000 - 12 13 TRASH COMPACTOR 3000 20 3 A 20 3 3000 PUMP 14 15 - 3000 - UNIT CONFERENCE B 9960 3000 - 16 17 - 3000 - - C - - 3000 - 18 19 AHU -1 3000 20 3 A 20 3 3000 WATER PUMP 20 21 - 3000 - - B - - 3000 3 22 23 - 3000 - - C - -- 3000 - 24 25 CONFERENCE FAN 3000 20 3 A 20 3 3000 HEAT PUMP 26 27 - 3000 - - B - -- 3000 - 28 29 - 3000 - - C - - 3000 - 30 31 UNIT A 3000 20 3 A 20 3 3000 UNIT C 32 33 - 3000 - - B - - 3000 - 34 35 - 3000 - - C - - 3000 - 36 37 AIR COMPRESSOR 3000 20 3 A 20 3 3000 UNIT 38 39 3000 - - B - - 3000 - 40 41 - 3000 - - C - - 3000 - 42 43 B1 -A1 3000 20 3 A 20 3 2033 MEDICAL RECORDS A/C NOTE 1 44 45 - 3000 - - B - - 2033 - 46 47 - 3000 - - C - - 2033 - 48 49 SPARE - 20 1 A 20 1 - SPARE 50 51 SPARE - 20 1 B 20 1 - SPARE 52 53 ISPARE - 20 1 C 20 1 - SPARE 54 55 NOT USABLE - 20 1 A 20 1 - NOT USABLE 56 57 NOT USABLE - 20 1 B 20 1 - NOT USABLE 58 59 NOT USABLE - 20 1 C 20 1 - NOT USABLE 60 61 NOT USABLE - 20 1 A 20 1 - NOT USABLE 62 63 NOT USABLE - 20 1 B 20 1 - NOT USABLE 64 65 NOT USABLE - 20 1 C 20 1 - NOT USABLE 66 67 NOT USABLE - 20 1 A 20 1 - NOT USABLE 68 69 NOT USABLE - 20 1 B 20 1 - NOT USABLE 70 71 NOT USABLE - 20 1 C 20 1 - NOT USABLE 72 73 NOT USABLE - 20 1 A 20 1 - NOT USABLE 74 75 INOT USABLE - 20 1 B 20 1 - NOT USABLE 76 77 NOT USABLE - 20 1 C 20 1 - NOT USABLE 78 79 NOT USABLE - 20 1 A 20 1 - NOT USABLE 80 81 NOT USABLE - 20 1 B 20 1 - NOT USABLE 82 83 NOT USABLE - 20 1 C 20 1 - NOT USABLE 84 NOTES: NOTE 1: PROVIDE A NEW 3P -20A CB WITH 3 #12, 1 #12G IN 3/4 "C. '1MNH1' LOAD SUMMARY PANEL: D6 LTS RCPTS MTRS MISC TOTAL (KVA) TOTAL (AMPS) TOTAL CONNECTED LOAD 010 0.0 141.1 0.0 141.1 169.7 DEMAND FACTOR SEE DEMAND FACTOR TABLE TOTAL DEMAND LOAD 0.0 0.0 143.3 0.0 143.3 172.4 CONTINUOUS (DESIGN) FACTOR 1.25 1100 1.00 1.00 TOTAL DESIGN LOAD 0.0 0.0 143.3 0.0 143.3 172,4 3 EXISTING DISTRIBUTION FED FROM: MSBH3 LOCATION: ELEC RM MAIN BUS: 225A MCB: N/A VOLTAGE: 480/277 AIC: 14,000A PANEL: D6 WIRES: 4W + G ENCLOSURE: NEMA 1 BUS TYPE: Copper MOUNTING: Surface PANEL LUGS: Main Lugs Only RCPTS MTRS MISC NORMAL NEUTRAL BUS: Yes GROUND BUS: Yes ISOLATED GROUND BUS: No 200% NEUTRAL: No CKT N0. DESCRIPTION 0.0 TOTAL LOAD VA LOAD (VA) 4.2 77.0 CIRCUIT BREAKER DEMAND FACTOR SEE DEMAND FACTOR TABLE REMARKS LTS RCPTS MTRS MISC AMPS POLES 1 NEW VAVS 1.00 4200 1.00 TOTAL DESIGN LOAD 4200 20 1 81.1 1 NOTE 1 1 102.6 2 SPARE -0 " uQ Ll � 0) as un rn o c o o o 0 - - � m m = E 3 AC COMPRESSOR a m o .0 33000 W T U w c 8 c� Ni 33000 50 71 o � X � N (!1 V a w x 3 4 SPARE - ............. __ o - _ 5 EXHAUST FAN 9960 9960 15 l 3 6 UNIT CONFERENCE 9960 9960 a <C 15 3 7 HEAT PUMP REVISIONS 9960 MARK: 2 REMARKS: OWNER RF ., JFSTFr) CHANGES 9960 3_ 15 1001091/201 OWNER REQUESTED 3 CHANGES 12/9/13 8 UNIT C 9960 9960 15 3 9 SPACE - 10 ISPACE NOTES: NOTE 1: PROVIDE A NEW 1P -20A CB IN AVAILABLE SPACE WITH 2 #12, 1 #12G IN 3/4 "C. 'D6' LOAD SUMMARY LTS RCPTS MTRS MISC TOTAL (KVA) TOTAL (AMPS) TOTAL CONNECTED LOAD 0.0 0.0 72.8 4.2 77.0 92.7 DEMAND FACTOR SEE DEMAND FACTOR TABLE TOTAL DEMAND LOAD 0.0 1 0.0 1 81.1 1 4.2 1 85.3 1 102.6 CONTINUOUS (DESIGN) FACTOR 1.25 1.00 1 1.00 1.00 TOTAL DESIGN LOAD 0.0 1 0.0 1 81.1 4.2 -f-85.3 1 102.6 J 4- W 0-w Q� �w oQ �k �P11 W11111;�a7 T P C f. n M g D :w) o 0 CJ a M N M V) * 0) m J -j0-) o) Y Q) LL �D vD g g -0 " uQ Ll � 0) as un rn o c o o o 0 � m m = E a m o .0 W T U w c 8 c� Ni 71 o � X � N (!1 V a w x > CD............ ............. __ o l cn n a <C REVISIONS MARK: 2 REMARKS: OWNER RF ., JFSTFr) CHANGES 3_ 1001091/201 OWNER REQUESTED CHANGES 12/9/13 J 4- W 0-w Q� �w oQ �k �P11 W11111;�a7 PANEL SCHEDULES 412474.00 Sheet Title: Sheet No: E8.00 E T P C f. n PANEL SCHEDULES 412474.00 Sheet Title: Sheet No: E8.00 E